Sei sulla pagina 1di 2

APPLICATION NOTE

Introduction to low voltage networks and the difficulties of fault location

Fault occurrences in medium voltage networks are usually covered by redundancy in the system which,
with appropriate switching, usually ensures a relatively uninterrupted continuation of the supply for the
customer. A lengthy wait until the fault can be corrected only results in the increased risk of a second
failure in this area, creating a customer outage that cannot be restored by switching.

In low voltage networks, which usually have no redundant feed, the time interval until the customer can be
reconnected to the power system greatly depends on the speed in locating the fault. Longer outage
periods due to a more remote location of the fault in the system create outage problems for the utility.

However, a low voltage installation also has advantages. The distances are relatively short and easily
manageable. In many cases, the joint position can also be very clearly delineated based on the known
positions of the private connections. Since 80-90% of cable faults occur in joints, anticipatory localisation
of the fault is possible.

Type and behaviour of cables in the low voltage network

Transient Irregular, short-term voltage drops without fuse triggering

Intermittent Irregular triggering of fuses at longer intervals

Ongoing Repeated triggering of fuses at shorter intervals

Permanent Interruptions of power and damaging short circuit currents

Many LV cable faults change over time from transient to permanent (“flickering lights” are possible signs
of a transient fault). In addition, LV cable faults are often unstable / non-linear and can therefore only be
located when the cable is conducting live voltage. Only when a fault has become permanent can it be
located using conventional techniques with the cable in a voltage-free state.

All unstable LV cable faults require a change in their fault state in order to be located. The only way of
doing this – with consumers connected – is to reconnect the mains voltage.

If the time period between re-energising and the permanent fault occurring is long, the more efficient and
easier method is to re-energising the cable via a mains fuse. If the intervals are shorter and where there is
sufficient space, automatic reconnection devices such as PowerFuse can be used to maintain the mains
supply and effect a change in the fault state to permanent.

The technical problem of fault location in branched networks

Since, in order to locate high-resistance cable faults, DC and surge pulse voltages in excess of
operational voltage must be used, the private connection fuses, including the earth connection, must be
removed. The problem of access to the service box arises, which is not always a given or available to the
utility.

Megger,
Megger, Valley Forge,
Forge, USA
USA us.megger.com

+1 610 676 8500 Intro to fault location in low voltage networks

P1
APPLICATION NOTE

Introduction to low voltage networks and the difficulties of fault location

A real problem in prelocating faults on cables with many T-branches arises from the pronounced
attenuation of the reflection measurement signals and the complexity of the reflectogram due to the
changes in impedance on the joints and branches.

Often, faults arising after the third or fourth T-joint are no longer recognisable due to these effects. Even
more difficult is the situation where faults are in branch joints, since these create a strong self-generated
reflection themselves. Even the tried and tested arc reflection method (ARM®) is equally affected by
these limitations.

In view of this, even experienced technicians today must often locate the fault by measuring various end
points of the branched cable. In certain cases, the cable is actually cut in order to limit the length of cable
system under test.

Megger,
Megger, Valley Forge,
Forge, USA
USA us.megger.com

+1 610 676 8500 Intro to fault location in low voltage networks

P2

Potrebbero piacerti anche