Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Anderson et al suggested empirical relations from which they were able to relate the degree
of expansion with the plasticity index.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -2/12
(From Prof. A. Tefera)
Following their investigation they came up with the following empirical equation:
S = 0.23PI - 3.12
where S is swelling potential
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -3/12
(From Prof. A. Tefera)
Ip Plasticity index.
Based on Eq. (6.1), they presented the relationship shown in Table 6.2.
Table 6.2: Relationship between Plasticity Index and Swelling Potential
Degree of Plasticity Index Swelling Potential
Expansion Ip S
Low 20 1.5
Medium 20 - 31 1.5 - 4.0
High 31 - 39 4.0 - 6.0
Very High 39 6
Defining activity as the ratio of the plasticity index to the percentage of the clay fraction(minus 2
micron size) present in the sample, two different types of charts were presented by different authors
to identify the swelling potential of expansive soils. The first chart, known as the Activity chart, is a
plot of plasticity index versus clay fraction. De
Bruyn et al plotted experimental data and found three distinct groupings according to the activity of
the soils. The soils were classified as Bad, Medium and Good according to their property with regard
to their effect on buildings erected on them. Here again the location of the predominant expansive
soils of Addis Ababa are indicated (Fig. 9.2). The second chart is presented by Seed et al [12], where
activity versus clay fraction is presented (Fig. 9.3). Additional information on expansive soils is found
in [14]. Using the above information judiciously, one would get a fair idea of the degree of potential
expansiveness of any soil under consideration.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -4/12
(From Prof. A. Tefera)
Activity chart
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -5/12
(From Prof. A. Tefera)
6.4 Methods of Preventing Damage
In order to minimize or to eliminate the danger of damage to buildings because of heave and
shrinkage, the following methods have been used [4]:
a. Moisture control
b. Soil stabilization
c. Structural measures.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -6/12
(From Prof. A. Tefera)
as two to three meters are common occurrences during the dry season. This seasonal fluctuation of
the moisture content along the depth becomes minimal from approximately three to four meters
down-wards. In addition to the fluctuation of the ground water one should also consider free water
which may seep under foundations, or the effect of evaporation which would cause moisture
migration. Hence a satisfactory solution to the problem would be to devise an economical way of
stabilizing the soil moisture under and around buildings. It does not matter whether the moisture
content is high or low, as long as it can be maintained constant throughout the year.
Depending upon the existing conditions, some prefer to keep the soils as wet as possible throughout
the year. Based on this approach, two methods have been presented by Deb and Chandra, India [8].
These methods consist of providing
a. sand drains
b. a flexible water-proof apron with sand drains.
The second method was found to be more effective and applied with reasonable success. Here
auger-bored holes of 20cm in diameter and 2 meters depth are drilled at 2 meters center to center
and about 1 meter away all around the building. The holes are filled with coarse sand and are
connected by surface drains. A watertight apron of 1 meter width is built around the building (Fig. 9.4,
and Fig. 9.5).
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -7/12
(From Prof. A. Tefera)
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -8/12
(From Prof. A. Tefera)
The other approach is to prevent the migration or flow of water to the vicinity of the building by
providing horizontal and vertical moisture barriers, and also subsurface and surface drainage.
Horizontal moisture barriers are installed around a building in the form of membranes. The purpose
of the horizontal barriers is to prevent excessive intake of surface moisture. Widely used horizontal
membranes are polyethylene membrane, concrete aprons and asphalt membrane, extending beyond
the limits of backfill.
Vertical moisture barriers are used around the perimeter of the building to cut off the source of water
that may enter the under slab soil. To serve as barriers in this category, one may use polyethylene
membrane, concrete, or other durable impervious material. The depth of the barriers should be equal
to or greater than the depth of moisture fluctuation. Backfill materials may be used as vertical
moisture barriers provided they are well compacted.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -9/12
(From Prof. A. Tefera)
The subsurface drainage system is used to intercept the gravity flow of free water, to lower the
ground water or perched water, and to arrest the capillary moisture movement. For this purpose
intercepting and peripheral drains are installed. It should be borne in mind that positive outlets
should be provided for subsurface drainage. For proper surface drainage, the ground surface around
the building should be graded so that surface water will drain away from the structure in all
directions. Roof downspouts must be directed away from the structure so that water does not seep
into the foundation soil. They should extend well beyond the perimeter of the foundation and should
be properly drained away.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -10/12
(From Prof. A. Tefera)
approach to compact swelling clays at moisture content slightly above their natural moisture content
and at low density should give good results. The main advantage of using this approach is that the
swelling potential can be reduced without the negative effects caused by introducing excessive
moisture into the soil, in which moisture migration to the underlying moisture-deficient soil takes
place. Even though the required depth of compaction depends on the potential expansiveness of the
soil and on the magnitude of the structural load, it may in general be adequate to compact to a depth
of 1.5 to 2 metres.
a. Floating foundation
b. Reinforcement of brick walls
c. Foundations on piles.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -12/12
(From Prof. A. Tefera)
frequently used and which is abundantly available in Ethiopia is red volcanic ash.
The slabs are designed assuming that they are anchored (fixed) in the beams and that a pressure of
20 kN/m2 acts from the soil. This magnitude is indeed small when considering that swell pressures
varying from 300 to 500 kN/m2 are commonly found. The beams are designed as beams on an elastic
foundation, using the appropriate modulus of sub grade reaction.
Before the slab and beams are cast, about one meter of the expansive soil is removed from the plan
area of the building. The soil is flooded with adequate water, and sufficient time is given for it to
swell. For practical reasons it is preferred to continuously saturate the foundation soil rather than
prevent the migration of moisture. On top of the expansive soil the compacted red ash is placed at
high water content. Sand drains are also provided around the plan area of the building. The sand
drains are 20cm in diameter and 2 meter deep and spaced at an interval of 2 meters, center to center
and at about 1.0 meter away all around the building. The holes are filled with coarse sand and are
connected by surface drains. A watertight apron of 1.0m width is paved around the building. It is
provided with a gradient sloping away from the building so that the accumulated water will be
directed into the surface drains. It is suggested to cover the surface drains with perforated precast
concrete slabs in order to retard evaporation. At times it may be necessary to add extra water to keep
the sand drains saturated all the time (Fig. 9.4 and Fig 9.5).
Such a method of construction has been tried in Addis Ababa, and the results have been mixed. In
some areas the buildings did not show any sign of distress, while in some areas considerable cracking
has been witnessed. Systematic research on such a phenomenon has not been done. It is clear from
the outset, however, that such methods of construction would be effectively used in areas where the
fluctuation of the ground water table is not too large. Before deciding on this method, the engineer
should get sufficient information regarding topography, ground water level if available, drainage and
depth of the expansive soil.
Design procedure for such stiffened slab has been recently published [9]. The effectiveness of the
method has yet to be proved in the future.
The other type of floating foundation that has been used in the design of dwellings on expansive soils
is a rigid mat. A heavily reinforced rigid mat is placed on leveled soil. The walls and columns are then
built on the foundation. The rationale in this design is that the rigid mat will eliminate any differential
heave, and the structure will "ride on" without suffering any internal distress. Cost-benefit analysis
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -13/12
(From Prof. A. Tefera)
should be made before deciding on such a design.
(ii) Loads
The loads considered are the dead load of the walls, the roof load, and the load due to any floor
carried by the wall. The total load is divided by the length of the wall and is considered as a uniformly
distributed load which is carried by the wall itself.
The bending moment in the wall is calculated using the following equation:
M= wl2/16
where
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -15/12
(From Prof. A. Tefera)
w uniformly distributed load
length of wall.
The main steel calculated is placed in the first two continuous horizontal joints in the brickwork
comprising the foundation, that is, after concrete strip footings have been built with brickwork to
form one horizontal surface over all the footings. An equal quantity of steel is also placed in the last
two horizontal joints at the top of the wall. Some or all of the main steel should be bent around the
corners.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -16/12
(From Prof. A. Tefera)
(vi) Horizontal Steel above Opening
The beams over openings must be at least six courses of brickwork high and the following steel
should be placed in the first horizontal joint above the openings in a wall:
a. Openings up to 1.0 meter span require two steel bars of ~ 10.
b. Openings over 1.0 meter and up to 2 meters span require two bars of ~ 12 or three of
~ 10.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -17/12
(From Prof. A. Tefera)
c. For openings over 2 meters span, the beam over the opening must be designed to carry its
dead load plus the roof load carried by it, using the usual formula for designing reinforced
concrete structure with appropriate reinforced brickwork constants. The reinforcement
must not be less than two bars of ~ 12, if the opening exceeds 2 meters span.
The steel should extend at least 60 diameters past the sides of the openings. If the ends of the steel
over adjacent openings are less than 30cm apart, the rods should not be cut but should be run
continuously over those openings.
Hangers made of galvanized wire should pass over this steel and extend down into the vertical joints
between the soffit bricks. This will prevent any of the soffit bricks falling away from the steel.
(vii) Horizontal Steel below Openings
This steel should be placed in the first continuous joint below the opening:
a. When the sum of the widths of openings in a wall is less than 30% of the length of the wall,
the same steel should be placed under the opening as is to be placed above the opening.
b. When the sum of the widths of openings in a wall is more than 30% but less than 50% of
the length of the wall, the steel just under the openings should be 1 ~ times that above the
openings and continuous where possible.
c. When the sum of the widths of the openings is more than 50% but less than 70% of the
length of the wall, the steel below the openings should be the same as the main steel and,
where possible, run the whole length of the wall.
d. When the openings are so numerous that the columns between the openings are very
slender, the wall must be considered as two separate beams acting together, the one below
the windows and the other above. It is recommended that such walls should not be used
with this type of construction, as it is not possible to reinforce the vertical column between
the openings satisfactorily.
The diameter of the vertical steel must be ~ 12 or more. Vertical rods should be placed at the end of
walls and on each side of all openings. The number of rods required at any particular point is as
follows:
a. If the sum of the spans of the openings is less than 30% of the length of the wall, one rod
should be placed at each end of the wall and one rod adjacent to each side of each opening.
b. If the sum of the spans of the openings is more than 30% but less than 50% of the length of
the wall, two rods must be placed at each end of the wall, and two rods adjacent to the
sides of the openings nearest each end. One rod must be placed on each side of all other
openings.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -18/12
(From Prof. A. Tefera)
c. If the sum of the spans of the openings is more than 50% but less than 70% of the length of
the wall, two rods must be placed adjacent to all openings and three rods at each end of
the wall.
d. Any wall with openings of more than 70% of its length must have the same vertical
reinforcing as in c above, but fine cracks will develop when movement takes place.
The vertical steel should start just below the main steel in the bottom of the walls. To give the vertical
steel good end anchorage to assist the bond, it must be firmly held at the ends against the brickwork.
The best way of achieving this is by threading the rods for a length of 2cm at the bottom and Scm at
the top, and using nuts to hold 5 x 5 x Yz em steel plate washers against the brickwork. When building
in the vertical steel, care must be taken to see that the bottom washer is tight against the bricks laid
on top of it, and that the nut is against the underside of the plate.
When the brickwork is complete to the top of the wall, a portion of the threaded top end will
protrude, and the washer is placed over this, and the top nut is then tightened. Typical wall
reinforcements are given in Figs. 9.7 to 9.9.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -19/12
(From Prof. A. Tefera)
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -20/12
(From Prof. A. Tefera)
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -21/12
(From Prof. A. Tefera)
ix) Design Details
Besides the provision of open joints and incorporation of steel, there are many other details of special
nature which have to be correctly executed.
a. Damage to the floors can be avoided by suspending them from the foundation walls.
b. Special attention must be given to the edges of the ceilings by not attaching them to the
wall.
c. Damp proofing of the walls below floor level is essential. The method of damp proofing, as
it forms a plane of weakness, is equally important. It would be sufficient to use a layer of
asphalt-impregnated felt sheeting. However, the sheeting should be stepped up and down
at about one meter interval as shown in the illustrative example (Fig. 9.7).
d. The outside steps must not be built against the brickwork but must have a layer of soft-
board built in between the steps and the brickwork.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -22/12
(From Prof. A. Tefera)
e. Water piping coming out of the ground and through an external wall must be cranked so
that it will have only a slight anchoring effect before being deformed.
f. It is extremely important that earthenware sewer pipes be jointed with bitumen and not
cement mortar, so as to render them slightly flexible. Asbestos pipes with flexible rubber
joints should be used for the sewers. Experience has shown that glazed stoneware pipes
fail at almost every joint with seasonal movements of the
ground, resulting in serious leakages which greatly increase the ground movement.
g. To prevent rain soaking into the ground near the house, impervious channels should be
provided to lead the water from the down pipes and to discharge it well away from the
building, into a storm-water drain if available.
Since reinforced brickwork is unknown in Ethiopia, brick layers, foremen and other supervisors are
unfamiliar with the techniques required when including reinforcement in brickwork. Further, the
importance of correctly placing the steel and attending to small details may not be fully appreciated.
It is stressed that when using this method all joints in the brickwork must be carefully filled.
Faults, repeatedly noticed on various housing projects carried out in other parts of the world, which
would have been eliminated with a full appreciation of what is required, were inaccurate placing of
steel bar
a. the vertical steel starting at wrong levels
b. the vertical steel not being of the correct length
c. the mortar not being well worked around the vertical steel
d. the vertical joints in the brickwork not being properly built
e. the clear gaps not being kept free of mortar
f. the clear gaps not being thoroughly cleaned after plastering the walls containing them
g. the plumbers and electricians placing pipes and conduit in a clear gap to save cutting
the separate chases in the brickwork.
It is also important that the mortar used should be of good quality. It is recommended that no lime be
used in any mortar for reinforced brickwork. A suitable mortar is one part cement to four parts of
clean sand.
Corrosion of the steel reinforcing is a very important factor in reinforced brickwork, and must always
be considered before adopting this type of construction.
Pile foundations provide a suitable solution for a variety of structures located on heaving soils. They
may prove economical in areas where considerable heave is to be expected, and the additional cost
can be balanced against the saving in future maintenance. In the category of pile foundations, one of
the following may be used:
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -23/12
(From Prof. A. Tefera)
b. Belled or single under-reamed piles for foundations of light structures in deep layers of
expansive soils
c. Double under-reamed piles for foundations of heavier structures in deep layers of expansive
soils.
The piles should be placed well below the active zone where the seasonal fluctuation of the moisture
content is minimum. Depending upon the depth at which the moisture content is constant, one opts
for one of the above three methods (Fig. 9.10).
In the design of the pile foundation in expansive soils, two factors should be considered. These are
(i) the ultimate bearing capacity
(ii) the tensile stress developed along the shaft as result of heaving.
The ultimate bearing capacity may be determined by using Eq. (8.70). In calculating the skin friction
component, the friction over the first two meters' length of piles at the top should be neglected since
over this length, generally, major shrinkage cracks exist.
For the straight bored piles, if the combined effect of the weight of the dead load and the skin friction
does not balance the uplift force due to swelling, the whole pile may be lifted and cause structural
damage to the building. One may estimate the total uplifting force from the following relations (Fig.
9.1 a)
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -24/12
(From Prof. A. Tefera)
where
D diameter of pile
u swelling pressure
h depth of pile in the active zone
J coefficient of uplift between concrete and soil
U total uplift force.
)
According to Chen [4], the value of J may be taken as 0.15, and the value of the swelling pressure
acting on the pier for soils with high degree of expansion is about 490 kN/m2, and for soils with
medium degree of expansion is about 245 kN/m2.
The critical factor which should be considered is the tension force produced within the pile as the
result of the swelling pressure. This force becomes more critical on belled or under-reamed piles
located in deep layers of expansive soils.
The principle underlying the use of under-reamed pile foundations for structures erected on
expansive soils is one of anchoring the building down, at that depth where changes in the moisture
content and the subsequent volumetric expansion of the soil will be negligible. The bottoms of the
piles are belled out with special under-reaming tools, and it is this under-reamed section which
provides the anchorage for the pile.
In order to understand the mechanics of the development of tensile stresses in the piles, it is
adequate to discuss the simple theory of Collins [5].
Consider an under-reamed pile of circular cross-section anchored to the bottom of an expanding layer
of soil as shown in Fig. 9.11.
Due to the skin friction between the soil and pile, tensile forces should be expected to be produced.
Considering elemental strip as shown, the small increment of tension will be
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -25/12
(From Prof. A. Tefera)
where
F = frictional force per unit area between pile and soil at the depth h
Ah = elemental strip at depth below the expanding soil
D = pile diameter.
Total tension at depth h:
The surface of a drilled cast in-situ pile is rough; hence one can assume an intimate contact between
soil and pile. It is reasonable therefore to assume that the frictional force occurring between the soil
and the pile at any point is equal to the shear strength of the soil in a vertical direction at that point.
When a certain amount of movement has been developed it could mobilize the whole of the shear
strength which is given by Coulomb's equation:
where
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -26/12
(From Prof. A. Tefera)
inter granular pressure acting normal to the surface of sliding
cohesion
angle of internal friction.
Ignoring corrections for pore water pressure and identifying k as the ratio between inter granular
pressures on the horizontal and vertical plane, i.e.,
Then,
Henc
eeee
For a uniform diameter pile, it can be assumed that the friction on the surface of the pile can be
considered as equal to the shear strength of the soil in a vertical direction, i.e., F = S.
Hence
At the bottom of the pile, T equals zero. Hence there must be a transition zone near
the under-
reamed section and the tension variation along the pile is as indicated in Fig. 9.11c.
or
The effect of P is to shift the zero line of the force diagram by an amount P. The above
equation holds good for all points between the surface of the soil and the top of the
under-ream, and the unknowns in the expression are k, c, andy. The values of c, ¢, and y
can be obtained from laboratory tests on undisturbed samples. It should be pointed out
that the type of test carried out will have an influence on the value of c and ¢ for the
same soil.
The two types of tests that are usually carried out for determining the soil parameters
are unconsolidated drained or consolidated drained triaxial tests. In tests conducted in
South Africa, actual cracks in test piles occurred at depths which conform to the
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -27/12
(From Prof. A. Tefera)
conditions k = 1, and with shear characteristics as found in the consolidated drained
triaxial tests.
Once the probable curve for the tensile forces in piles has been obtained, it can be
extended to greater depths.
Using the soil parameters for the k condition adopted, and repeating the calculations for
a range of pile diameter, a chart can be compiled [13].
From the chart, values of T + P can be read off for any pile with dimensions within normal
limits. Thus if the diameter and the load of the pile are known, the required amount of
tensile steel at any depth can be determined.
For the safe anchorage power of the under-ream, Collins [5] suggests the values given in
Table 9.3. The values have been compiled with a factor of safety of 2 for a 25cm diameter
pile. For piles other than 25cm in diameter, values may be obtained by assuming that,
other factors being equal, the anchorage power varies as the square of the diameter.
Table 9.3: Safe anchoring power of under-ream on 25cm diameter pile in kN[5]
a. There should be a clear space of at least 50cm under all grade beams, and this space must
remain clear throughout the life of the building. If the soil in between the piles rises, and if
the space becomes completely closed, the soil will press upwards against the beam and
might cause damage to the building.
b. Attention must be paid to drains and water pipes so that considerable movement can take
place without rupture of the pipes.
c. External constructions in contact with the soil must be completely free of the building.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -28/12
(From Prof. A. Tefera)
Exercise Problems
1. Design a footing foundation for the following soil profile. (Depth of foundation, Proportioning
of area, total reinforcement required)
Soil data:
all (kPa) Uplift pressure, Unit weight,
U (kPa) (kN/m3)
Layer 1 145 100 15.4
Layer 2 195 165 16.7
Layer 3 270 200 17.8
Loading:
PGK=600 kN, PQK=150 kN
RC data: C-25, S-300
Column Date: Reinf. 416, 40 cm x 25 cm
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -29/12
(From Prof. A. Tefera)
2. For the soil profile shown below, design a pile foundation which is to be placed at a level of -
7.5 m.
Layers 1 and 2 are the same soil types. But layer 1 is the active zone.
Data: qu = 150 kPa, end bearing capacity at a depth of 7.5 m is 560 kPa, swelling pressure, U = 165
kPa, the negative skin friction f’ = 25 kPa, of pile is 30 cm. Adopt a factor of safety of 2. (Determine
capacity of a single pile, check for uplift, check the tension condition in the pile,…)
Determine the allowable loads for the double under-reamed pile foundation shown below
penetrating the soil profile indicated.
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -30/12
(From Prof. A. Tefera)
Lecture Notes on Foundations on Expansive Soils by Dr. Tensay Gebremedhin, EiT-M, MU Page -31/12
(From Prof. A. Tefera)