SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬1 ‫ﺻﻔﺤﻪ‬

 
Specification for Instrument Cable
 
 

FINAL
02 FA AN MM 89.12.23
APPROVED
01 IFC FA BM AB 89.10.14 Generally Revised
00 IFC MK BM BM 89.07 -

PURPOSE OF
REV. PREPARED CHECKED APPROVED DATE REMARKS
ISSUE

DOCUMENT REVISION SHEET


- REVISED SHEETS ISSUED FOR
ONLY ATTACHED □
- REVIEW □
- APPROVAL □
- ENTIRE DOCUMENT - QUOTATION □
RE-ISSUED ■□ - PURCHASE □
- COMMENT □
- INFORMATION □
……………
- ENTIRE DOCUMENT

REVISED □
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬2 ‫ﺻﻔﺤﻪ‬

00 01 02 REMARK 00 01 02 REMARK
1 X X
2 X X
3 X X
4 X X
5 X X X Revised
6 X X
7 X X
8 X X
9 X X
10 X X
11 X X
12 X X
13 X X
14 X X
15 X X
16 X
17 X
18 X
19
20
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬3 ‫ﺻﻔﺤﻪ‬

Contents 

1  INTRODUCTION ............................................................................................................... 4 
2  DEFINITIONS .................................................................................................................... 4 
3  PURPOSE ......................................................................................................................... 5 
4  SCOPE .............................................................................................................................. 5 
5  CODES AND STANDARDS ................................................................................................ 5 
6  PRECEDENCE ................................................................................................................... 7 
7  AMBIENT CONDITIONS ................................................................................................... 7 
8  TECHNICAL REQUIREMENTS ........................................................................................... 7 
9  GENERAL INFORMATION FOR SELLERS ........................................................................ 13 
10  PREPARATION FOR SHIPMENT .................................................................................... 17 
 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬4 ‫ﺻﻔﺤﻪ‬

1 INTRODUCTION 
Iranian Gas Engineering & Development Company (I.G.E.D.C) has intended to perform gas 
transmission pipeline and gas compressor stations for transferring of 110 MMSCMD of 
natural gas to be fed from South Pars phases 22 ~ 24 from Assalouyeh to Bazargan. 
 Design of a new 56" gas transmission pipeline from Assalouyeh to Bazargan has been 
described under this EPC Contract. 
 
The purpose of this document together with the referred standards, specifications and 
project documents is to define the general requirements for Instrument Cables.  

2 DEFINITIONS 

PROJECT  56" gas transmission pipeline from Assalouyeh to Bazargan 

CLIENT  Iranian Gas Engineering & Development Company (IGEDC) 

MANAGING CONSULTANT  Ghods Niroo Consulting Engineers 

CONSULTANT  Haraz Rah Consulting Engineers 

EPC CONTRACTOR  Gharargah Khatam‐AL‐Anbia. Niroo Goostar Institute 

MANUFACTURER/ 
SUPPLIER/VENDOR  The manufacturer and/or vendor of a commodity, system, 
or piece of equipment to perform the specified duty. This 
may be the MANUFACTURER or his agent, an integrator or 
factory. Several manufacturers may supply equipment to 
the same SUPPLIER 

2.1 SHALL & SHOULD 
When used in this or referenced documents the following words are used in the manner 
described below: 
The words shall and must is to be understood as mandatory 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬5 ‫ﺻﻔﺤﻪ‬

The  word  should  as  strongly  recommended  to  comply  with  the  requirements  of  this 
document. 
The word ‘Will’ is used in the preferred sense. 
The word ‘Includes’ means ‘includes but not limited. 

3 PURPOSE 
The  purpose  of  this  document  together  with  the  referred  standards,  specifications  and 
project  documents  is  to  provide  a  basis  for  the  identification  and  standardisation  of 
information to be used in the Project. 
02
4 SCOPE 
This document together with the referred standards, specifications and project documents 
covers  the  minimum  requirements  for  instrument  cables  to  be  used  in  the  project.  This 
specification  shall  be  used  as  a  basis  of  design  for  preparation  of  detail  engineering  and 
purchase of instrument cables. 

5 CODES AND STANDARDS 
All work specified shall be in accordance with all applicable sections of the latest editions of 
the Codes and Standards (and their current amendments), listed as below: 

IPS‐C‐IN‐190  Construction and installation for Transmission 
systems 

IPS‐E‐IN‐190  Engineering and design for Transmission systems 

IPS‐M‐IN‐190  Material  and  Equipment  Standard  for  Transmission 


Systems 

IPS‐M‐EL‐271  Material and equipment for Low voltage cables and 
wires 

IEC 60028  International Standard of Resistance for Copper. 

IEC 60092‐3  Cables (construction, testing and installations) 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬6 ‫ﺻﻔﺤﻪ‬

IEC 60092‐375  General  Instrumentation,  Control  &  Communication 


Cables 

IEC 60189‐1 to 7.  L.F. Cables and Wires‐General 

IEC 60227‐1 to 5.  Conductors  &  cables  Insulated  with  P.V.C  Nominal 


Voltage 450/750V. 

IEC 60228 Class 2.  Conductors of Insulated Cables. 

IEC 60230   Impulse Tests on Cables and their Accessories. 

IEC 60245‐1 to 4   Rubber Insulated Conductors & Cables, Nominal Voltage 
450/750 Volts 

IEC 60331   Characteristics of Fire Resisting Electric Cables. 

IEC 60332‐1 to 3   Tests on Electric Cables Under Fire Conditions. 

IEC 60344  Guide to the calculation of resistance of plain and 
coated copper conductors of low‐frequency cables 
and wires 

IEC 60446   Identification of Colours or Numerals of Conductors 

IEC 60584   International  Thermocouple  Reference  Tables‐Type  ‘K’ 


Thermocouples. 

IEC 60754‐1   Tests  on  gases  Evolved  During  Combustion  of  Electric 


Cables 

IEC 60811  Common  test  Methods  for  Insulating  &  Sheathing 


Materials of Electric Cables. 

IEC 60885   Electrical  Test  Methods  for  Electrical  Cables,  Nominal 


voltage 450/750 Volts 

IEC 61034   Measurement  of  Smoke  Density  through  Burning  of 


‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬7 ‫ﺻﻔﺤﻪ‬

Electric Cables. 

API‐552  Transmission Systems 

BS‐6387  Performance  Requirements  for  Cables  required  to 


Maintain Circuit Integrity under Fire Conditions. 

NFC‐32070  Insulated  Conductors  of  Cables  and  Flexible  Cords  for 


Installation,  Classification  Tests  on  Cables  &  Cords  with 
respect to their behaviour in Fire 

ISO‐4589  Determination of Burning Behaviour by Oxygen Index. 

6 PRECEDENCE 
In the event of conflict between the various documents, their order of preference will be as 
follows: 
- Purchase Order 
- Material Requisition 
- This Specification 
- Other referenced Specifications 
- Codes and Standards 

7 AMBIENT CONDITIONS 
The  instrument  cables  shall  be  suitable  for  permanent  operation  with  environmental 
conditions as described in “SITE CONDITION”. 

8 TECHNICAL REQUIREMENTS 

8.1 Basic Requirements 
8.1.1 General 
All  cable  shall  be  water,  oil,  UV  resistant,  gas/vapor  tight,  burn  with  a  low  release  of 
halogens. 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬8 ‫ﺻﻔﺤﻪ‬

All cables shall comply with the relevant applicable IEC recommendations and with the 
regulation of the country of installation. 
Cables used for external installation shall be armoured. 
In  extreme  instances,  where  areas  are  susceptible  to  oil  or  condensate  spillage  or 
contamination, cables with laminated outer sheaths to be considered as an alternative 
to conventional lead covered cable. 
Cables installed within Local Equipment/Control Rooms shall be unarmoured. 
Flame retardant cables according to IEC 60332.3 shall be used for instrument cables as a 
minimum requirement. 
8.1.2 Particular requirements 
Cables shall be of the low smoke and low halogen type and shall be water, oil & sunlight 
resistant and gas & vapor tight. 
Cables shall be low fume emission for: 
- Sulphur 
- Nitrogen 
- Carbon Monoxide 

Smoke  emission shall be in  accordance  with requirements of  IEC  61034. Oxygen index 


shall be according to ISO 4589. 
The  outer  sheath  of  instrument  cables  shall  be  immune  to  the  effects  of  ultra  violet 
radiation. 
The inner sheath of Instrument cables shall be extended to fill all spaces between cores 
to prevent the passage of gas or other noxious substance along the cable. 
Allowances on delivered lengths shall be 0 to +3%. 
Pairs and triads in multi‐pair/triads cables shall be identified by printed numbers on one 
core of the pair or triad.  Each core in multi‐core shall be identified by a printed number, 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬9 ‫ﺻﻔﺤﻪ‬

the sequence running 1 to N. 
Cables for ‘Intrinsic Safety (IS)’ signals shall be with the following characteristics: 
- Mutual capacitance between cores 0.13 µF/km (maximum) 
- Capacitance between any core and screen 0.13 µF/km (maximum) 
- Inductance/resistance ratio 30 µH/Ohm (maximum) 
8.1.3 Installation conditions 
Instrument cables may be installed on open racks and shall withstand intense sunlight, 
seawater  spray,  H2S  +  CO2  sour  gas.    Covers  shall  be  provided  where  oil  spillage  can 
occur to protect cables. 
Cables  shall  be  secured  to  racks  by  cleats  and  shall  be  sealed  into  Local 
Equipment/Control Rooms by multi cable transit frames. 
Instrument cables may also be direct buried within trenches or ducts. 

8.2 Cable Specification 
8.2.1 Flame retardant cables 
Voltage grade: 
500 volts 
Type: 
Flame retardant according to IEC 60332.3. 
Conductor:  
Stranded tinned copper wire according to IEC 60228 class 2. 
Temperature class: 
90°C 

8.2.1.1 Instrument Analogue Signals: 
Cross section: 
For 24v D.C. Analogue Signals:    Single Pairs – 1.5 mm2, 7 strands 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬10 ‫ﺻﻔﺤﻪ‬

          Multi Pairs – 1.5 mm2, 7 strands 
Insulation: 
PVC, low smoke, low halogen, thickness in accordance with IEC 60092‐376 
Twinning: 
The  insulated  conductors  shall  be  twisted  together  to  form  a  pair/triad/quad. 
Lay of twist per pair/triad/quad shall be approximately 13 to 20 times per meter. 
Wrapping for individual screen (as specified): 
Each  pair/triad/quad  shall  be  wrapped  with  Polyester  tape  0.023  mm  thick,  helically 
wound with 25 % overlap. 
Lay‐up:  
The pairs shall be laid up to form a cable with a minimum of cross talk. 
Bonding wire: 
Stranded tinned copper drain wire as per IEC 60228. 
Overall screen (as specified): 
The  pairs/triads/quads  shall  be  screened  with  aluminium  backed  Mylar  tape  helically 
wrapped with a 25 % overlap.  Aluminium on the inside to be in continuous contact with 
a tinned stranded copper drain wire of the same diameter as the conductor. Thickness 
of screen to be 0.012 mm aluminium on 0.023 mm Mylar tape. 
Individual screen (as specified): 
Each  pair/triad/quad  shall  be  screened  with  aluminium  backed  Mylar  tape  helically 
applied with 25 % overlap.  Aluminium on the inside to be in continuous contact with a 
tinned stranded copper drain wire of the same diameter as the conductor.  Thickness of 
screen to be 0.012 mm aluminium on 0.023 mm Mylar tape. 
Each screen shall be insulated from the remaining cable components by the application 
of suitable tapes and numbered in accordance with the pair numbering system. 
Wrapping below inner sheath: 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬11 ‫ﺻﻔﺤﻪ‬

The screened cable shall be wrapped with Polyester tape helically wound. 
Inner sheath (except for unarmoured cables): 
PVC, low smoke, low halogen, thickness in accordance with IEC 60092‐375 
Armour (except for unarmoured cables): 
Galvanised mild steel wire braid armour. Density and thickness in accordance with IEC 
60092‐376 Paragraph 9. 
Overall outersheath: 
PVC, low smoke, low halogen, flame retardant type in accordance with IEC 60332‐3. 
Outersheath colour: 
LT. Blue for I.S. signals and Grey for Non‐I.S. signals 
Notes: All cables specified as individual screen shall also have an overall screen. 

8.2.1.2 Instrument Alarm, SOV & Power Supplies 
Cross Section: 
For 24v D.C. Alarm Signals:    Single and Multicores ‐ 1.5 mm2  min. 
For 110v A.C. (UPS)      2.5 mm2 min. to IEC 60092–353 
For 230v A.C. Power Supplies:    2.5 mm2 min. to IEC 60092‐353 
Insulation: 
PVC, low smoke, low halogen, thickness in accordance with IEC 60092‐375 
Wrapping below inner sheath: 
The cable shall be wrapped with Polyester tape helically wound. 
Inner sheath (except for unarmoured cables): 
PVC, low smoke, low halogen, thickness in accordance with IEC 60092‐375. 
Armour (except for unarmoured cables): 
Galvanised mild  steel wire braid armour, density and thickness in accordance with IEC 
60092‐376. 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬12 ‫ﺻﻔﺤﻪ‬

Overall outer sheath: 
PVC, low smoke, low halogen, flame retardant type in accordance with IEC 60332‐3. 
Outer sheath color: 
LT. Blue for I.S. signals and Grey for Non‐I.S. signals 
8.2.2 Earthing cables 
Conductors  :   Stranded tinned copper 
Number of Cores  :   One 
Outer sheath  :   PVC,  low  smoke,  low  halogen,  flame  retardant  type  in 
accordance with IEC 60332‐3 
Outer sheath color   :   In accordance with service (Yellow/Green, Green) 

8.3 Core colors: 
Single pair  :  Black, White 
Multi‐pair  :  Black, White 
The pairs shall be identified numerically and sequentially 
Single Triad :  :  White, Red, Blue 
Multi Triad :  :  White, Red, Blue 
The triads shall be identified numerically and sequentially. 
Single quad :  :  Black,  White,  Black  with  White  strips,  White  with  Black 
strips 
Multi quad :  :  Black,  White,  Black  with  White  strips,  White  with  Black 
strips 
The quads shall be identified numerically and sequentially. 

8.4 Marking 
8.4.1 Cables 
The  outersheath  of  cable  shall  be  embossed  at  every  3  meter  intervals  with  marks  to 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬13 ‫ﺻﻔﺤﻪ‬

distinguish the following data as a minimum: 
a) Manufacturer's name and year of manufacture 
b) Voltage grade (specified voltage) 
c) Number of core and core sizes 
d) Cable type 
e) Quality of outer sheath 

Single core cables shall be marked with painting and multi core cable shall be embossed 
marking type. 
8.4.2 Cables drums 
Cable  drums  shall  be  indelibly  marked  by  weatherproof  stenciling  at  last  one  on  each 
flange as follows: 
a) Manufacturer's name and year of manufacture  
b) Drum number 
c) Requisition number 
d) Requisition item number 
e) Rated voltage 
f) Cable type by abbreviation letter and outersheath diameter 
g) Number and cross section of cores 
h) Length of cable on the drum (in meters) 
i) Overall weight of cable and drum (in kg) 

9 GENERAL INFORMATION FOR SELLERS 

The requisition to which this specification is attached covers the manufacture and supply of 
Instrument Cables in accordance with this specification. 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬14 ‫ﺻﻔﺤﻪ‬

9.1 Codes and Standards 
Cable shall comply with the standards listed in this specification. (Refer to Section 2.) 

9.2 Cable Construction (General) 
Identifications  printed  onto  individual  core  insulation  shall  be  permanent  and  resist 
removal when abraded. 
The final cable make‐up shall be homogenous and circular in cross section. 
No splices are permitted in any cable conductors. Continuous conductors shall be used. 

9.3 Electrical Specifications 
Nominal  Conductor Resistance in  Ohms per 1000  meters at  20°C  shall  be  in accordance 
with IEC 60028: 
- Insulation Integrity Verified by Spark Test    6000 VAC 
- Finished product given dielectric test     1500VAC 
- Conductor to conductor and conductor to shield for one minute 
- Insulation Resistance Constant at 15.6°C     3000 
(Natural Material) 

9.4 Testing 
Factory  tests  on  completed  wire  and  cable  shall  be  in  accordance  with  IEC  60811  and 
other relevant standards listed for each cable type. 
However,  the  following  tests  shall  be  performed  on  each  drum  of  completed  cable  in 
addition to those listed in Electrical Specification clause: 
a) Continuity of conductors and shields 
b) Shield isolation jackets shall withstand a dry test of 2000VAC between shields for 
c) one minute 
d) The insulation resistance between shields shall be a minimum of 10 mega ohms 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬15 ‫ﺻﻔﺤﻪ‬

e) per 300m of cable corrected to 15.6°C 
f) Test of gases evolved during combustion of cables (IEC 60754). 
Three copies of cable test certificate for each manufactured cable shall be provided by the 
Seller. The following additional information shall be included in the certificate:  
a) Resistance of each copper conductor in ohms/1000 metre at 20 0C 
b) Maximum mutual capacitance values in pf/metre 
c) Maximum L/R Ratio for adjacent cores in uH/ohm 

9.5 End Sealing 
After testing, the ends of the cable shall be sealed by an approved method to prevent the 
ingress of moisture. Supplier shall state proposed method in his quotation. 

9.6 Drum Label 
Each drum shall be identified by an indestructible label securely attached, containing the 
following information: 
a) Requisition/Item No. 
b) Drum Number (where applicable) 
c) Cable Type Number 
d) Conductor Size 
e) Length (metres) 
f) Rated Voltage 
g) Weight of Cable and Drum (Kg) 

This  information  is  in  addition  to  any  other  marking  required  by  Purchaser’s  Materials 
Management and/or shipping Departments. 

9.7 Drum Lengths 
Cable  drum  length  shall  have  a  positive  tolerance  only.  Purchaser  reserves  the  right  to 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬16 ‫ﺻﻔﺤﻪ‬

reject drums with a negative tolerance.
Maximum Length for single pair cable shall be 500 meters. 

9.8 Cable Sample 
When specified in the requisition, Seller shall provide Purchaser with a 300mm length of 
each type of cable, clearly marked with its Type No, to enable glands to be checked. 

9.9 Cable Data 
Vendor  shall  submit  complete  data  sheet  to  the  purchaser  with  his  quotation.  The 
following  data  are  required  for  each  cable  type.  Seller  shall  complete  
Table 1 and return to Purchaser. Preliminary data shall be supplied at enquiry stage. Final 
data shall be supplied prior to commencement of production. 
a) Cable weight (kg/km) 
b) Maximum allowable pulling tensions (kN) 
c) Minimum pulling temperature (0C) 
d) Minimum bending radius (mm) 
e) Inductance/Resistance (L/R) ratio between the insulated conductors of any one pair. 
(uH/ohm) 
f) Maximum mutual capacitance per metre (pF/m) 
g) Resistance of each copper conductor in ohms/1000 metre at 200C (ohm/km) 
h) Cable  dimensions  relevant  to  sizing  cable  glands.  In  millimetres  with 
maximum/minimum tolerances allowable: 
- Overall diameter 
- Under armour diameter 
- Over armour diameter 
- Armour wire diameter 

  Items e, f, g are required only when specified in requisition. 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬17 ‫ﺻﻔﺤﻪ‬

10 PREPARATION FOR SHIPMENT 

Splices in individual conductors of single and multi‐pair cables, drain wire or shielding are 
not acceptable. 
Watertight seals shall be applied to the ends of the cable to prevent entrance of moisture 
during shipment or out‐of‐doors storage at the job site. 
The  manufacturer  shall  be  solely  responsible  for  the  adequacy  of  the  preparation  for 
shipment  provisions  employed  with  respect  to  materials  and  their  application  to  insure 
that  the  cable  reaches  its  destination  in  excellent  working  condition  when  handled  by 
commercial carrier systems. 
All drums shall have lagging to prevent damage to the finished cable. 
The manufacturer shall submit with his quotation, his standard “packaging” of drums. 
‫ﻃﺮاﺣﻲ و ﻣﻬﻨﺪﺳﻲ ﺗﻔﺼﻴﻠﻲ‬
«‫» ﺧﻂ ﻟﻮﻟﻪ ﺷﺸﻢ ﺳﺮاﺳﺮي ﮔﺎزاﻳﺮان‬

SPECIFICATION FOR INSTRUMENT CABLE


Pro.
PROJECT Scope DIS. Doc. SERIAL REV.
Part
‫ﮔﺮوه ﻣﻬﻨﺪﺳﻴﻦ ﻣﺸﺎور ﻫﺮازراه‬
IGAT 6 D PL IN SPC 0003 02 18‫ از‬18 ‫ﺻﻔﺤﻪ‬

TABLE 1 
CABLE DATA 
 
SELLER’S NAME  

CABLE TYPE NUMBER  

CABLE WEIGHT (KG/KM)  

MAX. ALLOWABLE PULLING TENSION (KN)  

MIN. PULLING TEMPERATURE (0C)  

MIN. BENDING RADIUS (MM)  

L/R RATIO (Uh/ohm)  

MAX. MUTUAL CAPACITANCE (pF/METRE)  

CONDUCTOR RESISTANCE (OHM/KM)  

OVERALL DIAMETER (Max/Min)  

UNDER ARMOUR DIAMETER(Max/Min)  

OVER ARMOUR DIAMETER (Max/Min)  

ARMOUR WIRE DIAMETER   
 
 