Stick (SMAW) Welding
Description
FLYING METAL can injure eyes. BATTERY ACID can BURN SKIN and EYES.
D Wear safety glasses with side shields or face
shield during servicing. D Do not tip battery.
D Be careful not to short metal tools, parts, or D Replace damaged battery.
wires together during testing and servicing. D Flush eyes and skin immediately with water.
TM-499 Page 1
STEAM AND HOT COOLANT can burn. TILTING OR TIPPING can cause injury.
D If possible, check coolant level when engine is D Do not put any body part under unit while lifting.
cold to avoid scalding. D Always use proper equipment (hoists, slings,
D Always check coolant level at overflow tank, if chains, blocks, etc.) of adequate capacity to lift
present on unit, instead of radiator. and support components (stator, rotor, engine,
etc.) as needed during job.
D If the engine is warm, checking is needed, and
there is no overflow tank, follow the next two PINCH POINTS can injure.
statements. D Be careful when working on stator and rotor assemblies.
D Wear safety glasses and gloves and put a rag over radiator cap.
D Turn cap slightly and let pressure escape slowly before completely
removing cap. H.F. RADIATION can cause interference.
MAGNETIC FIELDS can affect pacemakers. D High-frequency (H.F.) can interfere with radio
navigation, safety services, computers, and
D Pacemaker wearers keep away from servicing communications equipment.
areas until consulting your doctor.
D Have only qualified persons familiar with elec-
tronic equipment perform this installation.
D The user is responsible for having a qualified electrician prompt-
FALLING UNIT can cause injury. ly correct any interference problem resulting from the installa-
tion.
D Use equipment of adequate capacity to lift and D If notified by the FCC about interference, stop using the equip-
support unit and components. ment at once.
D Use lifting eye to lift unit only, NOT running D Have the installation regularly checked and maintained.
gear, gas cylinders, or any other accessories.
D Keep high-frequency source doors and panels tightly shut, keep
D Securely attach components to lifting equip-
spark gaps at correct setting, and use grounding and shielding to
ment.
minimize the possibility of interference.
D If using lift forks to move unit, be sure forks are long enough to
extend beyond opposite side of unit.
OVERUSE can cause OVERHEATING.
D Allow cooling period; follow rated duty cycle.
HOT PARTS can cause severe burns. D Reduce current or reduce duty cycle before
D Allow cooling period before servicing. starting to weld again.
D Wear protective gloves and clothing when D Do not block or filter airflow to unit.
working on a hot engine.
D Do not touch hot engine parts bare-handed. READ INSTRUCTIONS.
D Use Testing Booklet (Part No. 150 853) when
SHOCK HAZARD from testing. servicing this unit.
D Stop engine before making or changing meter D Consult the Owner’s Manual for welding safety
lead connections. precautions.
D Use at least one meter lead that has a self- D Use only genuine replacement parts.
retaining spring clip such as an alligator clip. D Reinstall injectors and bleed air from fuel system according to
D Read instructions for test equipment. engine manual.
Engine Choke
Read Operator’s
Manual A Amperes
V Volts
Alternating Current
Positive Negative Output
(AC)
s
Protective Earth
h
Hours Seconds Time
(Ground)
SECTION 3 − SPECIFICATIONS
NOTE This unit uses either a Kohler or a Honda engine. Differences between models are
noted throughout this manual.
Kohler CS12STG
Air-Cooled,
180 A, 25 V, One-Cylinder,
30% Duty Single-Phase, Four-Cycle,
Cycle 6 kVA/kW (Peak) Kohler: 12 HP (360 CC),
40 − 180 A 80
(60 Hz) 130 A, 25 V, (60 Hz) 5.5 kVA/kW 1.8 gal (6.9 L) Tank Gasoline Engine
CC/DC 60% Duty (Continuous) OR
40 − 160 A Cycle 70 50/25 A, Honda: Honda GX390
(50 Hz) (50 Hz) 110/220 V AC, 50 Hz 1.7 gal (6.4 L) Tank Air-Cooled,
100 A, 25 V,
120/240 V AC, 60 Hz One-Cylinder,
100% Duty
Cycle Four-Cycle,
13 HP (390 CC),
Gasoline Engine
TM-499 Page 3
3-2. Dimensions, Weights, And Operating Angles
Dimensions
Height 20-3/4 in (527 mm) D
Width 22-3/4 in (577 mm)
Depth 31-1/4 in (793 mm) Y Do not exceed tilt angles or engine could
B be damaged or unit could tip.
tip
A 31-1/4 in (793 mm)
Y Do not move or operate unit where it
B 10-1/2 in (268 mm) could tip.
C 13-45/64 in (348 mm)
A
D 22-3/4 in (577 mm)
E 1-3/4 in (44 mm) C
60 HZ−WELD
60 HZ−AUX
50 HZ−AUX
50 HZ−WELD
HIGH IDLE
198 575
TM-499 Page 4
3-4. Fuel Consumption (Honda-Powered Units)
802 122
Continuous Welding
100% Duty Cycle at 100 Amperes CC/DC
802 093
TM-499 Page 5
3-6. Generator Power Curves
The generator power curves show
the ac power available in amperes
at the receptacles.
A. 60 Hz Model
250
225
200
175
LOAD VOLTS
150
125
100
75
50
25
0
0 5 10 15 20 25 30 35
LOAD AMPS
B. 50 Hz Model
250
225
200
175
LOAD VOLTS
150
125
100
75
50
25
0
0 5 10 15 20 25 30 35
LOAD AMPS
198 570
TM-499 Page 6
3-7. Volt-Ampere Curves
The volt-ampere curve shows the
minimum and maximum voltage
and amperage output capabilities of
the welding generator. Curves of all
A. 60 Hz Model other settings fall between the
curves shown.
80
70
60
50
LOAD VOLTS
40
MAX
30
MID
20
MIN
10
0
0 25 50 75 100 125 150 175 200 225 250
LOAD AMPS
B. 50 Hz Model
80
70
60
50
LOAD VOLTS
40
30 MAX
MID
20
MIN
10
0
0 25 50 75 100 125 150 175 200 225 250
LOAD AMPS
198 570
TM-499 Page 7
SECTION 4 − INSTALLATION
4-1. Installing Welding Generator
Y Always securely fasten welding
generator onto transport vehicle
or trailer and comply with all DOT
and other applicable codes.
Movement Airflow Clearance
18 in
(460 mm)
18 in 18 in
(460 mm) (460 mm)
18 in 18 in
(460 mm) (460 mm)
Location
OR
install1 10/00*− 802 524-A / Ref. 151 556 / 158 936-A / S-0854
2 2
TM-499 Page 8
4-3. Grounding Generator When Supplying Building Systems
1 Equipment Grounding
1 2 Terminal
GND/PE
2 Grounding Cable
Use #10 AWG or larger insulated
copper wire.
3 Ground Device
Y Ground generator to sys-
tem earth ground if supply-
Use ground device as ing power to a premises
stated in electrical codes. (home, shop, farm) wiring
system.
2 3
800 576-B
802 511-A
TM-499 Page 9
4-5. Engine Prestart Checks (Honda-Powered Units)
Check all fluids daily. Engine must
be cold and on a level surface. Unit
is shipped with 10W30 engine oil.
Engine stops if oil level gets too low.
1/2 in
(13 mm) Full . Follow run-in procedure in en-
gine manual.
1 Fuel Valve
Open valve.
Gasoline
. Close fuel valve before moving
unit or carburetor may flood
and make starting difficult.
Fuel
Add fresh fuel before starting
engine the first time (see mainte-
nance label for specifications). Fill
fuel tank up to 1/2 in. (13 mm) from
top to allow room for expansion.
Check fuel level on a cold engine
before use each day.
Oil
After fueling, check oil with unit on
level surface. If oil is not up to full
mark on dipstick, add oil (see main-
tenance label).
1 . To improve cold weather
starting:
Open Keep battery in good condition.
Store battery in warm area.
802 094-A
+ −
Tools Needed:
3/8, 1/2 in
802 524 / Ref. S-0756-D
TM-499 Page 10
4-7. Connecting To Weld Output Terminals
1 Positive (+) Weld Output
Terminal
2 Negative (−) Weld Output
Terminal
For Direct Current Electrode Posi-
tive (DCEP), connect work cable to
Negative (−) terminal and electrode
holder to Positive (+) terminal.
For Direct Current Electrode nega-
tive (DCEN), reverse cable con-
nections.
1 2
Tools Needed:
3/4 in
196 914 / 495 178
Weld Output
Terminals
Y Stop engine before 10 − 60% 60 − 100%
connecting to weld out- Welding
Duty Duty 10 − 100% Duty Cycle
put terminals. Amperes
Cycle Cycle
Y Do not use worn, dam-
aged, undersized, or
poorly spliced cables.
100 4 (20) 4 (20) 4 (20) 3 (30) 2 (35) 1 (50) 1/0 (60) 1/0 (60)
150 3 (30) 3 (30) 2 (35) 1 (50) 1/0 (60) 2/0 (70) 3/0 (95) 3/0 (95)
200 3 (30) 2 (35) 1 (50) 1/0 (60) 2/0 (70) 3/0 (95) 4/0 (120) 4/0 (120)
* Thischart is a general guideline and may not suit all applications. If cable overheating occurs (normally you can smell it), use next size larger
cable.
**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
( ) = mm2 for metric use S-0007-E
***For distances longer than those shown in this guide, call a factory applications representative at 920-735-4505.
TM-499 Page 11
SECTION 5 − OPERATING THE WELDING GENERATOR
5-1. Controls (Kohler-Powered Units)
50 Hz
60 Hz
. Weld and generator power output stops if To Start (Electric): open fuel valve (see Sec-
tion 4-4), move throttle lever to Idle, set choke,
5 Engine Hour Meter
generator overheats or engine speed is 6 Welding Range Label
and turn engine switch to Start position. Open
too low. Use label to determine correct weld amper-
choke as engine warms. If engine does not
crank, use recoil starting procedure following age based on electrode size, type, and mate-
1 Engine Switch to start engine. rial thickness.
7 Current Control
Use switch to open ignition circuit, and to stop Y If engine does not start, let engine
engine. come to a complete stop before at- Use control to select weld amperage. Control
tempting restart. may be adjusted while welding.
2 Throttle Control Lever To Set Current Control: Use label to deter-
4 Starter Handle
mine correct size electrode for material thick-
To Start (Recoil): open fuel valve (see Sec- ness. Select electrode type and set current
Use lever to select engine speed. Use 50 Hz
tion 4-4), move throttle lever to Idle, set choke, control to corresponding amperage range.
or 60 Hz position for 50 or 60 Hz generator
and pull starter handle. Open choke as engine Adjust control to obtain desired weld
power. Use 60 Hz position for maximum weld
warms. performance.
output.
EXAMPLE:
To Stop: turn engine switch to Off.
3 Choke Control Lever Material Thickness: 1/8 to 1/4 in
. Always close fuel valve after stopping Electrode Diameter: 1/8
Use lever to change engine air/fuel mix. Move unit. Moving unit with fuel valve open may
Electrode Type: E-6013
lever to right if starting a cold engine. Move le- cause carburetor flooding and make
ver to left if starting a warm engine. starting difficult. Current Control Setting: 90 − 120 A
TM-499 Page 12
5-2. Controls (Honda-Powered Units) (See Section 5-3)
3 4
Recoil-Start
2 Electric-Start
60 Hz
50 Hz
TM-499 Page 13
5-3. Description Of Controls (Honda-Powered Units) (See Section 5-2)
. Weld and generator power output stops if To Start (Recoil): open fuel valve, turn engine
switch to On, move throttle lever to Idle, set
Use label to determine correct weld amper-
age based on electrode size, type, and mate-
generator overheats or engine speed is
choke, and pull starter handle. Open choke as rial thickness.
too low.
engine warms.
1 Engine Switch 7 Current Control
On models with recoil-start, use switch to To Start (Electric): open fuel valve, move
Use control to select weld amperage. Control
open ignition circuit, and to stop engine. throttle lever to Idle, set choke, and turn en-
may be adjusted while welding.
gine switch to Start position. Open choke as
On models with electric-start, use switch to engine warms. To Set Current Control: Use label to deter-
open ignition circuit, and to start and stop en-
Y If engine does not start, let engine mine correct size electrode for material thick-
gine.
come to a complete stop before at- ness. Select electrode type and set current
2 Throttle Control Lever control to corresponding amperage range on
tempting restart.
Use lever to select engine speed. Use 50 Hz nameplate. Adjust control within selected
or 60 Hz position for generator power. Use 60 To Stop: turn engine switch to Off. range to obtain desired weld performance.
Hz position for maximum weld output.
3 Choke Control Lever . Always close fuel valve after stopping EXAMPLE:
Notes
TM-499 Page 14
SECTION 6 − OPERATING AUXILIARY EQUIPMENT
NOTE The welding generator provides power while welding and with the Current control
in any position. However, under these conditions equipment connected to the
welding generator may be subject to larger than normal voltage fluctuations. It is
recommended that only lamps be powered under these conditions.
4 1 2 3 5
495 218
Y If unit does not have GFCI recep- RC1 supplies 60 Hz single-phase power at CB1 protects RC1 from overload. If CB1
tacles, use GFCI-protected exten- weld/power speed. Maximum output is 3.5 opens, RC1 does not work.
sion cord. kVA/kW.
5 Circuit Breakers CB2 And CB3
Y Power is still present at the 240 volt 2 120 V 20 A AC Duplex Receptacle
receptacle when only one circuit CB2 protects RC2 and CB3 protects RC3
RC2
breaker trips. from overload. If a circuit breaker opens,
3 120 V 20 A AC Duplex Receptacle the receptacle does not work.
Unplug power cord before attempt- RC3
ing to service accessories or tools. . Press button to reset circuit breaker.
RC2 and RC3 supply 60 Hz single-phase
Combined output of all receptacles limited
. Generator power decreases as weld power at weld/power speed. Maximum
output from RC2 or RC3 is 2.4 kVA/kW. to 6 kVA/kW rating of the generator. (See
current increases. Generator Power Guidelines in Owner’s
Set Amperage control at max. for full . Each receptacle of the duplex can pro- Manual.)
generator power. vide 15A/1800W. EXAMPLE: If 10 A is drawn from each 120
volt duplex receptacle, only 9 A is available
. Place throttle lever in Run position (far . Do not parallel the two 120V duplex from the 120 V twistlock receptacle.
right) for generator power. receptacles.
2 x (120 V x 10 A) + (240 V x 9 A) = 3.5 kVA/
1 120 V AC Twistlock Receptacle RC1 4 Circuit Breaker CB1 KW.
TM-499 Page 15
6-2. Optional Generator Power Panels
Generator Power Panel 495 315 Generator Power Panel 495 219
(USA) (USA)
Generator Power Panel 495 278 Generator Power Panel 495 253 Generator Power Panel 495 288
(Canada−CSA) (South Africa) (South America)
Generator Power Panel 495 289 Generator Power Panel 495 290 Generator Power Panel 495 283
(Australia) (Europe) (S.E. Asia)
TM-499 Page 16
6-3. Generator Power Panel Ratings
NOTE Unless otherwise stated, the rating of duplex outlets is the combined load of all
receptacles.
Total power from generator NOT to exceed 5500 Watts (60 Hz) or 5000 Watts (50 Hz)
Panel Panel
Panel Panel Panel 495 278 Panel 495 288 Panel Panel Panel
Protected
Receptacle 495 218 495 315 495 219 495 253 495 289 495 290 495 283
By (Canada- (South
(USA) (USA) (USA) CSA) (S. Africa) America) (Australia) (Europe) (S.E. Asia)
60 Hz 60 Hz 60 Hz 60 Hz 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz
25A/ 25A/
240 V 5500W 5500W
CB1,2
Twist Lock See See
Note 2 Note 2
15A/
240 V 3600W 15A/
CB1,2
Duplex See 3600W
Note 2
240 V 15A/
CB3,4
Duplex 3600W
230 V 15A/ 15A/ 15A/
CB1
Single 3600W 3600W 3600W
230 V 15A/ 15A/ 15A/
CB2
Single 3600W 3600W 3600W
230 V 15A/
CB1,2
Single 3600W
230 V 15A/
CB3,4
Single 3600W
120 V 30A/
CB1
Twist Lock 3500W
30A/
120 V CB1,3/ 3600W
Duplex CB2,4 See
Note 1
120 V 20A/
CB2
Duplex 2400W
20A/ 20A/
120 V 20A/ 2400W 2400W
CB3
Duplex 2400W See See
Note 3 Note 3
20A/ 20A/
120 V 2400W 2400W
CB4
Duplex See See
Note 3 Note 3
Total
Power NOT 5500W 5500W 5500W 5500W 5000W 5000W 5000W 5000W 5000W
to exceed
Notes: 1. Each receptacle of the duplex can provide 15A/1800W. Do not parallel the two 120V duplex receptacles.
2. Do not parallel the two 120V circuits.
3. Do not parallel the two duplex outlets.
For example, for the 495 218 Generator Power Panel,
Calculating total power provided by generator. 120V, 3000W heater 3000W
(See Generator Power Guidelines in Owner’s Manual.) 120V, 10A chain saw 1200W
Each receptacle can provide the watts or amps as shown 120V, 500W halogen lamp 500W
above. However, the total power can not exceed 5500W. Total 4700W This loading is OK.
The rating plate on electrical apparatus will contain the watts 120V, 3000W heater 3000W
consumed or the rated input amps. Watts may be calculated by
120V, 10A chain saw 1200W
multiplying the rated voltage by the rated input amps.
120V, 5A router 600W
watts = volts x amps 120V, 1000W halogen lamp 1000W
Total 5800W This loading is not OK.
It exceeds 5500W.
TM-499 Page 17
6-4. Wiring Instructions For Optional 120/240 Volt Twistlock Plug (NEMA L14-30P)
2 1 1 Plug Wired For 120/240 V,
3-Wire Load
3
When wired for 120 V loads, each du-
plex receptacle shares a load with
Tools Needed:
4 one half of the 240 V receptacle.
2 Neutral (Silver) Terminal
3 Load 1 (Brass) Terminal
120V 4 Load 2 (Brass) Terminal
6 240 V
5 Ground (Green) Terminal
120 V 5 6 Cord Grip
Strip cord jacket back enough to sep-
arate conductors.
Strip conductors enough to make
good contact with plug terminals.
Make plug connections and reinstall
outer shell and cord grip.
Tighten assembly screws onto shell.
Do not overtighten.
plug3-11/99 − 802 527
SECTION 7 − MAINTENANCE
NOTE Follow the storage procedure in the engine owner’s manual if the unit will not be
used for an extended period.
+30 +86
+20
+59
10W-30
+10
8h 0 +32
-10
-15
-20 -10
Unleaded
86 + Octane
6.5 l (1.7 US Gal,
11.4 lmp pt)
50 h
0.7 − 0.8 mm
(0.028 − 0.031 in)
200 h
TM-499 Page 18
7-2. Routine Maintenance
8h 20 h
50 h
100 h
200 h
300 h
Check valve
clearance.*
500 h
1000 h
Blow out or
vacuum inside.
During heavy OR
service, clean
monthly.
TM-499 Page 19
7-3. Overload Protection (Honda-Powered Units)
1 Ignition Circuit Breaker
(Electric-Start Models Only)
The circuit breaker protects the en-
gine battery charging circuit. A
short circuit or a battery connected
in reverse polarity will trip the circuit
breaker.
Press button to reset breaker.
Top View
Top View
3
2 1
TM-499 Page 20
7-5. Adjusting Engine Speed (Honda-Powered Units)
After tuning engine, check engine
speeds. See table for proper no
load speeds. If necessary, adjust
speeds as follows:
1400 ± 150 rpm Start engine and run until warm.
3 4
Tools Needed:
1/4, 3/8 in
802 097-A
TM-499 Page 21
SECTION 8 − THEORY OF OPERATION
1 Engine
8
Supplies force to turn revolving
fields. Generator
Power AC
2 Revolving Field (Rotor) Receptacles
Turns at 3700 rpm maximum (60
Hz) for weld and power. The speed
and excitation current of the field
coils determine voltages in stator 7
windings.
Generator Power
3 Stator Windings Circuit
Breakers
Supply power to exciter, generator
power, and weld circuits.
4 Integrated Rectifier SR1
Changes ac output of stator 1 2 3
windings to dc to supply excitation Generator Power
current to the exciter revolving field. Revolving
Engine Field
Weld
5 Control Board PC1 (Rotor) Stator Windings
Adjusts weld output by changing Exciter
revolving field current after
comparing feedback to amperage
setting of R1.
4
Uses current feedback signal for
foldback circuit to prevent stator Integrated
Engine Speed Feedback Signal
6 Current Control R1
Changes output of stator weld
windings by adjusting field current
level in revolving field. 5
Current
Control R1
TM-499 Page 22
9 Main Rectifier SR2
Changes ac weld current to dc.
10 Suppressor VR1/R2
Protects SR2 from overload.
11 Stabilizer L1
Smooths weld output current.
12 Shunt
Provides weld current feedback to
control board PC1.
13 HF Filter Board PC2
Protects unit from high frequency.
14 Positive (+) And Negative (−)
9 Weld Output Terminals
Provide weld output.
Main Rectifier
SR2
10
Suppressor
VR1/R2
12 11
Shunt Stabilizer
L1
13
HF Filter
Current Feedback Signal Board
PC2
14 14
Electrode Work
AC Or DC Control Circuits
Mechanical Coupling
Magnetic Coupling
TM-499 Page 23
SECTION 9 − EXPLANATION OF ELECTRICAL PARTS
elect_parts 7/04
BRUSHES
TM-499 Page 24
PART NAME FUNCTION PICTURE CIRCUIT SYMBOL
NRM OPEN
POINTS
FM
TM-499 Page 25
PART NAME FUNCTION PICTURE CIRCUIT SYMBOL
MA1
TM-499 Page 26
PART NAME FUNCTION PICTURE CIRCUIT SYMBOL
RC =
RC1 MOUNTED
TM-499 Page 27
PART NAME FUNCTION PICTURE CIRCUIT SYMBOL
S1 S1
TM-499 Page 28
PART NAME FUNCTION PICTURE CIRCUIT SYMBOL
S1 S1
S1 S1
S1 S1
TE1
TERMINAL STRIP An insulated connection point for wires. They 42 42 104 105 74
are used for the ease of making multiple 1T
connections and can be a convenient point A B C D E
for making electrical checks when
troubleshooting. (Notice the “jumper link” 104 105
connecting terminals A and B together.)
TM-499 Page 29
PART NAME FUNCTION PICTURE CIRCUIT SYMBOL
FERRITE
T1 CORE
AIR
T1 CORE
TM-499 Page 30
SECTION 10 − TROUBLESHOOTING
10-1. Troubleshooting Tables
A. Welding
Trouble Remedy
No weld output. Check weld connections.
Check resistance and connections of resistor R3; R3 is 20 ohms ±5%. Replace R3 if necessary.
Check engine speed, and adjust if necessary (see Section 7-4 or 7-5). Output stops if engine speed is
too low.
Check slip rings, and install new brushes if necessary (see Section 10-7).
Check resistance and connections of Current Control R1; R1 is 0 to 1000 ohms ±10%. Replace R1 if
necessary.
Check control board PC1 and connections, and replace if necessary (see Section 10-5). PC1 LED lights
when board is energized.
Check engine lamp coil and connections, and replace coil if necessary. Lamp coil supplies power to con-
trol board PC1. PC1 LED lights when board is energized (see Section 10-5).
Check capacitor C1 for a short or open, and replace if necessary. If C1 is open, also replace circuit board
PC1.
Disconnect stator weld leads from main rectifier SR2, and check continuity between stator weld leads.
Replace stator if necessary.
Disconnect leads 3 and 4 from brushes, and check continuity across slip rings. Replace rotor if
necessary.
Disconnect stator exciter leads (black) from integrated rectifier SR1, and check continuity between
exciter leads. Replace stator if necessary.
Check engine speed, and adjust if necessary (see Section 7-4 or 7-5).
Check slip rings, and install new brushes if necessary (see Section 10-7).
Check control board PC1 and connections, and replace if necessary (see Section 10-5). PC1 LED lights
when board is energized.
Check capacitor C1 for a short or open, and replace if necessary. If C1 is open, also replace circuit board
PC1.
Disconnect stator weld leads from main rectifier SR2, and check continuity between stator weld leads.
Replace stator if necessary.
Disconnect leads 3 and 4 from brushes, and check continuity across slip rings. Replace rotor if
necessary.
Disconnect stator exciter leads (black) from integrated rectifier SR1, and check continuity between
exciter leads. Replace stator if necessary.
TM-499 Page 31
Trouble Remedy
High weld output. Check Current Control R1 setting.
Check engine speed, and adjust if necessary (see Section 7-4 or 7-5).
Check resistance and connections of suppressor VR1/R2. R2 is 1000 ohms ±5%. Replace VR1/R2 if
necessary.
Check slip rings, and install new brushes if necessary (see Section 10-7).
Check control board PC1 and connections, and replace if necessary (see Section 10-5). Replace PC1
if shorted across receptacle RC4 pins 4 and 6. PC1 LED lights when board is energized.
Check capacitor C1 replace if open. If C1 is open, also replace circuit board PC1.
Check engine speed, and adjust if necessary (see Section 7-4 or 7-5).
Check control board PC1 and connections, and replace if necessary. PC1 LED lights when board is ener-
gized.
Check capacitor C1 for a short or open, and replace if necessary. If C1 is open, also replace circuit board
PC1.
Check stabilizer L1 for signs of winding failure. Check continuity across windings, and check for proper
connections. Replace L1 if necessary.
Disconnect leads 3 and 4 from brushes, and check continuity across slip rings. Replace rotor if
necessary.
B. Generator Power
Trouble Remedy
No output at ac receptacles. Reset circuit breakers (see Section 6-1).
Check resistance and connections of resistor R3; R3 is 20 ohms ±5%. Replace R3 if necessary.
Check engine speed, and adjust if necessary (see Section 7-4 or 7-5). Output stops if engine speed is
too low.
Check slip rings, and install new brushes if necessary (see Section 10-7).
Check control board PC1 and connections, and replace if necessary (see Section 10-5). PC1 LED lights
when board is energized.
Check engine lamp coil and connections, and replace coil if necessary. Lamp coil supplies power to con-
trol board PC1. PC1 LED lights when board is energized.
Check capacitor C1 for a short or open, and replace if necessary. If C1 is open, also replace circuit board
PC1.
Disconnect stator generator power leads from connection block 1T, and check continuity between gener-
ator power leads 1 and 3, and leads 2 and 4. Replace stator if necessary.
TM-499 Page 32
Trouble Remedy
Disconnect leads 3 and 4 from brushes, and check continuity across slip rings. Replace rotor if
necessary.
Disconnect stator exciter leads (black) from integrated rectifier SR1, and check continuity between
exciter leads. Replace stator if necessary.
High power output at ac receptacles. Check engine speed, and adjust if necessary (see Section 7-4 or 7-5).
Check control board PC1 and connections, and replace if necessary (see Section 10-5). Replace PC1
if shorted across receptacle RC4 pins 4 and 6. PC1 LED lights when board is energized.
Check capacitor C1 for a short or open, and replace if necessary. If C1 is open, also replace circuit board
PC1.
Disconnect leads 3 and 4 from brushes, and check continuity across slip rings. Replace rotor if
necessary.
Low power output at ac receptacles. Move throttle lever to Run (use 60 Hz position for 60 Hz equipment).
Check engine speed, and adjust if necessary (see Section 7-4 or 7-5).
Check capacitor C1 for a short or open, and replace if necessary. If C1 is open, also replace circuit board
PC1.
Disconnect leads 3 and 4 from brushes, and check continuity across slip rings. Replace rotor if
necessary.
Check engine speed, and adjust if necessary (see Section 7-4 or 7-5).
Check slip rings, and install new brushes if necessary (see Section 10-7).
Check control board PC1 and connections, and replace if necessary. PC1 LED lights when board is ener-
gized.
C. Engine
Trouble Remedy
Engine will not start. Check fuel level (see Section 4-4 or 4-5).
Open fuel valve (see Section 4-4 or 4-5). Close fuel valve before moving unit or carburetor may flood and
make starting difficult.
Check oil level (see Section 4-4 or 4-5). Engine stops if oil level is too low. Refill crankcase with proper
viscosity oil for operating temperature.
TM-499 Page 33
Trouble Remedy
Engine stopped during normal Check fuel level (see Section 4-4 or 4-5).
operation.
Open fuel valve (see Section 4-4 or 4-5). Close fuel valve before moving unit or carburetor may flood and
make starting difficult.
Check oil level (see Section 4-4 or 4-5). Engine stops if oil level is too low.
Check unit operating angle. Low oil level shutdown switch may stop engine if unit is tilted.
Battery discharges between uses (elec- Clean battery, terminals, and posts with baking soda and water solution; rinse with clear water.
tric-start models only).
Replace battery.
Unstable or sluggish engine speeds. Check engine speed, and adjust if necessary (see Section 7-4 or 7-5).
TM-499 Page 34
Notes
TM-499 Page 35
10-2. Troubleshooting Circuit Diagram For Welding Generator (Use With Section 10-3)
R6
V6, A, B
C, D
V3, R5
V1,
R3 V2, See Section 8 for
R4 PC2 information
I1
V4
R1
V10
R8
See also
Section 10-5
for PC1 data
V9,
R7 V7
V8
V11
R2
V9,
R7
TM-499 Page 36
197 857-E
TM-499 Page 37
10-3. Test Points And Values (Use With Section 10-2)
TM-499 Page 38
10-4. Waveforms For Section 10-2
Waveforms shown are for 60 Hertz models;
waveforms for 50 Hertz models are similar.
5 ms 50 V
gnd
5 ms 20 V
gnd
TM-499 Page 39
10-5. Control Board PC1 Testing Information
Be sure plugs are secure before
testing. See Section 10-6 for
specific values during testing.
1 Receptacle RC5
2 2 Receptacle RC4
3 LED1
LED1 lights when board is
energized.
TM-499 Page 40
10-6. Control Board PC1 Test Point Values
6 Circuit common
9 Shunt positive (less than 1 volt dc input with respect to pin 8 with 100 ampere, 25 volt weld load
RC5 1 0 volts dc
3 Circuit common
5 0 to +10 volts dc input from min. to max. of Current Control R1 with respect to pin 6
6 Circuit common
7 Weld feedback input; same as negative (−) weld output terminal voltage
8 0 volts dc
TM-499 Page 41
10-7. Replacing Brushes And Cleaning Slip Rings
Y Stop engine.
1 Generator End Panel
2 Brush Assembly
3 Brush Holder
4 Brushes
Remove end panel. Remove brush
assembly. Pull brushes from
holders.
Replace brushes if damaged, or if
brush is at or near minimum length.
5 Slip Rings
Visually inspect slip rings. Under
3
normal use, rings turn dark brown.
If slip rings are corroded or surface
is uneven, insulate brush leads,
start engine, and clean rings with a
1/4 in (6 mm) commutator stone. Remove as little
Or Less − Replace material as possible.
Y Stop engine. Close fuel
7/16 in − 1/2 in valve.
4 (11 − 12 mm) New
Install brushes, brush holders, and
brush arm.
Reinstall cover.
Tools Needed:
TM-499 Page 42
10-8. Checking Unit Output After Servicing
Start engine.
Move throttle control lever to 60 Hz
position.
1 Weld Output Terminals
Check open-circuit voltage across
weld output terminals. There
should be 68 volts dc present (see
Section 10-2).
2 AC Receptacles RC1, RC2,
And RC3
Move throttle lever to correct
position (50 or 60 Hz) for generator
power. Check voltage at each
receptacle. With no load applied,
voltage should be 10% above
receptacle rating on nameplate.
EXAMPLE: Correct no load voltage
for a 120 volt receptacle should be
132 volts ac.
If generator power or weld output
voltage is incorrect, adjust engine
2 speed (see Section 7-4 or 7-5).
Y Stop engine. Close fuel
valve.
Allow engine to cool, and complete
1 pre-operational checks in table.
Pre-Operational Checks
ST-802 524
TM-499 Page 43
SECTION 11 − DISASSEMBLY AND REASSEMBLY
11-1. Disassembly Of Unit
Use Section 10-2 to determine if
trouble is in stator, rotor, engine or
combination of these components.
Remove cover. Mark and discon-
nect stator leads.
Disassemble in sequence shown.
Y Use hoist and lifting strap to
carefully remove engine/
generator assembly.
Go to Section 11-2.
Tools Needed:
802 524
TM-499 Page 44
11-2. Removing Rotor And Reassembling Generator
Y Do not damage rotor or sta-
tor windings during this pro-
cedure.
Removing Rotor To remove rotor:
1 Rotor Removal Tool
(Customer Supplied)
2 Screw, 7/16-14 x 1-1/4
(Customer Supplied)
Remove rotor thru-bolt.
Make rotor removal tool from
stress-proof steel rod according to
specifications. Slide threaded end
1 of tool through rotor. Tighten tool in
engine shaft. Turn screw into rotor
2 while lightly tapping rotor lamina-
tions. (turning screw into rotor
forces rotor off engine shaft.)
Reassembly
3 Brushholder Assembly
4 Generator End Panel
5 Bearing Carrier
6 Rotor Assembly
7-1/2 in 1 in 7 Stator Assembly
(191 mm) (25.4 mm) 8 Generator Fan
9 Generator Guard
10 Engine Adapter
11 Engine
Cut screwdriver 5/16 in
slot in end of rod.
24 threads Reinstall engine and generator
per inch (8 mm) parts using torque values in table.
Reconnect all leads. Use cable ties
to secure leads in wiring harness
and away from moving or hot parts.
Reinstall cover.
Reassembling Generator
11
3
10
9
8
A 95 in lb (10.7 N.m)
A
4 5 B 205 in lb (23.1 N.m)
B 802 524 / 802 509
TM-499 Page 45
SECTION 12 − ELECTRICAL DIAGRAMS
. The circuits in this manual can be used for troubleshooting, but there might be minor circuit differences from your machine. Use circuit
inside machine case or contact distributor for more information.
The following is a list of all diagrams for models covered by this manual.
Circuit Wiring
Model Serial Or Style Number
Diagram Diagram
Welding Generator LA124002 and following (Kohler) 197 857-E 197 858-C
LA347885 and following (Honda)
NOTE The circuits for Honda-powered units were implemented prior to the effective date
of this manual.
SA-148 611-A
Figure 12-1. Circuit Diagram For HF Board PC2 Eff. w/ Serial No. LA124002 And Following (Kohler)
Or KH467216 And Following (Honda)
TM-499 Page 46
197 857-E
Figure 12-2. Circuit Diagram For Welding Generator Eff. w/ Serial No. LA124002 And Following (Kohler)
Or LA347885 And Following (Honda) (1 Of 2)
TM-499 Page 47
197 857-E
Figure 12-3. Circuit Diagram For Welding Generator Eff. w/ Serial No. LA124002 And Following (Kohler)
Or LA347885 And Following (Honda) (2 Of 2)
TM-499 Page 48
197 858-C
Figure 12-4. Wiring Diagram For Welding Generator Eff. w/ Serial No. LA124002 And Following (Kohler)
Or LA347885 And Following (Honda)
TM-499 Page 49
Apply small amount of conductive electric com-
pound (Part No. 603 978) to terminals where
factory-applied compound had been present.
201 026-A
Figure 12-5. Wiring Diagram For Generator Power Panels Eff. w/ Serial No. LA124002 And
Following (Kohler) Or LA347885 And Following (Honda) (1 Of 2)
TM-499 Page 50
Apply small amount of conductive electric com-
pound (Part No. 603 978) to terminals where
factory-applied compound had been present.
201 026-A
Figure 12-6. Wiring Diagram For Generator Power Panels Eff. w/ Serial No. LA124002 And
Following (Kohler) Or LA347885 And Following (Honda) (2 Of 2)
TM-499 Page 51
SC-198 222
Figure 12-7. Circuit Diagram For Control Board PC1 Eff. w/ Serial No. LA124002 And Following (Kohler)
Or LA033425 And Following (Honda)
TM-499 Page 52
TM-499C August 2004
Processes
Stick (SMAW) Welding
Description
13
12 not available unless listed.
14
15
16
17
18
19
27
20
21
26
25
24
22
11
28
10
29
23
30
9
8
2
1
7
6
5
4
3
31
45 46 47
32
48
33
34
35
36
37
38
49
39
40
41
44
43
42
802 509
+When ordering a component originally displaying a precautionary label, the label should also be ordered.
To maintain the factory original performance of your equipment, use only Manufacturer’s Suggested
Replacement Parts. Model and serial number required when ordering parts from your local distributor.
TM-499 Page 55
Eff w/LA124002 Thru LB111747 (Kohler Only)
. Hardware is common and not available unless listed.
2 3 4 5 8
1
6 9
10
Generator Power Panel 196 914 (CSA) Generator Power Panel 495 315
11 13
12 12
14
14
Generator Power Panel 495 253 Generator Power Panel 495 289
(South Africa) (Australia)
196 921
Figure 13-2. Generator Power Panels
Processes
Stick (SMAW) Welding
Description
13
12 not available unless listed.
14
15
16
17
18
19
27
20
21
26
25
24
22
11
28
10
29
23
30
9
49
8
2
1
7
6
5
4
3
31
45 46 47
32
48
33
34
35
36
37
38
39
40
41
44
43
42
49
802 509-A
TM-499 Page 60
Eff w/LB111748 Thru LC061260 (Kohler) / LB086216 Thru LC061260 (Honda)
2 3 4 5 . Hardware is common and not available unless listed.
8
1 6 9
10
Generator Power Panel 196 914 (CSA) Generator Power Panel 495 315 (USA)
11
13
12
12
14
14
Generator Power Panel 495 253 Generator Power Panel 495 289
(South Africa) (Australia)
15 21
17
16 22
18
19
20
Generator Power Panel 495 219 Generator Power Panel 495 290
(USA) (Europe)
25
23 26
24
Generator Power Panel 495 288 Generator Power Panel 495 283
(S. America) (S.E. Asia)
27 29 32 34
33
28
36
30
31 35
Generator Power Panel 495 298 Generator Power Panel 495 278
(USA) (Canada−CSA) 196 921
Processes
Stick (SMAW) Welding
Description
13
12 not available unless listed.
14
15
16
17
18
19
27
20
21
26
25
24
22
11
28
10
29
23
30
9
49
8
2
1
7
6
5
4
3
31
45 46 47
32
48
33
34
35
36
37
38
39
40
41
44
43
42
50
802 509-A
TM-499 Page 66
Eff w/LC061261 Thru LC552236 (Kohler & Honda)
3 4 5 6 . Hardware is common and not available unless listed.
1 7
2 8 10
9 11
Generator Power Panel 495 218 (USA) Generator Power Panel 495 315 (USA)
12
14
13
13
15
15
Generator Power Panel 495 253 (South Africa) Generator Power Panel 495 289 (Australia)
22
16
18
17 23
19
20
21
Generator Power Panel 495 219 (USA) Generator Power Panel 495 290 (Europe)
26
24 27
25
Generator Power Panel 495 288 (S. America) Generator Power Panel 495 283 (S.E. Asia)
28 30 33 35
29
34 37
31
36
32
Generator Power Panel 495 298 (USA) Generator Power Panel 495 278 (Canada−CSA)
Processes
Stick (SMAW) Welding
Description
13
not available unless listed.
12
14
15
16
17
18
19
27
20
21
26
25
24
22
11
28
10
29
23
30
9
49
8
2
1
7
6
5
4
3
31
45 46 47
32
48
33
34
35
36
37
38
50
39
40
41
44
43
42
802 509-A
TM-499 Page 70
Eff w/LC552237 And Following (Kohler & Honda)
Item Dia. Part
No. Mkgs. No. Description Quantity
TM-499 Page 71
Eff w/LC552237 And Following (Kohler & Honda)
Item Dia. Part
No. Mkgs. No. Description Quantity
TM-499 Page 72
Eff w/LC552237 And Following (Kohler & Honda)
3 4 5 6 . Hardware is common and not available unless listed.
1 7
2 8 10
9 11
Generator Power Panel 495 218 (USA) Generator Power Panel 495 315 (USA)
12
14
13
13
15
15
Generator Power Panel 495 253 (South Africa) Generator Power Panel 495 289 (Australia)
22
16
18
17 23
19
20
21
Generator Power Panel 495 219 (USA) Generator Power Panel 495 290 (Europe)
26
24 27
25
Generator Power Panel 495 288 (S. America) Generator Power Panel 495 283 (S.E. Asia)
28 30 33 35
29
34 37
31
36
32
Generator Power Panel 495 298 (USA) Generator Power Panel 495 278 (Canada−CSA)