DEMARCATION OF SCOPE FOR BAS SYSTEM

SCOPE OF WORK
Signal (including
Power
DESCRIPTION Supply Install High Level REMARKS
Supply
Interfacing)

Chilled Water Plant


complete integrated set c/w flow meter,
Btuh meter ACMV ACMV ACMV BAS HL paired temperature sensors & energy
calculator.
Temperature sensors BAS ACMV - BAS
Differential pressure sensors (remote point) BAS ACMV - BAS
Pumps VSD ACMV ACMV ACMV BAS HL
Main Chiller Starter Panel Digital Power Meter @ incoming ACMV ACMV ACMV BAS HL
Chiller Management System ACMV ACMV ACMV BAS HL
Motosied valves at cooling towers BAS ACMV - BAS
Thermometer ACMV ACMV ACMV -
Pressure gauge ACMV ACMV ACMV -

AHU Room
Incoming electricity supply by electrical
AHU starter panel ACMV ACMV ELEC BAS
contractor
VSD ACMV ACMV ACMV BAS HL
Space temperature sensors ACMV ACMV - BAS
In duct temperature sensors BAS BAS - BAS
VAV Box c/w Controller, actuators and space sensors ACMV ACMV ACMV BAS
PIBCV (modulating) ACMV ACMV ACMV BAS Spring return actuators
CO2 Sensor BAS BAS ACMV BAS
Chilled Water Supply and Return Temperature Sensor BAS BAS - BAS
Chilled Water Pressure and Differential Pressure Sensor BAS BAS - BAS
Air differential pressure sensor ACMV ACMV - BAS
Motorised Smoke Damper ACMV ACMV ACMV FIRE
Motorised Volume Control Damper ACMV ACMV ACMV BAS
Motorised Fire Damper ACMV ACMV ACMV FIRE
Actuators for Motorised Damper BAS BAS ACMV BAS Spring return actuators
Delta P sensors for filters BAS BAS - BAS
Electrostatic Filters ACMV ACMV ACMV -
UVGI system ACMV ACMV ACMV -
SCOPE OF WORK
Signal (including
Power
DESCRIPTION Supply Install High Level REMARKS
Supply
Interfacing)
Thermometer ACMV ACMV ACMV -
Pressure gauge ACMV ACMV ACMV -

FCU
Thermostat ACMV ACMV - BAS
PIBCV ACMV ACMV ACMV BAS
Incoming electricity supply by electrical
FCU starter panel ACMV ACMV Elec BAS
contractor

Lift Lobby and Staircase Pressurization System (Fire mode)


Motorised Smoke Damper ACMV ACMV ACMV FIRE
Spring return actuators & overriding signals
Actuators for Motorised Damper BAS BAS ACMV FIRE
from fire.
Differential Pressure Sensor BAS BAS - BAS
VSD ACMV ACMV ACMV BAS HL
Incoming electricity supply by electrical
Fan Starter Panel ACMV ACMV Elec FIRE
contractor

Lift Lobby and Staircase Pressurization System (Ventilation mode)


Motorised Smoke Damper ACMV ACMV ACMV BAS
Actuators for Motorised Damper BAS BAS ACMV BAS Command from BAS
Differential Pressure Sensor BAS BAS - BAS
VSD ACMV ACMV ACMV BAS HL
Incoming electricity supply by electrical
Fan Starter Panel ACMV ACMV Elec FIRE
contractor

Toilet Exhaust System


Incoming electricity supply by electrical
Fan Starter Panel ACMV ACMV Elec -
contractor

Office Smoke Spill Fan


Fan Starter Panel ACMV ACMV ACMV Fire