E2K-420-0218 Rev. 3
September 2018
ed
t i nu
o n
c
Dis
Installation and Operation Manual Table of Contents
E2K-420-0218 Rev. 3 September 2018
Table of Contents
Section 1: Important Notes
1.1 User Safety..................................................................................................... 1
1.2 Purpose.......................................................................................................... 1
1.3 Storage Procedures........................................................................................ 2
Section 3: Installation
3.1 Preparing the Stem Nut.................................................................................. 9
3.2 Mechanical Installation onto the Valve......................................................... 10
3.3 Electrical Connections.................................................................................. 11
3.3.1 Remove Separate Terminal Chamber (STC) Cover.............................. 11
3.3.2 Sealing Cable/Conduit Entries........................................................... 12
3.3.3 Recommended Terminal Connections............................................... 12
3.3.4 Cable Connections............................................................................ 13
3.3.5 Replace Terminal Compartment Cover.............................................. 13
3.3.6 External Earth/Ground Connections.................................................. 13
3.4 Display Backup Module (DBM) – Optional.................................................... 14
3.5 Discrete Controlled Inputs........................................................................... 15
3.6 Auxiliary Control Module (ACM) – Optional.................................................. 17
3.6.1 Wiring the ACM................................................................................. 17
3.6.2 Analog Controlled – Power Supply Connections................................ 19
3.6.3 Network Controlled........................................................................... 22
3.7 Auxiliary Relay Module (ARM) Wiring........................................................... 23
3.8 Remote Display Module (RDM) Connection to the Actuator – Optional........ 25
3.8.1 24 Vdc Power Source......................................................................... 26
3.8.2 115/230 Vac Power Source................................................................ 27
3.8.3 Two RDMs (One 24 Vdc and One 115/208/220/230
Vac Power Source)............................................................................. 27
3.8.4 RDM Connections and Dip Switch Settings........................................ 27
Table of Contents I
Table of Contents Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
Section 4: Operation
4.1 Local Display Module Display Module with Bluetooth® - Model 87340......... 29
4.1.1 Graphics Display and Message Center................................................ 30
4.1.2 Control Knob and Selector Knob........................................................ 30
4.1.3 LEDs.................................................................................................. 30
4.1.4 Normal Display Function................................................................... 31
4.2 Remote Display Module (RDM) Display Module with Bluetooth® - Model 87340.... 32
4.2.1 RDM Operation with LDM.................................................................. 32
4.3 Initializing the Actuator................................................................................ 33
4.3.1 Setting Position Limits....................................................................... 33
4.3.2 View Existing Settings....................................................................... 33
4.4 Local Control Operation............................................................................... 37
4.5 Remote/Auto Control Operation.................................................................. 38
Section 6: Troubleshooting
6.1 Troubleshooting Problems/Corrective Action for Actuator Operation.......... 72
6.2 Display Diagnostics...................................................................................... 73
6.2.1 Display Alarm Log.............................................................................. 74
6.2.2 Display Torque Profile........................................................................ 75
6.2.3 Display Torque Archive...................................................................... 76
6.2.4 Display Operation Log....................................................................... 76
6.2.5 Display Operation Archive................................................................. 77
6.2.6 Display Hardware.............................................................................. 77
II Table of Contents
Installation and Operation Manual Table of Contents
E2K-420-0218 Rev. 3 September 2018
Section 7: Maintenance
7.1 Maintenance Schedule................................................................................. 79
7.2 Lubrication................................................................................................... 79
7.3 Pressure Relief.............................................................................................. 79
7.4 Fuse Replacement........................................................................................ 79
7.5 Lifting .......................................................................................................... 80
7.6 Battery Disposal .......................................................................................... 80
7.7 Cleaning of LDM........................................................................................... 80
7.8 Improper Use............................................................................................... 80
7.9 Battery Replacement – “Clicker”................................................................... 80
Appendix A:
A.1 Exploded View (Model-500 Torque Unit Only).............................................. 82
A.2 M-500 with Thrust Base Installation Drawing............................................... 83
A.3 Module Identification and Location.............................................................. 85
A.4 Infrared Controller (IRC) – “Clicker”.............................................................. 86
A.5 IrDa Port...................................................................................................... 87
A.6 Disconnect - Circuit Breaker......................................................................... 87
A.7 Common Bolt Tightening Torques................................................................ 89
A.8 Bluetooth Specifications.............................................................................. 91
List of Figures
Figure 2-1 Declutch Lever and Handwheel ......................................................................... 5
Figure 2-2 Setting Limits – Electrical Operation ................................................................. 6
Figure 2-3 Setting Limits – Manual Operation ................................................................... 7
Figure 3-1 Preparing the Stem Nut .................................................................................... 9
Figure 3-2 Removal of STC Cover ..................................................................................... 11
Figure 3-3 Power Terminal Connections .......................................................................... 13
Figure 3-4 Control Terminal Connections ........................................................................ 13
Figure 3-5 Earth/Ground Connection .............................................................................. 14
Figure 3-6 Control Input Wiring ....................................................................................... 15
Figure 3-7 Inhibit and ESD Wiring .................................................................................... 16
Figure 3-8 TEC2 PST Wiring Diagram ............................................................................... 16
Figure 3-9 ACM Wiring Connections - ACM (Analog Control Module) .............................. 17
Figure 3-10 ACM Installation Connections - ACM (Network Control Module) ................... 18
Figure 3-11 ACM Wiring Connections .............................................................................. 18
Figure 3-12 ACM – Analog Output with External Power Supply ....................................... 19
Figure 3-13 ACM – Analog Output with Internal Power Supply ......................................... 19
Figure 3-14 ACM – Analog Input with External Power Supply ........................................... 20
Figure 3-15 ACM – Analog Input with Internal Power Supply ............................................ 20
Figure 3-16 Futronic – 3 Wire Analog Control with External Power Supply .........................21
Figure 3-17 Futronic – 3 Wire Analog Control with Internal Power Supply .................... 21
Figure 3-18 ARM Wiring Diagram .................................................................................... 23
Figure 3-19 ARM Wiring Connections ............................................................................. 24
Figure 3-20 Connecting RDM Cables to the STC .............................................................. 25
Figure 3-21 RDM Interface Module (Support Both 24V DC and AC) .................................. 26
Figure 3-22 TEC2 Wiring Diagram ............................................................................. 28
Figure 4-1 TEC2 Controller .............................................................................................. 29
Figure 4-2 Local Display Module (LDM) ............................................................................ 29
Figure 4-3 Normal Display ............................................................................................... 31
Figure 4-4 Display Settings ............................................................................................. 36
IV Table of Contents
Installation and Operation Manual Table of Contents
E2K-420-0218 Rev. 3 September 2018
Table of Contents V
Table of Contents Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
List of Tables
Table 3-1 Connecting Actuator A to Actuator B ............................................................... 22
Table 3-2 ARM Wiring Connections ................................................................................. 23
Table 3-3 RDM Connections with Internal Power Source (24VDC) ................................... 27
Table 3-4 RDM Connections with External Power Source (External AC) ............................ 27
Table 3-5 Dip Switch (SW5 and SW6) Settings .................................................................. 27
Table 4-1 LDM Rotating Knobs ......................................................................................... 30
Table 4-2 Normal Display Functions ................................................................................. 31
Table 4-3 RDM and LDM Operation Priority ..................................................................... 32
Table 4-4 Default Configuration Settings ......................................................................... 34
Table 5-1 Relay Outputs #1 through #5 Configuration ..................................................... 53
Table 5-2 Relay Output Function List ................................................................................ 54
Table 5-3 Relay Outputs #9 through #12 Configuration ................................................... 56
VI Table of Contents
Installation and Operation Manual Section 1: Important Notes
E2K-420-0218 Rev. 3 September 2018
WARNING:
Alerts user of potential danger; failure to follow the warning notice could result in serious
personal injury or death.
CAUTION:
Identifies precautions the user must take to avoid personal injury or equipment damage.
NOTE:
Highlights information critical to the user’s understanding of the TEC2 valve actuator
installation or operation.
1.2 Purpose
This installation and operation manual explains how to install, operate, and maintain the
TEC2 valve actuator.
TEC2 actuators are intended for automating part-turn and multi-turn valves within the
specified torque ranges for given model.
WARNING:
Read this manual in its entirety before installing, operating, or performing
maintenance on the TEC2 valve actuator.
Use caution when working on, with, or around valves and actuators.
High pressures, forces, voltages, and flammable media can be present.
Failure to follow instructions for proper electrical wiring, storage, setup, and
maintenance may cause serious injury, damage equipment, or void warranty.
Important Notes 1
Section 1: Important Notes Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
2 Important Notes
Installation and Operation Manual Section 2: Quick Start
E2K-420-0218 Rev. 3 September 2018
NOTE:
The actuator has been configured as specified by the customer and no further changes
should be required. If full valve data was not provided, actuator will be shipped with
default configuration per Table 4.4, Default Configuration Settings, unless specific
configuration was requested.
WARNING:
Use caution when working on, with, or around valves and actuators.
High pressures, forces, voltages, and flammable media can be present.
WARNING:
Verify voltage rating on nameplate before connecting power.
CAUTION:
It is recommended the valve be positioned using the handwheel while setting
the limits to prevent valve damage.
1) Valve Operation
1) Valve Operation
The position limits are now set. The actuator will operate in the normal LOCAL and
REMOTE modes.
4 Quick Start
Installation and Operation Manual Section 2: Quick Start
E2K-420-0218 Rev. 3 September 2018
NOTE:
The user is not required to exit setup after setting limits for the first time. At the
completion of setting the limits, the actuator should be in the “STOP” mode and the valve
should be at its open limit. The LDM should display “100%,” and the red LED should be ON.
The graphics display of the valve should represent full open.
Declutch Lever
TEC2000/TEC2 Enclosure
Hand Crank
Declutch Lever
TEC2000/TEC2 Enclosure
e d
nt inu
co
Dis
Quick Start 5
Section 2: Quick Start Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
LOCAL (BACK)
Open Valve
Then Select
Close Valve
Then Select
STOP
STOP
STOP YES
Accept
Valve Save
Close NO Limits?
Limit?
YES YES
Rotate Selector
Set Local
Knob “NEXT” to
And
Open Valve Toggle Through
The Displays.
NEXT
To Normal Display
6 Quick Start
Installation and Operation Manual Section 2: Quick Start
E2K-420-0218 Rev. 3 September 2018
LOCAL (BACK)
Open Valve
Close Valve Then
Then Select Select “STOP”
STOP
STOP
STOP YES
Accept
Valve Save
Close NO Limits?
Limit?
YES YES
Rotate Selector
Set Local
And Knob “NEXT” to
Open Valve Toggle Through
The Displays.
NEXT
Declutch actuator.
Rotate handwheel to
“OPEN” position limit. EXIT?
When done, select NO
“STOP”.
To Normal Display
Quick Start 7
Section 2: Quick Start Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
2. Select NEXT to advance through the displays until “NETWORK SETUP?” appears.
3. Rotate the control knob to YES. “NETWORK NODE ADDRESS XXX” appears.
4. Rotate the control knob to NO to increment the address numbers. Hold in the NO
position until the desired address is reached.
NOTE:
If the desired address is a lower number than what is displayed, continue to
increment the numbers until the highest numbered address is reached.
The address numbers will then start with the lowest numbered address
and continue to increment.
5. When the correct address is displayed, rotate the control knob to YES.
8 Quick Start
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
Section 3: Installation
WARNING:
Failure to follow instructions for proper electrical wiring, storage, setup, and
maintenance may cause serious injury, damage equipment, or void warranty.
WARNING:
Use caution when working on, with, or around valves and actuators.
High pressures, forces, voltages, and flammable media can be present.
NOTE:
The actuator can be direct mounted to the valve shaft or stem, or can be close coupled to
the auxiliary gear drives. See Appendix for the appropriate drawings.
TEC2000/TEC2 Enclosure
ed
t i nu
o n
c
Dis
Installation 9
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
1. Unscrew Locknut (piece #55) while holding Bronze Stem Nut (piece #54) or Steel
Bore and Key Bushing. Remove the Stem Nut and Key (piece #52).
2. Lubricate Stem. Run Stem Nut (piece #54) down Stem to verify Acme thread fit.
Remove Stem Nut (piece #54) and set aside.
3. Model 3000-8000 may include thrust base assemblies. See Appendix for instructions.
2. Insert the screws through the valve flange into the actuator and engage at least
one full screw diameter deep into the bottom base.
3. Tighten to a preload.
See Appendix for common bolt tightening torques.
NOTE:
Mounting screws are provided only if EIM supplied the adapter. Verify screws are through
the adapter; engage a minimum of one screw diameter deep into the actuator base.
4. Screw the Stem Nut (piece #54) onto the Stem until it enters the Drive Sleeve.
5. Place Key (piece #52) in line with the Drive Sleeve Keyway. Insert Key (piece #52).
6. Turn the Handwheel in the Open direction to pull the Stem Nut (piece #54) into
the Drive Sleeve until it bottoms out.
NOTE:
Valve will begin to open.
7. Place the Locknut (piece #55) over the Valve Stem. Screw the Locknut
(piece #55) firmly into place against the top of the Stem Nut (piece #54)
using a drift to tighten.
8. Use a number 30 (0.1285) drill bit: drill a hole 3/4 inch (19mm) deep into the
Drive Sleeve assembly threads for the Locknut Lockpin (piece #56).
Use the groove in the Stem Nut Locknut threads as a guide.
9. Install Locknut Lockpin (piece #56) into drilled hole to prevent the
Stem Nut Locknut (piece #55) from working loose and turning.
NOTE:
When installing, the Locknut Lockpin (piece #56) should extend 1/4 inch (6mm) inch
above the Drive Sleeve assembly to allow for easy removal.
CAUTION:
Locknut must be screwed very tightly against stem nut.
10 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
NOTE:
Valve actuator requires a circuit breaker within the line of sight, sized for the motor
currently specified on the nameplate.
See Appendix Section A.7, for the circuit breaker options.
Remove cover with a strap wrench, drift, or pinch bar by rotating the
cover counterclockwise.
TEC2000/TEC2 Enclosure
e d
nt inu
co
Dis
Installation 11
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
1. Loosen terminal block connectors L1, L2, L3 and GND screws with a common
or Phillips head screwdriver.
2. If bare wire is being used, strip insulation a maximum of 0.4 inch (10 mm).
3. Insert wire or wire lug under terminal block connector screw clamps and
tighten.
Figure 3-3 details power terminal size and length of bare wire strip. Figure 3-4 details
control terminal size and length of bare wire strip.
12 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
1. Connect the main power supply cables, including the earth/ground wire using
#1 Phillips or 3/16 inch (5mm) slotted tip screwdriver.
2. Attach earth/ground wire to internal ground lug using 1/4 inch #11 slotted
screwdriver.
3. Use the barrier strip clamp screws to connect the control wires.
4. Ensure all connections are hand tight, including any unused
terminal connections.
The main power supply and ground wire connections are screw size M4.
The control connection screw size is M3.
NOTE:
Clean electrical enclosure threads thoroughly and lightly grease with a dielectric grease
before closing.
1. Using a 1/4 inch (6mm) slotted tip screwdriver back out the 5/16 inch
(8mm) set screw.
2. Connect 14 AWG or larger earth/ground wire; tighten setscrew.
Installation 13
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
The DBM can be provided as an option with the TEC2 or it can be purchased later.
If purchased separate, install as follows. If provided with the TEC2, proceed with
Step No. 2 to activate.
1. Mount the DBM under the Auxiliary Control Module (ACM) on the cover plate
and connect to the Central Control Module (CCM) via a 3-wire cable.
14 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
NOTE:
The battery should not be enabled until the unit is field commissioned and ready for
power to be applied.
The battery can only be replaced with an Ultralife U9VL 9V battery. To prevent losing the
clock settings, install one new battery before removing one old one. Two batteries can be
installed for extended life.
Installation 15
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
External
Open Inhibit Power
5 Supply
Close Inhibit
6 + 18-150 VDC
ESD
7 or
Z
0V common - 20-250 VAC
8
5 Open Inhibit
6 Close Inhibit
7 ESD
Internal
8 Power
Supply
0V common
10
9 +24 VDC
NOTE:
See Section 3.6.2, Analog Controlled - Power Supply Connections for 3 wire analog.
Stop/PST 3
PST Start
Common 4
RO #3 14
Green Light
Common 15
(PASS)
RO #4 16
Red Light
0 VDC 10
(FAIL)
24 VDC 9
16 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
AIN1+
3
AIN1-
5
Common (0V) for Inhibit/ESD Inputs (4-6) All Analog I/O are Isolated,
Shield
8
Loop Powered
}
9
(-) AO1-
11 13 15 17 19
AO2+
Relay Output #1 Limit Switch Open (LSO) } AO2-
Relay Output #2 Limit Switch Close (LSC) } Spare (n/c)
DCMlink (+)
Relay Output #3 Intermediate Limit A (LSA) } Spare (n/c)
Relay Output #4 Intermediate Limit B (LSB) } DCMlink (-)
The ARM can be installed with the Futronic ACM by stacking it on top of the Futronic ACM
and connecting to the STC. See Section 3.7, Auxiliary Relay Module (ARM) Wiring.
Installation 17
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
1
Open Digital Input #1
Close Digital Input #2
2
Stop Digital Input #3
25 27 29 31 33 35 37 39 41 43
AIN1+
3
Common (0V) for Control Inputs (1-3)
26 28 30 32 34 36 38 40 42 44
4
AIN1-
5
Open Inhibit Digital Input #4 AIN2+
6
Close Inhibit Digital Input #5 AIN2- ACM Option
ESD Digital Input #6 Shield
7
Common (0V) for Inhibit/ESD Inputs (4-6) All Analog I/O are Isolated,
Shield
8 10 12 14 16 18 20 22 24
Loop Powered
} (+)(-)
9
AO1+ with Channel to Channel Isolation
User Power Supply 24VDC Power Supply
AO1-
11 13 15 17 19
AO2+
Relay Output #1 Limit Switch Open (LSO) } AO2-
Relay Output #2 Limit Switch Close (LSC) } Spare (n/c)
DCMlink (+)
Relay Output #3 Intermediate Limit A (LSA) } Spare (n/c)
Relay Output #4 Intermediate Limit B (LSB) } DCMlink (-)
} CAM Option
Relay Output #5 Monitor Relay N.O. } (+)
Shield Network Port A
Monitor Relay N.C. } (-)
}
Emergency Stop (N.C.) Shield
21 23
Remote Display Model Communication Port (+) (+) Network Port B
Emergency Stop (N.C.) (-)
Remote Display Model Communication Port (-)
Earth Ground ACM_CAM Option
Notes:
1. All digital inputs have an input voltage range of 18-150 Vdc or 20-250 Vac.
2. All digital relay outputs are rated for 5 A @ 30 Vdc or 5 A @ 250 Vac
Resistive,
2 A Inductive load.
3. Jumpers can be added between Terminals 8 and 10, Terminals 32 and 34,
Terminals 36 and 38, and Terminals 40 and 42 but are not required.
4. Emergency Stop requires jumper (between Terminals 20 and 22) or
normally closed contacts (actuator stops when contacts open).
5. Remote display communication port is RS-485.
6. If bare wires (without terminals) are connected, remove a maximum of
1/4 inch (6 mm) insulation.
ACM Wiring
Terminals
25 to 44
18 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
Installation 19
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
+ +
+
- - 24 VDC
25 +
-
- AIN#1
26
27 +
- AIN#2
28
29
Earth
9 +
+ +
- 24 VDC
10
+ - -
25
AIN#1
-
26
27 +
AIN#2
28 -
29
Earth
20 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
Figure 3-16 Futronic – 3 Wire Analog Control with External Power Supply
Z
3-Wire 3
Toggle (-) 20-250VAC
Common 0v 4
4-20mA Position
Set Point
(+)
(+)
External 24VDC Input
(-) (-)
25 (+)
AIN#1
26 (-)
29 Earth Ground
Figure 3-17 Futronic – 3 Wire Analog Control with Internal Power Supply
Open Open
1
Close Close
2
Internal
3-Wire 3 Power
Toggle Supply
Common 0v 4
4-20mA Position
9
(+) Set Point
(-) 24VDC (+)
10
(+) (-)
25
(-) AIN#1
26
29 Earth Ground
Installation 21
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
NOTE:
Factory personnel must install the ACM and CAM. These modules (CAMs) may be
installed in the field only by factory-trained technicians using a special passcode to
enter the “FACTORY SETUP” mode.
Connect the actuators as shown in Table 3-1 for RS-485 redundant bus or E>Net
networks. If another protocol is selected then refer to the wiring diagram supplied
with the actuator for connections.
NOTE:
If E>Net network topology is specified, insert a jumper between Terminals 40 and
42 to connect the network cable shield throughout the network and connect a
single point earth/ground elsewhere.
22 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
Connect the ARM within the controller in accordance with Table 3-2. See Section 3.3,
Electrical Connections for general electrical connection requirements.
AIN1+
3
AIN1-
5
Common (0V) for Inhibit/ESD Inputs (4-6) All Analog I/O are Isolated,
Shield
8 10 12 14 16 18 20 22 24
Loop Powered
}
9
AO2+
Relay Output #1 Limit Switch Open (LSO) } AO2-
Relay Output #2 Limit Switch Close (LSC) } Spare (n/c)
DCMlink (+)
Relay Output #3 Intermediate Limit A (LSA) } Spare (n/c)
Relay Output #4 Intermediate Limit B (LSB) } DCMlink (-)
Installation 23
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
ARM Wiring
Terminals
39 to 44
24 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
NOTE:
If RDM 1 or 2 is enabled and not connected, the actuator will be in stop mode and
cannot be operated until RDM is connected or disabled.
RDM
Wiring
Terminals
21, 23, and 24
Installation 25
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
NOTE:
By using two cables, Belden 8719, or equivalent for power and Belden 9841 or
equivalent for RS-485 communication, the distance limitation is increased to
4,000 feet (1,200 meters).
Figure 3-21 RDM Interface Module (Support Both 24V DC and AC)
P2
SW1 1-6
26 Installation
Installation and Operation Manual Section 3: Installation
E2K-420-0218 Rev. 3 September 2018
3.8.3 Two RDMs (One 24 Vdc and One 115/208/220/230 Vac Power Source)
To use two RDMs, one can receive 24V DC power from the actuator and the other
has to get power from an external AC source, 115/208/220/230 Vac.
Installation 27
Section 3: Installation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
L1 3 - Phase
Motor
L2 Power
Thermal Motor
Protector
Control L3 Supply
Module
GND
1 Open
2 Close
24 VDC
Power 3 Stop
Supply
Digital Inputs
4 Common 0V
5 Open Inhibit
Central Control Module
Note: Maximum Power Rating: 15.12 Watts 6 Close Inihbit
Maximum Source Current: 0.63 Amps
7 ESD
8 Common 0V
9 +24 VDC
10 0 VDC
R0#1 11 LSO
12 Common
R0#2 13 LSC
Local Display Module Remote Display Module
(1 or 2 May be fitted) Contact Outputs R0#3 14 LSA
1 1 1 5
+ 36
External Close Close Close Inhibit DCMlinkTM
Z
Power - 38
4 2 2 6
Supply Common 0V +
18-150 VDC
Z
or - ESD
Stop
20-250 VAC
4 3 7
Common 0V + +
Z
Z
NOTES: 1) All digital inputs have an input votage range or 18-150 VDC or 20-250 VAC. LSO Open Limit
2) All digital relay outputs are rated for 5A @ 30 VDC or 5A @ 250 VAC Resistive, 2A inductive load. LSC Close Limit
3) Jumpers shown connected between terminals are permissible but not required. LSA Open Limit
LSB Close Limit
4) Emergency stop requires jumper or normally closed contact (actuator stops when contact open)
5) Remote display communication port is RS-485.
6) If bare wires (without terminals) are connected, remove a maximum of .25 inch insulation.
7) User replaceable primary fuses (F1 and F2) are located in the Terminal Chamber Enclosure.
All transformer secondary fuses are automatic resetting.
8) Contacts Outputs and Output Switch Contact Development Chart shown for default configuration only. DWN BY JTD ORIGINAL DATE 4-21-03
User may redefine all Outputs (See TEC200O Installation & Operation Manual E2K-405-0902). WIRING
DIAGRAM TEC-001
NOTE:
The Local Display Module (LDM) is a part of the actuator and is powered internally by a low voltage DC.
The Remote Display Module (RDM) is powered by two options, either 24VDC or 90-250VAC 50/60Hz.
28 Installation
Installation and Operation Manual Section 4: Operation
E2K-420-0218 Rev. 3 September 2018
Section 4: Operation
Figure 4-1 TEC2 Controller
LEDs
Graphics Display
Message Center
Control Knob
Selector Knob
Operation 29
Section 4: Operation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
NOTE:
If the selector knob remains in either NEXT or BACK position, the display will scroll.
4.1.3 LEDs
There are three LEDs on the LDM:
• Red
• Green
• Yellow
The default function of these LEDs is detailed in Table 4-2.
See Section 5.5.2, Valve Control Setup to reverse Red to indicate closed/closing and
Green to indicate opened/opening.
30 Operation
Installation and Operation Manual Section 4: Operation
E2K-420-0218 Rev. 3 September 2018
Figure 4-3 details the display during normal function. The bar graphs, position
digits, icons, and LEDs indicate normal activity, i.e., the valve opening, closing, or
stopping in mid-travel. The message center remains blank until alarms are active
or the valve is opening, closing, full open, or full close. Table 4-2 details various
normal activities and how each is displayed.
The valve has stopped and is 75% opened. The yellow LED is ON and the message
center is clear.
Operation 31
Section 4: Operation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
NOTE:
If the RDM does not receive communication messages from the Central Control Module
(CCM) within 5 seconds after power is applied, the RDM will display the flashing message
“CCM LINK FAILED” and all three LEDs will blink. This will also occur if communication is
lost for 5 seconds or more.
If RDM 1 or 2 is enabled and not connected, the actuator will be in stop mode and cannot
be operated until RDM is connected or disabled.
Mode of Operation LDM, RDM #1, RDM #2 and Selector Switch Position
At least one module must have the selector switch in the STOP
STOP
position.
At least one module must have the selector switch in the LOCAL
LOCAL
position and none have the selector switch in the STOP position.
All modules must have the selector switch in the REMOTE
REMOTE
position.
32 Operation
Installation and Operation Manual Section 4: Operation
E2K-420-0218 Rev. 3 September 2018
NOTE:
A passcode is not needed for the initial position limit settings. However, any limit
setting changes required after initialization requires a passcode and are changed
via the “CHANGE SETTINGS” mode. See Section 5.5.3, Set Valve Travel Limits.
CAUTION:
It is recommended that the final valve position be set using the handwheel
while setting the limits to prevent valve damage.
There are two different routines for setting limits. Initial limit settings can be set as
described in Section 2, Quick Start. Limit settings can be changed as described in
Section 5.5.3, Set Valve Travel Limits.
Once the limits have been set, check the settings as follows.
1. Move the valve in the close direction. The Red LED should go off and the
Green LED should blink within one handwheel turn.
2. Move the valve in the open direction. The Green LED should go off and the
Red LED should be blinking within one handwheel turn.
The actuator will operate in the normal LOCAL and REMOTE modes.
Exit “SETUP” mode.
1. Rotate the selector knob to NEXT to cycle through the displays until
“EXIT?” is displayed.
2. Rotate the control knob to YES.
Discrete Outputs
Valve Discrete
(Relays (ARM Relays Inhibit and ESD
Control Inputs
1 thru 5) 9 thru 12)
DI#1= Active on RO#9 = Lost Power
Mode = 3 Wire RO#1= LSO Open Inhibit = OFF
CLOSED contact Alarm
Close Direction
DI#2= Active on
= (Gearing RO#1= N.O. RO#9 = N.O. Close Inhibit = OFF
CLOSED contact
Dependent)
DI#3= Active on
Seat = Position RO#1= Continuous RO#9 = Flash Local ESD = OFF
OPEN contact
DI#4= Active on RO#10 = Motor
Close Torque = 50% RO#2= LSC Remote ESD = OFF
CLOSED contact Overload Alarm
DI#5= Active on Lost Com ESD =
Open Torque = 50% RO#2= N.O. RO#10 = N.O.
CLOSED contact OFF
Local Control = DI#6= Active on Stayput on ESD
RO#2= Continuous RO#10 = Flash
Maintain OPEN contact = ON
Remote Control = RO#11 = Lost *ESD Override on
RO#3= LSO
Maintain Phase Alarm Thermal = OFF
ESD Override on
Torque Retry = OFF RO#3= N.O. RO#11 = N.O.
Local = OFF
Remote Display 1 ESD Override on
RO#3= Continuous RO#11 = Flash
= OFF Stop = OFF
Remote Display 2 RO#12 = Over ESD Override on
RO#4= LSC
= OFF Torque Alarm Inhibit = OFF
Close LED = Green ESD Override on
RO#4= N.O. RO#12 = N.O.
Open LED = Red Torque = OFF
Low Battery Alarm ESD Delay 0.0
RO#4= Continuous RO#12 = Flash
= OFF Seconds
Valve Stall Delay Go to _% Open on
RO#5= MONITOR
Time = 8 Sec ESD = 0
Retain Setpoint =
RO#5= Continuous
OFF
LSA Position = 25%
LSB Position = 75%
* Overriding the thermal motor protection will invalidate the hazardous area certification.
34 Operation
Installation and Operation Manual Section 4: Operation
E2K-420-0218 Rev. 3 September 2018
2. Place the selector knob in the NEXT position to advance through each
display until “DISPLAY SETTINGS?” is displayed.
NOTE:
The “DISPLAY SETTINGS?” mode can be accessed without entering a passcode;
however no changes can be made to the settings in this mode. To make any
changes see Section 5, Customizing Actuator Settings.
Operation 35
Section 4: Operation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
BACK NEXT
BACK
VALVE CONTROL Control Mode Drive Sleeve <pos or trq> Torque Close Torque
SETUP? YES <control mode> YES Close: <cw or ccw> YES Position Seat YES Backseat <on/off> YES <xx>%
Open Torque Local Control Remote Control Torque Retry Remote Display 1
<xx>% YES <LocalCtrlSetting> YES <RemoteCtrlSetting> YES <on/off> YES <on/off>
YES
OR
NEXT
36 Operation
Installation and Operation Manual Section 4: Operation
E2K-420-0218 Rev. 3 September 2018
NOTE:
The actuator is shipped configured for inching mode unless specified at the time order is
placed; i.e. the actuator is shipped in the “Maintained” mode.
3. Place the control knob in either the OPEN or CLOSE position and continue to hold.
After 0.5 seconds the actuator will move in the open or close direction.
4. Release the knob to stop the actuator movement. The knob will return to the
neutral position.
3. Place the control knob in either the OPEN or CLOSE position. Momentarily hold for
0.5 seconds and release. The actuator will move in the open or close direction to
the end of travel.
OR
• Place the control knob in the opposite direction of the current movement
for less than 1.0 second.
NOTE:
If the control knob is held in the opposite direction for more than 1.0 second, the actuator
will reverse direction after stopping for approximately 0.5 seconds to allow instant
reversing without valve plugging or causing high stresses and damage to the actuator.
Operation 37
Section 4: Operation Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
NOTE:
See Table 4.4 for defaults.
• Two-wire control
• Three-wire control
• IrDA port
• Three-wire analog
• Analog
• Network
2. Use the selector knob (NEXT/BACK) to select “CONTROL MODE” under “VALVE
CONTROL SETUP?”
3. Use the control knob (NO) to select the desired control mode. See Section 5.5.2,
Valve Control Setup.
4. Exit “SETUP” mode and place selector knob in the REMOTE position.
5. Apply the control signal and maintain. After 0.5 seconds the actuator will move in
the open or close direction.
5. Momentarily pulse either OPEN or CLOSE control signal for 0.5 seconds minimum.
The actuator will move in the open or close direction to the end of travel.
6. Momentarily pulse the remote stop signal to stop the actuator movement.
38 Operation
Installation and Operation Manual Section 4: Operation
E2K-420-0218 Rev. 3 September 2018
Two-Wire Control
The two-wire control mode uses only one contact to control the valve. When the contact is
closed, the valve opens, and when the contact is open, the valve closes. The contact open
and close status can be reversed in the “SETUP” mode. See Section 5.5.4, Discrete Input
Setup.
Three-Wire Control
The three-wire control mode uses two maintained contacts to open or close the valve.
This is an “inching” type mode. Remote seal-ins, “Momentary” mode, may be activated in
the “SETUP” mode. If the three-wire control is used with the seal-ins activated, the valve
cannot be stopped while being remotely controlled; the valve can only be stopped via the
inhibit or emergency stop inputs.
Four-Wire Control
The four-wire control mode uses three maintained contacts to open, close, or stop the
valve. The default configuration sets the stop input to be active on open contact.
The default configuration can be modified in the “SETUP” mode. See Section 5.5.4,
Discrete Input Setup.
Operation 39
Section 5: Customizing Actuator Settings Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
1. Place the selector knob in the STOP position. Setup may be performed at any one
location; i.e. at the LDM or any RDM that is connected.
NOTE:
STOP button on the Clicker only stops a moving valve.
2. Rotate the control knob to YES, then NO, then YES, then NO in rapid succession
and then release. “SETUP” icon will be displayed on the display module and
“SETUP?” will be displayed on the message center.
NOTE:
Do not hold the knob in any one position longer than 0.5 seconds.
3. Rotate the control knob to YES. A series of questions will be displayed as detailed
in Figure 5-1.
NOTE:
If the control knob is placed in the NO position or if NEXT or BACK is selected in
lieu of YES, the display will return to the normal display mode.
4. Use the control knob to answer “YES” or “NO” to the displayed questions.
Use the selector knob, NEXT and BACK, to advance through the setup selections.
NOTE:
If a knob entry is not made within 120 seconds, the actuator will exit the “SETUP” mode
and revert to the normal display.
NOTE:
No Passcode is required for viewing any of the settings.
Passcode will be needed for changing any of the parameters.
YES
NO
Go to
Display Unit
Figure 5-3
BACK
Parameters? YES
NO
Change Go to
Settings?
YES Figure 5-4
NO
Go to
NEXT
Display
Settings? YES Figure 4-5
NO
Display Go to
Diagnostics? YES Figure 6-1
NO
To modify previously set limits see Section 5.5, Change Settings and Section 5.5.3, Set
Valve Travel Limits.
2. If English is the desired language, answer “NO.” “ADJUST CONTRAST?” will appear.
Go to Step No. 4.
4. If contrast adjustment is needed, answer “YES.” Then select NO and hold until the
desired contrast is reached. Select YES. “CHANGE DISPLAY?” appears.
5. Select NO to exit.
Go to BACK NEXT
Figure 5-15
NO
BACK
NO NO NO
NO
or
Next
English, Spanish,Portuguese, Increment 1 to 64
Russian, French,Mandarin, In Step Size of 1
Italian, German
Go to
Figure 5-16
2. Use the selector knob (BACK/NEXT) to view parameters as shown in Figure 5-3.
The tag name, method of control, and network address may be entered or changed via the
“Change Settings” mode. See Section 5.5, Change Settings.
All other parameters viewed are factory setup and cannot be changed by the user.
Go to
Figure 5-2
BACK NEXT
BACK
NO NO NO NO
NO
or
Next
NO NO NO NO
Run:<run amp> Torque Spring: Max Torque: Batery Enable? <current date>
Stall:<stl amp> YES <torq spring> YES <max torq> % YES <Yes/No> YES <current time> YES
NO NO NO NO
Not
LDM Bluetooth RDM1 Bluetooth RDM2 Bluetooth BT Discovery Implemented
<enable/disable YES <enable/disable YES <enable/disable YES <enable/disable YES Yet
NO NO NO NO
NO NO NO NO
Go to Next Display
Figure 5-4
2. Enter passcode.
NOTE:
A passcode must be entered to change settings.
3. Use the selector knob (NEXT/BACK) to scan the display for the desired setting to
change the following:
• Discrete input
• Discrete output
• Two-speed timer
• Analog
• Network
• Tag name
• Passcode
YES NO
BACK
NO NO NO
Set Go to Change Go to
Travel
Figure 5-7 Figure 5-2
BACK
NO
NO
Discrete Go to Tag Go to
Input Is ACM Installed? Name
Setup? YES Figure 5-9 Setup? YES Figure 5-15
NO
NO
Go to
NEXT
Discrete
Output Change Go to
YES Figure 5-10 Display?
Setup? YES Figure 5-2
BACK
NO
NO
Inhibit Go to
and ESD YES Figure 5-11
Setup? Passcode Go to
Setup? Figure 5-16
YES
NO
NO
Two-Speed Go to
Timer YES Figure 5-12 Go to
Setup? Battery
NEXT
NO
Set Time Go to
And YES Figure 5-18
Date
NO
Go to
Bluetooth?
YES Figure 5-19
NO
Save
Change
Settings? YES
NO
NOTE:
When “Z” is displayed the data will rollover to “0” and
continue incrementing.
NOTE:
If the passcode is not the correct passcode, the display will return to
“CHANGE SETTINGS?” display. See Figure 5-5.
Go to
Figure 5-3
BACK NEXT
BACK
NO
NO NO NO NO
YES
Go to Next Display
YES See Figure 5-4
NO
Go to Next Display
See Figure 5-4
2. Use the selector knob (NEXT/BACK) to scan the settings until the desired
setting is reached. Place the control knob in the NO position to increment
through each setting’s associated choices. Answer “YES” to accept the
desired choice. See Figure 5-6.
BACK
NO NO NO NO NO NO
YES NO
Torque Backseat Close Torque Open Torque Local Control Remote Control
<xx>% <xx>% <LocalCtrlSetting> <RemoteCtrlSetting>
<on/off> YES YES YES YES YES
NO NO NO NO NO
NO NO NO NO
Increment torque Increment remote Increment remote Change LED color choice:
retry choice: display 1 choice: display 2 choice: close GREEN/open RED
On or OFF On or Off On or Off close Red/open Green
Clear
Increment from 1 to 60 Between Reset the Archinve the
the alarm
in step size of 1 On and Off operations log torque profile
logs
Go to Next Display
See Figure 5-4
1. If the close limit is acceptable, answer “YES.” If not rotate the selector
knob to LOCAL. Close valve to desired limit, rotate selector knob to STOP,
and
answer YES.
2. If the open limit is acceptable, answer “YES.” If not rotate the selector
knob to LOCAL. Open valve to desired limit, rotate selector knob to STOP,
and
answer YES.
See Figures 5-7 and 5-8.
BACK
NO NO
NO
LOCAL LOCAL
YES
SAVE LIMITS?
NO
Go to
Figure 5-4
Go to
Figure 5-6
BACK NEXT
BACK
NO NO
NO
LOCAL LOCAL
NO
or
NEXT
Go to
Figure 5-4
YES
YES
BACK
Go to
Figure 5-4 DI #3 Active on NO Increase DI #3 Active
<open/close> Contact Choice:
CONTACT OPEN or CLOSE
YES
YES
NEXT
YES
YES
3. Use the control knob (NO) to select desired configuration for each relay.
Configu-
Default Configure Default Configure
Relay rable
Function N.O./N.C. Setting Flashing
Function
LSO See Table 5-2
RO#1 Valve full Relay Output Yes N.O. Yes
OPEN Function List
LSC See Table 5-2
RO#2 Valve full Relay Output Yes N.O. Yes
CLOSE Function List
LSO See Table 5-2
RO#3 Valve Full Relay Output Yes N.O. Yes
Open Function List
LSC See Table 5-2
RO#4 Valve Full Relay Output Yes N.O. Yes
Close Function List
Monitor
Host Control – 1 N.O. and
RO#5 Valve not No Yes
see NOTE 1 N.C.
available
NOTE:
Host Control means the control of this relay has been given to the network if a
Controlinc card has been installed. The relay will not function if the Controlinc card
is not installed. Flashing means the output will cycle ON and OFF in one-second
intervals while the function is active.
• VALVE DRIFT
• LSC (Close limit) • LOCAL (MOVED BY • ESD ACTIVE
HANDWHEEL)
• LSA (Intermediate limit A) • STOP (SS OFF) • LOST POWER • LOST ANALOG
• MOTOR
• LSB (Intermediate limit B) • REMOTE • ACTUATOR FAIL
OVERLOAD
• HOST CONTROL
• OPENING • OPEN TORQUE • LOST PHASE (Controlled by
Network)
• LOST COM
• CLOSING • CLOSE TORQUE • OPEN INHIBIT
A/B
• OVER TORQUE
• MOVING • CLOSE INHIBIT • UNIT ALARM
(Open or Close)
• Partial Stroke
Test (PST)*
DISCRETE Relay #1
<trigger>
Relay #1
<N.O. / N.C.>
Relay #1
<cont / flash>
Relay #2
<trigger>
Relay #2
<N.O. / N.C.>
Relay #1
OUTPUT SETUP? YES YES YES YES YES YES <cont / flash> YES
NO NO NO NO NO NO
BACK
Increment thru list Increment Relay Increment Relay Continuous Increment thru list Increment Relay Increment Relay Continuous
of relay triggers Normally Open / Close Choice: or Flashing Choice: of relay triggers Normally Open / Close Choice: or Flashing Choice:
(see list below) N.O. or N.C. Continuous or Flashing (see list below) N.O. or N.C. Continuous or Flashing
NO NO NO NO NO NO
Increment thru list Increment Relay Increment Relay Continuous Increment thru list Increment Relay Increment Relay Continuous
Go to of relay triggers Normally Open / Close Choice: or Flashing Choice: of relay triggers Normally Open / Close Choice: or Flashing Choice:
Figure 5-4 (see list below) N.O. or N.C. Continuous or Flashing (see list below) N.O. or N.C. Continuous or Flashing
YES
NO NO NO NO
Increment Relay #5 Increment Relay Continuous Relays #9 to #12 are Increment Position Increment Position
Choice as: or Flashing Choice: configured the Same 1-99% in 1-99% in
Generic or Monitor Continuous or Flashing as #1 to #4 Steps of 1% Steps of 1%
NOTE:
*Only available for Relays 3 and 4.
Relays #9 through #12 are the auxiliary relays when the Auxiliary Relay Module
(ARM) is installed. To configure these relay outputs, follow Step No.1 through
No. 3 listed above. See Table 5-3.
NOTE:
The ARM cannot be added when the Controlinc ACM is installed.
2. Use the selector knob (NEXT/BACK) to review the settings for Control
Inhibits and Emergency Shut Down.
3. Use the control knob (NO) to select either ON or OFF for each setting;
then answer “YES.”
Figure 5-11 Inhibit and ESD SetupFigure 5-11 Inhibit & ESD Setup
YES YES
YES YES
Go to
Next Figure 5-12 Hard Wired ESD ESD Override
<Yes=On; On Stop:
BACK
No=Off> <Yes=Off;
No=On>
YES YES
YES YES
NEXT
YES YES
<ValvePos= NO 0-60mSec
Stayput, ESD
Open, Close> On ESD
in 0.25
Delay
<Yes=Off; No=On> increments
YES YES
Go to
Next Figure 5-4
NOTE:
All three timers, close, open, and anti-water hammer, can operate at the same time.
If two timer ranges overlap, the anti-water hammer timer overrides all timers.
NO
NO NO NO NO
NO
OPEN Open Timer Timer Start Timer Stop Pulse On Time: Pulse Off Time:
TIMER SETUP? YES <On / Off>
YES
Position:
<xx>%
YES Position:
<xx>%
YES <xx.x> Sec
YES <xx.x> Sec
YES
NO NO NO NO
NO
YES
NO NO
NOTE:
Only displayed/applicable if the ACM is installed and analog control is enabled in
the valve control setup. See Section 5.5.2, Valve Control Setup.
All analog I/O are loop powered.
3. Use the control knob (NO) to increment the bandwidths and delay
time, to select polarity and lost signal parameters, and to calibrate
analog in/out.
To calibrate analog output AO#2, the user must connect a calibrated precision
4-20mA current meter to terminals to 33(+) and 34(-).
NOTE: The actuator senses that the Futronic ACM is installed and adjusts the display sequence to display
only one input. Figure 5-13 Analog Setup
Go to Figure 5-13
BACK Position
Bandwidth = Control Mode Analog? Analog Input #1
<x.x>% NO Alarm
<0.1-5.0% in 0.1% <on/off>
YES
ANALOG YES
increments>
SETUP?
YES YES
NO
OR
NEXT
Delay Time = NO
<xx.xx> SEC
<0-60 sec in 1 sec Analog Control AIN 1?
increments> NO
YES NO
YES
Input
Polarity Close =
<4/20>mA
ACM Installed?
Analog
YES NO Input #2
Alarm
YES
NEXT
<on/off>
Output YES
Polarity Close =
<4/20>mA
YES NO
AO #1 Source
<position, setpoint,
torque, network>
NO <LostSigAction>
On Lost
Stayput or Signal?
Go To Position YES
YES
AO #2 Source
<position, setpoint,
Go to Position on torque, network>
Lost Signal? NO
YES
YES
Calibration Setup
Return to Analog Setup?
In Figure 5-13
BACK
Calibrate
AIN #1 YES
4-20MA?
NO
NO NO
NO NO NO
Calibration Setup
Return to Analog Setup?
In Figure 5-13
BACK
Calibrate
AIN #2 YES
4-20MA?
NO
NO NO
NO NO NO
Calibrate Go to
AO#1
NO
Figure 5-13-2
4-20MA?
YES
NO NO
NO
YES
NEXT
Increase Value Increase Setting
0.01 mA 0.01MA?
NO
NO
OR
YES NEXT
Decrease Value Decrease Setting
0.01 mA 0.01MA?
YES
NO
NO
YES
NEXT
Increase Value Increase Setting
0.01 mA 0.01MA?
NO
NO
OR
YES NEXT
Decrease Value Decrease Setting
0.01 mA 0.01MA?
YES
YES
NO NO
NO
YES
NEXT
Increase Value Increase Setting
0.01 mA 0.01MA?
NO
NO
OR
YES NEXT
Decrease Value Decrease Setting
0.01 mA 0.01MA?
YES
NO
NO
YES
NEXT
Increase Value Increase Setting
0.01 mA 0.01MA?
NO
NO
OR
YES NEXT
Decrease Value Decrease Setting
0.01 mA 0.01MA?
YES
NOTE:
Only displayed/applicable if the Communication Adapter Module (CAM) and
the ControIinc ACM are installed, and the network control is enabled.
See Section 5.5.2, Valve Control Setup.
3. Use the control knob (NO) to increment the node address, response delay,
and analog I/O scale, and to select the parity, and analog scale.
Protocol is set at the factory by the selected CAM based on purchase order
information. Protocol may not be changed by the user in the field. Only factory
technicians may change the CAM or protocol in the field.
Baud rate is automatically defined by the Controlinc ACM and no setup is required.
To calibrate analog inputs, the user must connect a calibrated precision 4-20mA
current source to Terminals 25(+) and 26(-) for AIN#1 or Terminals 27(+) and 28 (-)
for AIN#2. To calibrate analog output, the user must connect a calibrated precision
4-20mA current meter to Terminals 29(+) and 30(-) for AO#1.
YES
NO NO NO NO NO
NO
OR
NEXT Increment from Increment from Increment from Increment alarm Increment parity
001 to 254 001 to 255 001 to 255 choice: choice: NONE, ODD
<YES or NO> or EVEN
Go to
Figure 5-2
NO NO NO NO
NO
NO NO NO
Write Protect?
<YES/NO>
BAUD RATE:
4800, 9600, 1440,
19200, 38400, NO
57600, 115200 &
128000
Increment choice:
<YES or NO>
YES NO
NETWORK Network Node
SETUP? YES
Address <xxx>
<001-245>
YES
Enable Net B
NO Alarm?
<alarm>
OR
NEXT
YES NO
Go to next display
Response Delay
See Figure 5-4
<xxx>MS
YES NO
Chan B Parity?
<parity>
YES NO
Enable Net A
BACK
Alarm?
<alarm>
YES NO
Chan B
Baudrate?
<baud>
YES NO
Chan A Parity?
<parity>
YES NO
Chan B
Stop Bit?
<stopbit>
YES NO
NEXT
Chan A
Baudrate?
<baud>
YES NO
Chan B
Word Length?
<wlength>
YES NO
Chan A
Stop Bit?
<stopbit>
Write
Protect?
<YES/NO>
YES NO
2. Use the control knob (NO) to increment the data entry selection for
each character.
NOTE:
The tag name consists of a maximum of sixteen characters. Spaces and dashes are
included in the sequence of “space,” “-,“ “0-9,” “A-Z.”
4. Use the selector knob (BACK) to make changes to the previous characters
in the tag name while entering the data.
Menu Setup
Go to
TAG NAME SETUP MENU
Figure 5-13 Figure 5-15
BACK NEXT
BACK
NO
OR
NEXT
NO NO NO
BACK
Increment Increment Increment
characters: sp, -, characters: sp, -, characters: sp, -,
0-9, A-Z, 0-9, A-Z, 0-9, A-Z,
YES
NEXT
OR
BACK
NO NO NO
2. Use the control knob (NO) to increment the data entry selections of 0-9
and A-Z for each character. The passcode consists of 3 characters.
3. Use the selector knob (BACK) to make changes to the previous characters
in the passcode while entering theMenu
data. Setup
BACK
NOTE:
This new passcode must be entered the next time Continue
changes this processare made.
TAG NAME ACCEPT?
for 16 characters
ACCEPT? ACCEPT?
SETUP? YES x YES xx YES xx YES
NO
OR
NEXT
NO NO NO
YES
NEXT
OR
BACK
NO NO NO
BATTERY Battery
ENABLE? YES Enable?
NEXT
OR
BACK
NO
Increment
choice:
<YES/NO>
Customizing Actuator Settings 69
NO
OR
NEXT
NO NO NO
Figure 5-17 Battery Enable Menu
BACK
Increment Increment Increment
characters: sp, -, characters: sp, -, characters: sp, -,
0-9, A-Z, 0-9, A-Z, 0-9, A-Z,
YES
PASSCODE
ENABLE?
ACCEPT
YES
ACCEPT
Enable?
ACCEPT
YES Alam: OFF/ON YES
Passcode Passcode Passcode
SETUP? YES
CharacterNEXT
1:0
YES
Character 2:00
YES
Character 3:000
YES
OR
NEXT
BACK
OR NO NO
BACK
NO NO NO
Increment Increment
Increment Increment choice: Increment choice:
character: 0-9, A-Z, character: 0-9, A-Z, <YES/NO> character: 0-9, A-Z, <YES/NO>
BATTERY Battery
ENABLE? YES Enable?
NEXT
OR
BACK
NO
NEXT
SET TIME & DATE MENU
Figure 5-18 BACK NEXT
NEXT
OR
BACK NO NO NO NO NO
Increment year: Increment month: Increment day: Increment hour: Increment minute:
00 to 99 JAN to DEC 1 to 31 0 to 23 0 to 59
Go to Save
Figure 5-4 Change
YES Settings?
CAUTION:
CLEAR LOGS only clears the alarm log, torque profile, and resets the
operation log.
Go to Figure 5-4
Set Time & Date
BACK NEXT
BACK
BLUETOOTH LDM
Bluetooth
RDM1
Bluetooth
RDM2
Bluetooth
BTDiscovery Bluetooth
Name
Save
Change
YES YES YES YES <Enable Disable> YES YES
<Enable Disable> <Enable Disable> <Enable Disable> <Tag Serial> Settings?
YES
NO NO NO NO NO NO
NO
OR
NEXT Increment choice: Increment choice: Increment choice: Increment choice: Increment choice:
<ENABLE or DISABLE> <ENABLE or DISABLE> <ENABLE or DISABLE> <ENABLE or DISABLE> <TAG or SERIAL>
Go to Figure 5-4
Save Change Settings Modified Variables
are saved to EEPROM
and Update Registry
Go to Figure 5-4
Restore Factory Settings
NOTE:
Only 1 Bluetooth module can be enabled.
Section 6: Troubleshooting
CAUTION:
This actuator is non-intrusive. Do not open the control compartment on the actuator
unless absolutely necessary. It was sealed in dry-clean conditions in the factory and
entry into this compartment should not be necessary. Unauthorized entry could void
the warranty.
If the LDM does not receive communication messages from the CCM within 5 seconds after power is applied
or loses communication for 5 seconds or more, it will display a flashing message "CCM LINK FAILED" and
blink all three LEDs.
72 Troubleshooting
Installation and Operation Manual Section 6: Troubleshooting
E2K-420-0218 Rev. 3 September 2018
NOTE:
When the “SET LIMITS BEFORE OPERATING” alarm is displayed, no other alarms will be
displayed until the limits are set.
Go to next display.
See Figure 5-1
BACK
DISPLAY
HARDWARE Display Go to
DIANOSTICS? YES
Alarm
YES Figure 6-2
Log?
NO
Display Go to
BACK
Torque
YES Figure 6-3
Profile?
NO
Display Go to
Torque
YES Figure 6.2.3
Archive?
NO
NEXT
Display Go to
Operate
YES Figure 6-4
Log?
NO
Display Go to
Operate
YES Figure 6-5
Archive?
NO
Display Go to
Hardware
YES Flowchart 6-6
State?
NO
OR NO
NEXT
EXIT?
Troubleshooting 73
Section 6: Troubleshooting Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
At the time the alarm occurs, the alarm is displayed on the bottom line of the
message center. This display lists the last nine alarms that have occurred. The first
alarm listed is the most recent to occur. The alarm list progresses from the most
recent to the oldest. The following alarms may be displayed.
NOTE:
When the “SET LIMITS BEFORE OPERATING” alarm is displayed, no other alarms
will be displayed until the limits are set.
NOTE:
The control knob (YES/NO) can be used to view the alarms however do
not cycle the control knob between NO and YES because the unit could
display the “SETUP” mode.
Go to
Figure 6-1
BACK NEXT
BACK
DISPLAY 1 <alarm 1> 3 <alarm 3> 5 <alarm 5> 7 <alarm 7> 9 <alarm 9>
ALARM LOG? YES 2 <alarm 2> YES 4 <alarm 4> YES 6 <alarm 6> YES 8 <alarm 8> YES 10 <alarm 10> YES
NO
OR
NEXT
NO NO NO NO NO
Go to
Figure 6-1
6.2.2 Display Torque Profile BACK NEXT
BACK
Torque profile is data on the last stroke. Torque data is recorded at 10% intervals of
valve travel and is displayed for both open and close directions. Pullout torque is peak
DISPLAY 1 <alarmtorque
1> recorded in3> the open direction
3 <alarm 5 <alarm 5> from 0 to 90%
7 <alarm while
7> unseating the
9 <alarm 9> valve.
ALARM LOG? YES 2 <alarm 2> 4 <alarm 4>
YES 6 <alarm 6>
YES 8 <alarm 8>
YES 10 <alarm 10>YES YES
NO
OR
1. At the “DISPLAY TORQUE PROFILE?” prompt, answer “YES.”
NEXT
NO 2. Use
NO the control knob
NO (YES) to review
NO the torque profiles.
NO See Figure 6-3.
NOTE:
Two positions of torque data are shown for each “YES” that is selected.
DISPLAY Pull-out
Torque
TORQUE PROFILE YES
<xx>%
YES
NO BACK NEXT
OR
NEXT
NO NO NO NO NO
NO
NO
NO NO NO NO
NO
DISPLAY Pull-out
TORQUE ARCHIVE Torque
<xx>%
NO
YES
NO
OR
NEXT BACK NEXT
NO NO NO NO NO
NO
NO
NO NO NO NO
Troubleshooting 75
DISPLAY OPERATION LOG
Figure 6-4 BACK NEXT
@10 Torque = @30 Torque = @50 Torque = @70 Torque =
Display Open @
<xx>% <xx>% <xx>% <xx>%
Torque YES YES YES YES YES
@20 Torque = @40 Torque = @60 Torque = @80 Torque =
Section 6: Troubleshooting Profile?
<xx>% <xx>% Installation and Operation Manual
<xx>% <xx>%
September 2018 E2K-420-0218 Rev. 3
NO NO NO NO NO
NO
Motor starts value is the number of times the motor has been started. The strokes
value displayed is the number of full strokes from limit to limit. Stroke time can be
measured as follows:
@10 Torque = @30 Torque = @50 Torque = @70 Torque =
Display Open @
<xx>% <xx>% <xx>% <xx>%
Torque YES YES YES YES YES
@20 Torque = @40 Torque = @60 Torque = @80 Torque =
Archive?
<xx>% <xx>% <xx>% <xx>%
1. Reset operation log.
2. Stroke the valve. Stroke time is equal to the motor run time.
NO NO NO NO NO
NO
Motor run time is the total motor operational time.
NO
2. Select “VALVE CONTROL SETUP?”
NO NO NO NO
See Section 5.5.2, Valve Control Setup
DISPLAY Motor
Starts
Strokes Motor
Run Time
OPERATE LOG? YES <xxx,xxx,xxx> YES <xxx,xxx,xxx> YES <hr:min:sec> YES
NO
OR
NEXT
NO NO NO
Operation archive
DISPLAY OPERATION LOGdisplays operation data from the initial commissioning.
See Figure 6-5. The operation archive cannot be reset
Figure 6-4 in the “CHANGENEXT
BACK SETTINGS”
mode. The operation archive can be reset in the “FACTORY SETUP” mode;
however the actuator must be decommissioned and travel limits must be reset
before operating as detailed in Section 4.3.1, Setting Position Limits.
DISPLAY Motor
Starts
Strokes Motor
Run Time
OPERATE LOG? YES 1. At the “DISPLAY
<xxx,xxx,xxx>YES <xxx,xxx,xxx>
OPERATE ARCHIVE”
YES prompt,
<hr:min:sec>answer
YES“YES.“
NO
OR 2. Use the control knob (YES) to review the operation archive.
NEXT
NO NO NO
DISPLAY Motor
Starts
Strokes Motor
Run Time
OPERATE ARCHIVE? YES <xxx,xxx,xxx> YES <xxx,xxx,xxx> YES <hours> YES
NO
OR
NEXT
NO NO NO
DISPLAY HARDWARE
Figure 6-6
• RefreshLost
every Link
30 seconds
• Failed
2. Use DISPLAY#2
the
REMOTE
control knob (YES)<analog_state>
to review the hardware
Analog
status.
Network
<network_state>
EFM
<efm_state>
<rem_disp#2_state> <state: NORMAL/ <state: NORMAL/ <state: NORMAL/
<state: NORMAL/ NOT CONFIGURED/ NOT CONFIGURED/ SHUTDOWN/
YES YES YES YES NO
See Figure 6-6. NOT CONFIGURED/ UNDER RANGE/ SPI LINK LOST/ACM FAILED>
LOST LINK/FAILED> OVER RANGE> FAILED/HOST LOST
Troubleshooting 77
NO NO
Figure 6-5 BACK NEXT
Section 6: Troubleshooting
DISPLAY Motor Strokes Motor
Installation and Operation Manual
Starts Run Time
September 2018
OPERATE ARCHIVE? YES <xxx,xxx,xxx> YES <xxx,xxx,xxx> YES <hours> YES E2K-420-0218 Rev. 3
NO
OR
NEXT
NO NO NO
DISPLAY HARDWARE
Figure 6-6
REMOTE
APD Module Central Control Local Display DISPLAY#1
DISPLAY Inside <apd_state> <cen_ctrl_state> <lcl_disp_state> <rem_disp#1_state>
HARDWARE? YES Temperature=
<xx>C
YES <state: NORMAL/ YES <state: NORMAL/ YES <state: NORMAL/ YES <state: NORMAL/ YES
FAILED> LOST LINK /FAILED> LOST LINK /FAILED> NOT CONFIGURED/
NO LOST LINK / FAILED>
OR
NEXT NO
NO NO NO NO
NO
Refresh every
30 seconds
NO
NO NO
78 Troubleshooting
Installation and Operation Manual Section 7: Maintenance
E2K-420-0218 Rev. 3 September 2018
Section 7: Maintenance
7.1 Maintenance Schedule
TEC2 Series Actuators have been designed and manufactured to provide years of trouble
free service. Minimal maintenance is required.
It is not unusual to experience some minor grease weeping around seals during
periods of long storage or inactivity. This is simply a separation of the oil in the
compound and is not detrimental to the actuator operation. Once operation has
begun, this situation should disappear.
7.2 Lubrication
Normal operation may not require lubricant during the life of the actuator. The basic
lubricants used are multi-purpose extreme pressure specially formulated having a
molybdenum disulfide additive.
1. After actuator has been located in the field and valve position has been
determined, remove 1/2 NPT plug from the highest 1/2 NPT vent location on
the gearbox.
2. Replace with Relief Vent Fitting Part No. 83385. See the EIM outline drawing
supplied with the order submittal package for possible vent locations.
NOTE:
Model 500 will not have a pressure relief fitting. (Model 500 Discontinued)
Maintenance 79
Section 7: Maintenance Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
7.5 Lifting
Lifting eye should never be used for lifting and moving any TEC2 actuator.
TEC2 actuators should be moved using straps.
80 Maintenance
Installation and Operation Manual Section 8: Regulatory Information
E2K-420-0218 Rev. 3 September 2018
CSA * RDM
Class I, Groups B, C, D; Class II, Groups E,F,G; Class III; T6: Type 6P/4X
CBM
Class I, Groups C and D; Class II, Groups E,F,G; Class III; T6; Type 6p/4X
SIRA 03ATEX1510X
II 2 GD
Ex d IIB T4 Gb
Ex d IIB + H2 T135ºC Db IP68
Ex tb IIIC T135ºC Db IP68
Ta -20ºC to +60ºC
The M8 fasteners used to secure each cover to the electronics enclosure and the RDM cover
to the RDM enclosure are of property class (or ‘grade’) 8.8. The fasteners used to secure the
ATEx * motor enclosure to the electronics enclosure, the electronics enclosure to the gear box and
the end caps to the motor frame are of property class (or ‘grade’) 5. Replacement fasteners
shall meet these minimum values.
RDM
II 2 GD
Ex d IIB +H2 T6 Gb
Ex tb IIIC T85ºC Db 1P68
Ta -20ºC to +60ºC
II 2 GD
Ex d IIB +H2 T6 Gb
Ex tb IIIC T85ºC Db 1P68
CEPEL 08.1640X
InMetro * Ex d IIB T4 Gb
IP68; Ta 60ºC
-20ºC ≤ Tamb ≤ +60ºC
Note:
*For Model 500 - Certification pending agency approval
RecapMark Rev A 1/2013
(Model 500 Discontinued)
Regulatory Information 81
Appendix Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
Appendix A:
A.1 Exploded View (Model-500 Torque Unit Only)
(Model 500 Discontinued)
Bushing Underside
Bushing Upside
82 Appendix
12 11 10 9 8 7 6 5 4 3 2 1
A.2
Appendix
REVISIONS
Copyright © 2014 Emerson Process Management Valve Actuation LLC REV ECN DATE
08-VAED-A
00 Released 12/31/2014
H H
A 6
E2K-420-0218 Rev. 3
2
5
G 10 G
4
9 F
F
Installation and Operation Manual
A 1
3 7
E
E
SECTION A-A
8 1
- Peer
C C
5 4045222617 O-Ring 568-226-70D 1
6 4060001200 Ret-Ring - 5100-2.00 1
* Variable part: Refer to JOB SPEC SHEET for specific 7 4045222417 O-Ring 568-224-70D 1
parts for each actuator serial number.
8 4042205631 SHSS 1/4-20 UNC 1
9 4045214817 O-Ring 568-148-70D 1
B 10 4300090030 Grease fitting, 1/8-27 NPT SS 1 B
TITLE:
12 11 10 9 8 7 6 5 4 3 2 1
M-500 with Thrust Base Installation Drawing
83
September 2018
Appendix
84
12 11 10 9 8 7 6 5 4 3 2 1
REVISIONS
Copyright © 2014 Emerson Process Management Valve Actuation LLC REV ECN DATE
08-VAED-A
00 Released 12/31/2014
Appendix
H H
September 2018
A
2 5 6
G 10 G
4
F F
9
1
A 3
7
E
E SECTION A-A
8 1
TITLE:
12 11 10 9 8 7 6 5 4 3 2 1
Appendix
E2K-420-0218 Rev. 3
Installation and Operation Manual
REVISIONS
A.3
Appendix
14
(LDM)
(ACM)
(CCM)
2 of 2
P8
J8
GRD
GND
P8
J8
E2K-420-0218 Rev. 3
P9
(HOUSING)
P3
P12
(MOTOR)
P11
J11
P11
J11
01 (CAM)
J17
P17
(TSM) 8 ckts (CCM)
OPTIONAL
P13
(APD) (CCM)
(LDM)
GRD (APD)
P7 P5 P15
P9 P2 P2
6 ckts
14 ckts 09
Installation and Operation Manual
14 08 3 ckts
02 1 of 2
12 ckts
03 (DBM)
6 ckts OPTIONAL
BATTERY
04
2 ckts 05
07 16 ckts
15
(PSM) 3 each
12 H1
06
H2 P6
4 ckts Item # Description Qty. Length P/N
01 20 AWG (Red) 8 ckts 12" 87086-1
02 20 AWG (Red) 14 ckts 20" 87087-1
11
3 each 03 20 AWG (Red) 12 ckts 20" 87087-3
04 20 AWG (Red) 6 ckts 20" 87087-4
05 22 AWG (Red) 16 ckts 12" 87207-1
06 20 AWG (Red) 4 ckts 6" 87207-2
10 13
T1
T2
T3
L2
L1
L3
GRD
(Model 500 Discontinued)
P2
P3
09 26 AWG (Red, Black) 3 ckts 12" 87207-5
T1 T2 T3
10 18 AWG (Red) 2 each 9.5" 37222-2
(STC)
(IOM Card)
L1 L2 L3
11 14 AWG (Black) (3ea.) 3 each 20" 37222-9
12 14 AWG (Red) 2 each 14" 37222-10
13 14 AWG (Green) 1 each 4" 37222-11
(IOM Card)
14 14 AWG (Green) 2 each 8" 37222-12
(EXTENSION) 15a 14/12/10 AWG, Class F 3each 24" - 27" N/A (OEM)
15b 14/12/10 AWG, Class H 3each 24" - 27" N/A (OEM)
Module Identification and Location
DIMENSIONS
IN INCHES ANGLES + 0.5° X.XXXX + .001 X.XXX + .005 X.XX + .020 FINISH 125 RMS
DWN DATE SCALE A SCALE C SHEET
EAN 06/17/14 NT NT 1 of 1
CHKD DATE
DR 06/17/14 TM
APPRVD DATE
TITLE
RG 06/17/14
MATERIALS Model 500 Wiring w/ MCM Ext
CLASS CODE SIZE DWG NO. REV
Copyright 2014, Emerson Process Management Valve Actuation LLC, All Rights Reserved. - _____
10 C A
85
September 2018
Appendix
Appendix Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
• YES
• NO - Stop
• NEXT - Open
• BACK - Close
These button functions correspond to the YES, NO, NEXT, and BACK functions of the
control knobs on the LDM. The “Clicker” transmits operation commands only and the
feedback information is displayed in the LDM LCD or the RDM LCD.
1. Enter “SETUP” mode using the control knobs as defined in Section 5.1, Entering
Setup Mode.
2. Select “LOCAL IrDA PORT” for control mode under Valve Control Setup.
See Section 5.5.2, Valve Control Setup.
3. Place the selector knob in the REMOTE position. Press the applicable “Clicker”
button (Open, Close, Stop) for the desired function while “pointing” the back of
the “Clicker” at the LDM or the RDM.
86 Appendix
Installation and Operation Manual Appendix
E2K-420-0218 Rev. 3 September 2018
The local IrDA port control mode allows the actuator to be controlled via the IrDA port.
The “Clicker” with an IrDA port may be used.
The “Clicker” will transmit STOP, OPEN, and CLOSE only.
NOTE:
The setup mode cannot be entered via the IrDA port if this mode is selected in the
“SETUP” mode. “SETUP” mode must be entered via the local control knobs and the
control mode must be changed to a control mode other than IrDA port before the
IrDA port can be used for setup.
Appendix 87
Appendix Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
CBM Suitable to Remote Wall or Pipe Mount. Also Available as Close-Coupled to Actuator.
Circuit Breaker Module (CBM) – Aluminum Circuit Breaker Module (CBM) – Stainless Steel
88 Appendix
Installation and Operation Manual Appendix
E2K-420-0218 Rev. 3 September 2018
Tightening Torque = K * D * P
K = 0.2 (dry.unlubricated)
Clamp Load (P) = 75% of the Proof Load
D = Nominal Thread Size
Tightening Torque = K * D * P
K = 0.2 (dry.unlubricated)
Clamp Load (P) = 75% of the Proof Load
D = Nominal Thread Size
The values presented in these tables are representative and have been compiled for the user’s benefit. Results can be influenced by
any number of variables including 1) excessive lubrication, 2) excessive design clamp load, 3) nicked or binding threads, 4) non-parallel
mating surfaces, and 5) inadequate torque control, to name a few. Therefore, Load expressly disclaims liability of any kind associated with
the application of the data shown herein.
Appendix 89
Appendix Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
Tightening Torque = K * D * P
K = 0.2 (dry.unlubricated)
Clamp Load (P) = 75% of the Proof Load
D = Nominal Thread Size
Tightening Torque = K * D * P
K = 0.2 (dry.unlubricated)
Clamp Load (P) = 75% of the Proof Load
D = Nominal Thread Size
The values presented in these tables are representative and have been compiled for the user’s benefit. Results can be influenced by
any number of variables including 1) excessive lubrication, 2) excessive design clamp load, 3) nicked or binding threads, 4) non-parallel
mating surfaces, and 5) inadequate torque control, to name a few. Therefore, Load expressly disclaims liability of any kind associated with
the application of the data shown herein.
90 Appendix
Installation and Operation Manual Appendix
E2K-420-0218 Rev. 3 September 2018
Electrical Characteristics
Radio Characteristics
Freq. Bluetooth
Parameter Min. Typ. Max. Units
(GHz) Specification
2.402 - -80 -86 dBm
Sensitivity at 0.1% BER 2.441 - -80 -86 ≤ -70 dBm
2.480 - -80 -86 dBm
2.402 0 2 4 dBm
RF Transmit Power 2.441 0 2 4 ≤4 dBm
2.480 0 2 4 dBm
2.402 - 5 75 kHz
Initial Carrier Frequency Tolerance 2.441 - 5 75 75 kHz
2.480 - 5 75 kHz
20dB bandwidth for modulated carrier - 900 1,000 ≤ 1,000 kHz
Drift (Five slots packet) - 15 - 40 kHz
Drift Rate - 13 - 20 kHz
2.402 140 165 175 kHz
Δf1avg Max Modulation 2.441 140 165 175 > 140 kHz
2.480 140 165 175 kHz
2.402 140 190 - kHz
Δf2avg Min Modulation 2.441 140 190 - 115 kHz
2.480 140 190 - kHz
Appendix 91
Appendix Installation and Operation Manual
September 2018 E2K-420-0218 Rev. 3
Range Characteristics
Range Distance
After One Wall 55 feet
After Two Walls 60 feet
After Three Walls 36 feet
The range values are approximate and may vary depending on RF environment.
Bluetooth hops in a pseudo-random fashion over the 79 frequencies in the ISM band
to adapt to the interference, hence range depends on RF interference environment.
92 Appendix