MODEL:
WST12MC16S
WST09MH16S
WST12MH16S
Part 2 Specifications.....................................................................................................3
2.1 Unit Specifications..................................................................................................3
2.2 Operation Characteristic Curve............................................................................15
2.3 CapacityVariation Ratio AccordingtoTemperature...............................................15
2.4 Operation Date.....................................................................................................16
2.5 Noise criteria curve tables for both models..........................................................16
Part 9 Troubleshooting...............................................................................................57
9.1 Precautions Before Performing Inspection or Repair...........................................57
9.2 Confirmation.........................................................................................................57
9.3 Judgement by Flashing LED of Indoor/Outdoor Unit...........................................57
9.4 How to Check Simply the Main Part.....................................................................59
9.5 2-way, 3-way Valve Appearance..........................................................................63
WST12MC16S
WST09MH16S
WST12MH16S
Outdoor Unit
WST12MC16S
WST09MH16S
WST12MH16S
FAN AUTO
OPER
AIR HEALTH X-FAN
HUMIDITY
FILTER
TURBO
HOUR
ON/OFF
ON/OFF MODE
FAN
YB1F2F
1
Safety Precautions
1.Safety Precautions
Important!
or rubbish.
The unit should be installed according to the instructions
This air conditioning system meets strict safety and in order to minimize the risk of damage from earthquakes,
operating standards. As the installer or service person, typhoons or strong winds.
it is an important part of your job to install or service the When the refrigerant touches the fire etc., it was decomposed
system so it operates safely and efficiently. and a poisonous gas is generated.
To prevent injury to the user or other people and Use only the specified refrigerant to charge the refrigerant
property damage, the following instructions must circuit.
Do not mix it with any other refrigerant and do not allow air to
be followed.
remain in the circuit.
Follow each installation or repair step exactly as shown. Air enclosed in the circuit can cause high pressure resulting
Observe all local, state, and national electrical codes. in a rupture and other hazards.
Pay close attention to all warning and caution notices After completing installation work, make sure that refriger-
given in this manual. ant gas has not leaked.
About the pictures: The limit density is made not to be exceeded even if the refrig-
erant leaks by any chance.
Warning Erroneous handing gives a high possi-
Turn the power off at the main power box (mains) before open-
bility to induce serious results such as
ing the unit to check or repair electrical parts and wiring.
death or heavy injury.
Keep your fingers and clothing away from any moving parts.
Erroneous handing may induce serious Clean up the site after you finish, remembering to check that
Caution
injury depending on the situation. no metal scraps or bits of wiring have been left inside the unit
being serviced.
The unit must be properly earth connected.
Warning
All electric work must be performed by licensed technician, ac-
cording to local regulations and the instructions given in this Caution
manual.
Do not supply power to the unit until all wiring and tubing Never install on the place where a combustible gas might
are completed or reconnected and checked. leak. The gas may ignite or explode when the gas leaks and
Highly dangerous electrical voltages are used in this collects in surround of the unit.
system. Carefully refer to the wiring diagram and these When the unit is installed at telecommunication centers or
instructions when wiring. Improper connections and inad- hospitals, take a proper provision against noise.
equate grounding can cause accidental injury or death. When installing at a watery place, provide an electric leak
Ground the unit following local electrical codes. breaker.
Connect all wiring tightly. Loose wiring may cause over- Do not wash the unit with water.
heating at connection points and a possible fire hazard. Be very careful about unit transportation. The unit should not
There is risk of fire, electric shock, explosion, or injury. be carried by only one person if it is more than 20kg. It occasion-
ally causes the damage of the unit and health to be impaired.
Ask your dealer or specialized subcontractor for installation or
Do not touch the heat exchanger fins with your hands.
repair work.
Doing so may cut your hands.
Make sure the ceiling/wall is strong enough to hold the Do not touch the compressor or refrigerant piping without
unit’s weight. The outdoor unit should be installed in a wearing glove on your hands. Touching directly such part can
location where air and noise emitted by the unit will not cause a burn or frostbite as it becomes high or low temperature
disturb the neighbors. according to the refrigerant state.
Properly insulate any tubing run inside a room to prevent Do not operate the air conditioner without the air filter set
"sweating" that can cause dripping and water damage to place. Dust may accumulate, and cause a failure.
walls and floors. At emergency (if you smell something burning), stop opera-
The outdoor unit must be installed on stable, level surface, tion and turn the power source switch off.
in a place where there is no accumulation of snow, leaves
2
Specifications
2.
Specifications
3
Specifications
7
Specifications
13
Specifications
9
7
8
6
7
5
6
Current(A)
Current(A)
5 4
4
3
Condition
3 Condition
Indoor:DB 20ć
Indoor:DB 27ć WB19ć 2 Indoor air flow: Super High
Indoor air flow: Super High
2 Pipe length:7.5m
Pipe length:7.5m
Voltage:230V
Voltage:230V 1
1
0 0
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Compressor Speed(rps) Compressor Speed(rps)
110 120
100 100
90 80
Capacity ratio(%)
Capacity ratio(%)
80 60
70 40
Condition Condition
Indoor:DB27℃ WB19℃ Indoor:DB20℃
Indoor air flow: Super High Indoor air flow: Super High
60 20 Pipe length:7.5m
Pipe length:7.5m
50 0
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 -15 -10 -5 0 5 10
Outdoor temp. (°C) Outdoor temp. (°C)
15
Specifications
Heating
NOTES :
Disacharge pressure
(2) Connecting piping condition : 7.5 m
48
Noise dB(A)
30
46
44 Cooling
09K
42
20
Low Middle High 40
20 30 40 50 60 70 80
Indoor fan motor rotating speed
Compressor frequency(Hz)
16
Constrction views
3. Construction Views
3.1 Indoor Unit
770 201
283
770
126.5 548.5
258.5
283
550
710 318
299
470
17
Refrigerant System Diagram
GAS SIDE
Discharge
HEAT
EXCHANGE
(EVAPORATOR) Suction Accumlator
COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE
COOLING
GAS SIDE
3-WAY VALVE
4-Way valve
Muffler
Discharge
HEAT
EXCHANGE
(EVAPORATOR) Suction Accumlator
COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE
COOLING
HEATING
18
Schematic Diagram
5. Schematic Diagram
5.1 Electrical Date
Indoor Unit
Symbol Color symbol Symbol Color symbol
WH WHITE BN BROWN
YE YELLOW BU BLUE
RD RED BK BLACK
YEGN YELLOW GREEN PROTECTIVE EARTH
Outdoor Unit
Symbol Parts name Symbol Color symbol
L1 REACROR WH WHITE
PCB1~PCB2 PRINTED CIRCUIT BOARD YE YELLOW
S10/S11S40/S70/S80/S90 CONNECTOR RD RED
SAT OVERLOAD BN BROWN
COMP COMPRESSOR BU BLUE
PROTECTIVE EARTH BK BLACK
YEGN YELLOW GREEN
Indoor Unit
XT
OUTDOOR UNIT
YEGN
PE
DISP1 DISP2 SWING-UD
EVAPORATOR
M2
AP1
DISPLAY SWING
MOTOR
INDOOR UNIT
19
Schematic Diagram
Outdoor Unit
L1
OG OG
RT3
0
RT4
0
RT5
0
L1
POWER L2
HR1
HR2 XT
PCB1 BU
INDOOR UNIT
S90 AC2 N(1)L1
HA1 BK
S10 S11
S 2
HA2 PCB2 BN
BN AC1 3 L2
BU HL3 HL2
YEGN
HN3 HN2 E1
S40 S70 BU YEGN
YEGN
U V W E2
PE
RD YEBU
X1 YEGN
RDYEBU WH WH PE PE
CLAPBOARD ELECTRICAL BOX
YEGN M SUB-ASSY
YEGN U V W
COMP.
FAN
SAT PE MOTOR OUTDOOR UNIT
PE
L1
4YF
OG OG
RT3
0
RT4
0
RT5
0
L1
POWER L2
HR1
HR2 XT
PCB1 BU
INDOOR UNIT
20
Schematic Diagram
TOP VIEW
1 2 3 4 5 6
8
9
1 Interface of input live wire
10 2 Interface of communication wire
3 Interface of input neutral wire
4 PG motor control interface
5 Feedback interface from PF
motor
6 Interface of pipe temperature
sensor
7 Interface of ambient temperature
sensor
8 Interface of air guide motor
9 Display interface
10 Protective tube
BOTTOM VIEW
21
Schematic Diagram
communication
ground
wire
wire
Display
board
infrared
receiver
22
Schematic Diagram
TOP VIEW
BOTTOM VIEW
23
Schematic Diagram
FRONT VIEW
BOTTOM VIEW
24
Schematic Diagram
TOP VIEW
BOTTOM VIEW
25
Function and Control
2 MODE
Press it to select operation mode(AUTO/COOL/DRY/FAN/HEAT).
FAN AUTO
OPER
AIR HEALTH X-FAN
3 - : Press it to decrease temperature setting.
HUMIDITY
4
FILTER + : Press it to increase temperature setting.
TURBO
HOUR 5 FAN
ON/OFF
Press it to set fan speed.
5 6
FAN 8
7 8 Press it to set left & right swing angle.
12 TURBO
13 SLEEP
14 LIGHT
Press it to turn on/off the light.
1 ON/OFF :
Press this button to start the unit operation .Press this button again to stop the unit operation.
2 MODE :
Each time you press this button,a mode is selected in a sequence that goes from AUTO, COOL,DRY, FAN,
and HEAT*, as the following:
After energization, AUTO mode is defaulted. In AUTO mode, the set temperature will not be displayed on the
LCD, and the unit will automatically select the suitable operation mode in accordance with the room temp
erature to make indoor room comfortable.
26
Function and Control
3
Press this button to decrease set temperature.Holding
. it down above 2 seconds rapidly decreases set temperature. In
AUTO mode, set temperature is not adjustable.
4 +:
Press this button to increase set temperature.Holding it down above 2 seconds rapidly increases set temperature. In
AUTO mode, set temperature is not adjustable.
5 FAN :
This button is used for setting fan speed in the sequence that goes from AUTO, , , to , then back to Auto.
Auto
6 :
● Press button to start or stop up & down swing function.The remote controller defaults to simple swing condition.
● Press + button and button at the same time at unit OFF to switch between simple swing and static swing,
blinking 2 seconds.
● In static swing condition, press button, the swing angle of up & down louver changes as below:
● If the unit is turned off during swing operation,the louver will stop at present position.
7 HEALTH SAVE:
Press HEALTH part of this button to turn on or off HEALTH function. Pressing SAVE part of this button, is displayed
and the unit goes into SAVE operation mode. Press SAVE part of the button again to cancel SAVE function .During
SAVE operation, the tmperature and fan speed is not adjustable.
8 :
● Press button to start or stop left & right swing function.The remote controller defaults to simple swing condition.
● Press + button and button at the same time at unit OFF to switch between simple swing and static swing,
blinking 2 seconds..
● In static swing condition, press button, the swing angle of left & right louver changes as below:
● If the unit is turned off during swing operation,the louver will stop at present position.
9 X-FAN:
Pressing X-FAN button in COOL or DRY mode,the icon "X-FAN" is displayed and the indoor fan will continue operation
for 10 minutes in order to dry the indoor unit even though you have turned off the unit.
After energization, X-FAN OFF is defaulted. X-FAN is not available in AUTO,FAN or HEAT mode.
10 TEMP:
Pressing TEMP button, (set temperature), (indoor ambient temperature) and (outdoor ambient
temperatur) is displayed circularly .The unit defaults not to display the icon. During operation of TEMP button, the set
temperature is always displayed.
Note: Outdoor ambient temperature is only displayed for some models.
27
Function and Control
11 TIMER:
Press TIMER button at unit ON to set TIMER OFF, HOUR OFF blinking. Press TIMER button at unit OFF to set TIMER
ON, HOUR ON blinking. In this case, pressing + or - button changes time setting. Holding down either button rapidly
changes time setting (time setting range 0.5-24hours). Press TIMER button again to confirm setting, HOUR ON/OFF
stopping blink. If there is not any operation of button within 5 seconds during HOUR ON/OFF blinking, TIMER setting
will be canceled.
12 TURBO:
Press this button to activate / deactivate the Turbo function which enables the unit to reach the preset temperature in
shortest time. In COOL mode, the unit will blow strong cooling air at super high fan speed. In HEAT mode, the unit will
blow strong heating air at super high fan speed. (This function is not applicable for some models).
13 SLEEP :
Press this button to go into the SLEEP operation mode. Press it again to cancel. This function is available in COOL ,
HEAT (Only for models with heating function) or DRY mode to maintain the most comfortable temperature for you.
14 LIGHT:
Press LIGHT button to turn on the display's light and press this button again to turn off the display's light. If the light is
tunrned on, is displayed. If the light is tunrned off disappears.
Notes:
When replacing the batteries, do not use old or different batteries,
otherwise, it may cause malfunction.
If the wireless remote controller will not be used for a long time,
please remove batteries to prevent damage from leaking batteries.
The operation should be performed in its receiving range.
It should be kept 1m away from the TV set or stereo sound sets.
If the wireless remote controller does not operate normally, please
take the batteries out and replace them after 30 seconds. If still not
Sketch map for
operating properly, replace the batteries. replacing batteries
28
Function and Control
29
Function and Control
B In this mode, the system selects the running mode (cooling, heating, and fan)
automatically according to the ambient temperature. The display shows the
actual running mode and setting temperature. There will be 30s delay for
A mode conversion. The protection function is the same as that of other modes.
1. When T amb>=25 o C, the cooling mode is selected.
Indoor temperature-object temperature 2. for heat pump unit: when Tamb<=22 o C, the unit runs in heating mode
3. for cooling only unit: when Tamb < 22o C, the unit runs in fan mode. .
4. When 22 o C <T indoor amb< 25 o C, upon initial startup, the unit will
1. In this mode, the fan motor runs at low fan speed while swing works enter auto mode and run in automatic fan mode. If the other mode
changes into auto mode, the previous running mode will remain.
according to setting state. The range of setting temperature is 16~30 o C
(61~86¨H).
2. When outdoor malfunction or protection stoppage happen,
the indoor fan will remain the original running state and the error LED will light.
1. In this mode, the indoor fan may run at high, medium, low and automatic
speed. The compressor, outdoor fan and 4-way valve all stop running.
o
2. In this mode, the range of setting temperature is 16~30 C (61~86¨H).
C
2. Protection function: in heating mode, when the compressor stops as
a result of malfunction, the indoor fan blows residual heat.
3. Defrosting control: when the defrosting signal is revived, the
defrosting mark H1 will be shown. The e-heater and indoor fan stop.
30
Function and Control
Timer off: the timer off function can be set when the unit is on. When the
setting time for timer off is reached, the unit will stop. The timing interval is
After energization, the motor of upper and lower swing will enable the air 0.5hour, and the setting range is 0.5~24hours.
deflector to be open and then be close completely. And the air outlet is close. Clock (start and stop time can be set. The accuracy is minute. E.g.: timer
In heating mode, if the swing function is not set, the upper and lower air on at 8:00a.m.; timer off at 17:30p.m.)
Timer on: if the timer on function is set when the system is on, the system
deflector will rotate to maximum in clockwise direction. Then it will rotate
will go on running. If the timer on function is set when the system is off, the
to place D. Under other state, the upper and lower air deflector will rotate to system will start running in the previously set mode when the setting time is
level L. If the swing function is set when starting the unit, the air deflector reached.
Timer off: if the timer off function is set when the system is off, the system
will swing between place L and D. there are 7 states for air deflector: in will keep off even though the setting time is reached. If t he timer off
Place L, Place A, Place B, Place C, Place D, and swing between Place L and function is set when the system is on, the system will stop running when the
place D, stop in any place between Place L and place D. When the unit is setting time is reached.
turned off, the air deflector will stay in place 0. The swing is available only Timer modification: when the system is under timer state, start or stop of the
unit can be set via remote ON/OFF button and the timer can be reset. The
when the swing function is set and the indoor fan is running.
system runs according to the latest setting state.
Note: When place L to B, place A to C, and place B and D is set, the air
When both the timer on and timer off are set: the system runs according to
deflector will swing between place L to D.
the current setting state. When the setting time is reached, the unit will start
and stop running. In that case, the unit will run according to the previously
setting mode when the setting time for timer on is reached. The unit will stop
O(0°)
running while the setting time for timer off is reached.
If the setting time for timer on and timer off is the same, the unit will stop
running no matter what the current state is.
L
A Memory: mode, up and down swing, light, setting temperature, setting fan
B speed, general timer (not clock), Fahrenheit / Celsius. After de-energized,
the unit can run according to the memory if it is energized again. If the tim
C
function is not set in the last remote control, the system will run according to
D
the last remote control. If the timer function is set in the last control before it
is de-energized, the system will memorize the last timer setting. The setting
time is recalculated since the energization of the unit. If the timer function is
1. It is applicable to cooling mode, dehumidifying mode and heating mode. set in the last control and the setting time is reached before the unit is
2. In cooling mode or dehumidifying mode, 1 hour after the sleep curve is de-energized, the unit will run according to the previous running mode after
set, the setting temperature will rise by 1 ć . 2 hours later, the setting
it is energized again. But the timer function will terminate. The clock will
temperature will rise by 2 ć . After that, the setting temperature will not
not be memorized.
change any more
In cooling and heating mode (not available in auto, dehumidify, fan mode),
set
Set temp. Tset press the Turbo button, the fan speed displayed super high speed in the
remote controller and the indoor fan rotates at super high speed.
set (11) Turbo function
In cooling and heating mode (not available in auto, dehumidify, fan mode),
set press the Turbo button, the fan speed displayed super high speed in the
1h 2h About 2h remote controller and the indoor fan rotates at super high speed.
3. In heating mode, 1 hour after the sleep curve is set, the setting temperature (12) Health function
will decrease by 1 ć . 2 hours later, the setting temperature will decrease by When the indoor fan motor is running, the Health function is set by pressing
2 ć . After that, the setting temperature will not change any more. remote controller (If there is no Health button on the remote controller, the
1h 2h About 2h Health function opening is defaulted).
(13) I Feel function
set If the remote controller receives the I Feel order, the controller will work at
the ambient temperature value which is sent by remote controller (Except the
set defrosting and anti-cool wind, which still adopts the sampling value of AC
Set temp. Tset
itself ambient temperature sensor), the remote controller will send ambient
set temperature value to controller every 10mins. After 11mins, if the controller
hasn’t received the ambient temperature value from the remote controller for
long time, then it will run according to the current ambient temperature of AC.
The main board has general timer function and clock function. The timer
If the function has not been set, the ambient temperature will adopt the sensor
function can be selected by remote controller with different function
sampling value of AC itself. If power off happens, this function will not be
(1) General timer (start and stop time can be set. The accuracy is minute.
memorized.
E.g.: timer on for 1 hour; timer off for 1.5 hours.)
Timer on: after setting timer on, the unit will run at setting time according to
the original setting mode. The timing interval is 0.5hour, and the setting
range is 0.5~24hours.
31
Function and Control
Frequency Control
<Outline>
When starting the compressor, or when conditions are varied due to the change of the room, the frequency must be initialized according
to the D value of the indoor unit and the Q value of the indoor unit.
Q value: Indoor unit output determined from indoor unit volume, air flow rate and other factors.
1. P control
Calculate D value in each sampling time (20 seconds), and adjust the frequency according to its difference from the frequency
previously calculated.
2. I control
If the operating frequency is not change more than a certain fixed time, adjust the frequency up and down according to the D value,
obtaining the fixed D value.
When the D value is small...lower the frequency.
When the D value is large...increase the frequency.
3. Frequency management when other controls are functioning
When frequency is drooping;
Frequency management is carried out only when the frequency droops.
For limiting lower limit
Frequency management is carried out only when the frequency rises.
4. Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set depending on indoor unit.
When low noise commands come from the indoor unit or when outdoor unit low noise or quiet commands come from indoor unit, the
upper limit frequency must be lowered than the usual setting.
3-minutes Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.(except when defrosting)
Frequency
FCG 3 88
FCG3
FCG 2 64
FCG2
FCG 1 48 FCG1
TCG1 240
TCG2 360 Time
TCG 1sec TCG 2sec TCG 3sec
TCG3 180
32
Function and Control
Stop zone
Drooping zone
Keep zone
Up zone
Heat exchanger
Reset zone
thermistor
temperature
2 Hz drooping
1.0second after After 2.5 seconds
rushing in the
drooping zone Compressor stops
1 Stop zone
2 Drooping zone
3 Keep zone
Reset zone
When a “stop current” continues for 2.5 seconds after rushing on the stop zone, the compressor operation stops.
If a “drooping current” is continues for 1.0 second after rushing on the drooping zone, the frequency will be 2 Hz drooping.
Repeating the above drooping continues until the current rushes on the drooping zone without change.
In the keep zone, the frequency limit will remain.
In the return / reset zone, the frequency limit will be cancelled.
Limitation of current drooping and stop value according to the outdoor air temperature
1. In case the operation mode is cooling
* The current droops when outdoor air temperature becomes higher than a certain level (model by model).
2. In case the operation mode is heating
* The current droops when outdoor air temperature becomes higher than a certain level (model by model).
33
Function and Control
During cooling operation, the signals being sent from the indoor unit allow the operating frequency limitation and then prevent freezing
of the indoor heat exchanger. (The signal from the indoor unit must be divided into the zones as the followings.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from operation start.
Control in Each Zone
Heat exchanger
thermistor temperature Return/Reset zone
A Up zone
B Keep zone
C Drooping zone
D Stop zone
E
Stop zone
Drooping zone
Keep zone
Up zone
Heat exchanger
thermistor temperature Reset zone
Defrost Control
Outline
Heat Pump Only
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat exchanger temperature must be more
than its fixed value when finishing.
Detail
Conditions for Starting Defrost
The starting conditions must be made with the outdoor air temperature and heat exchanger temperature. Under the conditions that the
system is in heating operation, 6 minutes after the compressor is started and more than 44 minutes of accumulated time pass since
the start of the operation or ending the defrosting.
Conditions for Canceling Defrost
The judgment must be made with heat exchanger temperature. (39°F~72°F)
34
Function and Control
PI control
Frequency
0Hz
60sec.
50sec. 600sec. 50sec.
ON
Compressor
OFF
ON
Four way valve
OFF
5sec. 5sec.
ON
Fan
OFF
Fan Control
Outline
Fan control is carried out according to the following priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control in cooling operation
5. Tap control when drooping function is working
6. Fan control in forced operation
7. Fan control in indoor/outdoor unit silent operation
8. Fan control in powerful mode
9. Fan control in normal operation
Detail
Fan OFF Control when Stopped
* Fan OFF delay for 60 seconds must be made when the compressor is stopped.
Tap Control in indoor/outdoor unit silent operation
1. When Cooling Operation
When the outdoor air temperature is lower than 99°F, the fan tap must be set to L.
2. When Heating Operation
When the outdoor air temperature is higher than 39°F, the fan tap must be turned to L (only for heat pump model).
35
Installation Manual
Important Notices (1)The air inlet and outlet vent should be far from the obstruction,
make sure that the air can be blown through the whole room.
1. The unit installation work must be done by qualified (2)Select a position where the condensing water can be easily
personnel according to the local rules and this drained out, and the place is easily connected for outdoor unit.
(3)Select a location where the children can not reach.
manual.
(4)Can select the place where is strong enough to withstand the
2. Before installating, please contact with local
full weight and vibration of the unit. And will not increase the noise.
authorized maintenance center, if unit is not installed
(5)Be sure to leave enough space to allow access for routine
by the authorized maintenance center, the malfunction maintenance. The height of the installed location should be
may not solved, due to discommodious contacts. 250cm or more from the floor.
3. When removing the unit to the o.ther place, please (6)Select a place about 1m or more away from TVset or any other
firstly contact with the authorized Maintenance electric appliances.
Center in the local area. (7)Select a place where the filter can be easily taken out.
(8)Make sure that the indoor unit installation should accord with
installation dimension diagram requirements.
Basic Requirements For Installation (9)Do not use the unit in the immediate surroundings of a laun-
Position dry a bath a shower or a swimming pool.
* Place where strong heat sources, vapors, flammable gas or unit will not inconvenience neighbors, animals, plants.
volatile object are emitted. (2)Select a location where there should be sufficient ventilation.
* Place where high-frequency waves are generated by radio (3)Select a location where there should be no obstructions cover
equipment, welders and medical equipment. the inlet and outlet vent.
* Place where a lot of salinities such as coast exists. (4)The location should be able to withstand the full weight and
* Place where the oil (machine oil) is contained in the air. vibration of the outdoor unit and permit safe installation.
* Place where a sulfured gas such as the hot spring zones is (5)Select a dry place, but do not expose under the direct sunlight
generated. or strong wind.
* Other place with special circumstance. (6)Make sure that the outdoor unit installation dimension should
accord with installation dimension diagram, convenient for
maintenance, repair.
7.1 Tools Required for Installation (7)The height difference of connecting the tubing within 5m, the
(not supplied) length of connecting the tubing within 10m.
(8)Select a place where it is out of reach for the children.
1. Gauge manifold
(9)Select a place where will not block the passage and do not
2.Electronic balance for refrigerant charging
influence the city appearance.
3. Phillips head screwdriver
4. Knife or wire stripper
5. Carpenter’s level 7.3 Installation of Indoor Unit
9. Hammer
10. Drill The mounting plate should be installed on a wall which can sup-
11. Tube cutter port the weight of the indoor unit.
12. Tube flaring tool 1) Temporarily secure the mounting plate to the wall, make sure
13. Torque wrench that the panel is completely level, and mark the boring points on
14. Adjustable wrench the wall.
15. Reamer (for deburring) 2) Secure the mounting plate to the wall with screws.
16. Vacuum pump (For R410A)
17. Gas leakage detector
36
Installation Manual
241.7
Pipe
Reamer
41.3 41.3
54.5 160 50 160 54 Point down
Gas pipe end
330.5 331 Through-
the-wall
770 Liquid pipe end hole φ65mm
Keep here the piece cut out Drain hose
from the unit for piping position Unit: mm Putting nut on
* The removed pipe port cover can be
Removed pipe
Remove flare nuts attached to indoor and outdoor unit, then
kept in the mounting plate pocket.
port cover put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)
A Mounting plate
Flare nut
Copper tube
• For walls containing metal frame or metal board, be sure to use
a wall embedded pipe and wall cover in the feed-through hole to
prevent possible heat, electrical shock, or fire.
• Be sure to caulk the gaps around the pipes with caulking mate- Flaring work
rial to prevent water leakage. Firmly hold copper pipe in a die in the dimension shown in
1) Bore a feed-through hole of 65mm in the wall so it has a down the table above.
slope toward the outside. Handle
"A"
φ 65 Outside diameter A
Wall hole cover
(field supply) mm inch mm
Wall embedded pipe
(field supply) Ø6.35 1/4 0~0.5
Ø9.52 3/8 0~0.5
3.1 Flaring work Ø12.7 1/2 0~0.5
Flaring work Ø15.88 5/8 0~1.0
Main cause for refrigerant leakage is due to defect in theflaring
Ø19.05 3/4 1.0~1.3
work. Carry out correct flaring work using the follow-ing procedure.
Cut the pipes and the cable Check
1. Use the piping kit accessory or pipes purchased locally. 1.Compare the flared work with figure below.
2. Measure the distance between the indoor and the outdoor unit. 2.If flare is noted to be defective, cut off the flared section and re-
3. Cut the pipes a little longer than the measured distance. flare it.
Smooth all round
4. Cut the cable 1.5m longer than the pipe length. Inside is shiny without scratches
= Improper flaring =
Copper
pipe 90e Slanted Uneven Rough
37
Installation Manual
3.2 Connection of piping 5. Insert the connecting cable fully into the terminal block and
1.Align the center of the pipes and sufficiently tighten the flare nut secure it tightly with screws.
by hand. 6. Tightening torque: 1.2 N•m (0.12 kgf•m).
7. Secure the connecting cable with the cord clamp.
8. Attach the terminal cover, rear plate bushing and air inlet grille
on the indoor unit.
Indoor unit tubing Flare nut Pipes
CAUTION
2.Tighten the flare nut with a wrench.
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
Open-end wrench (fixed)
• Check local electrical regulations for any
Flare nut specific wiring instructions or limitations.
Wrench Connection pipe
Earth wire
If drain hose extension or embedded drain piping is required,
use appropriate parts that match the hose front end. Connecting cable
Insert drain hose into the handle of drain pan, and join
drain hose and connecting hose according to the figure by.
Shield pipe
1
Terminal block
CAUTION
CAUTION
Insert the drain hose and drain cap into the drain port, mak-
ing sure that it comes in contact with the back of the drain
port, and then mount it. If the drain hose is not connected
properly, leaking will occur.
70 mm
Wiring the connecting cable can be carried out without remov- 10 mm Earth line
ing the front panel.
1. Remove the air inlet grille. Open the air inlet grille upward and
pull it toward you.
2. Remove the terminal cover and cord clamp.
10 mm
3. Insert the connecting cable (or as according to local regula- 50 mm
tions/codes) into the pipe hole on the wall.
4. Pull the connecting cable through the cable slot on the rear
panel so that it protrudes about 15 cm out of the front.
38
Installation Manual
1) No gap
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap. If applied,
2) 2. Firmly insert drain cap. deterioration and leakage of the
drain plug may occur.
Insert a hexagon wrench
• How to attach the drain hose (4 mm)
The piping can be lead out from right, right rear, left left rear. Insert the drain hose firmly until the connector contacts the insulation, then
secure it in place using the original screw.
Right-side, right-back, or right-bottom piping
1)After making slits on the front panel with a knife or similar tool, 1.After making slits on the front panel with a knife or similar tool,
cut them out with a pair of nippers or an equivalent tool. cut them out with a pair of nippers or an equivalent tool.
Attach the drain hose to the underside of the refrigerant pipes
with an adhesive vinyl tape.
2) Wrap the refrigerant pipes and drain hose together with an
insulation tape.
Slit
2.Overlap the connection pipe insulation material and the indoor
unit pipe insulation material. Bind them together with vinyl tape
so that there is no gap.
Bind with vinyl tape Plastic bands Insulation material
Right piping
Pipe (top)
Rear piping
Bottom Indoor unit drain hose
piping (bottom)
Left-side, left-back, or left-bottom piping 3.Wrap the area which accommodates the rear piping housing
• Interchange the drain cap and the drain hose. section with vinyl tape.
CAUTION Connection Indoor
pipe unit pipe
(1) In order to align the drain hose and drain cap, be
sure to insert securely and vertically. Incline inser- Vinyl tape Wrap with vinyl tape
tion will cause water leakage. (wide)
Wrap with vinyl tape
(2) When inserting, be sure not to attach any material
besides water. If any other material is attached, it
will cause deterioration and water leakage. Pipe
(3) After removing drain hose, be sure not to forget
mounting drain cap.
(4) Be sure to fix the drain hose with tape to the bottom
Vinyl tape(wide)
of piping.
Drain hose
(5) Prevent drain water frozen under low tempera-
Indoor unit
ture environment.
When installing indoor unit's drain hose outdoors, necessary Auxiliary pipes
measure for frost protection should be taken to prevent drain Connecting
cable
water frozen.
• Under low temperature environment (when outdoor tem- Installation
perature under 32 °F), after cooling operation is executed, plate
water in the drain hose could be frozen.
Once drain water is frozen, the drain hose will be blocked 4.Bundle the piping and drain hose together by wrapping them
and water leakage may be resulted for indoor unit.
with vinyl tape for enough to cover where they fit into the rear
For left outlet piping, cut off the piping housing section.
piping outlet cutting groove
with a hacksaw.
Indoor unit installation
1) Pass the drain hose and refrigerant pipes through the wall
Remove the drain cap by pulling hole, then set the indoor unit on the mounting plate hooks by
Indoor unit at the projection at the end of using the markings at the top of the indoor unit as a guide.
drain hose Drain cap the cap with pliers, etc.
39
Installation Manual
A Mounting plate
Drain-water hole
Marking
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)
2) Swing the indoor unit to right and left to confirm that it is firmly
hooked on the installation plate. Remove the Valve cover from the unit by loosening the screw.
3)While pressing the indoor unit onto the wall, hook it at the lower Align the center of the pipings and sufficiently tighten the flare
part on the installation plate. nut by hand.
Pull the indoor unit toward you to confirm that it is firmly
hooked on the installation plate.
For detaching the indoor unit from the installation plate pull the
indoor unit toward you while pushing the bottom up at the
specified places.
Finally, tighten the flare nut with torque wrench until the wrench
clicks.
Outdoor unit
Push Liquid side piping
Push (Smaller diameter)
50 mm Torque wrench
or more
Gas side piping
(Bigger diameter)
Do not put the Do not put the drain
drain hose end hose end in the
into water. drainage ditch.
5)Put water in the drain pan and make sure that the water is
being drained outside.
Caution: 2.Overlap the connection pipe insulation material and the indoor
Install the drain pipe for proper drainage. Improper drainage can unit pipe insulation material. Bind them together with vinyl tape
result in water dripping inside the room. so that there is no gap.
7.4 Installation of Outdoor Unit After the piping has been connected to the indoor unit, perform
the air purge.
* Holes are provided on the base plate of the outdoor unit to AIR PURGE
ensure that the defrost water produced during heating opera- Evacuate the air in the connecting pipes and in the indoor
tions is drained off efficiently. unit using a vacuum pump.
* If a centralized drain is required when installing the unit on a Do not use the refrigerant in the outdoor unit.
balcony or wall. For details, see the vacuum pump manual.
* If the drain port is covered by a mounting base or floor surface,
Air purging with vacuum pump
place additional foot bases of at least 30mm in height under the
Be sure to use a vacuum pump with counter-flow prevention
outdoor unit’s feet.
function so that oil inside the pump does not flow back into the
* In cold areas, do not use a drain hose with the outdoor unit.
air conditioner pipes when the pump stops. (If oil inside the
(Otherwise, drain water may freeze, impairing heating
vacuum pump enters into the air conditioner circuit which uses
performance.)
R410A, trouble with the refrigeration system may develop.)
40
Installation Manual
1. Connect the charge hose from the manifold valve to the service
port of the gas side packed valve. 1) Strip the insulation from the wire (20mm).
2. Connect the charge hose to the port of the vacuum pump. 2) Connect the connection wires between the indoor and outdoor
3. Open fully the low pressure side handle of the gauge manifold units so that the terminal numbers match. Tighten the terminal
valve. screws securely.
4. Operate the vacuum pump to begin evacuating. Perform evacu- The screws are packed with the terminal board.
ating for about 15 minutes if the piping length is 20 meters (15 Terminal block
41
Exploded Views and Parts list
42
Exploded Views and Parts list
45
Exploded Views and Parts list
PartCode
Description
NO WST12MC16S WST12MH16S Qty
Product Code CB146N0540 CB146N0550
1 Front panel 2 2001251001 2001251001 1
2 Front Case 2001237501 2001237501 1
3 Remote Controller 30510062 30510062 1
4 Rear grill sub-assy 2 11002001 11002001 1
5 Main Board 30138131 30138129 1
6 Ambient Temperature Sensor 390000453 39000305 1
7 Temperature Sensor 39000305 390000453 1
8 Indicator Light Cover 22242084 22242084 1
9 Terminal Board 42011233 42011233 1
10 Indicator shield cover 22242083 22242083 1
11 Electric Box Sub-Assy 2020227702 2020221703 1
12 Electric Box Cover Sub-Assy 20122109 20122109 1
13 Electric Box Assy 2020227602 2020217403 1
14 Drainage Pipe Sub-assy 0523204101 0523204101 1
15 Crank 73012005 73012005 1
16 Step Motor 1521210701 1521210701 1
17 Motor Press Plate 26112191 26112191 1
18 Fan Motor 1501209301 1501209301 1
19 Wall Mounting Frame 0125201801 0125201801 1
20 Rear Case assy 2220211902 2220211902 1
21 Pipe plug (outlet) 76712020 76712020 1
22 Cross Flow Fan 10352423 10352423 1
23 Helicoid tongue 26112486 26112486 1
24 Air Louver 10512160 10512160 2
25 Shaft of guide louver 1054202001 1054202001 2
26 Guide Louver 10512119 10512119 1
27 Rear grill sub-assy 24212911 24212911 1
28 Evaporator Assy 01002745 01002745 1
29 Evaporator Support 24212108 24212108 1
30 Filter Sub-Assy 1112208201 1112208201 2
31 Support of catechin 24212910 24212910 2
48
Exploded Views and Parts list
49
Exploded Views and Parts list
53
Troubleshooting
9. Troubleshooting
9.1 Precautions before Performing Inspection or Repair
Be cautious during installation and maintenance. Do operation following the regulations to avoid electric shock and casualty or even death due to drop
Take sufficient care to avoid directly touching any of the circuit parts without first turning off the power.
At times such as when the circuit board is to be replaced, place the circuit board assembly in a vertical position.
Normally,diagnose troubles according to the trouble diagnosis procedure as described below.(Refer to the check points in servicing
written on the wiring diagrams attached to the indoor/outdoor units.)
9.2 Confirmation
(1)Confirmation of Power Supply
Confirm that the power breaker operates(ON) normally;
(2)Confirmation of Power Voltage
Confirm that power voltage is AC 208~230 ± 10%.
If power voltage is not in this range, the unit may not operate normally.
57
Troubleshooting
code malfunction Error display Repair method code malfunction Error display Repair method
Dual 8 LED Dual 8 LED
display display
1 Storage slug EE Heating Replace indoor 15 Sync failure H7 Heating Check if the resistance of compressor and
LED-pause 3s main board LED-pause 3s resistance to ground is normal. If the
and blink 15 and blink 7 compressor is normal, the outdoor main
times times boar d may be wrong.
2 Indoor PCB EE Heating Replace indoor 16 Current diction U5 Cooling Replace outdoor main board
malfunction LED-pause 3s main board malfunction of LED-pause 3s
and blink 15 complete unit and blink 13
times times
3 Anti-freezing E2 Running LED- Outdoor 17 Outdoor ambient F3 Cooling Is it loose? Measure the resistance value
protection pause 3s and ambient temperature sensor LED-pause 3s with universal meter
blink 2 times temperature is malfunction and blink 3
too low times
4 Overload of H4 Heating System is 18 Discharge E4 Running Is it loose? Measure the resistance value
system LED-pause 3s abnormal, protection of LED-pause 3s with universal meter
and blink 4 check if the compressor and blink 4
times evaporator and times
condenser is
dirty and
blocked
5 No motor of H6 Running LED- Is electromotor 19 Break-circuit and F5 cooling LED- Is it loose? Measure the resistance value
indoor unit pause 3s and mounted short-circuit of pause 3s and with universal meter
feedback blink 11 times normally? outdoor discharge blink 5 times
temperature sensor
6 Indoor pipe F2 cooling LED- Is it loose? 20 Break-circuit and F4 cooling LED- Is it loose? Measure the resistance value
temperature pause 3s and Measure the short-circuit of pause 3s and with universal meter
sensor blink 2 times resistance outdoor condenser blink 18 times
malfunction value with temperature sensor
universal meter
7 Internal ambient F1 Cooling LED- Is it loose? 21 Overheat of carbon P8 heating LED- Is outdoor ambient temperature is too
temperature pause 3s and Measure the fin pause 3s and high? Is radiator mounted correctly?
sensor blink 1 times resistance blink 19 times
malfunction value with
universal meter
8 Zero passage UF Heating and Replace indoor 22 DC overcurrent UU Heating and
abnormal cooling LED main board cooling LED
blinks 7 times blink 11 times
at the same at the same
time time
9 Overload of H3 heating LED- Inspect 23 Temperature P7 heating LED- Replace outdoor main board.
compressor pause 3s and connection sensor malfunction pause 3s and
blink 3 times state of the of carbon fin blink 18 times
overload wire.
10 Startup failure Lc heating LED- Check if the 24 Lack of Freon or F0 cooling LED-
pause 3s and resistance of block protection pause 3s and
blink 11 times compressor blink 10 times
and resistance
to ground is
normal. If the
compressor is
normal, the
outdoor main
boar d may be
wrong.
11 No motor of UH Heating and This 25 DC input voltage is PH cooling LED- Is voltage of AC power supply normal?
outdoor unit cooling LED malfunction too high pause 3s and
feedback blink 8 times may happen blink 11 times
at the same when outdoor
time DC
electromotor is
used.
12 Overcurrent E5 Running LED- Is electric 26 DC input voltage is PL Heating LED- Is voltage of AC power supply normal?
protection pause 3s and network too low pause 3s and
blink 5 times variable? blink 21 times
13 4-way valve U7 cooling LED- Replace 4-way 27 Communication E6 Running LED- Is outdoor connecting wire reliably
conversion pause 3s and valve. malfunction pause 3s and connected?
abnormal blink 20 times blink 6 times
14 Phase current U1 Heating LED- Replace 28 Setting error, indoor UA Heating and Outdoor unit is not matched with indoor
detection pause 3s and outdoor main and outdoor unit cooling LED unit.
malfunction of blink 13 times board. abnormal blink 12 times
compressor at the same
time
remar 4min after protection stop of compressor, the malfunction is shown in error code. In other situation, the malfunction will be displayed by press the light button for 6 times within 4s.
ks
58
7URXEOHVKRRWLQJ
+RZWR&KHFNVLPSO\WKHPDLQSDUW
Indoor fan does not rotate without feedback
Main detection point:
z Is the control panel reliably connected with the electromotor? Is it loose? Is the connecting sequence correct?
z Is the input voltage within the normal range (measure the voltage between L and N of the wiring block XT with AC voltage gauge.)
Energize the
unit and start it
Voltage between L
and N of indoor
wiring block
Check the
Voltage > 200V? Y connecting
state of the
connecting terminal
Adjust
Reliable N
connection connecting state
N
remove the N
error?
Y
Replace motor
Y
Finish
59
Troubleshooting
Energize the
unit and start it
N
Y
Replace
temperature sensor? N Remove error? Remove error?
Y
N
Remove error?
Replace main
board of indoor unit Y
N
Y Y
Replace parts
of outdoor
electric box
Finish
60
Troubleshooting
Energize the
unit and start it
N Startup failure?
Connect it according
Is compressor wire COMP(UVW) N
to line chart
connected correctly?
Replace
compressor
finish
Y
Y
Is outdoor N
Y Remove staff Reliable connected?
fan blocked by stuff?
Is wire of compressor(U,V,W)
Y
well connected? N
Replace parts of
Replace parts of
N outdoor electric box
outdoor electric box
Y
Remove error?
N
Y Remove error? N
Y Replace
outdoor fan
N Replace
compressor
Replace
compressor
Finish
Finish
61
Troubleshooting
Is overload wire
reliably connected? N
Remove malfunction? Y
Replace parts
of outdoor electric box
Remove malfunction? Y
Refrigerant leakage,
recharge the refrigerant
Finish
E6 communication
error is displayed
Is connecting
wire reliably connected? N
Remove malfunction? Y
Replace parts of
outdoor electric box
Finish
62
Troubleshooting
Valve cap
Hexagonal wrench (4mm) Open position
Flare nut Flare nut Closed position
Open position
Closed position Pin
To To
piping piping Service Service
connection connection port cap port
To outdoor unit To outdoor unit
63
Troubleshooting
Gas side
Clsed
3-way
valve
Vacuum pump
Lo
OPEN CLOSE
* Procedure
(1)Connect the charge hose from the manifold valve to the ser- CAUTION:
vice port of the gas side packed valve. If gas leakage are discovered in step 5 above, take the
following mesures :
(2)Connect the charge hose to the port of the vacuum pump. If the gas leaks stop when the piping connections are
tightened further, continue working from step 6. If the
(3) Open fully the low pressure side handle of the gauge mani- gas leaks do not stop when the connections are
fold valve.
retightened, repair the location of the leak, discharge
all of the gas through the service port, and then recharge
(4)Operate the vacuum pump to begin evacuating. Perform
with the specified amount of gas from a gas cylinder.
evacuating for about 15 minutes if the piping length is 20 meters
(15 minutes for 20 meters) (assuming a pump capacity of 27
liters per minute). Confirm that the compound pressure gauge
reading is –101 kPa (–76 cmHg).
(8)Mount the valve stem nuts to the 2-way and 3-way valves.
64
Troubleshooting
Gas side
Closed
3-Way
valve
Lo
CLOSE CLOSE
• Procedure
(1) Confirm that both the 2-way and 3-way valves are set to (7) Immediately set the 3-way valve to the closed position.
the open position. – Do this quickly so that the gauge ends up indicating 3 to 5kg/
– Remove the valve stem caps and confirm that the valve stems cm2g.
are in the raised position.
– Be sure to use a hexagonal wrench to operate the valve stems.
(8) Disconnect the charge set, and mount the 2-way and 3-
way valve’s stem nuts and the service port nut.
(2) Operate the unit for 10 to 15 minutes. – Use torque wrench to tighten the service port nut to a torque of
1.8 kg.m.
– Be sure to check for gas leakage.
(3) Stop operation and wait for 3 minutes, then connect the
charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to the service port.
(6) Operate the air conditioner at the cooling cycle and stop it
when the gauge indicates 1kg/cm2g.
65
Troubleshooting
Gas side
Closed
3-Way
valve
Gas cylinder
Lo
R410A OPEN CLOSE
• Procedure
(1) Confirm that both the liquid side valve and the gas side (6) Disconnect the charge set and the gas cylinder, and set
balve are set to the closed position. the Liquid side and Gas side valves to the open position.
– Be sure to use a hexagonal wrench to operate the valve stems.
(2) Connect the charge set and a gas cylinder to the service
port of the Gas side valve. (7) Mount the valve stem nuts and the service port nut.
– Leave the valve on the gas cylinder closed. – Use torque wrench to tighten the service port nut to a torque of
1.8 kg.m.
– Be sure to check for gas leakage.
(3) Air purging.
– Open the valves on the gas cylinder and the charge set. Purge
the air by loosening the flare nut on the liquid side valve ap-
proximately 45o or 3 seconds then closing it for 1 minute;repeat
3 times. CAUTION: Do not leak the gas in the air during Air Purging.
– After purging the air, use a torque wrench to tighten the flare
nut on liquid side valve.
66
Troubleshooting
Gas side
3-Way
valve Open
Lo
OPEN CLOSE
• Procedure
(1) Confirm that both the 2-way and 3-way valves (3) Open the valve (Lo side) on the charge set and
are set to the back seat. discharge the refrigerant until the gauge indi-
cates 0 kg/cm2G.
(2) Connect the charge set to the 3-way valve’s – If there is no air in the refrigerant cycle (the
port. pressure when the air conditioner is not running
– Leave the valve on the charge set closed. is higher than 1 kg/cm2G), discharge the refrig-
– Connect the charge hose to the service port. erant until the gauge indicates 0.5 to 1
kg/cm2G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
67
Troubleshooting
Evacuation
(All amount of refrigerant leaked)
Gas side
3-Way
valve Open
Vacuum pump
Lo
OPEN CLOSE
• Procedure
(1) Connect the vacuum pump to the center hose (3) Close the valve (Lo side) on the charge set,
of charge set center hose turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
(2) Evacuation for approximately one hour. tely 5 minutes after turning off the vacuum
– Confirm that the gauge needle has moved pump).
toward -76 cmHg (vacuum of 4 mmHg or less).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
68
Troubleshooting
Gas Charging
(After Evacuation)
Gas side
Open
3-Way
Check valve valve
Charging
cylinder
Lo
(1) OPEN CLOSE
• Procedure
\
(1) Connect the charge hose to the charging This is different from previous procedures.
cylinder. Because you are charging with liquid refrigerant
– Connect the charge hose which you dis-con- from the gas side, absolutely do not attempt to
nected from the vacuum pump to the valve at charge with larger amounts of liquid refrigerant
the bottom of the cylinder. while operating the air conditioner.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys-
tem can be charged with liquid. (4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
(2) Purge the air from the charge hose. – Stopping partway will allow the gas to be dis-
– Open the valve at the bottom of the cylinder charged.
and press the check valve on the charge set to – If the system has been charged with liquid
purge the air. (Be careful of the liquid refriger- refrigerant while operating the air conditioner
ant). The procedure is the same if using a gas turn off the air conditioner before disconnecting
cylinder. the hose.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant. (5) Mount the valve stem nuts and the service
– If the system can not be charged with the spec- port nut.
ified amount of refrigerant, it can be charged – Use torque wrench to tighten the service port
with a little at a time (approximately 150g each nut to a torque of 1.8 kg.m.
time) while operating the air conditioner in the – Be sure to check for gas leakage.
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then (Note: Below information only for reference)
repeat the procedure (pumping down-pin).
69
Removal Procedure
Hooks
70
Removal Procedure
Right
Rotary shaft
71
Removal Procedure
1 Remove a service
cover mounting screw.
Open service cover
upward.
screws
5. Removal of front grille assembly
72
Removal Procedure
Hooks
1 Unfasten the hooks at
the upper 2 positions.
Hooks
Vertical blade
73
Removal Procedure
Terminal board
2 Disconnect the
connection wires.
Connecting
wires
(R11268)
(R11244)
74
Removal Procedure
Bottom frame
Hook
75
Removal Procedure
Hooks
76
Removal Procedure
Swing motor
77
Removal Procedure
78
Removal Procedure
CAUTION
Wooden base
Do not contaminate any gas
(including air) other than the
specified refrigerant (R-410A)
into refrigerant cycle.
(Contaminating of air or other
2 Place a plastic sheet gas causes abnormal high
under the drain pan as pressure in refrigerating
remaining drain may cycle, and this results in pipe
leak.
breakage or personal
injuries.)
Drain hose
Extension drain hose
Connecting wires
79
Removal Procedure
Liquid piping
Gas piping (R8019)
80
Removal Procedure
Auxiliary piping
81
Removal Procedure
Bearing
82
Removal Procedure
83
Removal Procedure
1. Features
84
Removal Procedure
Front panel.
85
Removal Procedure
Fan motor
Partition plate
86
Removal Procedure
Sound blanket.
Caution
Be careful about the four way
valve, pipes and so on, which
were heated up by a gas
brazing machine, so as not
to get burnt your hands.
87
Removal Procedure
Remove compressor
88
11. Care and Cleaning
11ˊCleaning Refrigeration System
In addition to replacement of compressor, capillary and strainer, the whole refrigeration system
shall be completely cleaned, as the refrigerant in the system is contaminated by a lot of acid HEAT EXCHANGE
(EVAPORATOR)
oxydum generated from insulation breakdown, turn-to-turn short circuit or burning out of winding
of compressor’s motor during malfunction.
The refrigeration oil in the mild-contaminated refrigeration system shall be limpid when
discharging from the process pipe of compressor. It shall be faint yellow (normally white) if
COMPRESSOR CAPLIARY
testing by lacmus paper. While severe- contaminated, it is black and the testing lacmus paper HEAT EXCHANGE
(CONDENSER)
becomes red 5min later.
The abluent R113 is used to clean the system.
STRAINER
Confirm the contamination degree by checking color and smell of refrigerant before cleaning BATH
PUMP 槽
the system, as shown in the figure.
Check the refrigeration oil for impurity by discharging a little of oil from the process pipe of
compressor.
Cleaning Procedure:
1. Charge the abluent R113 into the fluid bath. Start up the pump to clean the system about
1hr if mid-contaminated or 3-4hr if severe-contaminated. In order to avoid blockage of strainer,
the abluent and the strainer shall be replaced after long-time cleaning.
2. The abluent after cleaning of the system can be recovered from liquid pipe and it can be
reused after processing.
3. The refrigeration pipeline should be blown off by nitrogen and dried after cleaning.
Disconnect the parts in the broken frame with the pipeline and install blind plates on ring
flanges of liquid suction and pumping pipes before drying process. In order to quickly dry the
system, make vacuum pumping while blow off hot wind to external refrigeration pipeline.
Afterwards, reassemble the pipeline (charge nitrogen while welding) and replace the
compressor and strainer.
Cautions:
1. In order to avoid leakage of abluent, pressure hose should be adopted and joint parts
should be tightly wrapped.
2. The expansion valve adopted by the unit shall be replaced by by-pass pipe.
3. Remove the moisture contained in the refrigeration system.
4. Use nitrogen to blow off the acid generated from burning out of compressor
89