Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Control Output 1
Indication Accuracy
• Relay output
• Thermocouple input:
• Voltage output (for driving SSR)
±0.3% of PV
• Current output
• Pt input: ±0.2% of PV
• Analog input: • PF (shift) Key
±0.2% of FS • Temperature status display
Auxiliary Outputs
• Independent heating and
cooling PID control •2
Sampling Period
• Changed parameter display
• 50 ms • Display brightness setting
Communications
• None
• RS-485
Event Inputs
• None
•2
1
E5CC-800
Model Number Legend and Standard Models
Model Number Legend
E5CC-800 48x48mm
Control output 1 Auxiliary output Communications Heater burnout Event inputs Power supply voltage Model
Relay output E5CC-RX2ASM-800
Voltage output 100 to 240 VAC E5CC-QX2ASM-800
Current output E5CC-CX2ASM-800
- -
Relay output E5CC-RX2DSM-800
Voltage output 24 VAC/VDC E5CC-QX2DSM-800
-
Current output E5CC-CX2DSM-800
Relay output E5CC-RX2ASM-801
100 to 240 VAC
Voltage output E5CC-QX2ASM-801
Two Two
Relay output E5CC-RX2DSM-801
24 VAC/VDC
Voltage output E5CC-QX2DSM-801
One
Relay output E5CC-RX2ASM-802
100 to 240 VAC
Voltage output E5CC-QX2ASM-802
-
Relay output E5CC-RX2DSM-802
RS-485 24 VAC/VDC
Voltage output E5CC-QX2DSM-802
Current output 100 to 240 VAC E5CC-CX2ASM-804
- Two
Current output 24 VAC/VDC E5CC-CX2DSM-804
Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.
2
E5CC-800
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA
Control
Voltage output
output Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Number of outputs 2
Auxiliary
output N.O. relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V
Number of inputs 2 or 4 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or
Multi SP
serial communications.
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, 40% AT,
100% AT, MV limiter, input digital filter, self tuning, PV input shift, run/stop, protection functions,
Other functions
extraction of square root, MV change rate limit, temperature status display, moving average of input
value, and display brightness setting
-10 to 55°C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50°C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
3
E5CC-800
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Setting
number
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
●Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Setting number 25 26 27 28 29
4
E5CC-800
Alarm Outputs
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP
X X
ON ON The alarm will turn ON if the process value is larger than the
8 Absolute-value upper-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-limit ON ON A standby sequence is added to the absolute-value upper-lim-
10 OFF PV OFF PV
with standby sequence 0 0 it alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-limit
11 OFF PV OFF PV
with standby sequence 0 0 alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute value ON ON This alarm type turns ON the alarm when the set point (SP) is
14 OFF SP OFF SP
upper limit 0 0 higher than the alarm value (X).
X X
SP absolute value ON ON This alarm type turns ON the alarm when the set point (SP) is
15 OFF SP OFF SP
lower limit 0 0 smaller than the alarm value (X).
X X
MV absolute value ON ON This alarm type turns ON the alarm when the manipulated
16 OFF MV OFF MV
upper limit *9 0 0 variable (MV) is higher than the alarm value (X).
X X
MV absolute value ON ON This alarm type turns ON the alarm when the manipulated
17 OFF MV OFF MV
lower limit *9 0 0 variable (MV) is smaller than the alarm value (X).
*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4 Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as “L” and “H.” For Upper- and Lower-Limit Alarm Described Above *2
*2 Set value: 1, Upper- and lower-limit alarm
• Case 1 and 2
Case 1 Case 2 Case 3 (Always ON)
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
H<0, L<0
L H SP SP L H H SP L • Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
*6 Refer to the E5@C Digital Controllers User's Manual (Cat. No. H174) for
H>0, L<0
information on the operation of the standby sequence.
SP H L |H| ≤ |L|
*7 Refer to the E5@C Digital Controllers User's Manual (Cat. No.H174) for
*3 Set value: 4, Upper- and lower-limit range information on the loop burnout alarm (LBA).
Case 1 Case 2 Case 3 (Always OFF) *8 Refer to the E5@C Digital Controllers User's Manual (Cat. No. H174) for
H<0, L<0 information on the PV change rate alarm.
L H SP SP L H H SP L *9 When heating/cooling control is performed, the MV absolute upper limit
H<0, L>0 H>0, L<0 H<0, L>0 alarm functions only for the heating operation and the MV absolute lower
|H| < |L| |H| > |L| H L SP |H| ≥ |L| limit alarm functions only for the cooling operation.
H>0, L<0
SP H L |H| ≤ |L|
5
E5CC-800
Characteristics
Thermocouple: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. *1
Indication accuracy Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit
(at the ambient temperature of 23°C) Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2
Analog input: (±1%FS) ±1 digit max.
CT input: (±5%FS) ±1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Affect of signal source resistance
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
resistance 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Malfunction 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Shock resistance 100 m/s2, 3 times each in X, Y, and Z directions
Destruction
Malfunction 300 m/s2, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 120 g, Mounting Bracket: Approx. 10 g
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Approved standards UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL), Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *5
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°Cmax. is
not specified. The indication accuracy of B thermocouples in the 400 to 800°Crange is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C,
whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
*2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 Refer to information on maritime standards in Shipping Standards on page 35 for compliance with Lloyd's Standards.
6
E5CC-800
7
E5CC-800
500
300
100
50
30
10
5
E5CC-800
3 250 VAC, 30 VDC
(resistive load)
cosφ = 1
1
0 1 2 3 4 5 6
Switching current (A)
External Connections
E5CC-800
Control output 1 E5CC-@@ 2 @ S M - 8@ @
Relay output (1) (2) (3) (4) (5) (6)
250 VAC, 3A
↑
(resistive load) Terminal type
Voltage output
(for driving SSR) Auxiliary outputs 1, 2
12 VDC, 21 mA Relay outputs
Current output
Models with 2 auxiliary The E5CC-800 is set for a K-type thermocouple (input type = 5) by
0 to 20 mA DC
4 to 20 mA DC outputs: 250 VAC, 3 A default. An input error (s.err) will occur if the input type setting does
Load: 500 Ω max. (resistive load) not agree with the temperature sensor. Check the input type.
1 13 7
2 14 8
(5) Sensor (Temperature/Analog) Input 3 15 9
(3) Input Power Supply
4 16 10
TC Pt I V 100 to 240 VAC 24 VAC/VDC
A + 4 5 17 11
4 4 4
B mA 6 18 12 11 11
- 5 5 5 - 5
B - V 12 12
+ 6 6 6
+
6
(no polarity)
(6) Options
801 802 804
Event Inputs 1 Communications (RS-485), Communications (RS-485),
and 2, and CT1 CT1 and Event Inputs 3 and 4
B(+) B(+)
13 13 13
RS-485 RS-485
EV1
14 14 14
A(-) A(-)
EV2 15 15 15
16 16 16
CT1 CT1
17 17 EV3
17
18 18 EV4 18
8
E5CC-800
Isolation/Insulation Block Diagrams
Auxiliary output 1
Auxiliary output 2
: Reinforced insulation
: Functional isolation
Nomenclature
E5CC-800 Front panel
Temperature unit
PV or specified parameter
Top View of E5CC-800
No. 2 display
9
E5CC-800
Dimensions (Unit: mm)
Controllers
E5CC-800 Panel Cutout
4
73.1 Mounted Separately Group Mounted
60 (48 × number of units - 2.5)+1.0
0
48 × 48 1
45+0.6
0
45+0.6
0
48.8
10
Terminal Cover
(E53-COV23)
22 44.8
9.1
● Waterproof Packing The Waterproof Packing is provided with the Temperature Controller.
Y92S-P8 (for DIN 48 × 48) Order the Waterproof Packing separately if it becomes lost or damaged.
(Provided with the Controller.) The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
10
E5CC-800
● Adapter
Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@.
2. Only black is available.
Fixture (Accessory)
4.7 76
69.6 to 77.6
72 × 72
67 × 67 87
48 × 48
2.2 4.7
62.8
To back of the E5CC-800
Mounted to E5CC-800
48
80.5
11
E5CC-800
12
67.6
12
E5CC-800
● Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
25 3
Winding resistance: 18±2 Ω
10.5
10 100Ω
E54-CT3
2.36 dia.
30 RL=10Ω
1
12 dia.
9
100μV
10
40 × 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
100V
Frequency: 50 Hz
Armature Distortion
Approx. 3 dia. Plug ∞
10 factor
1kΩ
10%
Lead 500Ω 3%
1 1%
100mV
18
100Ω
50Ω
• Plug 10
RL=10Ω
1
Approx. 6 dia.
100μV
(22)
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
13
MEMO
14
Digital Temperature Controller (Simple Type)
Event Inputs
• None
•2
•4
15
E5EC/E5AC-800
Model Number Legend and Standard Models
Model Number Legend
E5EC-800 48x96 mm
Auxiliary Heater Event Power supply
Control output 1 Control output 2 Communications Model
output burnout inputs voltage
Relay output - E5EC-RX2ASM-800
Voltage output - E5EC-QX2ASM-800
Current output - E5EC-CX2ASM-800
100 to 240 VAC
Relay output Relay output E5EC-RR2ASM-800
Voltage output Relay output E5EC-QR2ASM-800
Current output Relay output E5EC-CR2ASM-800
- - -
Relay output - E5EC-RX2DSM-800
Voltage output - E5EC-QX2DSM-800
Current output - E5EC-CX2DSM-800
24 VAC/VDC
Relay output Relay output E5EC-RR2DSM-800
Voltage output Relay output E5EC-QR2DSM-800
Two
Current output Relay output E5EC-CR2DSM-800
Relay output Relay output E5EC-RR2ASM-808
100 to 240 VAC
Voltage output Relay output E5EC-QR2ASM-808
RS-485 Two
Relay output Relay output E5EC-RR2DSM-808
24 VAC/VDC
Voltage output Relay output E5EC-QR2DSM-808
One
Relay output Relay output E5EC-RR2ASM-810
100 to 240 VAC
Voltage output Relay output E5EC-QR2ASM-810
- Four
Relay output Relay output E5EC-RR2DSM-810
24 VAC/VDC
Voltage output Relay output E5EC-QR2DSM-810
Current output Relay output 100 to 240 VAC E5EC-CR2ASM-804
RS-485 - Two
Current output Relay output 24 VAC/VDC E5EC-CR2DSM-804
Relay output (Open)* Relay output (Close)* - E5EC-PR0ASM-800
- -
Relay output (Open)* Relay output (Close)* - 100 to 240 VAC E5EC-PR2ASM-800
Two
Relay output (Open)* Relay output (Close)* RS-485 Two E5EC-PR2ASM-804
* Position proportional control model.
E5AC-800 96x96 mm
Auxiliary Heater Event Power supply
Control output 1 Control output 2 output Communications burnout inputs voltage Model
16
E5EC/E5AC-800
Heating and Cooling Control
l Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
Waterproof Packing
Applicable Controller Model
E5EC-800 Y92S-P9
E5AC-800 Y92S-P10
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.
Waterproof Cover
Applicable Controller Model
E5EC-800 Y92A-49N
E5AC-800 Y92A-96N
17
E5EC/E5AC-800
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
E5EC-800 6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Power consumption
E5AC-800 7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or 2.4 W max. at 24 VDC
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA
Control
Voltage output Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
output
(for driving SSR) (The maximum load current is 21 mA for models with two control outputs.)
Current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Number of outputs 1, 2, or 3 (depends on model)
Auxiliary
output N.O. relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V
Number of inputs 1, 2, or 3 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Potentiometer input 100 Ω to 10 kΩ
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Indication method Character height: E5EC-800: PV: 18.0 mm, SV: 11.0 mm
E5AC-800: PV: 25.0 mm, SV: 15.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or
Multi SP
serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, 40% AT,
100% AT, MV limiter, input digital filter, self tuning, PV input shift, run/stop, protection functions, ex-
Other functions
traction of square root, MV change rate limit, temperature status display, moving average of input val-
ue, and display brightness setting
-10 to 55°C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50°C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
18
E5EC/E5AC-800
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 -199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Setting
range
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
●Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Setting number 25 26 27 28 29
19
E5EC/E5AC-800
Alarm type
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3).*6
sequence SP SP
X X
ON ON The alarm will turn ON if the process value is larger than the
8 Absolute-value upper-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-limit ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-limit
11 OFF PV OFF PV
with standby sequence 0 0 alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute value ON ON This alarm type turns ON the alarm when the set point (SP) is
14 OFF SP OFF SP
upper limit 0 0 higher than the alarm value (X).
X X
SP absolute value ON ON This alarm type turns ON the alarm when the set point (SP) is
15 OFF SP OFF SP
lower limit 0 0 smaller than the alarm value (X).
X X
MV absolute value ON ON This alarm type turns ON the alarm when the manipulated
16 OFF MV OFF MV
upper limit *9 0 0 variable (MV) is higher than the alarm value (X).
X X
MV absolute value ON ON This alarm type turns ON the alarm when the manipulated
17 OFF MV OFF MV
lower limit *9 0 0 variable (MV) is smaller than the alarm value (X).
*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4. Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as “L” and “H.” For Upper- and Lower-Limit Alarm Described Above *2
*2. Set value: 1, Upper- and lower-limit alarm
Case 2
• Case 1 and 2
Case 1 Case 3 (Always ON)
H<0, L<0
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
L H SP SP L H H SP L • Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
H>0, L<0
*6. Refer to the E5@C Digital Controllers User's Manual (Cat. No. H174) for in-
SP H L |H| ≤ |L|
formation on the operation of the standby sequence.
*7. Refer to the E5@C Digital Controllers User's Manual (Cat. No. H174) for in-
*3. Set value: 4, Upper- and lower-limit range
formation on the PV change rate alarm. This setting cannot be used with a
Case 1 Case 2 Case 3 (Always OFF)
position-proportional model.
H<0, L<0 *8. Refer to the E5@C Digital Controllers User's Manual (Cat. No. H174) for in-
L H SP SP L H H SP L
formation on the PV change rate alarm.
H<0, L>0 H>0, L<0 H<0, L>0 *9. When heating/cooling control is performed, the MV absolute upper limit
|H| < |L| |H| > |L| H L SP |H| ≥ |L| alarm functions only for the heating operation and the MV absolute lower
H>0, L<0 limit alarm functions only for the cooling operation.
SP H L |H| ≤ |L|
20
E5EC/E5AC-800
Characteristics
Thermocouple: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit
Indication accuracy
Analog input: ±0.2% FS ±1 digit max.
(at the ambient temperature of 23°C)
CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Influence of temperature *2
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2 Analog input: (±1%FS) ±1 digit max.
CT input: (±5% FS) ±1 digit max.
Input sampling period 50ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close)
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
Integral time (I)
Position-proportional (Floating)
1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ω max.)
Affect of signal source resistance
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
resistance 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Malfunction 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
resistance 100 m/s2, 3 times each in X, Y, and Z directions
Destruction
Malfunction 300 m/s2, 3 times each in X, Y, and Z directions
E5EC-800 Controller: Approx. 210 g, Mounting Brackets: Approx. 4 g × 2
Weight
E5AC-800 Controller: Approx. 250 g, Mounting Brackets: Approx. 4 g × 2
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Approved standards UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL), Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *5
EMI EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1. The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at
any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a
temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater, ±1 digit max. The
indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
*2. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3. K thermocouple at -100°C max.: ±10°C max.
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5. Refer to information on maritime standards in Shipping Standards on page 35 for compliance with Lloyd's Standards.
21
E5EC/E5AC-800
500
SYSMAC CS Series, CJ Series, or 300
CP Series
Mitsubishi Electric PLCs E5EC/E5AC-800
100 250 VAC, 30 VDC
MELSEC Q Series or L Series (resistive load)
cosφ = 1
• When Temperature Controllers are 50
30
connected, the parameters can be
copied from the Temperature Controller
that is set as the master to Temperature 10
Controllers that are set as slaves.
5
Number of connected Temperature
Controllers: 32 max. (including master) 3
22
E5EC/E5AC-800
External Connections
E5EC/E5AC-800
E5EC-@@ 2 @ S M - 8@ @ E5AC-@@ @ @ S M - 8@ @
Control output 1
(1) (2) (3) (4) (5) (6) (1) (2) (3) (4) (5) (6)
Relay output
250 VAC, 5 A ↑ ↑
(resistive load) Terminal type Terminal type
(6) Options
Voltage output
(for driving SSR) 804 808 810
12 VDC, 40 mA Auxiliary outputs 1, 2 Communications Communications, 2 event Four event inputs
When There Is a and 2 event inputs inputs, and 1 CT input and one CT
Control Output 2: Relay output B(+) B(+)
21 mA Model with 2 auxiliary 13 13 13
Control output 2 outputs: 250 VAC, 3 A RS-485 RS-485
14
Current output 14 14
EV3
Relay output (resistive load) A(-) A(-)
0 to 20 mA DC 15 15 15
4 to 20 mA DC 250 VAC, 5 A EV4
16 16 16
Load: 500 Ω max. (resistive load)
17 17 17
EV1 EV1 EV1
(3) Input Power Supply 18 18 18
The E5EC-800 is set for a K-type thermocouple EV2 EV2 EV2
(input type = 5) by default. An input error (s.err) will 100 to 240 VAC 24 VAC/VDC 19 19 19
occur if the input type setting does not agree with CT1 CT1
1 1 20 20 20
the temperature sensor. Check the input type.
21 21 21
2 2
(1) Control output (no polarity)
RX QX CX
Models with Models with 1 Models with 1
1 Relay Voltage Output Current Output
Output (for Driving SSR) 1 13
OUT1 OUT1 OUT1 2 14
3 3 +Q 3 + C
R - - 3 15
4 4 4
4 16
5 5 5 Potentiometer input
5 17
6 6 6 19
6 18 O
QR* RR* PR 7 19 20
W
Models with Voltage Models with 2 Models with 2 8 20 21
C
Output (for Driving SSR) Relay Outputs Position-proportional
and Relay Output Relay Output 9 21
OUT1 OUT1 Open
10 22 (5) Sensor (Temperature/Analog) Input
3 +Q 3 3
R R 11 23 TC Pt I V
4 - 4 4
12 24
A + 22
OUT2 OUT2 Close 22 22 22
5 5 5 - 23 B mA -
R R R 23 23 23
6 6 6 B - V
+ 24 24 24
+
24
CR*
Models with
Current Output
and Relay Output
OUT1
3 + C
4 -
OUT2
5
R
6
* E5EC-800 Only
23
E5EC/E5AC-800
Isolation/Insulation Block Diagrams
Sensor input, CT input, and potentiometer input
Communications and event inputs
Voltage output (for driving SSR) and current output
Power
Relay output
Supply
Auxiliary output 1
Auxiliary output 2
Auxiliary output 3
: Reinforced insulation
: Functional isolation
Nomenclature
E5EC-800
Front panel
Operation indicators
No. 2 display
SP or specified parameter value
E5AC-800
Front Panel
No. 2 display
SP or specified parameter value
24
E5EC/E5AC-800
Dimensions (Unit: mm)
Controllers
E5EC-800
(64)
4
48 60 44
1
96 110 91
Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
92-0.8
0
25
E5EC/E5AC-800
E5AC-800
(64)
4
60
96 1 91
110 91
92+0.8
0
26
E5EC/E5AC-800
● Mounting Adapter
Y92F-51 (for DIN 48 × 96)
(Two Adapters provided.)
One pair is provided with the Controller.
Order this Adapter separately if it becomes lost or damaged.
21.9 21.9
(2) (2)
131.7 131.7
27
E5EC/E5AC-800
● Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
25 3
Winding resistance: 18±2 Ω
10.5
10 100Ω
E54-CT3
2.36 dia.
30 RL=10Ω
1
12 dia.
9
100μV
10
40 × 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
100V
Frequency: 50 Hz
Armature Distortion
Approx. 3 dia. Plug ∞
10 factor
1kΩ
10%
Lead 500Ω 3%
1 1%
100mV
18
100Ω
50Ω
• Plug 10
RL=10Ω
1
Approx. 6 dia.
100μV
(22)
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
28
E5CC/E5EC/E5AC-800
Operation
Setting Levels Diagram
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
O Key once.
Operating
Advanced Function
Setting Level
*1. To use a key procedure to move to Manual Control Level, set the Auto/Manual Select Addition parameter to ON and set the PF Setting parameter to a-m (Auto/
Manual).
*2. The No. 1 display will flash in the middle when the keys are pressed for 1 s or longer.
29
E5CC/E5EC/E5AC-800
Error Displays (Troubleshooting)
When an error occurs, the No. 1 display or No. 2 display shows the error code.
Take necessary measure according to the error code, referring the following table.
Display Name Meaning Action Operation
After the error occurs and it is
The input value exceeded the control Check the wiring for input to be sure displayed, the alarm output will
range.* it is wired correctly, not broken, and operate as if the upper limit was
The input type is not set correctly. not shorted. Also check the input exceeded.
The sensor is disconnected or short- type. It will also operate as if transfer
circuited. If there are no problems in the wiring output exceeded the upper limit.
The sensor is not wired correctly. or input type settings, cycle the If an input error is assigned to a
The sensor is not wired. power supply. control output or auxiliary output, the
If the display remains the same, output will turn ON when the input
* Control Range replace the Digital Temperature error occurs.
s.err Input error Temperature resistance Controller.
thermometer or thermocouple input: If the display is restored to normal,
The error message will appear in the
display for the PV.
SP Lower Limit - 20°C to SP Upper then the probable cause is external
Limit + 20°C noise affecting the control system. Note: 1. The heating and cooling
(SP Lower Limit - 40°F to SP Upper Check for external noise. control outputs will turn
Limit + 40°F) OFF.
ESIB input: Note: For a temperature resistance 2. When the manual MV, MV
Same as specified input range. thermometer, the input is at stop, or MV at error is
Analog input: considered disconnected if the set, the control output is
Scaling range -5% to 105% A, B, or B’ line is broken. determined by the set
value.
This is not an error. It
is displayed when the
[[[[ Below -1,999 control range is wider Control continues and operation is
than the display normal.
range and the PV The value will appear in the display
Display range exceeds the display for the PV.
-
exceeded range. The PV is Refer to the E5@C Digital Controllers
displayed for the User’s Manual (Cat. No. H174) for
range that is given on information on the
]]]] Above 9,999
the left (the number controllable range.
without the decimal
point).
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
A/D controller must be repaired. outputs, and transfer outputs turn
There is an error in the internal
e333 converter
circuits.
If the display is restored to normal, OFF. (A current output will be approx.
error then a probable cause can be 0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
controller must be repaired. outputs, and transfer outputs turn
Memory There is an error in the internal
e111 error memory operation.
If the display is restored to normal, OFF. (A current output will be approx.
then a probable cause can be 0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
Control continues and operation is
normal.
This error is displayed when the peak The error message will appear for the
ffff Overcurrent
current exceeds 55.0 A.
-
following displays.
Heater Current Value 1 Monitor
Leakage Current Value 1 Monitor
The No. 1 display for the following
parameter flashes in Operation Level
If there is a HB or HS alarm, the No. or Adjustment Level.
ct1 HB or HS
1 display will flash in the relevant - Heater Current Value 1 Monitor
alarm
lcr1 setting level. Leakage Current Value 1 Monitor
However, control continues and
operation is normal.
"----" will be displayed for the Valve
Opening Monitor parameter if any of
the following error occurs.
Potentiometer • Motor calibration has not been Close control: The control output is
Input Error performed. OFF or the value that is set for the
---- (Position- • The wiring of the potentiometer is Check for the above errors. MV at PV Error parameter is output.
proportional incorrect or broken. Floating control: Operation will be
Models Only) • The potentiometer input value is normal.
incorrect (e.g., the input is out of
range or the potentiometer has
failed).
30
E5CC/E5EC/E5AC-800
Operation
Parameters
The related setting items in each level are described below. If you press the Mode Key at the last setting item, the display will return to the first
setting item in the same level.
M M M M
cmwt Communications p Proportional Band 25 Process Value/Set al1h Alarm Value
0 Point (2) Upper Limit 1
0
off Writing 8.0
M M M M
Auto/Manual Switch
ct1 Heater Current 1 i Integral Time a-m PID 1 control only. al1l Alarm Value
233
Press the Added for Auto/Manual 0 Lower Limit 1
0.0 Value Monitor
M M M M
lcr1 Leakage Current c-p Proportional Band ct-1 Heater Current 1 Value
al2h Alarm Value
0.0 Monitor Upper Limit 2
0
0 1 Monitor 8.0 (Cooling)
M M M
M
c-i lcr1 Leakage Current 1 al2l Alarm Value
hs1 HS Alarm 1 Integral Time
233 (Cooling) 0.0 Monitor 0 Lower Limit 2
50.0
M M M
M
sp-0 SP 0 c-d Derivative Time r-s RUN/STOP o MV Monitor
40 (Cooling) run 0.0 (Heating)
0
M M M
M
c-o MV Monitor
sp-1 SP 1 c-db Dead Band 0.0 (Cooling)
0 0.0 Press the
M
M M Valve Opening O Key
Manual Reset Value v-m
sp-2 SP 2 of-r Clear the offset during Monitor less than 1 s.
0 50.0 stabilization of P or PD
control. M
M M
sp-3 SP 3 hys Hysteresis (Heating)
Press the O and Press the O and
0 1.0
M M Hysteresis settings M Keys for at least 3 s. M Keys for at least 1 s. Communications Setting Level
Note: Displayed only for models with communications. Changes
sp-4 SP 4 chys Hysteresis (Cooling)
Protect Level are effective after cycling power or after a software reset.
0 1.0
Note: The time taken to move to the protect level can be
M M adjusted by changing the "Move to protect level time" setting.
sp-5 SP 5 sprt SP Ramp Set Value
Protocol Setting*3
0 off psel sdwt Send Data Wait unit Communications
20 Time 0 Node Number
M M oapt
Operation/Adjustment Protect: fins
Restricts displaying and modifying menus in
sp-6 SP 6 0 M M M
ol-h MV Upper Limit operation, adjustment, and manual control levels.
Highest
0 100.0 M Initial Setting/Communications Protect: u-no Communications maxu Communications up 1 Upload Setting 1
⋅⋅⋅⋅
Unit No. 0
M M icpt This protect level restricts movement to the initial 0
Unit No.*3
0
sp-7
1 setting, communications setting, and advanced
M M M
SP 7
ol-l MV Lower Limit
M function setting levels.
0 0.0
Setting Change Protect:
bps Communications area Area up13 Upload Setting 13
M M wtpt 57.6 Baud Rate 0 0
off Protects changes to setups by
M M M
db Position
Proportional M
operating the front panel keys.
2.0
Dead Band len Communications adrh First Address dn 1 Download Setting 1
pfpt PF Key Protect 7 Data Length Upper Word
⋅⋅⋅⋅
0 0
M off
M M M
oc-h Open/Close
Hysteresis
M
0.8
chgp Display Changed Parameters sbit Communications adrl First Address dn13 Download Setting 13
2 Stop Bits 0 Lower Word 1000
M off
M M M M
plcm Communications
Monitor
1234 prty Communications rwat Receive Data copy Copy*3
*1. When the PF Setting parameter is set to A-M. even Parity 1000 Wait Time*3 off
M
*2. When the PF Setting parameter is set to PFDP. M M M
SP Slope
*3. Used with component communications. sps *3
1.000
M
SP Offset
spos *3
0.0
31
E5CC/E5EC/E5AC-800
Monitor/Setting 5
Monitor/Setting 5
Monitor/Setting 5
Monitor/Setting 5
Monitor/Setting
Item Display 1 Item Display 2 Item Display 3 Item Display 4 Item Display 5
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
/ Hysteresis
URTW SP Ramp Time Unit ELE Cold Junction
CNO Assignment
/
PQ Open in Alarm /
/ Limit the set point
/ / RXTR PV Rate of Change
QUV Control Output 2
UNN SP Lower Limit Signal Type
JDW HB ON/OFF
CQH Alarm 2 OFF Delay Calculation Period
/ QP /
/ /
GX Event Input / JEVO Heating/Cooling
EPVN PID ON/OFF OUR Assignment 1 COCF Auto/Manual Select QHH Tuning Method
QPQH JDN Heater Burnout Latch QHH Addition
/
/ QHH
/ /
GX Event Input / QORY Minimum Output
UJE Standard or UVQR Assignment 2 OCPV Manual Output Method ON/OFF Band
UVPF Heating/Cooling JDJ Heater Burnout JQNF
/ Hysteresis /
/ /
UV GX Event Input / RH PF Setting
ST
OCPK Manual MV Initial Value UJHV
QP For input type of
temperature, standard
PQPG Assignment 3
UVD ST Stable Range
/
/ / /
OQV Travel Time / NDC LBA Detection Time RXFR PV Decimal Point
OCX Moving Average Count
QP Display
/ HH
/
Move to Advanced /
COQX /
Function Setting Level:
Displayed when initial setting/ NDCN LBA Level RXUV PV Status Display
QFR MV Display
Function
QHH
32
E5CC/E5EC/E5AC-800
Safety Precautions
● Be sure to read the precautions for all E5CC/E5EC/E5AC-800 models in the website at: http://www.ia.omron.com/.
33
E5CC/E5EC/E5AC-800
34
E5CC/E5EC/E5AC-800
Shipping Standards
The E5CC-800, E5EC-800, and E5AC-800 comply with Lloyd's standards. When applying the standards, the following installation and wiring
requirements must be met in the application.
Application Conditions
●Installation Location
The E5CC-800, E5EC-800, and E5AC-800 comply with installation category ENV1 and ENV2 of Lloyd's standards. Therefore, they must be
installed in a location equipped with air conditioning. They cannot be used on the bridge or decks, or in a location subject to strong vibration.
●Waterproofing
The degree of protection is as shown below. Sections without any Water Proof Packing
specification on their degree of protection or those with IP@0 are not Panel
35
E5CC/E5EC/E5AC-800
E5EC/E5AC-800 ●Precautions when Wiring
Adapter
• Separate input leads and power lines in order to prevent external
Adapter noise.
Panel
• Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205
Terminal Cover to 0.8231 mm2) twisted-pair cable.
• Use crimp terminals when wiring the terminals.
(E53-COV24)
• Use the suitable wiring material and crimp tools for crimp terminals.
• Tighten the terminal screws to a torque of 0.43 to 0.58 N•m.
Terminal Cover
• Use the following types of crimp terminals for M3 screws.
(E53-COV24)
5.8 mm max.
Adapter
Terminal Cover
(E53-COV17) Enlarged illustration of
(Sold separately) Terminal Section
E5EC/E5AC-800
Slightly bend the E53-COV24 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction.
Enlarged illustration of
36
MEMO
37
MEMO
38
Read and Understand this Catalog
Please read and understand this catalog before purchasing the product. Please consult your OMRON representative if you have
any questions or comments.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of the
product in the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
Note: Do not use this document to operate the Unit.