INVERTER LCD FRONT PANEL USER MANUAL

 
BUTTONS 

MENU SELECT BUTTONS  


MENU SELECT buttons are used to navigate between menus.

MENU SET BUTTONS


MENU SET buttons are used to make settings on menus. USE “UP” button to set the parameter
on the upper side and use DOWN button to set the parameters on the below.
Buttons are operated by pushing and holding for 1 second. After making the adjustments /setting
by using UP and DOWN buttons, settings can be saved by using RIGHT button. To cancel the
menu without saving, LEFT button is used.
MENU SET buttons increase the parameter. After parameter reaches to the maximum value,
parameter value will go back to the minimum and keep increasing from the minimum to
maximum again. So, for decreasing a parameter, value must be increased to maximum and after
reaching to minimum, desired value can be achieved by increasing the parameter from minimum.

NOTE-1: The values below are chosen for inverter with 1 phase bypass input, 144V DC input, 1
phase output.
NOTE-2: The values signed with RED are the values that can be adjusted by MENU SET
buttons. After parameter setting is finished, RIGHT button will save and navigate to the next
menu and LEFT button will navigate to the previous menu without saving. To operate the
buttons, push to the button and hold for 1 sec.
MENU WINDOWS 
MENU‐1: Opening Window 
To make inverter “ON”, push to the UP button. To make inverter
     “OFF”, push to the DOWN button. While the inverter is “OFF”,
load will be supplied from the bypass if by-pass is connected.

 
MENU‐2: Output Monitoring Window (Main Menu and Screen Saver)
(V) Output Voltage, (LOAD) Output Load % and (f) Output
Frequency can be monitored from this screen.
 
MENU-3: By-Pass Monitoring Window
(V) By-Pass Voltage (LOAD) By-Pass Load % ve (f) By-Pass
Frequency can be monitored from this screen.
 
MENU ‐4: DC Bus Voltage and Device Internal Temperature Monitoring Window
(DC BUS) DC Bus Voltage and (internal T) device internal
temperature can be monitored from this screen.
   

Since above 3 windows are monitoring menus, MENU SET buttons   are not used. 

MENU ‐5: Operating Mode and Automatic “ON” Setting Window

Push  UP  button  to  select  “Invertor  operating  mode”  and  push 
DOWN button for “Auto On” selection.  
     

‐There are 3 options for “inverter operating mode”: 
  1. UPS    2.Eco    3.By‐Pass Inh.  

MENU ‐6: Output Voltage Setting Window  
To increase inverter Output Voltage, push UP button. To
decrease inverter Output Voltage, push DOWN button.
 
MENU -7: Minimum DC Bus and Low Battery Voltage Setting Window

Push UP button to adjust “Auto On” voltage level. 
  Push DOWN button to adjust “Low Battery” alarm level.  
MENU -8 :Date Time Setting
 
 
On the screen, date is 03 April 2010 and time is 12:32:55.
Date and time is adjustable by using UP and DOWN
       buttons. UP button is for navigation between menus and
DOWN button is to increase.
 

 
MENU -9: Event History and Monitoring Window
 
The events on the history can be monitored from this menu.
Maximum 250 last events are stored. There are 29 different
event codes. In the example on the left side, first event is
   
shown from 32 events in total. All events can be monitored
  using UP and DOWN buttons.
7 : Event Code   180 : Event Value  3 : Day 
  4 : Month    12 : Hour     35:  Minute  
Event history can be erased by pushing to the RIGHT button
  for 20 seconds. This action will reset the software to the
 
factory settings.
Explanations of the event codes are given as below:
 

Event Codes
0. Output High 10. Load on By-Pass 20. Back Feed Normal
1. Output Low 11. Maintenance Switch ON 21. Inverter Aşırı Yüklü
2. Output Normal 12. Maintenance Switch OFF 22. Yük Normal
23. DC Fuse Tripped / DC MCB
3. By-Pass High/Low 13. Over Temperature
OFF
24. DC Fuse Normal / DC MCB
4. By-Pass Normal 14. Temperature Normal
ON
25. By-Pass Fuse Tripped / DC
5. Battery Fuse Tripped 15. Inverter Failure
MCB OFF
26. By-Pass Fuse Normal / DC
6. Battery Fuse Normal 16. Inverter Normal
MCB ON
7. DC High/Low 17. IGBT SCR Fuse Tripped 27. Internal over temperature
8. DC Normal 18. IGBT SCR Fuse Normal 28. Internal temperature Normal
9. Load on Inverter 19. Back Feed Failure
 
 
MENU ‐10: Alarm and Communication Window 
Alarm sound can be increased or can be made OFF by using
UP button.
    RS-485 communication address number can be adjusted by
 
  DOWN button.
MENU ‐11 :Output Frequency Setting Window 

Output frequency can be selected as 50Hz or 60Hz by UP


    and DOWN buttons.
 
 
 
 
 
 
 MENU -12 : Password Window 

To activate the user password, create a “new password” by


    using UP and DOWN buttons and save.
To cancel your  password, enter the valid password, then
enter “0-0-0-0”  and save. In case of forgotten password,
  push to the RIGHT button for 20 seconds and reset the
software to the factory settings.
INVERTER FRONT PANEL STATUS & ALARM INDICATIONS

Bypass/Mains and Inverter Output is not synchronous. While this LED is


active, transfer between Inverter and Bypass will be inhibited

DC bus voltage value is higher than maximum (or lower than minimum)
DC Bus voltage value. If this LED becomes on, then the Inverter will be
shut down.

By-Pass voltage is out of the operating range (+/-%15). In this case, load
will not be transferred from inverter to bypass and if inverter is “OFF”,
inverter does not start and become “ON”.

Battery fuse is in “OFF” position or By-Pass SCR Fuse is


  tripped (open circuit). In this case, load will not be
transferred from inverter to bypass and if inverter is “OFF”,
  inverter does not start and become “ON”.
DC input fuse is in “OFF” position.

Output load current exceeds %100 load current limit. In this condition,
the operating periods are as follow: %100-%125 10min., %125-%150 1
min., %150-%300 5 sec., at %300 0 sec.

Device internal temperature exceeds 55°C. If temperature do not return to


normal conditions in 2 min., the device will shut down itself.

The fast acting fuse which protects the IGBT modules is tripped (open
circuit).

If the temperature of the cooler on the By-Pass and Output Thyristors


exceeds 70°C, this LED flashes continuously. After 1,5 min., the device
shut downs itself and this LED remains “ON” permanently.

Inverter output voltage is higher than the voltage range of +%15 due to
an unexpected situation.

Inverter output voltage is lower than the voltage range of -%15 due to an
unexpected situation.
If the temperature of the cooler on the IGBT modules exceeds 70°C, this
LED flashes continuously. After 1,5 min., the device shut downs itself and
this LED remains “ON” permanently.

The load is supplied through By-Pass.

DC bus voltage value is between the input DC range of Inverter.

The load is supplied through Inverter.


Device is shut down due to a failure. If this LED is “ON” then, one or more
red (failure) LEDs must be “ON” as well, depending on the reason of the
failure.

Inverter can be started without Bypass while this mode is active.

The system is in OFF-LINE mode. As long as the Bypass/Mains voltage


is present, load is supplied through By-Pass. When Bypass/Mains voltage
is out of range, load is transferred to inverter without interruption and
load is supplied continuously.

This UPS is in Auto ON mode which enables to automatically start the


UPS if the UPS shut down itself due to an alarm (except the red LED
alarms) and afterwards returns back to normal conditions.

Transfer Switch (3 Position) is on Maintenance Bypass Mode. 
If the inverter is “ON” and Transfer switch position is changed 
to  Maintenance  Bypass  Mode,  then  Inverter  will  be  shut 
down automatically and will not start as long as Maintenance 
switch is “ON”.   