Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CHAPTER I
THE PROBLEM AND ITS BACKGROUND
The Chapter 1 should contain a discussion of each of the following topics:
1.1 Introduction
1.2 Background of the study
1.3 Objectives
1.4 Significance
1.5 Scope and Limitations
1.6 Conceptual Framework
1.7 Operational Definition of Terms
1.8 Design Considerations
PAGE|2
1.1 INTRODUCTION
In the most general sense, air conditioning can refer to any form of technology that
modifies the condition of air (heating, (de-)humidification, cooling, cleaning, ventilation, or
air movement). In common usage, though, "air conditioning" refers to systems which cool
air. In construction, a complete system of heating, ventilation, and air conditioning is
referred to as HVAC. The basic concept behind air conditioning is said to have been
applied in ancient Egypt, where needs were hung in windows and were moistened with
tricking water. The evaporation of water cooled the air blowing through the window. This
process also made the air more humid, which can be beneficial in a dry desert climate. In
Ancient Rome, water from aqueducts was circulated through the walls of certain houses
to cool them. Other techniques in medieval Persia involved the use of cisternsand wind
towers to cool buildings during the hot season.
by American inventor Willis Carrier. The introduction of residential air conditioning in the
1920s helped enable the great migration to the Sun Belt in the United States.
The first modern air conditioning system was developed in 1920 by a young
electrical engineer named Willis Haviland Carrier. It was designed to solve a humidity
problem at the Sackett-Wilhelm Lithographing and Publishing Company in Brooklyn. N.Y.
Paper stock at the plant would sometimes absorb moisture from the warm summer air,
making it difficult to apply the layered inking techniques of the time. Carrier treated the air
inside the building by blowing it across chilled pipes. The air cooled as it passed across
the cooled pipes, since cool air can’t carry as much moisture as warm air, the process
reduced the humidity in the plant and stabilized the moisture content of the paper.
Reducing the humidity also had the side benefit of lowering the air temperature and a
new technology was born.
Most homes in warm climates have air conditioning. For some air conditioning may
be a luxury, but for many, it is a necessity. Given the expense of the equipment and the
power to run it, ASHRAE wants consumers to be informed about their air conditioning
systems. These ten points should make a consumers more aware of the air conditioning
system and better able to care for it and use it well. Should it become necessary to replace
that system, seek out a qualified HVAC professional. The previous points have focused
on cooling, but the original definition of air conditioning contains more than that; an ideal
air conditioner should heat, cool, clean, ventilate, humidity and dehumidify as needed to
provide health and comfort. In fact the second most important objective of the original
definition is to provide ventilation. Whether or not the piece of equipment we call an air
conditioner provides it, ventilation is needed.
PAGE|4
The BPO is owned and personally operated by managers who have been in the
industry for many years. We pride ourselves of our experienced, professional and hard
working team who are all fluent, well versed in English and graduates of prestigious
colleges and universities.
Asia Pacific Business Process Outsourcing values excellence and integrity. Our
center makes sure that we exhaust all means necessary for our clients to get their
money’s worth and more. Our services are fairly priced and affordable but at the same
time of high quality. Contact us and let us know more about what your requirements are,
so we find the best way to provide you optimum results.
PAGE|5
The general objective of a study states what researchers expect to achieve by the
study in general terms. It is possible (and advisable) to break down a general objective
into smaller, logically connected parts. These are normally referred to as specific
objectives. Specific objectives should systematically address the various research
questions. They should specify what you will do in your study, where and for what
purpose.
1. To develop a smart air quality monitoring system that can intelligently interface
with existing ventilation and air treatment systems to maximize their energy
efficiency and effectiveness.
1. Extreme conditions such as heat and humidity can impact on our overall physical
intellectual activity, making even the simplest of tasks an absolute chore. Having a
proper air conditioning system in place helps reduce heat and humidity, thus reducing
the impact on our ability to perform and complete work tasks.
2. The lower temperatures that air conditioners create can help reduce dehydration as
they lessen the likelihood of excessive sweating. However, there is a footnote worth
mentioning here, which we will discuss later in this article.
3. When the air conditioning system has been installed properly, it effectively helps
renew and improve air quality.
PAGE|8
First of all, there is a footnote that comes with the fact that air conditioners can help
reduce dehydration in terms of staving off sweating, their design also means that they
also cause dehydration.
To keep it basic, air conditioning works by reducing the humidity and heat within
an a set environment. The way it does this is by removing moisture from the air and then
pushing cooler temperatures through; this known as evaporation cooling. Over time this
means the area will have less and less moisture in the air, which can lead to dehydration.
2. Be mindful of the fact that sudden shifts in temperature (from very hot to very cold)
can impact on your health. Such shifts can affect respiratory system and can lead to
falling sick. The suggested ideal temperature for an air condition units ranges
anywhere between 21 to 25 degrees Celsius. Keep it within that range and you’ll find
that the shift between temperatures won’t feel as severe. If it starts to get too cold
within you vehicle or sleeper cabin, put the temperature up one or two degrees.
3. Another effect long exposure to an air conditioned environment can have is that of
tiredness. Particularly when using recycled air, this leads to an increase in CO2 while
straight oxygen reduces. To combat this, either change your air conditioner to accept
incoming air from outside or occasionally turn off your air conditioning, roll down the
windows and let the fresh air wake you back up.
PAGE|9
From the review of related literature and studies, the researcher may formulate a
theoretical scheme for his research problem. This scheme is a tentative explanation or
theoretical explanation of the phenomenon or problem and serves as a basis for the
formulation research hypotheses. Thus, the conceptual framework consists of the
investigator’s own position on a problem after his exposure to various theories that have
bearing on the problem. It is the researcher’s new model which has its roots on the
previous model which the researcher had studied.
PAGE|10
The basic requirements for realistic estimates of heating and cooling loads is an
accurate survey of the load components of the space to be air conditioned.
1. Orientation of the building geographic location of the space to be air conditioned with
respect to:
a. Compass Points – sun and wind effects
b. Nearby Permanent Structures – shading effect
c. Reflective Surfaces – water, sand, parking lots etc.
2. Use of Space(s) – office, hospital, department store, specially shop, factory, machine
shop, assembly parts, etc.
4. Ceiling height – floor to floor height, floor to ceiling, clearance between suspended
ceiling beams.
5. Construction Materials – types of materials, thickness for floors, walls, roof, ceiling
floors, partitions and their relative positions in the structure.
6. Surrounding Conditions – exterior color of the wall and roof, shaded by adjacent
building or sunlight. Attic spaces vented or unvented, gravity or force ventilation.
Surrounding spaces conditioned or unconditioned temperature of non-conditioned
adjacent space such as furnace and boiler room and kitchen. Floor on ground, crawl
space and basement.
7. Windows – type of glass, single or multi-plane, wood or metal sash, single or double
hung, size and location type of shading device, dimension of reveals and overhangs.
PAGE|11
10. Lighting type – incandescent, fluorescent, recessed, exposed wattage of lamps and
type of fixture if the lights are recessed, the type of air flow over the lights, exhaust, return
or supply, should be anticipated. At times it is required to estimate the wattage on a basis
of watts per square meter, due to lack of exact information.
12. Ventilation – one per person, cms per square meter scheduled ventilation. Excessive
smoking or odors, code requirements. Exhaust fans – type, size, speed and cms delivery.
13. Thermal storage – includes system operating scheduled (12, 16 or 24 hours per day
) specifically during peak outdoor conditions, permissible temperature swing in space
during a design days, rugs or floors, nature of space materials enclosing the space.
4. Analysis – Before the frame can be analyzed and the structural members
designed it is necessary to determine the magnitude the loads and other actions such as
thermal movements, which may result in stresses in the structure. The main load types
are the self-weight of the structure (and non-structural components), imposed floor
PAGE|13
loadings, environmental loading including wind and snow, and induced additional loads
caused by frame imperfections and away.
CHAPTER II
REVIEW OF RELATED LITERATURE AND STUDIES
The chapter 2 should contain a discussion of each of the following topics:
Water Systems. These systems include chilled water, hot water and
condenser water systems. A water system consists of pumps, piping work, and
accessories. The water system is sometimes called the water side of a central or space-
conditioning system. Central Plant Refrigeration and Heating Systems. The refrigeration
system in the central plant of a central system is usually in the form of a chiller package
with an outdoor condensing unit. The refrigeration system is also called the refrigeration
side of a central system. A boiler and accessories make up the heating system in a central
PAGE|17
plant for a central system, and a direct-fired gas furnace is often the heating system in
the air handler of a rooftop packaged system. Control Systems. Control systems usually
consist of sensors, a microprocessor- based direct digital controller (DDC), a control
device, control elements, personal computer (PC), and communication network. Based
on Commercial Buildings Characteristics 1992, Energy Information Administration (EIA)
of the Department of Energy of United States in 1992, for commercial buildings having a
total floor area of 67,876 million , of which 57,041 million or 84% is cooled and 61,996
million or 91% is heated, the air-conditioning systems for cooling include: Individual
systems 19,239 million (25%) Packaged systems 34,753 million (49%) Central System
14,048 million (26%) Space – Conditioning systems are included in central systems. Part
of the cooled floor area has been counted for both individual and packaged systems. The
sum of the floor areas for these three systems therefore exceeds the total cooled area of
57,041 million .
(http://www.itiomar.it/pubblica/dispense/MECHANICAL%20ENGINEERING%20HANDB
OOK/Ch09.pdf)
PAGE|18
In the next two levels, students continue their learning in controls, forced air
gas/oil heating systems, hydronics, as well as refrigeration concepts while continuing to
work on essential skills in communications, ethics, mathematics and related sciences.
PAGE|19
Bring Your Own Device (BYOD): Students are expected to have and use a
laptop or mobile computing device when registered in this on-campus program. Hardware
and software specifications required by your program are outlined at
http://algonquincollege.com/byod. Mobile devices/laptops and supplies can be purchased
directly from Algonquin’s New Technology Store at Educational rates.
SUCCESS FACTORS:
This program is well-suited for students who:
Enjoy a hands-on approach to learning about the heating, refrigeration and air
conditioning industry.
(http://www.algonquincollege.com/acce/program/heating-refrigeration-and-air-
conditioning-technician/#courses)
PAGE|20
2.4 SYNTHESIS
CHAPTER III
RESEARCH METHODOLOGY
Suppose the descriptive method of the research was used in the study of the
teaching of science in the high schools of Province A. Briefly the discussion follows: The
descriptive method of research was used in the study. Descriptive method of research is
a fact-finding study with adequate and accurate interpretation of the findings. It
describes with emphasis what actually exist such as current conditions, practices,
situations, or any phenomena. Since the present study or investigation was concerned
with the present status of the teaching of science in the high schools of Province A, the
descriptive method of research was the most appropriate method to use.
PAGE|24
OUTDOOR CONDITIONS:
Temperature: Dry bulb = 35°C
Wet bulb = 22°C
Daily Range = 11°C
Wind Velocity: 55 m/s
INDOOR CONDITIONS:
Relative Humidity (Ǿ) = 50%
Dry bulb = 22°C
The Current Cooling Load Temperature (CLTD) / Cooling Load Factor (CLF)
method was developed as a hand calculation method, which would use tabulated CLTD
and CLF values. The tabulated CLTD and CLF data were calculated using the transfer
function method, which yielded cooling loads for standard environmental conditions and
zone types.
The CLTD/CLF method uses predetermined set of data to expedite and simplify
the process of cooling/heating load approximation. The data is divided into many
different sections based on many different variables. These variables include external
loads ( heat gain through roofs, heat gain through walls, glass and partition, roof, floors,
slabs) and internal loads ( people, lighting, appliances and ventilation, infiltration).
EXTERNAL LOADS
g. Insulations
= [( CLTD+LM) K+ (25.5 - ) + (- 29.4)] f
Where:
CLTD - Cooling Load Temperature Difference based on Table 3.8
K – Color adjustment factor and is applied after first making month latitude
adjustment
F – Factor for attic fan or ducts about ceiling applied after all other
adjustments have been made
= (U)(A)()
Where:
C. GLASS
Where:
SHGF – maximum solar heat gain by orientation latitude and month from
Table 3.25
Q= UAΔT
Where:
INTERNAL LOADS
A. PEOPLE (OCCUPANTS)
= (/person)(no. of people)(CLF)
B. LIGHTING
Q=q(Fu)(Fs)(CLF)
Where:
q – power rating
Fs – ballast factor
C. APPLIANCES
= (q)(Cs)(CLF)
= (q)()
Where:
PAGE|29
q – power rating
= 1.23QΔT
= 3010QΔW
Where:
The heat gain through building structure such as walls, floors, doors and window
constitutes the major portion of sensible heat load. Passive cooling is a building design
approach that focuses on heat gain control and heat dissipation in a building in order to
improve the indoor thermal comfort with low or nil energy consumption. This approach
works either by preventing heat from entering the interior ( heat gain prevention ) or by
removing heat from the building ( natural cooling ) utilizes on-site energy, available from
the natural environment, combined with the architectural design of building components
(e.g. building envelope), rather than mechanical systems to dissipate heat. Therefore,
natural cooling depends not only on the architectural design of the building but how it
uses the local site natural resources as heat sinks (i.e. everything that absorbs or
dissipates heat.)
Heat gain due to solar energy incident on a surface will defend upon the physical
characteristics. For transparent surface, such as windows, the solar energy passing
through the surfaces in watts is:
= (SC)(SHGF)(A)(CLF)
Where:
SC – shading coefficient
A shading coefficient Sc is used to adjust the SHGF values for other types of
glass or to account for inside shading devices. Typical values of the shading coefficient
SC for several types of glass with and without internal shading are presented in table. If
the internal surfaces shade the window, SHGF values for north latitude are for the
shaded portion of the windows.
One more factor must be considered since the solar energy entering the spaces
does not appear instantaneously as a load on the cooling system. The radiant energy is
first, absorbed by the surfaces in the space, during which time these surface
temperatures increase at a rate dependent on their dynamic thermal characteristics.
Thus, the solar absorbed is delayed before being transferred to the air in the space by
convection. Since this process may involve a significant time lag, it is also usual to
include cooling load factor calculating the cooling load attributable to radiation through
PAGE|32
glass values of CLF derived from an extensive computer analysis are presented in
table.
PAGE|33
3.6 HEAT GAIN THROUGH INFILTRATION ON AIR LEAKAGE WITH THE SPACE
Infiltration is the uncontrolled entry of unconditioned outside air directly into the
building, resulting from natural forces, such as wind and buoyancy due to the
temperature difference inside and outside.
Recommended infiltration rates are ½ air change per hour for most air conditioning
cases or ¼ air change per hour for double glazing or if special measure have been
taken to prevent infiltration.
PAGE|34
= RATING × Fu ×
Where:
= (CLF)
Where:
CLF – cooling load factor from the table 4-6 no. of hours after light are turned on
vs. hours of operation
CLF = 0.72
CLF = 0.75
CLF = 0.78
PAGE|35
= Cooling load in W
INTERNAL LOAD
The various internal loads consist of sensible and latent heat transfer due to
occupants, processes appliances and lighting. The lighting load is only sensible, the
conversion of sensible heat gain (from lighting, people, appliances, etc.) to space cooling
load is affected by the thermal storage characteristics of that space and is thus subject to
appropriate cooling load factors to account for the time lag of the cooling load caused by
the building mass. The weighing factors equation determine the CLF factors. CLF= Q
cooling load / Q internal gains.
For heat producing equipment, it is also necessary to estimate the power used
along with the period and/or frequency of use in a manner similar to that used for lighting.
For equipment having a little radiant energy transmission the CLF can be assumed equal
to 1.
Internal heat gain is the sensible and latent heat emitted within an internal space
from any source that is to be removed by air conditioning or ventilation, and/or results in
an increase in the temperature and humidity within the space. Benchmark values for
internal heat gains are based on either surveys of measured internal heat gains from a
number of buildings of particular types and usage, or empirical values found appropriate
from experience, survey and considered good practice in the industry.
PAGE|36
PEOPLE
All active animal bodies including humans lose heat to their surroundings due to
their metabolic activity, which is related to the activity to subject in performing (i.e
sedentary, sleeping, dancing etc.). The heat can be released as sensible or latent heat.
The sensible heat release is due to the higher temperature the surface of the skin can
have in respect to the surrounding environment, while the latent heat is released by
means of respiration and sweating. Table 6.3 provides representatives heat emissions
from an average adult male in different states of activity. The figures for a mixture of males
and females assume typical percentages of men, women and children for the stated
building types.
Where:
N-p = number of people (maximum or design from occupancy criteria for building)
day = 0 when there are no people in the room = 1 when the maximum design
number of people are in the room 0<=Fd<=1
qs = sensible heat gain (SHG) per person for the degree or type of activity in the
space (ASHRAE table 8.18)
ql = latent heat gain (LGH) per person for the degree or type of activity in the space
(ASHRAE Table 8.18)
CLF-h = cooling load factor (CLF) for the given hour. This depends on the zone
type, hour entering space, and number of hours after entering into space (ASHRAE
Table 8.19)
The sensible heat has to be first absorbed by the surroundings and then released
into the air. The cooling load factor accounts for this time delay. The latent heat is an
instantaneous cooling load so there is no cooling load factor associated with it. The
following table gives example of SGH and LGH from people. It demonstrates the range
of heat gain value due to people. When this information is combined with design space
occurancy density (25 /person for an aerobics class and 250 /person for an apartment)
the heat gain from people becomes very significant.
LIGHT
All the electrical energy used by a lamp is ultimately released as heat. The energy
is emitted by means of conduction, conduction, convection or radiation. When the light is
switched on the luminaire itself absorbs some of the heat emitted by the lamp. Some of
this heat may then be transmitted to the building structure, depending on the manner in
twhich the luminaire is mounted. The radiation energy emitted from a lamp will result in
the heat gain to the space only after it has been absorbed by the room surfaces.this
storage effect results in a time lag before the heat appears as a part of the cooling load.
In determining the internal heat gain due to artificial lighting the following must be known:
PAGE|38
*Total electrical input power *Fraction of heat emitted which enters the space *Radiant,
convective and conductive ratio of the heat emitted by the lighting system.
The heat release of lighting and appliances is then linked to the total floor area of
the building. This approximation is based on the experience that larger houses generally
have a larger number of lights and other appliances. Special features like heated fish-
tanks contribute, as well.
𝑸𝒔 = 𝒎𝒑 𝑪𝒑 (𝒕𝒑 − 𝒕𝒓 )
Where :
𝒕𝒓 = room temperature,
𝒕𝒑 = product temperature,
Where:
The entry of outside air into the space influence both the air temperature and
humidity level in the space. Usually a distinction is made between two effects, referring
to the temperature effect as sensible load and the humidity effect as latent load.
INFILTRATION
Where:
V = wind velocity
= 49 m/s
THE DUCT SYSTEM, used in air heating and air cooling your home, is a collection
of tubes that distributes the heated or cooled air to the various rooms. This system can
make a big difference in both the cost and the effectiveness of of heating and cooling the
home. The duct system can have an important effect on health of the occupants through
the distribution of indoor air pollution. Changes and repairs to a duct system should
always be performed by a qualified professionals.
Ducts are used in heating, ventilation and air conditioning (HVAC) to deliver and
remove air, and exhaust air. Ducts commonly also deliver ventilation air as part of the
supply air. As such, air ducts are one method of ensuring acceptance indoor air quality
as well as thermal comfort.
Duct work on the principle air pressure difference. It is a pressure difference exists,
air will move from the higher pressure area to the lower pressure places. The greater this
pressure difference, the faster the air flow. Ducts commonly used for carrying air are
round, square or rectangular. The square or rectangular conforms better to building
construction. It fits into walls and calling better than round ducts. It is easier to install
rectangular ducts between joints and studs. For the design, we used a rectangular duct.
DUCT SIZING
Velocity method
Constant pressure loss method (or equal friction method)
PAGE|43
The main goal of designing HVAC duct systems is to use the lowest cost ( read
smallest ) duct sizes that can be used without violating certain sizing constraits. First and
operating cost considerations dictate that duct systems should be designed to operate at
the lowest possible static pressure. The most widely used method to size duct is constant
friction loss method. The other methods are velocity reduction method and static regain
method.
EQUATIONS:
f = friction factor
p = density, kg/
D = duct diameter
∈ 𝑣2
ΔP =
2𝑔
Where:
v – velocity of air
Lay out the most convenient system of placing the various ducts to obtain
adequate distribution and to facilitate construction.
From the heating or cooling load, calculate the air requirements at each duct, zone,
or division of the building.
Determine the sizes of these outlet branches, using a proper velocity or pressure
drop to deliver the required quantity.
Calculate the size of each duct by one of the following methods:
- The assumed velocity method
- The constant pressure drop method
- Balanced pressure loss method
- Static regain method
Determine from the calculations described in procedure 4, the circuit that offers the
greatest frictional resistance. It is not necessarily true that the selected circuit is
frequently the longest circuit. The maximum resistance determines the static
pressure the fan must deliver to supply the air through the ducts.
Most common elbows used in duct system are of 90 – degree turn, either circular
or rectangular section.
𝑣2
Ploss = 𝜌 (geometric factor)
2
BRANCH TAKEOFFS
When a main duct supplies air to several branch ducts, a takeoff must be provided
for each branch. From the upstream position 1 there is a pressure loss both to the
downstream position 2 and into the branch to point 3.
The pressure loss 1 to 2 is due to the pressure build-up from the higher velocity at
1 to the lower velocity at 2.
𝜌 𝑣
Ploss = v22 ( )(0.4) (1- 𝑣2 )2
2 1
Where:
V = velocity, m/s
The pressure loss is expressed in terms of p for several different angles of takeoff.
(𝑣3 )
= 𝜌 ( geometric factor ), Pa
2
Since rectangular ducts are widely used in an air conditioning practice, an equation
for the pressure drop in rectangular duct is necessary, as presented below.
𝐿 𝑣2
Δp = f 𝐷 𝜌
𝑒𝑞 2
Where:
𝑓(𝑎+𝑏)𝐿𝑣 2 𝜌
Then the equation of Δp = 4𝑎𝑏
Determination of pressure drop using fig. 6-2 (stocker, p 107) and using the new
equivalent diameter.
Deq = 1.3
Where:
RELATED DESIGN
The CACS of Al Goto King in Balagtas, Batangas City will be designed similar to
the view, section and isometric layout presented below.
PAGE|47
Fan power ( FP ) is a parameter that qualifies the energy efficiency of fan air
movement systems. It is a measure of the electric power that is needed to drive a fan ( or
collection of fans), relative to the amount of air that is circulated through the fans. T is not
constant for a given fan, but changes with both air flow rate and fan pressure rise.
The ideal power consumption for a fan (without losses) can be expressed as,
Pi =dp q (1)
Where:
FAN EFFICIENCY
The fan efficiency is the ratio between power transferred to airflow and the power
used by the fan. The fan efficiency is in general independent of the air density and can
be expressed as:
𝜇𝑓 = dp q / P (2)
Where:
P = dp q / 𝜇𝑓 (3)
P = dp q / 𝜇𝑓𝜇𝑏𝜇𝑚 ) (4)
Where:
𝜇𝑏 = belt efficiency
𝜇𝑚 = motor efficiency
PAGE|49
Where:
Where:
Near all of the energy lost in a fan will heat up the air flow and the temperature
increase can be expressed like
dt = dp / 1000 (6)
where:
CHAPTER IV
DATA ANALYSIS AND FINDINGS
4.2 Heat Flow thru Building Structure Calculation and Solar Load through Solar
Radiation Calculation
Exterior Wall
Description Resistance
Outside Air Film 0.0290
Finish 0.031
Face Brick, 90 mm
=(0.76)(90 mm)(1000 mm) 0.0684
Concrete Block 0.18
Cement 0.04
Finish 0.031
Inside Air Film 0.120
RTOTAL = 0.4994
U = 1/ 0.4994 = 2.0024
Window Glass
Description
Outside Air Film 0.029
Aluminum Frame 0.000025
Glass 0.06
Air Space 0.150
Aluminum Frame 0.000025
Inside Air Film 0.125
RTOTAL = 0.42405
U = 1/ 0.42405 = 2.3582
PAGE|53
4.2 Heat Flow thru Building Structure Calculation and Solar Load through Solar
Radiation Calculation
Production Area
Facing South
𝑊
Thermal Conductivity of Wall (UW) = 2.0024 𝑚2 −℃
𝑊
Thermal Conductivity of Glass (UG) = 2.3582
𝑚2 −℃
𝑄𝑤 = 𝑈𝑊 𝐴𝑇 ∆𝑇
𝑊
𝑄𝑤 = (2.0024 ) (20.8 𝑚2 )(32℃ − 23℃)
𝑚2 − ℃
𝑄𝑤 = 𝟑𝟕𝟒. 𝟖𝟓 𝑾𝒂𝒕𝒕𝒔
𝑄𝐺 = 𝑈𝐺 𝐴𝐺 ∆𝑇
𝑊
𝑄𝐺 = (2.3582 ) (9.6𝑚2 )(32℃ − 23℃)
𝑚2−℃
𝑄𝐺 = 𝟐𝟎𝟑. 𝟕𝟓 𝑾𝒂𝒕𝒕𝒔
𝑤
Solar Heat Gain Factor (SHGFMax.) = 700 𝑚2
Facing West
𝑊
Thermal Conductivity of Wall (UW) = 2.0024 𝑚2 −℃
𝑊
Thermal Conductivity of Glass (UG) = 2.3582 𝑚2 −℃
𝑄𝑤 = 𝑈𝑊 𝐴𝑇 ∆𝑇
𝑊
𝑄𝑤 = (2.0024 2
) (32.16 𝑚2 )(32℃ − 23℃)
𝑚 −℃
𝑄𝑤 = 𝟓𝟕𝟗. 𝟓𝟕 𝑾𝒂𝒕𝒕𝒔
𝑄𝐺 = 𝑈𝐺 𝐴𝐺 ∆𝑇
𝑊
𝑄𝐺 = (2.3582 ) (14.4 𝑚2 )(32℃ − 23℃)
𝑚2−℃
𝑄𝐺 = 𝟑𝟎𝟓. 𝟔𝟐 𝑾𝒂𝒕𝒕𝒔
Office
Facing West
𝑊
Thermal Conductivity of Wall (UW) = 2.0024 𝑚2 −℃
𝑊
Thermal Conductivity of Glass (UG) = 2.3582 𝑚2 −℃
𝑄𝑤 = 𝑈𝑊 𝐴𝑇 ∆𝑇
𝑊
𝑄𝑤 = (2.0024 ) (6.24 𝑚2 )(32℃ − 23℃)
𝑚2 − ℃
𝑄𝑤 = 𝟏𝟏𝟐. 𝟒𝟓 𝑾𝒂𝒕𝒕𝒔
𝑄𝐺 = 𝑈𝐺 𝐴𝐺 ∆𝑇
𝑊
𝑄𝐺 = (2.3582 ) (4.8 𝑚2 )(32℃ − 23℃)
𝑚2−℃
𝑄𝐺 = 𝟏𝟎𝟏. 𝟖𝟕 𝑾𝒂𝒕𝒕𝒔
PAGE|56
Facing North
𝑊
Thermal Conductivity of Wall (UW) = 2.0024 𝑚2 −℃
Pantry
Facing East
𝑊
Thermal Conductivity of Wall (UW) = 2.0024 𝑚2 −℃
𝑊
Thermal Conductivity of Glass (UG) = 2.3582 𝑚2 −℃
𝑄𝑤 = 𝑈𝑊 𝐴𝑇 ∆𝑇
𝑊
𝑄𝑤 = (2.0024 ) (6 𝑚2 )(32℃ − 23℃)
𝑚2 −℃
𝑄𝑤 = 𝟏𝟎𝟖. 𝟏𝟑 𝑾𝒂𝒕𝒕𝒔
𝑄𝐺 = 𝑈𝐺 𝐴𝐺 ∆𝑇
𝑊
𝑄𝐺 = (2.3582 ) (1.2𝑚2 )(32℃ − 23℃)
𝑚2−℃
𝑄𝐺 = 𝟐𝟓. 𝟒𝟕 𝑾𝒂𝒕𝒕𝒔
Conference Room
PAGE|58
Facing East
𝑊
Thermal Conductivity of Wall (UW) = 2.0024 𝑚2 −℃
𝑊
Thermal Conductivity of Glass (UG) = 2.3582 𝑚2 −℃
𝑄𝑤 = 𝑈𝑊 𝐴𝑇 ∆𝑇
𝑊
𝑄𝑤 = (2.0024 ) (8.96𝑚2 )(32℃ − 23℃)
𝑚2−℃
𝑄𝑤 = 𝟏𝟔𝟏. 𝟒𝟕 𝑾𝒂𝒕𝒕𝒔
𝑄𝐺 = 𝑈𝐺 𝐴𝐺 ∆𝑇
𝑊
𝑄𝐺 = (2.3582 2
) (4.8 𝑚2 )(32℃ − 23℃)
𝑚 −℃
𝑄𝐺 = 𝟏𝟎𝟏. 𝟖𝟕 𝑾𝒂𝒕𝒕𝒔
File Storage
Facing East
𝑊
Thermal Conductivity of Wall (UW) = 2.0024 𝑚2 −℃
𝑊
Thermal Conductivity of Glass (UG) = 2.3582 𝑚2 −℃
𝑄𝑤 = 𝑈𝑊 𝐴𝑇 ∆𝑇
𝑊
𝑄𝑤 = (2.0024 ) (10.72 𝑚2 )(32℃ − 23℃)
𝑚2−℃
𝑄𝑤 = 𝟏𝟗𝟑. 𝟏𝟗 𝑾𝒂𝒕𝒕𝒔
𝑄𝐺 = 𝑈𝐺 𝐴𝐺 ∆𝑇
𝑊
𝑄𝐺 = (2.3582 ) (4.8 𝑚2 )(32℃ − 23℃)
𝑚2 − ℃
𝑄𝐺 = 𝟏𝟎𝟏. 𝟖𝟕 𝑾𝒂𝒕𝒕𝒔
𝑤
Solar Heat Gain Factor (SHGFMax.) = 645 𝑚2
𝑄𝑤 = 𝑈𝑊 𝐴𝑇 ∆𝑇
𝑊
𝑄𝑤 = (2.0024 ) (11.2 𝑚2 )(32℃ − 23℃)
𝑚2
−℃
𝑄𝑤 = 𝟐𝟎𝟏. 𝟖𝟒 𝑾𝒂𝒕𝒕𝒔
𝑄𝐺 = 𝑈𝐺 𝐴𝐺 ∆𝑇
𝑊
𝑄𝐺 = (2.3582 ) (4.8 𝑚2 )(32℃ − 23℃)
𝑚2 −℃
𝑄𝐺 = 𝟏𝟎𝟏. 𝟖𝟕 𝑾𝒂𝒕𝒕𝒔
File Storage
𝑄𝐿 = 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 + 𝐿𝑖𝑔ℎ𝑡𝑠
𝑄𝐿 = 150 𝑊 + 118.08 𝑊
𝑄𝐿 = 𝟐𝟔𝟖. 𝟎𝟖 𝑾𝒂𝒕𝒕𝒔
Production Area
𝑄𝐿 = 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 + 𝐿𝑖𝑔ℎ𝑡𝑠 + 𝐸𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡
𝑄𝐿 = 907.5 𝑊 + 354.24 𝑊 + 12(390 𝑊)
𝑄𝐿 = 𝟓𝟗𝟒𝟏. 𝟕𝟒 𝑾𝒂𝒕𝒕𝒔
Conference Room
𝑄𝐿 = 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 + 𝐿𝑖𝑔ℎ𝑡𝑠
𝑄𝐿 = 360 𝑊 + 118.08 𝑊
𝑄𝐿 = 𝟒𝟕𝟖. 𝟎𝟖 𝑾𝒂𝒕𝒕𝒔
Office
𝑄𝐿 = 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 + 𝐿𝑖𝑔ℎ𝑡𝑠 + 𝐸𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡𝑠
𝑄𝐿 = 165 𝑊 + 78.72 𝑊 + 2(390 𝑊)
𝑄𝐿 = 𝟏𝟎𝟐𝟑. 𝟕𝟐 𝑾𝒂𝒕𝒕𝒔
NO. OF LAMP
ROOM 𝐹𝑈 𝐹𝑏 CLF Q
LIGHTS RATING
PRODUCTION
9 40 1 1.2 0.82 354.24
AREA
CONFERENCE
3 40 1 1.2 0.82 118.08
ROOM
FILE
3 40 1 1.2 0.82 118.08
STORAGE
OFFICE 2 40 1 1.2 0.82 78.72
PANTRY 1 40 1 1.2 0.82 39.36
MALES
1 40 1 1.2 0.82 39.36
TOILET
FEMALES
1 40 1 1.2 0.82 39.36
TOILET
PAGE|64
NO. OF
Rooms
CLF QP(w) QL(w)
OCCUPANT
PRODUCITON
11 1 82.5 907.5
AREA
CONFERENCE
6 1 60 360
ROOM
PANTRY 2 1 75 150
MEN’S TOILET 1 1 60 60
WOMENS
1 1 60 60
TOILET
PAGE|65
CLF = 1.0
Production Area
138.225
𝑁𝑂. 𝑜𝑓 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = = 11 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠
12.5
File Storage
21.5
𝑁𝑂. 𝑜𝑓 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = = 2 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠
12.5
Conference Room
24.25
𝑁𝑂. 𝑜𝑓 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = = 6 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠
12.5
Office
24.15
𝑁𝑂. 𝑜𝑓 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 = = 2 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠
12.5
ROOM TEMPERATURE = 23 ℃
𝑡𝑠 = 18 ℃ ƿ = 1.21262 kg / 𝑚3
FILE STORAGE
𝑄𝑆 = 4.81712 kJ / s
4.81712 𝑘𝐽/𝑠
m= 𝑘𝐽
1.0062 −℃ ( 23−18)℃
𝑘𝑔
m = 0.957487577 kg/s
𝑚𝑓𝑖𝑙𝑒 𝑠𝑡𝑜𝑟𝑎𝑔𝑒
𝑄𝐹𝐼𝐿𝐸 𝑆𝑇𝑂𝑅𝐴𝐺𝐸 =
ƿ
0.957487577 𝑘𝑔/𝑠
𝑄𝐹𝐼𝐿𝐸 𝑆𝑇𝑂𝑅𝐴𝐺𝐸 =
1.21262 𝑘𝑔/𝑚3
CONFERENCE ROOM:
PAGE|68
𝑄𝑆 = 2.24478 kJ/s
𝑘𝐽
2.24478
𝑆
m= 𝑘𝐽
1.0062
𝑘𝑔−℃ (23−18)℃
m = 0.4461896243 kg/s
𝑚𝑐𝑜𝑛𝑓𝑒𝑟𝑒𝑛𝑐𝑒 𝑟𝑜𝑜𝑚
𝑄𝐶𝑂𝑁𝐹𝐸𝑅𝐸𝑁𝐶𝐸 𝑅𝑂𝑂𝑀 =
ƿ
0.4461896243 𝑘𝑔/𝑠
𝑄𝐶𝑂𝑁𝐹𝐸𝑅𝐸𝑁𝐶𝐸 𝑅𝑂𝑂𝑀 =
1.21262 𝑘𝑔/𝑚3
11.70891 𝑘𝐽/𝑠
𝑄𝑆 =
3
3.90297 𝑘𝐽/𝑠
m= 𝑘𝐽
1.0062 −℃ (23−18)℃
𝑘𝑔
m = 0.7757841383 kg/s
𝑚/𝐷𝑈𝐶𝑇(𝑃𝑅𝑂𝐷.𝐴𝑅𝐸𝐴)
Q/DUCT =
ƿ
0.7757841383 𝑘𝑔/𝑠
Q/DUCT = 𝑘𝑔
1.21262 3
𝑚
PAGE|69
Q/DUCT = 0.6397586534 𝒎𝟑 /𝒔
OFFICE ROOM
𝑄𝑆 = 2.59944 kJ/s
𝑚𝑜𝑓𝑓𝑖𝑐𝑒 𝑟𝑜𝑜𝑚
m=
ƿ
2.59944 𝑘𝑗/𝑠
m= 𝑘𝑗
1.0062 −℃923−18)℃
𝑘𝑔
m = 0.5166845558 kg/s
𝑚𝑜𝑓𝑓𝑖𝑐𝑒 𝑟𝑜𝑜𝑚
𝑄𝑂𝐹𝐹𝐼𝐶𝐸 𝑅𝑂𝑂𝑀 =
ƿ
0.5166845558 𝑘𝑔/𝑠
𝑄𝑂𝐹𝐹𝐼𝐶𝐸 𝑅𝑂𝑂𝑀 = 𝑘𝑔
1.21262 3
𝑚
𝑄𝑆 = 21.37025 kj/s
21.37025 𝑘𝑗/𝑠
m= 𝑘𝑗
1.0062 −℃(23−18)℃
𝑘𝑔
m = 4.247714172 kg/s
𝑚𝑚𝑎𝑖𝑛 𝑑𝑢𝑐𝑡
𝑄𝑚𝑎𝑖𝑛 𝑑𝑢𝑐𝑡 =
ƿ
4.247714172 𝑘𝑔/𝑠
𝑄𝑚𝑎𝑖𝑛 𝑑𝑢𝑐𝑡 =
1.21262 𝑘𝑔/𝑚3
DUCT SIZE:
(4𝐻 2 )0.625
0.65m = 1.3
(5𝐻)0.25
H = 0.314m
W = 4(0.314)
W = 1.256m
PAGE|71
W = 4H
(𝑊𝐻)0.625
Deq = 1.3
(𝑊+𝐻)0.25
FILE STORAGE:
(4𝐻 2 )0.625
0.37 m =
(5𝐻)0.25
H = 0.18m
W = 4(0.18)
W = 0.72m
PAGE|72
OFFICE ROOM:
(4𝐻 2 )0.625
0.30m = 1.3
(5𝐻)0.25
H = 0.145m
W = 4(0.145)
W = 0.59m
CONFERENCE ROOM:
(4𝐻 2 )0.625
0.2875m = 1.3
(5𝐻)0.25
H = 0.139m
W = 4(0.139)
W = 0.556m
PRODUCTION AREA/DUCT:
(4𝐻 2 )0.625
0.35m = 1.3
(5𝐻)0.25
H = 0.169 m
W = 4(0.169 m)
W = 0.676 m
PAGE|73
𝑘𝑔
@ 𝑡3 = 18℃ &𝜔3 = 0.007698
𝑘𝑔𝑑.𝑎.
PAGE|74
@ 32℃ & 90 %
Using Psychrometric Chart:
𝑘𝐽
ℎ1 = 100
𝑘𝑔
Return Air:
𝑚𝑟 = 𝑚 − 𝑚𝑜
𝑘𝑔 𝑘𝑔
𝑚𝑟 = 4.37 − 0.4373
𝑠 𝑠
𝑘𝑔
𝑚𝑟 = 3.9327
𝑠
Refrigeration Load:
= 𝑚𝑜 (ℎ1 − ℎ3 ) + (ℎ4 − ℎ3 )
𝑘𝑔 𝑘𝐽 𝑘𝐽 𝑘𝐽 𝑘𝐽
= 0.4373 (100 − 37 ) + (43 − 37 )
𝑠 𝑘𝑔 𝑘𝑔 𝑘𝑔 𝑘𝑔
= 51.1461 𝑘𝑊
*1 TR = 3.516 kW
1 𝑇. 𝑅.
51.1461 𝑘𝑊 = = 𝟏𝟒. 𝟓𝟓 𝑻. 𝑹.
3.516 𝑘𝑊
PAGE|75
REFRIGERANT R134A
∆𝑇 = 8
h1 = 408.66 kj/kg
h2 = 426.6 kj/kg
h3 = 287.5 kj/kg
h4 = 287.5 kj/kg
HEAT REJECTION:
𝑄𝑅 = m ( h2 – h3 )
TR = m (h1 – h4)
𝑘𝑗
3.516
14.55 𝑡𝑜𝑛𝑠 ( 𝑠)
𝑇𝑅 1 𝑡𝑜𝑛
m=
(ℎ1−ℎ4)
=
408.66−287.5 𝑘𝑗/𝑘𝑔
PAGE|76
m = 0.42 kg/s
𝑄𝑅 = (0.42 kg/s)(426.6-287.5)kj/kg
𝑄𝑅 = 58.422 kW
𝑄𝑅 = 𝑚𝑤 𝑐𝑝𝑤 (8)
𝑄𝑅 58.422𝑘𝑗/𝑠
𝑚𝑤 =𝑐 = 𝑘𝑗
𝑝𝑤 (8) 4.187 −𝐾(8)𝐾
𝑘𝑔
𝑚𝑤 =1.74kg/s
PAGE|77
@ 32℃ DB & 24 ℃ WB
h1 = 71.86 kj/kg
v1 = 0.885 𝑚3 /𝑘𝑔
@ 24℃ SATURATED
h2 = 94.8 kj/kg
@ 32℃
h3 = 𝑐𝑝𝑤 𝑇𝑊
h3 = 4.187 (32)
h3 = 133.984 KJ/KG
ENERGY BALANCE
𝑚𝑎 = vol. of air / V1
PAGE|78
𝑚3 /𝑠
𝑚𝑎 = 1 = 1.13 kg/s
0.885 𝑚3 /𝑘𝑔
MASS BALANCE
m4 = m3-𝑚𝑎 (w2-w1)
m4 = 1.74-1.13(0.0256-0.0156)
m4 = 1.7287 kg/s
MAKE UP WATER
m5 = 1.13 (0.0256-0.0156)
m5 = 0.0113kg/s
EFFICIENCY
𝑡3−𝑡4
eff. = 𝑡3−𝑡
𝑊𝐵1
h4 = m3h3-𝑚𝑎 (h2-h1)/m4
h4 = 119.86
PAGE|79
h4 = 119.86
t4 = 28.58℃
32−28.58
eff. = 𝑥 100%
32−24
eff. = 42.75%
COOLING APPROACH
C.A = t4-𝑡𝑤𝑏1
= 28.58-24
C.A = 4.58℃
PAGE|80
CHAPTER 5
This is the last chapter of the thesis and the most important part because it is here
where the findings, and the whole thesis for that matter, are summarized generalization
in the form of conclusions are made; and the recommendation for the solutions and
problem discovered in the study are addressed to those concerned.
PAGE|81
5.1 summary
Air conditioning is the process of altering the properties of air, primarily temperature and
humidity to more comfortable conditions, typically with aim of disturbing the conditioned
air to an occupied space to improve thermal comfort and indoor air quality,
Control for all part of a building, air conditioned buildings are often have sealed
windows, because often windows would work against the system intended to maintain
constant indoor air conditions, outside fresh air is generally drawn into the system by
vent into the indoor heat exchanger section creating positive air pressure.
Central air conditioning is one of the most convenient and energy efficient ways
to get relief from hot, humid summer weather in the glen view and wilmettte area,
weather youre planning to install an A/C system for the first time or looking to upgrade
your current system. Its important to understand your HVAC operation.
The ‘central’ in central air conditioning comes frome the fact that the system
conditions the entire building from one large central location in your home. This system
cools and dehumidifies the air, then blows the cool air into your duct system and out
through the supply air registers located in each room.
In the dark contrast, window A/C units cool only one room of area. Trying to cool an
entire home with a window unit in each room would require not only inconvenience of
managing each separate unit, but it would also require more energy and be excessively
noisy.
Central air conditioning systems are typically combined with the furnace system,
if your home has one (or use dedicated air handler if it doesn’t) and both use the same
electrical system duct work.
PAGE|82
The function of air conditioning is to control the temperature humidity, purity (that
is removal of the dust and other impurities) and air movement or circulation
Psychometric – is the study of the properties of mixtures of air and water vapor.
Saturated air – is air whose condition is such that any decease in temperature
will result in condensation of the water vapor into liquid.
Dry air – is the non conditioning components of the mixture. Mainly the nitrogen
and the oxygen.
Vapor – is the condensable component of the mixture the water vapor which
exists in a saturated or superheated state.
When liquid turns into gas or “evaporates” it absorbs heat. This is why pouring
water over your skin makes you feel cooler in hot weather. Air conditioners use
chemical compound known as refrigerant that turns from liquid to gas at low
temperature, refrigerant move through the air conditioning system, absorbing heat from
your house and transferring it out doors in continuous cycle.
1. Cold refrigerant is pumped through the evaporator coil. A fan blows air over
the coil, and the refrigerant in the coil absorbs heat from the air. The now-cool
air is blown into your ducts to be distributed through your home. As the
refrigerant absorbs heat. It evaporates into low-pressure gas.
2. Hot low pressure refrigerant gas moves to the compressor, which increases
the pressure and the temperature of the gas.
3. Hot high pressure refrigerant gas moves to the condenser. The gas releases
heat and, as it does so. It condenses back into a liquid.
4. The liquid refrigerant flows to the expansion valve, which regulates how much
refrigerants gets through the evaporator. From here the refrigerant flows to
the evaporator to start the cooling cycle over again.
Pressure Classification
Duct system are also divided into three pressure classification matching the way
supply fans are classified.
Static pressure
The pressures are total pressure and include all the losses through the air source unit,
the supply duct work, and the air terminals, return grilles, and return duct work.
VELOCITY CLASSIFICATION
PAGE|84
Ducts are classified according to the velocity they are subjected to. Ducts are classified
into 3 basic categories.
1. Low velocity duct systems: Low velocity ducts are characterized by air velocities
in the range of 400 to 2000 feet per minute (fpm)
2. Medium velocity duct systems: Medium velocity (MV) duct system are
characterized by air velocities in the range of 2000 to 2500 fpm.
3. High velocity Duct system: High Velocity (HV) duct systems are characterized by
air velocities in the range of 2500 to 3500.
B. Duct shape
5.2 CONCLUSION
Central air conditioning systems keep the condenser on the outside of the
building to keep noisy operations that are necessary to cool a home away from the
building. Many central air conditions cause noise inside the home so there is no need to
be disturbed by excess noise in order to enjoy cooling power of an air conditioner.
Comfort of the home owner and occupants of home are maximized when they were
able to simultaneously stay cool and enjoy quiet.
The central air conditioners have different structures altogether. The condenser
typically sits on the roof or in the backyard. A set of pipes runs coolant from the
condenser into an air handler, which is usually located near the home’s furnace. The air
handle blows the cold air through the homes duct system and into individual room.