Sei sulla pagina 1di 6

Voltage dips in ship systems

J. Prousalidis, E. Styvaktakis, E. Sofras, I.K. Hatzilau, D. Muthumuni

Abstract: In this paper, voltage dips (an important aspect of Simulations in PSCAD environment (the computer
power quality) are presented in the context of ship power systems. program of Manitoba HVDC Research Center) are used for
Voltage dips are analyzed with respect to their origin (fault, motor analysis purposes.
starting, transformer saturation) considering the characteristics of
the on-board installations. Emphasis is given to voltage dips and
power quality issues of the All Electric Ship. Related issues are II. BACKGROUND
presented and discussed.
A. Voltage dips
Keywords: power quality, voltage dips(sags), ship power Voltage dips (a temporary reduction in rms voltage) are
systems. responsible for the tripping of computers, electronic
I. INTRODUCTION equipment and process control equipment. The behavior of
these types of equipment can be a reset, incorrect operation
Ship Electric power plants similarly to continental grids or shutdown depending on the design and the inherent
suffer from several power quality problems. The protection system of the load. For adjustable speed drives,
particularly complicated structure of shipboard installations depending on the load of the drive, the reduction in speed or
comprising DC and AC subsystems of several operation torque might not be tolerated, by the process driven by the
frequency and voltage levels is expected to worsen even drive. Problems are also caused to the drive controller or the
further with the advent of All Electric Ship (AES) buildings PWM inverter. Induction motors might not also manage to
(referring to full electric propulsion and extended reaccelerate after the reduction in speed that is caused by
electrification of all shipboard installations). the voltage dip [3]. Contactors are also sensitive to dips.

Power quality phenomena in this context have already been Voltage dips are characterized by their rms magnitude and
studied by the authors in previous papers [1-2]. The aim of duration. Duration is the time that the rms voltage remains
this paper is to identify and study the different types of below a certain threshold and dip magnitude is the
voltage dips (sags) that occur in ship systems considering remaining rms voltage considering the phase with the
the particularities of these systems. In this way, maximum voltage. A typical threshold is 10% of the
identification of the characteristics of different types of pre-event voltage.
voltage dips in ship system for planning and operating
purposes is done while situations that could cause problems
in ship operation are further investigated. Moreover, the B. Ship Power Systems - The All Electric Ship
extraction of voltage dip features is highlighted for electric Ship power systems require high levels of reliability as their
system monitoring purposes. Protection issues relative to operation is closely linked to human safety [4]. The
voltage dips and shipboard standards for voltage quality increased use of electric propulsion leads to an increased
are discussed. installed generating capacity, the use of different voltage
levels and, in general, to more complicated systems.
_________________________________________ Considering that the load demand is typically comparable
The work of this paper was supported in part by the research project to the generation capacity and that ship systems are isolated
"Pythagoras-II" within the "Operational Programme for Education and it becomes obvious that, compared to the interconnected
Initial Vocational Training - EPEAEK-II"-frame. terrestrial power systems, these systems present new
J. Prousalidis is an Assistant Professor at the School of Naval and Marine challenges.
Engineering of National Technical University of Athens, 9 Heroon
Politechniou St, 15773 Athens, Greece (jprousal@naval.ntua.gr). The eventual complete electrification of all systems
E. Styvaktakis, PhD, is with the Hellenic Transmission System Operator onboard according to All Electric Ship (AES) concept is
HTSO SA, Amfitheas 11, N. Smirni, 17122, Athens, Greece
(estyvaktakis@desmie.gr). expected to create a need for a closer look on the power
E. Sofras is a PhD cantidate at the School of Naval and Marine quality aspects of these systems. Thus, considering the
Engineering of National Technical University of Athens. great variety of electric loads to be installed onboard in
I. K. Hatzilau is professor with the Department of Electrical Engineering conjunction with their huge energy demands leads up to the
and Computer Science in the Hellenic Navy Academy, Peiraeus, Greece.
D. Muthumuni, PhD is with the Manitoba HVDC Center, Manitoba, conclusion that almost all AES- evolution trends would be
Canada. inherently correlated to several adverse power quality
phenomena. Considering voltage dips with respect to ship
power systems of interest is on:

1-4244-0947-0/07 $25.00 © 2007 IEEE. 309


1. Large motors and the voltage dips related to them that
may effect other loads in the system
2. System design and protection issues.
3. Motor drive converters applied to main and auxiliary
propulsion systems and their voltage dip ride through
capability.

III. FAULT-INDUCED VOLTAGE DIPS


Faults (due to the short circuit current) lead to voltage dips
of a magnitude that depends on the impedance of the source
(system’s strength), system configuration, fault impedance,
fault type and distance to the fault. Fault-induced events
present the most severe characteristics. Their duration
depends mainly on the protection system operation. That
varies from half-cycle (fuse operation) to several cycles Fig. 1. Simulated Ship Power System
(operation of circuit breakers).
Fig. 2 shows the voltage dip in the generators terminals
Advanced classification methods have been proposed that caused by a 3-phase fault in the 4 kV voltage level. It can be
consider all three phases motivated by the fact that the seen that voltage drops to approximately 0.4 pu (identical
relation between the phases is important for the equipment for all three phases) although voltage in the 4 kV system
performance [3] or by the fact that valuable information can becomes zero at the fault point. The influence of the motor
be extracted considering all three phases [5]. load can be seen both during the fault and after fault
clearing. Fault clearing causes a fast voltage increase to
The calculation of the dip magnitude for a fault somewhere 0.80 pu and then the voltage increases gradually towards
within a radial distribution system requires the point of the normal voltage due to the motor load influence.
common coupling (PCC) between the fault and the load to
1.2
be found. The dip magnitude (%) at the load position equals
the voltage at the PCC (neglecting all load currents): 1.1

1
ZF (1)
Vdip= E 0.9
Z F +Z S
Voltage rms (pu)

0.8
where ZS is the source impedance at the PCC, ZF is the 0.7
impedance between the PCC and the fault (including any
fault impedance), while E the corresponding pre-fault 0.6

voltage. 0.5

0.4
Motors that experience a voltage drop will temporary 0.3
operate as generators supporting voltage. This shows up in
the voltage recording as a slow decay in voltage magnitude, 0.2
0 0.5 1 1.5 2 2.5 3 3.5 4
during the fault. After fault clearing, motors re-accelerate Time (sec)
delaying the full recovery of voltage and creating a Fig. 2. Voltage dip due to a 3-phase fault
post-fault dip as described in [3] that could cause motor
Voltage dips propagate in the system and their
stalling.
characteristics change as they propagate through
transformers. Fig. 3 shows the voltage dip in the generators
A. Voltage dips and propagation terminals caused by a 2-phase fault in the 4 kV voltage
level. The delta-star transformer that connects the two
The electrical power system of Fig. 1 was simulated in
voltage levels transforms the relationship of the voltage
order to investigate the characteristics of fault-induced
drop in the three phases. A characterization method has
voltage dips in naval systems. This system consists of four
been proposed in [3] for voltage dips due to faults that takes
generators and three different voltage levels (6 kV, 4 kV
into account the different transformer connections. An
and 0.38 kV). Induction motor load is a significant part of
extensive analysis of voltage dips in naval systems, based
the available generation.
on this classification, has been presented by one of authors
in [6].
Faults in the lower voltage level effect mainly loads fed by
the same busbar as the resulting voltage dips do not
Considering Eq.1, it should be mentioned that the
propagate upwards in the system (the impedance of the
magnitude of the drop depends on the available source
transformer is large compared to the source impedance in
impedance.
medium voltage).

310
corresponding voltage dip depend on the induction motor
1.2
data (size, starting method, load, etc) and the strength of the
1.1 system at the point the motor is connected. The magnitude
1 of the dip depends strongly on the system parameters. The
0.9
duration of the voltage dip due to motor starting depends on
a number of motor parameters with the most important
Voltage rms (pu)

0.8
being the motor inertia [3]. The duration of the dip is
0.7 prolonged if other motor loads are connected to the same
0.6 busbar, as they keep the voltage further down.
0.5

0.4
Fig. 5 shows a voltage dip caused by the starting of a
medium voltage auxiliary propulsion motor of 1.4 MW by
0.3
an 8 MVA generator. It can be seen that voltage drops to
0.2
0 0.5 1 1.5 2 2.5 3 3.5
0.85 pu and gradually recovers approximately 1 sec after.
Time (sec) The voltage dip is the same for all three phases.
Fig. 3. Voltage dip due to a 2-phase fault
Large power motors starting consecutively during ship
Therefore, the number of generators in operation effects maneuvering (e.g. driving thruster systems) can cause such
significantly the magnitude of the voltage dip experienced severe voltage dips.
by the loads.
Finally, single-phase faults consist a specific case of
voltage dips in most ship power systems due to their 1

ungrounded nature. In case of a faulted phase, the load is


still supplied via the healthy ones –which is the main reason
Voltage rms (pu)

0.95
of installing the ungrounded system onboard- but at a
significantly higher voltage level for both phases, namely
√3 or 1.73 p.u., see Fig. 4. Therefore, the system suffers 0.9
from a voltage swell rather than a dip, which stresses
equipment insulation.
0.85

1.8 0.8
0 0.5 1 1.5 2
1.6 Time (sec)
1.4 Fig. 5. Voltage dip due to motor starting
Voltage rms (pu)

1.2 Summarizing, voltage dips due to induction motor starting


1 are:
0.8 • non-rectangular: voltage recovers gradually.
0.6
• symmetrical: all phases present the same behavior.
0.4
V. TRANSFORMER SATURATION DIPS
0.2

0 When a transformer is energised under a no-load condition,


0 0.5 1 1.5 2 2.5 3 3.5 4
Time (sec)
the magnetizing current necessary to maintain the magnetic
flux in the core is in general only few percent of the
Fig. 4. Voltage dip (swell) due to a 1-phase fault nominal rated load current.
Summarizing, voltage dips due to faults are:
• rectangular: voltage recovers fast after fault clearing During transformer energising, a transient occurs to change
operation. the flux in the core to the new steady state condition. In
• symmetrical or asymmetrical: depending on the type of general this will cause the flux to go above the saturation
fault that caused them. value once each cycle until the average value of the flux
over a cycle has decayed to nearly zero. This temporary
over-fluxing of the transformer core causes high values of
IV. INDUCTION MOTOR DIPS the magnetizing current, which is highly asymmetrical and
During start-up of an induction motor takes current five to decays exponentially. This phenomenon is known as
six times larger than normal. This current remains high magnetising inrush current and its magnitude depends on
until the motor reaches its nominal speed. This lasts from the point on the wave where the energization switching
several seconds to one minute. The characteristics of the takes place and the core residual flux. As the core is forced

311
into saturation the transformer draws a large current from
50
the supplying network. When the voltage reverses its
polarity in the next half cycle, the maximum flux in the core 45

is less than the maximum flux density in the no-load

Harmonics (% of the fundamental)


40 second

situation. The transformer inrush current is therefore 35


asymmetrical and contains a DC component, which might 30
take seconds to disappear depending on the damping of the
25
system [5]. The voltage dip caused by the magnetising
third fourth
inrush current can be long in duration and drive other 20

near-by transformers into saturation (sympathetic 15

saturation, [7,8]). In general, any voltage change in the 10


transformer terminals (like a voltage dip) could lead it into 5 fifth

saturation due to the resulting transient in the core. 0


sixth

0 50 100 150 200 250 300


Time (msec)
Fig. 6 presents a transformer saturation voltage dip caused
by the energizing of a transformer in the network of Fig. 1. Fig. 7. Voltage harmonics in time due to transformer saturation
A sharp voltage drop (approximately 0.2 pu for the worst
phase) is followed by a gradual recovery. As can be seen in Considering that the use of harmonic filters is extended in
Fig. 7, the voltage presents temporary harmonic distortion. ship systems due to the multiple use of power converters
The Short Time Fourier Transform has been used for the this example shows that these filters must be disconnected
estimation of the harmonics (from 2nd to 5th) of the voltage during transformer energizing, a practice followed in many
of one of the phases of Fig. 6. The 2nd harmonic is industrial power systems.
contributing the most. This increased harmonic distortion
can cause undesired protection operation. 1
Voltage (pu)
0.5
Summarising, voltage dips due to transformer saturation 0 (a)
are: -0.5
• non-rectangular: voltage recovers gradually as the inrush -1
current decays. 0 50 100 150 200 250 300
Time (msec)
• non-symmetrical: each phase presents a different degree
Voltage magnitude (pu)

of saturation. 1
• rich in harmonics: due to the asymmetry of the inrush
current. 0.8
(b)

1
0.6
0 50 100 150 200 250 300
Voltage (pu)

0.5
Time (msec)
0
-0.5 Fig. 8. (up): Voltage waveforms during transformer energizing, (down):
corresponding voltage rms magnitude
-1
0 50 100 150 200 250 300
Time (msec)
VI. SHIPBOARD STANDARDS
Voltage magnitude (pu)

1.1

1 Table 1 shows the limits proposed by several classification


0.9
societies and international associations regarding the limits
of voltage transients. Voltage dips fall in this category.
0.8

0.7 TABLE I. Classification Society Rules & Standards ([8-11])


0 50 100 150 200 250 300
Time (msec)
REGISTER VOLTAGE TRANSIENT
ABS (2005) BV(2003)
Fig. 6. (up): Voltage waveforms during transformer energizing, (down): DNV(2001) GL(2004) ±20% (1,5s)
corresponding voltage rms magnitude PRS (2002) RINA(2005)
(LRS) (2001) +20%, -15% (1,5s)
The harmonic distortion caused by transformer saturation
IEEE Std 45-1998 ±16%(2s)
can lead to more severe dips if any system resonance is
STANAG 1008 (Ed.8, Ed.9) ±16%(2s) [ ±22%(2s) ]*
excited. Fig. 8 shows the voltage dip occurring when the USA MIL-Std-1399 ( like ST.1008 )
same transformer as above is energized through a busbar * under some circumstances
where a 3rd harmonic filter (single-tuned filter) is connected.
The 3rd harmonic filter causes a parallel resonance in a IEEE Std 45-1998 [9], additional to the values of Table 1,
frequency slightly lower than the 3rd harmonic and the provides guidelines regarding motor starting and limits for
harmonics of the transformer inrush current are amplified the resulting voltage dips. The lower allowed voltage dip is
leading to a more severe dip (0.1 pu lower than before). 30% (70% remaining voltage) in the case of a group of

312
motors that automatically restart upon closing a feeder automatic transfer switches, ferroresonance transformers,
breaker. Special attention is given to the generator sizing series connected voltage source converters, etc [3,14,15].
when large motors are connected to the system.
600
Load immunity is an issue that, at the moment, is not
S pik e T ra ns ien t covered extensively by standards and regulations. As the
500 use of sensitive equipment increases in naval systems, this
S p ike & T ra n sien t
Bo un d ary area a cc ord in g issue will become more important. For power converters
250 to S T AN AG 1 00 8 E d .9
that are used for propulsion purposes, the voltage ride
through capability is, up to a certain extend, cost related. By
adding capacitance (in low power electronics and AC
200
(%) change in nominal voltage

P ro h ib ited area
150
drives) and with appropriate control algorithms (for DC
drives) the sensitivity of the equipment to voltage dips is
100 reduced [3].

50
VII. VOLTAGE DIP RELATED ISSUES
+-- 10%

0
N OM INA L
VO LTAG E
As mentioned above, the duration of fault -induced dips is
mainly depended on the response of the protection system
-50

N o d am ag e a rea
(fault clearing) which, in the event of a fault, should isolate
-100
the part of the system where the fault is. Protection of ship
0.0001 0.001 0.01 0.1 1 10 100
Steady power systems is typically based on overcurrent elements
Tim e (sec) state

(relays or fuses). However, the protection coordination in


Fig. 9. ITIC compared to STANAG 1008 (dashed these systems is not an easy task. As the length of the cables
line) (applicable to 120 V equipment - 60 Hz) is typically short, the different parts of the system, in terms
of impedance, are separated mainly by the transformers.
STANAG 1008 [10] (a standard referring to the electrical
This makes selectivity difficult and leads to unnecessary
power plants in NATO naval vessels) states that:«The
protection operations and load interruptions.
definitions, user information and characteristics in this
agreement refer essentially to a healthy electrical power
The variations in source impedance is also a parameter that
supply system and include transient conditions that result
naval protection systems must take into account because
from normal system operations, such as motor starts and
these variations can lead to incorrect protection operations.
switching events. The STANAG does not describe system
At this point it should be also mentioned that different
behavior under abnormal conditions, e.g. short circuit
grounding practices are used in ship and this certainly
faults, loss of generator sets or malfunction of associated
influences protection operation. For ungrounded systems,
controls, as this behaviour depends heavily on the design
for example, detection of single phase faults can be a
characteristics of individual systems». Consequently,
difficult task.
STANAG 1008 does not include limits and guidelines with
respect to abnormal conditions for the design of naval
Faster protection operation and efficient protection
systems although these conditions produce transients and
coordination will reduce the duration of fault-induced
spikes are even more severe than the ones in normal system
voltage dips. Additionally, it is important to highlight that
operations.
by improving the protection of the ship systems the risk of
Comparing the voltage limit curve provided by STANAG
unwanted protection is minimized in the case of the other
1008 with the ITIC [13] (a curve often applied for assessing two types of events (motor and transformer related).
the performance of power systems in terms of power
quality) one can see (Fig. 9) that STANAG does not Sophisticated protection methods are available that can
accommodate dips of short duration and large magnitude accommodate the special characteristics of the naval
caused mainly by faults (up to 2 seconds the curve equals to system. For example, differential protection (unit
80% of nominal voltage). For shipboard standards, it is protection) improves significantly protection performance
important to take into account abnormal conditions: by discriminating faults by other types of disturbances. This
type of protection is used for transformers in terrestrial
(a) in the design stage in order to minimize their impact by systems. Furthermore, adaptive protection is able to take
making appropriate decisions from a system point of view into account the changes in the system (like the variations
(b) in coordinating load immunity and mitigation devices in source impedance) and adjust relay settings to the new
(c) in designing appropriate protection devices and conditions offering better performance [16-17]. In terms of
equipment with higher immunity to power quality design and operating practices, the increase in the size of
parameters. generating capacity of ship systems rises the issue of short
circuit current. As more generation is installed on-board the
Mitigation devices for voltage dips are ups, flywheel, equipment has to cope with higher currents in the case of a
fault. To avoid the cost of higher rating equipment it is

313
common practice to split the network into different parts. systems, protection is probably the most critical issue as it
Although this practice reduces the short circuit current, it influences the dip duration, and up to a great extent, the
influences significantly the voltage quality of the network, ability of loads to operate without problems during faults.
not only in terms of dips but also in terms of harmonics and Faster protection schemes with efficient algorithms can
other power quality aspects. Stiffer systems (higher short reduce the dip duration (by reducing the fault clearing time)
circuit current) are less sensitive to power quality and minimize the risk of incorrect operation.
phenomena and in many cases the extra cost of higher rated
equipment is justified by the benefits in power quality.
IX. ACKNOWLEDGEMENTS
The work of this paper is part of the research project "Pythagoras-II"
Regarding motor dips, a number of technical solutions for within the "Operational Programme for Education and Initial Vocational
staring are available. They prevent severe voltage dips and Training - EPEAEK-II"-frame. The Project is co-funded by the European
allow motor starting without problems, by limiting the Social Fund (75%) and Greek National Resources (25%).
inrush current. These measures are [18]:
1. Starting-up via autotransformer X. REFERENCES
2. Starting-up via autotransformer and capacitor
3. Soft starting via power electronic devices [1] I.K. Hatzilau, J. Prousalidis, E. Styvaktakis, F. Kanellos, S. Perros, E.
Sofras, ”Electric power supply quality concepts for the All Electric Ship
(AES)”, 2006 World Marine Transport Technology Conference, London
For transformer saturation events, as mentioned above, (UK), March 2006.
special attention must be given to their interaction with [2] I.K. Hatzilau, J. Prousalidis, E. Styvaktakis, E. Sofras “Voltage and
harmonic filters to avoid severe dips, increased harmonic Current Spikes & Transients - Power Supply Quality aspects for the AES”,
distortion, and protection maloperation. Proceedings of 2005 All Electric Ship Symposium (AES2005), Paris
(France), October 2005.
[3] M.H.J. Bollen, “Understanding power quality problems: voltage sags
VIII. CONCLUSIONS and interruptions”, IEEE Press, N.Y., 1999.
[4] J.V. Amy, “Considerations in the design of naval electric power
In this paper an important aspect of power quality, voltage systems,” Proceedings of the Power Engineering Society Summer Meeting,
vol. 1, pp 331-335, 2002.
dips, is presented with respect to on-board installations. [5] E. Styvaktakis, M.H.J. Bollen, “Signatures of voltage dips:
Voltage dips are categorized in terms of their origin into transformer saturation and multistage dips”, IEEE Trans. on Power
three classes: fault-induced, motor starting and transformer Delivery, vol.18, no.1, pp. 265-270, January 2003.
saturation. Voltage dips due to faults can be severe [6] S. Spagkouros, J. Prousalidis, " Electric Power Quality problems in
ship systems: A classification method ", IASME TRANSACTIONS, Issue
depending on the voltage level where the fault takes place. 2, Volume 1, April 2004, pp. 337-342.
The influence of induction motor load on the voltage dip is [7] H.S. Bronzeado, P.B. Brogan, and R. Yacamini, “Harmonic analysis of
important as it can prolong its duration. The duration of transient currents during sympathetic interaction,” IEEE Transactions on
this type of dips depends on the protection system response PowerSystems, vol. 11, no. 4, pp. 2051–2056, November 1996.
[8] J.M. Prousalidis, A.G. Georgopoulos, N.D. Hatziargyriou, B.C. Papadias,
to the fault. Motor starting can be of considerable "Investigation of Transformer Sympathetic Inrush", Proceedings of 2nd
magnitude depending on the motor, its load, other motors International Conference on Electromagnetic Transients, IPST ’97, Seattle
near-by, etc. Transformer saturation dips are due to the (USA), July 1997, pp. 197-202.
inrush current upon energizing. There are associated with [9] IEEE Standard 45-1998, “IEEE Recommended Practice for Electrical
Installations on Shipboard”.
increased harmonic distortion that could lead to more [10] STANAG 1008, ”Characteristics of Shipboard Electrical Power
severe voltage dips in the presence of single-tuned Systems in Warships of the North Atlantic Treaty.
harmonic filters. Therefore, transformer energizing should [11] USA MIL-STD-1399(NAVY), “Interface standard for Shipboard
be avoided when harmonic filters are connected. systems – Section 300A – Electric Power, Alternating Current”.
[12] IEC-60092/101, “Electrical installation in Ships - Definitions and
General Requirements”, 1994.
In terms of characterization, voltage dips due to faults [13] TC3 of the Information Technology Industry Council (ITIC) , “ITIC
present an almost rectangular shape in their rms and can be (CBEMA) Curve”, 2000
either symmetrical or asymmetrical depending on the type [14] S. Samineni, B. Johnson, H. Hess, and J. Law, “Modeling and
of fault and the transformer connections between the fault Analysis of a Flywheel Energy Storage System with a Power Converter
Interface,” presented at the International Conference on Power Systems
and the point where the dip is measured. Induction motor Transients (IPST), New Orleans, USA, 2003.
dips are symmetrical and non-rectangular as the three [15] M. Moschakis, J. Prousalidis, N. Hatziargyriou," Performance
phases behave the same and voltage recovers back to Assessment of STC used for Alternative Naval Power Supplying Units ",
normal gradually. Transformer saturation dips are IASME TRANSACTIONS, Issue 2, Volume 1, April 2004, pp.394-399.
[16] D. Whitehead and N. Fischer, “Advanced Commercial Power System
non-rectangular and non-symmetrical as the voltage dip of Protection Practices Applied to Naval Medium Voltage Power System,”
each phase depends on the point-on-the-wave where the Electric Ship Technologies Symposium, Philadelpia, PA, July 2005.
switching takes place. [17] K.L. Butler, N.D.R. Sarma, C. Whitcomb, H. Do Carmo, and H.
Zhang, “Shipboard systems deploy automated protection,” IEEE
A presentation of naval standards on voltage dips is also Computer Applications in Power, vol. 11, no. 2, pp. 31-36, April 1998.
given. Special attention is paid to STANAG 1008, while it [18] P. Vallianatos, J. Prousalidis, E. Styvaktakis, ”On starting-up large
power motors rotating high inertia loads in autonomous systems”,
is highlighted that standards must take into account power
Proceedings of International Conference on Electric Machines
quality issues towards the complete electrification of ships. (ICEM-2006), Chania (Crete), September 2006.
Finally, considering the characteristics of ship power

314

Potrebbero piacerti anche