Enclosure B174
Battery backup
The Enclosure B174 Outdoor
Battery Backup Cabinet is the
recommended battery
backup solution for outdoor
radio base stations (RBS and
Enclosures) supplying -48 V
DC power in the event if AC
mains failure.

The Enclosure B174 has a


compact footprint with high
battery capacity, up to
-48 V/840 Ah, to support high
power sites with long backup
time. The active cooling
maximizes battery life in any
climate by means of a very
energy efficient design.
The optional integrated
heater ensures sufficient
battery capacity also in cold
climates. The cabinet is
designed to ventilate
hydrogen gas to a safe level
under all conditions. No
ventilation tubes are required.

For installation and


maintenance safety, optional
battery string circuit breakers
are available.
Cable lead-in, via sealed
cable glands, is possible from
both sides and from the
bottom.
 

Technical specification for Enclosure B174


MECHANICAL SPECIFICATION
System weight (excl. batteries): 135 kg (EQ Zone 1 standard version)
235 kg (EQ Zone 4 version)
Battery weight: 210 - 1056 kg depending on configuration
Dimension (W x H x D): 700 x 1850 x 860 mm (overall, including protruding roof)
700 x N/A x 625 mm (base footprint)

ELECTRICAL SPECIFICATION
DC output: -48 VDC / 200 A or 2x200 A with 2’nd BFU option
(Note: 2x200 A requires minimum 2 battery strings/shelves)
Supports one or two (divided capacity) radio base stations - RBS 6000
Battery characteristics: 4 x 48 V / 170 Ah to 210 Ah (AGM standby batteries)
4 x 48 V / 170 Ah to 200 Ah (AGM high cycling batteries)

CLIMATE SYSTEM
Power consumption: 300 W / (Peak, during heating)
235 W / (Peak, during cooling)
<27 W / <48W (Average during cooling @ 25 °C / 35 °C)

ENVIRONMENTAL SPECIFICATION
Temperature range: Normal operation: -33 to +50 °C
Transportation (< 3 months), excl. batteries: -40 to +70 °C
Relative humidity: Normal operation: 15 - 100% at 25 °C
Transportation (< 3 months), excl. batteries: 5 - 100%
Cabinet: Outdoor class IP45, cable connection space: IP55
F-gases: R134a, 255 gr.
Safety approvals: IEC/EN 60 950-1, IEC/EN 62 368-1, and UL 62 368-1, CE, CB, UL, CSA
EMC approvals: CISPR 22/EN 55022, FCC part 15, GR-1089-CORE, ICES-003
Earthquake: IEC 60721-4-3 class 4M5, GR-1089-CORE and ETSI
EN 300 019-1-4 class 4.1 according to IEC 60068-2-57, assuming proper
installation and usage of Enclosure B174 approved batteries and accessories only

SUPERVISION AND CONTROL


Concept: All cooling functionality is supervised and controlled via the Climate Control Unit
(CCU)
Binary Alarm Outputs (to Enclosure B174 cooling system status and door alarms
RBS):
Status information Three visible LEDs on the CCU panel
indicators:

Telefonaktiebolaget LM Ericsson 