TRANSMITTER DATA
MANUFACTURER Fuji electronic SERIAL NO. A9C3557T
MODEL : FKCB35V4-PECYY-AA TEST PROCEDURE No. -
TRANSMITTER RANGE O - 200 "H2O P&ID No. :
DCS RANGE - DATASHEET
TEST EQUIPMENT Pneumatic haand pump,multimeter,hart communicator,common tool's
TEST DETAILS
CALIBRATION FIGURES
BEFORE CALIBRATION
CALIBRATION POINTS RISING FALLING UNITS
INPUT 0 - 200 0 50 100 150 200 150 100 50 0 "H2O
OUTPUT 4 - 20 3.853 7.891 11.837 15.688 19.711 15.688 11.837 7.891 3.853 mA
ACCURACY ERROR
AFTER CALIBRATION 4.00 8.00 12.00 16.00 20.00 16.00 12.00 8.00 4.00
CALIBRATION POINTS RISING FALLING UNITS
INPUT 0 - 200 0 50 100 150 200 150 100 50 0 "H2O
OUTPUT 4 - 20 4.000 8.000 12.000 16.000 20.000 16.000 12.000 8.000 4.000 mA
DCS
ACCURACY ERROR
TAG VALUE
VALUE ACTUAL READING OF PT&TT THAT PT - 0 bar
FIELD DCS DEDICATE TO METERING CALCULATION TT - 30.9 °c
"H2O -
ACTUAL INDICATION READING HORIZONTAL OK
0 -
FLOW DIRECTION UPWARD -
VERTICAL
DOWNWARD -
TRANSMITTER SQ ROOT -
OUT-PUT LINEAR OK GROUNDING OK
LOOP TEST TO CONTROL ROOM - CONFORMITY CABLE GLAND OK
TEST LABEL AFIXED OK HOOK UP OK
SITE PRODUCTION