Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
UNIT-II
VOLTAGE AND REACTIVE POWER CONTROL
(2.3)
5
Fig. 2.2 Phasor diagram for system in Fig. 2.1.
o From the fig 2.2, it is clear that the load voltage V2 is not affected much
due to the real component of the load P as it is normal to the vector V1
whereas the drop due to reactive component of load is directly
subtracted from the voltage V1.
o Assuming the voltage drop due to real power negligible, the voltage
drop is directly proportional to the reactive power Q. The relation is
given by
(2.4)
o In order to keep the receiving end voltage V2 fixed for a particular
sending end voltage V1, the drop (Q/V1)X must remain constant. Since,
in this the only variable quantity is Q, it is this reactive vars which must
be locally adjusted to keep this quantity fixed
¢ Overhead lines
at loads below natural or surge impedance load (SIL), produce Q
at loads above SIL, absorb Q
¢ Underground cables
have high SIL due to high capacitance 10
always loaded below SIL, and hence generate Q
¢ Transformers
Absorb Q due to shunt magnetizing reactance and series
leakage inductance
¢ Loads
A typical "load bus" is composed of a large number of
devices
Composite characteristics are normally such that a load
bus absorbs Q
Industrial loads usually have shunt capacitors to improve
power factor
12
(2.5)
¢ Zn is called the natural impedance of the line and the loading
condition in which the VARs absorbed are equal to the vars
generated by the line is called the surge impedance loading
(SIL) and it is here where the voltage throughout the length of
the line is same i.e. if the transmission line is terminated by a
load corresponding to its surge impedance the voltage at the
load is constant.
o In case I 2ωL > V 2ωC the voltage will sag
and if I 2ωL < V 2ωC (light load condition)
the voltage will rise (see Fig. 2.3).
o Normally the loading is greater than SIL
and, therefore, the condition I 2ωL > V 2ωC
exists and the net effect of the line will be
to absorb (sink) the reactive VARs.
o Under light load conditions the effect of shunt
Fig. 2.3: Variation of
capacitors is predominating and the line will voltage as a function
work as VARs generator (source). of distance of line. 13
TRANSFORMERS
¢ The equivalent circuit of a transformer for power frequency is
given in Fig. 2.4.
16
SYNCHRONOUS MACHINES
17
Case 1: If E cos δ > |V|
¢ then Q > 0 and the generator produces reactive power i.e., it
acts as a capacitor.
¢ This inequality is generally satisfied when the generator is
over excited. Since cos δ = cos (– δ) the inequality is true for
both as when machine is working as a generator or as a
motor.
¢ Therefore, it can be said that an over-excited synchronous
machine produces reactive power and acts as a shunt
capacitor.
18
o This characteristic of the
machine i.e. it draws
leading or lagging current
depending upon the
excitation is nicely shown
as a V curve in Fig. 2.5.
Fig. 2.5 V-curves of synchronous
machine.
¢ When the machine is used over-excited it is known as
synchronous capacitor and the special feature of the
machine is that then it is run under no load condition;
thereby δ = 0 in the inequality and |E| > |V| i.e., Q
can be continuously and simply controlled by
controlling |E| i.e., by varying the d.c. excitation.
¢ In case the inequality is satisfied both ways during
the operation of the machine, it is then known as 19
synchronous phase modifier.
¢ A synchronous phase modifier has a smaller shaft and
bearing and higher speeds as compared to a
synchronous motor used for mechanical loads.
¢ A synchronous phase modifier has a higher overall
efficiency as compared with a synchronous motor.
¢ Standard machines are designed for full load output
at leading power factor and can carry about 50% of
their rated capacity when the p.f. is lagging.
¢ A machine designed to operate at full load for lagging
p.f. is physically larger, is more expensive and has
greater losses.
20
SHUNT REACTORS
¢ The shunt reactors are used across capacitive loads or lightly
loaded lines to absorb some of the leading vars to control the
voltage across the load to within certain desirable limits.
¢ Shunt compensation with reactors:
increases effective ZC
reduces the effective natural load , i.e., voltage at which flat
voltage profile is achieved
¢ Line reactors assist in limiting switching surges
¢ In very long lines, at least some reactors are required to be
connected to lines
¢ Usually required for EHV lines longer than 200 km.
¢ Similar in construction to transformers, but have a single
winding (per phase) on an iron core with air-gaps and
immersed in oil.
21
¢ Either single-phase or three-phase construction
SHUNT REACTORS CONNECTIONS
¢ They are connected either:
directly to the lines at the ends, or
to transformer tertiary windings; conveniently switched
as var requirements vary
Fig. Line and Bus connected EHV Fig. Line and Transformer 22
reactors connected reactors
SHUNT CAPACITORS
¢ The shunt capacitors are used across an inductive load so as to
supply part of the reactive VARs required by the load so that the
reactive VARs transmitted over the line are reduced, thereby the
voltage across the load is maintained within certain desirable limits.
¢ Used in transmission systems to compensate for I 2X losses
¢ Connected either directly to H.V. bus or to tertiary winding of
transformers
¢ Usually switched: a convenient means of controlling voltage
¢ Shunt capacitor compensation of transmission lines decreases ZC
and increases θ, i.e., electrical length
¢ Advantages: low cost and flexibility of installation and
operating.
¢ Disadvantages: Q output is proportional to square of the
voltage; hence Q output reduced at low voltage
¢ Application: Shunt capacitors are used extensively in
distribution systems for power factor correction and feeder 23
voltage control
SHUNT CAPACITOR CONNECTIONS
(2.11)
29
COMPARISON BETWEEN SYNCHRONOUS
AND STATIC CAPACITORS
¢ A great advantage of the synchronous capacitor is its flexibility for
use for all load conditions because it supplies VARs when over-
excited, i.e. during peak load conditions and it consumes vars when
under-excited during light load conditions.
¢ There is smooth variation of reactive VARs by synchronous
capacitors as compared with step by step variation by the static
capacitors.
¢ Synchronous machines can be overloaded for short periods whereas
static capacitors cannot.
¢ For large outputs the synchronous capacitors are much better than
the static capacitors from economic viewpoint because otherwise a
combination of shunt capacitors and reactors is required which
becomes costlier and also the control is not smooth as is achieved
with synchronous capacitors.
¢ The main disadvantage of the synchronous capacitor is the
possibility of its falling out of step which will thus produce a large
sudden change in voltage. Also these machines add to the short 30
circuit capacity of the system during fault condition.
STATIC VAR COMPENSATORS (SVC)
¢ Shunt connected static VAR generators and/or absorbers whose
outputs are varied so as to control specific power system
quantities
¢ The term static is used to denote that there are no moving or
rotating components
¢ Basic types of SVCs:
Thyristor-controlled reactor
Thyristor-switched capacitor
Saturated reactor
¢ A static VAR system (SVS) is an aggregation of SVCs and
mechanically switched capacitors or reactors whose outputs are
coordinated
¢ When operating at its capacitive limit, an SVC behaves like a31
simple capacitor
SVC (CONT’D)
32
Fig: Composite characteristics of an SVS
SVC (CONT’D)
33
SVC (CONT’D)
35
Fig: SVS steady-state characteristics
COMPARATIVE SUMMARY OF ALTERNATIVE
FORMS OF COMPENSATION
¢ Switched shunt capacitor compensation generally provides the
most economical reactive power source for voltage control
ideally suited for compensation transmission lines if reduction
of ZC, rather than reduction of line length θ is the primary
consideration
however, heavy use of shunt capacitor compensation could
result in poor voltage regulation and may have an adverse
effect on system stability
37
TAP CHANGING TRANSFORMERS
¢ The main job of a transformer is to transform electric energy
from one voltage level to another.
¢ Almost all power transformers on transmission lines are
provided with taps for ratio control i.e., control of secondary
voltage.
¢ There are two types of tap changing transformers:
(i) Off-load tap changing transformers.
(ii) On-load (under-load) tap changing transformers.
¢ The tap changing transformers do not control the voltage by
regulating the flow of reactive vars but by changing the
transformation ratio, the voltage in the secondary circuit is
varied and voltage control is obtained. This method is the
most popular as it can be used for controlling voltages at all
levels.
38
TAP-CHANGING TRANSFORMERS
¢ Transformer with tap-changing facilities constitute an important
means of controlling voltages throughout the power system
Fig. 2.7 Off-load tap changing transformer. Fig. 2.8 On-load tap changing transformer.
o Thus six operations are required for one change in tap position.
o The voltage change between taps is often 1.25 per cent of the nominal
voltage where nominal voltages are the voltages at the ends of the
transmission line and the actual voltages are tsV1 and trV2 where ts and tr
are the fractions of the nominal transformation ratios, i.e., the tap 42
ratio/nominal ratio.
OPERATION OF A TRANSMISSION LINE WITH TAP
CHANGING TRANSFORMERS
¢ Consider the operation of a radial transmission line with
tap changing transformers at both the ends as shown in
Fig. 2.9.
¢ It is desired to find out the tap changing ratios required to
completely compensate for the voltage drop in the line.
¢ We assume here that the product of ts and tr is unity as this
ensures that the overall voltage level remains of the same
order and that the minimum range of taps on both
transformers is used.
43
Fig. 2.9 Radial transmission line with on-load tap changing transformer at
both the ends.
OPERATION OF A TRANSMISSION LINE WITH
TAP CHANGING TRANSFORMERS (CONT’D)
From Fig. 2.9, we have
(2.12)
(2.14)
44
OPERATION OF A TRANSMISSION LINE WITH TAP
CHANGING TRANSFORMERS (CONT’D)
(2.15)
(2.16)
(2.17)
(2.18)
o From the equation (2.18), for particular values of V2 and V1 and the
load requirements P and Q, the value of ts can be obtained.
47
Fig. 2.10 Booster transformer along with regulating transformer.
ADVANTAGES AND DISADVANTAGES OF BOOSTER
TRANSFORMER
¢ ADVANTAGES:
1.The transformer can be used at any intermediate point in the
system.
2.When it is used along with a fixed ratio transformer it can be
taken out for inspection or overhaul without affecting much the
system.
3.The rating of the booster is the product of the current and the
injected voltage and is hence only about 10% of that of a main
transformer.
¢ DISADVANTAGES
1.The two are more expensive than a transformer with on-load
tap changing gear.
2.They are less efficient due to the losses in the booster.
3.They take more floor space.
¢ APPLICATION 48
49
Fig. E.2.1
SOLUTION TO EXAMPLE 2.1
Solution:
Nominal voltages are assumed and voltage drops in the circuits are
neglected.
To find out the total power active and reactive we add up all the
active powers connected to the system and reactive power
connected to the system plus the reactive power losses in the lines
and the transformers.
Taking voltage as 1.0 p.u. everywhere,
Power at bus A = Active power 0.5 p.u. and reactive power 0.375 p.u.
The total reactance between bus C and A = 0.075 + 0.04 = 0.115 p.u.
50
SOLUTION TO EXAMPLE 2.1 (CONT’D)
Active power tapped at bus C = 1.5 p.u. and reactive power 2.0 p.u.
Total active power between E & C = 0.5 + 1.5 = 2.0 p.u.
Reactive power between E & C = 0.375 + 0.0449 + 2.0 = 2.4199 p.u.
Total reactance between E & C = 0.05 + 0.025 = 0.075 p.u.
Fig. E.2.2 52
SOLUTION TO EXAMPLE 2.2
Solution: It is desired to have Vs = Vr and tstr = 1.0.
The load is 150 MW and 72.65 MVAr
53