Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Application of Standards
Rao S. Thallam
Fellow, IEEE
Salt River Project
Phoenix, AZ, USA
Presented at:
National Workshop on Electric Power Quality
Nov 10, 2004
Indian Institute of Technology, Kanpur
Kanpur, UP, India
• Introduction
• THD and TDD
• Displacement and True Power Factor
• K-Factor and Transformer Derating
• When should you be concerned?
• Application of IEEE 519 Standard
• Harmonics Measurements
• Industrial Customers
• Commercial Customers
• IEC Standards
• Conclusions
1
"This alternating current thing
is just a fad. It is much too
dangerous for general use"
Thomas Alva Edison
I(t)
Nonlinear Resistor
V(t) V
2
Decomposition into Harmonic
Components
60 Hz
(h = 1)
+ 180 Hz
(h = 3)
+
300 Hz
(h = 5)
+
420 Hz
(h = 7)
+ 540 Hz
(h = 9)
+
660 Hz
(h = 11)
+ 780 Hz
(h = 13)
+
·
·
·
Pure
Sinusoid Distorted Load
Current
3
Why bother about Harmonics?
4
Total Harmonic Distortion
2
h = ∞ Vh
THD = x 100 .
h = 2 V2
1
h=∞ I2h
THD = x100
h= 2 I 2
1
5
Total Demand Distortion Factor
(TDD)
6
Power and Power Factor
When significant distortion is present
PF = Cos θ
“Displacement
Power Factor”
7
True Power Factor
P
PF =
S
Engineering Speak
Translation:
We are guessing.
8
Engineering Speak
“We are making modifications to
address minor difficulties”
Translation:
We are starting over.
Engineering Speak
“Test results are gratifying”
Translation:
It worked and boy are we surprised!
9
Engineering Speak
“We are trying some new
approaches”
Translation:
We threw some new guys on it.
K-Factor
K-Factor is ratio of eddy current losses
due to distorted current compared to the
losses for the same rms fundamental
frequency current
Example:
Eddy Current Losses with 100 A rms with harmonics =
270 Watts
Eddy Current Losses with 100 A rms 60 Hz sine wave =
27 Watts
K - Factor = 270/27 = 10
10
K-Factor
h=∞
K = Ih (pu)2 h2
h =1
K-Factor
Assumes eddy current losses are
proportional to f 2 - OK for small
conductor sizes and low harmonics
At higher frequencies, eddy current loses
are proportional to f
Transition frequency depends on winding
configuration, material
Al - 2200 Hz, Cu - 700 Hz
K-factor over estimates harmonics effect
at higher frequencies
11
THD and K-Factor
(Example Calculation)
Harmonics for 3-ph PWM type ASD
Fund. = 100 A rms
5th : 60 A rms = 0.6 pu
7th : 40 A rms = 0.4 pu
11th : 30 A rms = 0.3 pu
13th : 20 A rms = 0.2 pu
THD = Sqrt (0.62 + 0.42 + 0.32 +0.22)* 100 = 81 %
K = 12 + 0.62 * 52 + 0.42 * 72 + 0.32 *112+0.22*132
= 1 + 9 + 7.84 + 10.89 + 6.76 = 35.49
Transformer Derating
12
K-rating
K-rated transformers can handle non-
sinusoidal load current up to the full load
rating with k-factor up to the k-rating of
the transformer
K-rated transformers are designed to
have lower eddy current losses
Current Weighting
Type of Load Typical Waveform Distortion Factor (Wi)
1.0
Sources of Harmonics
0.5
0.0
-1.0
0 10 20 30 40
Time (mS)
1.0
0.0
loads
-0.5
-1.0
0 10 20 30 40
Time (mS)
1.0
0.0
no series inductance
-0.5
-1.0
0 10 20 30 40
Time (mS)
1.0
0.0
-1.0
0 10 20 30 40
Time (mS)
1.0
0.0
-1.0
0 10 20 30 40
Time (mS)
1.0
0.5
0.0
-0.5
-1.0
0 10 20 30 40
Time (mS)
1.0
0.0
Regulator
-0.5
-1.0
0 10 20 30 40
Time (mS)
13
Example 1 - dc drive
14
Example 3 - PWM drive with choke
15
Example 5 - electronic ballast
Line Current for Electronic Ballast
1.00
Max: 0.784
Current (Amps)
0.75 Min: -0.792
0.50
Avg: 0.305828
Abs: 0.792
0.25 RMS: 0.334094
CF : 2.37059
0.00 FF : 1.09242
-0.25
-0.50
-0.75
-1.00
0 10 20 30 40 50
Time (mS)
Line to Neutral Voltage for Electronic Ballast
200
Max: 170
150 Min: -170
Voltage (V)
100
Avg: 109.055
Abs: 170
50 RMS: 120.727
CF : 1.40814
0 FF : 1.10703
-50
-100
-150
-200
0 10 20 30 40 50
Time (mS)
16
Harmonic Standards
Several Countries have developed
Standards to limit harmonics
IEEE 519-1992
IEEE 519A-2004?
IEC 61000-3-2, 61000-3-4, 61000-3-12
IEEE 519
IEEE 519 “Recommended Practices and
Requirements for Harmonic Control in
Electric Power Systems”
Specifies load current harmonic limits
at PCC
Specifies supply voltage harmonic
limits at PCC
IEEE 519A “Guide for Applying
Harmonic Limits on Power Systems”
17
IEEE 519 Standard Limits
HARMONICCURRENT DISTORTIONLIMITS IN%OF IL
V< 69 kV
ISC/ IL h < 11 11 < h < 17 17 < h < 23 23 < h < 35 35 < h TDD
<20 4.0 2.0 1.5 0.6 0.3 5.0
20-50 7.0 3.5 2.5 1.0 0.5 8.0
50-100 10.0 4.5 4.0 1.5 0.7 12.0
100-1000 12.0 5.5 5.0 2.0 1.0 15.0
>1000 15.0 7.0 6.0 2.5 1.4 20.0
Application Concerns
• Selecting PCC
• Calculating ISC and IL
• What is TDD ?
• Measurement Problems
• Time Varying Harmonics
• General Procedure for Applying Harmonic
Limits
• Cost of Problems vs. Cost of Solutions
• Distributed Generation Limits
18
What is PCC ?
19
IEEE 519 Standard Limits
(Utility)
HARMONIC VOLTAGE DISTORTION LIMITS
(in % of Nominal Fundamental Frequency Voltage)
20
IEEE 519 Standard
Limits apply for the “worst case” for
normal operation (lasting longer than one
hour)
For shorter periods, during start-ups limits
may be exceeded by 50%
Even harmonics are limited to 25% of odd
harmonic limits
Co-gen - use Isc / IL < 20, irrespective of
actual value
21
Presentation of Results –
snap shots
Presentation of Results –
Time Trends
22
Harmonic Voltage Measurements
• Measure at PCC
• Low Voltage – measure with direct
connection
• Higher Voltages – Connect with PT –
frequency response is good to 3 k Hz (50th
harmonic)
• Avoid CCVTs – frequency response is not
good
Evaluation Procedure
SDw = ( SDi × Wi )
i
23
Current W eighting
Type of Load Typical W aveform D istortion Factor (W i )
1.0
Current
0.0
-0.5
-1.0
0 10 20 30 40
Time (mS)
1.0
0.5
high 2nd,3rd,
Semiconverter 4th at partial 2.5
Current
0.0
-0.5 loads
-1.0
0 10 20 30 40
Time (mS)
1.0
Current
0.0
-1.0
0 10 20 30 40
Time (mS)
1.0
Current
0.0
or dc drive
-1.0
0 10 20 30 40
Time (mS)
1.0
Current
0.0
-1.0
0 10 20 30 40
Time (mS)
1.0
0.5
Current
0.0
-0.5
-1.0
0 10 20 30 40
Time (mS)
1.0
ac V oltage 0.5
varies w ith
Regulator firing angle 0.7
Current
0.0
-0.5
-1.0
0 10 20 30 40
Time (mS)
Fluorescent
Lighting 17% 0.5
Evaluation Procedure
• If SDw / Ssc < 0.1%, then automatic
acceptance
• SDw is weighted disturbing power
• Ssc is short circuit capacity at PCC
• If customer has or considering PF
Correction Capacitors, harmonic
evaluation is always necessary
24
UTILITY CUSTOMER
Choose PCC
Is Power Factor
Yes Correction Existing or
Planned?
No
Stage 2:
Does facility No
meet harmonic
limits?
Verification Measurements
and Calculations
(if necessary)
25
Applying Harmonic Limits For
Industrial Facilities
1. Choose PCC
2. Characterize Harmonic Loads
3. Determine if PF Correction Needed
4. Calculate Expected Current Harmonics
at PCC
5. Design Harmonic Control Equipment, if
necessary
6. Verify performance with measurements
26
Applying Harmonic Limits For
Commercial Customers
27
Voltage Distortion Limits
(% of nominal fundamental frequency
voltage)
Individual Harmonic Total Voltage
Bus Voltage at PCC (Vn) Voltage Distortion (%) Distortion - THDVn (%)
Vn ≤ 69 kV 3.0 5.0
28
Time-Varying Harmonics
29
Time Varying Harmonics –
Total Duration Limits
Total Duration of Total Duration of Acceptable
Harmonic Bursts (Ttotal) Harmonic Bursts harmonic distortion
(Ttotal in %) level
Ttotal ≤ 15 min. Ttotal ≤ 1% 3.0 ×(design limits)
30
Time Varying Harmonics
(24 hour period)
Total Duration of Maximum Acceptable
Harmonic Bursts Duration of a Harmonic
Single Harmonic Distortion Level
Burst
<15 minutes < 15 seconds 3.0 x design limit
>15 minutes and >15 sec and < 30 2.0 x design limit
< 1.2 hours minutes and
Measurements
• Define measurement specification
– Many commercial meters exist
• 8, 12, and 16 cycle windows
• 128 and 256 samples/cycle
• Filtering
– IEC 61000-4-30 offers potential
• Specific requirements
• Captures 3s, 10m, and 2hr values
31
IEC Standards
Apply at equipment level, 240 V or less, 1-ph,
690 V or less, 3-ph, 50 or 60 Hz
61000-3-2: loads with input current < 16 A
61000-3-12: loads with input current >16A and
<75A (published in 2004)
61000-3-4: loads with input current > 75 A
Use varies from country to country, mandatory
in EC
UL certification available in US
IEC 61000-3-2
Class A - General Purpose loads, 3-ph
balanced equipment (plus any eqpt not in
B,C,D)
Class B - Portable tools
Class C - Lighting equipment
Class D - Equipment with “special wave
shape” (conduction angle < 600), P < 600W
32
Class A (Balanced 3-ph Equipment)
Harmonic Max. Permissible Harmonic
Order Current (Amps)
3 2.3
5 1.14
7 0.77
9 0.4
11 0.33
13 0.21
15-39 0.15 x 15/n
2 1.08
4 0.43
6 0.30
8-40 0.23 x 8/n
33
Class C Equipment (Lighting >25W)
2 2
3 30 x PF
5 10
7 7
9 5
11-39 3
(odd harmonics only)
3 3.4 2.30
5 1.9 1.14
7 1.0 0.77
9 0.5 0.40
11 0.35 0.33
13-39 3.85/n 0.15 x 15/n
(odd harmonics only)
34
! "# $
IEC 61000-3-4
35
IEC Standards
IEC Standards are based on European
distribution system
3 ph, 3-wire feeder, and 3-ph, 3-wire
branches, 11 or 12 kV
3-ph (delta-star), large (500 kVA - 1000
kVA) distribution transformers
400/230V, 3-ph long secondary
USNC - IEC standards in US
36
Comparison of European and North
American Systems
European North American
Feeder 3-ph, 3-wire 3-ph, 4-wire
Branch 3-ph, 3-wire 1-ph, 2-wire
Transformer 500 kVA-1MVA 50 kVA-100kVA
Connection Y/∇ Gr Y / Gr Y
Secondary 400/230V, 3-ph 120/240V, 1-ph
Length Long short
37