Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
- All in one -
This new revolutionary and unique device is used for cable and cable sheath testing, fault prelocation
as well as for sheath fault pin pointing according to the step voltage method.
The special measuring bridge performs measurements according to Murray and Glaser methods.
With the integrated high voltage DC source, shirla can prelocate low as well as high resistive cable
faults. The measuring principle enables the prelocation of earth related sheath faults and any kind of
earth related cable faults in shielded as well as unshielded cables.
Bridge methods are basically used for prelocation of low resistive faults. By using a high voltage source that is
integrated in the latest generation of measuring bridge instruments “shirla*”even high resistive faults can be
prelocated. All bridge measurement methods that work with direct current for locating faults in cables (Glaser
and Murray) are based in principle on modified Wheatstone circuits.
The bridge is balanced when points a and b are subject to the same potential. In this situation, the galvanometer shows
zero. Points a and b are at the same potential when the following condition is fulfilled:
R1 R R
= 2 resp. R4 = 2 × R3
R3 R4 R1
If R4 is the resistance Rx being sought then Rx can be defined as:
R2 * R3
Rx =
R1
Fig. 2.1; Wheatstone circuit
α
lx = *l
100
Rf
lx
Fig. 3.1.1; fault situation, core to core fault
Rf
Rf
L3 core
L2 core
L1 core
Sheath
Rf
lx
lx
L3 core
L2 core
L1 core
Sheath
Rf
Rf
Fig. 4.2.1; fault situation – core to core fault Fig. 4.2.2; Murray connection – core to ground fault
situation – core to core fault
Shirla Application Guide Page 8 of 26 Vers. 1 TN
21.04.2010
Core to Sheath Fault:
=> one healthy conductor required
lx
=> cable sheath grounded on the near end
L3 core
L2 core
L1 core
Sheath
Rf
Measurement 2
• Change short circuit bridges to
Station C (defined by result of Measurement 1) FAULT LOCATION REPORT
• Define sections: SHIRLA V0.5.0
FILENAME: SH-L_002.TXT
Section 1: 700m 240mm² AL 2010-01-01 16:17
Section 2: 150m 150mm² AL -----------------------------
Cable Sections:
1: 700 m 240 mm² Al ... main strand
2: 150 m 150 mm² AL … side strand
lx
Sheath
L3 core
L2 core Core
L1 core
Sheath L1
Rf
L1, faulty
Fig. 5.1.1; Fault situation – core to sheath fault lx
Sheath L1
1. define sectors
FAULT LOCATION REPORT
Sector 1 … 1000m, 35mm² Cu … sheath SHIRLA V0.5.0
FILENAME: SH-L_001.TXT
Sector 2 … 1000m, 240mm² Al … core 2010-01-01 15:06
2. result < 50% (50% = 1000m) -----------------------------
3. correct indication in meter, %-value = 1/2 Fault Location REPORT
Cable Sections:
1: 1000 m 35 mm² Cu ... Sheath
2: 1000 m 240 mm² AL … .Core
L3 core Resistive
L2 core Cable Fault
L1 core
Sheath L1
Core
Rf
lx
Core
L3 core
L2 core
L1 core
Sheath L1
Rf
L2 or L3 core
lx
L1 core, faulty
Rf
lx
Sheath
=> Two healthy conductors required
=> Cable Sheath resistive Fault to Ground
L3 core
Connection according to Glaser L2 core
L1 core
Sheath L1
Rf
1) Sheath L2
2) Sheath L1
Core L1, L2 or L3
e.g. 1000m, 240mm², CU
Fig. 6.1.2; Shirla display, Fig. 6.1.3; connection acc. to Glaser, extended measuring leads K2, G2
multi-sector mode
FAULT LOCATION REPORT
SHIRLA V0.5.0
E.g. total length 1000m, FILENAME: SH-L_001.TXT
2010-01-01 15:06
240/35mm², Al,Cu -----------------------------
Cable Sections:
1: 1000 m 35 mm² Cu ... Sheath
2: 1000 m 240 mm² AL … .Core
Requirement:
- min. 1 healthy core or healthy sheath L1 sheath
Rf
Fig. 6.1.10; Shirla connected for testing & pin-pointing; cable with multiple sheath fault
K1, G1
Rf 1 Rf 2 Rf 3
Fig. 6.1.12; Multipe Sheath Fault with Fault Rf1, Rf2, Rf3
Shirla Application Guide Page 19 of 26 Vers. 1 TN
21.04.2010
Table with examples of fault indication – multiple faults
Total length Fault No. 1 Fault No. 2 Fault No. 3 Indicated average
1000m, U= 10kV Rf 1 Rf 2 Rf 3 Fault Distance
I set = 3mA
Equal resistance ratio 10kOhm, 1mA 10kOhm, 1mA 10kOhm, 1mA Approx. 500m
R total = 3,3kOhm 250m 500m 750m
R total = 476Ohm 1kOhm, 1,43mA 1kOhm, 1,43mA 10kOhm, 0,14mA Approx. 386m
250m 500m 750m
R total = 476Ohm 1kOhm, 1,43mA 10kOhm, 0,14mA 1kOhm, 1,43mA Approx. 500m
Symmetrical ratio 250m 500m 750m symmetric
R total = 667Ohm 1kOhm, 2mA 2kOhm, 1mA - Approx. 333m
250m 500m (250m +1/3 of 250m)
R total = 667Ohm - 1kOhm, 2mA 2kOhm, 1mA Approx. 583m
500m 750m (500m +1/3 of 250m)
R total = 667Ohm 1kOhm, 2mA - 2kOhm, 1mA Approx. 416m
250m 750m (250m + 1/3 of 500m)
Fig. 6.1.13; Table of examples, ration of fault resistance and location – calculated average distance
Rf
Inner sheath
connected
Outer sheath
grounded
Rf
Fig. 6.2.3; sheath fault location, cable drum in water bath; direct connection on both cable ends
Rf
Fig. 6.2.5; Connection acc. to Glaser; special connection clamps; extended connection lead G2, K2
Cable faults that are showing up in a solid grounded condition do not enable to create a flashover at
the faulty point by means of a surge generator. Therefore no acoustic signal is audible and the cable
fault pinpointing according to the acoustic fault location is not possible. This condition is mainly
resulting from a completely burnt cable fault that is
furthermore resistive to the surrounding soil. These kinds of
cable faults can be pinpointed by means of the step voltage
method explained below.
Faults in low voltage cables as well as pilot cables (signal lines)
are often difficult to be pin-pointed, because the maximum
voltage that may be applied to these cables does not enable to
Fig. 7.1.1; Earth fault in LV cable, solid
force sufficient surge energy to create a strong flashover that
short circuit between all cores
can be pinpointed by means of the acoustic method. As these
cables are mainly unshielded, the fault in most cases also
appears towards the surrounding soil. Also here, the step
voltage method is the suitable pin-pointing method.
The 3rd fault type showing similar conditions is the cable sheath
fault. A fault in the outer protective PVC insulation of a XLPE
cable can not be located via the acoustic method, as no defined
potential point, where the flashover can take place, is given.
Here, also the step voltage method enables the localisation. This
method also enables to locate several sheath fault locations Fig. 7.1.2; Detection of mechanically
along a cable. damage joint via step voltage method
Fig. 7.1.3; sheath faults, termite damage on outer sheath, mechanical damage at joint
Output Voltage , Current defines the size and intensity of the voltage
funnel.
High Voltage and max. current => most successful
V5
V4
V3
V2
V1 Fig. 7.2.1; step voltage method, two
Potential lines earth probes connected to UL30
on surface receiver
surface
shirla
Fig. 7.2.3; voltage funnel detected via potential lines on the surface
In case of multiple sheath faults, e.g. 3 faults, all faults can be located as explained below during one passage
over the cable route. This requires appropriate practice and one should know that the step voltage shows
several passing through zero position that might irritate (5 passing through zero / 3 faults).
Fig. 7.2.5; Shirla connected for fault pin-pointing, multiple fault indication
1 3 5
2 4
The applied voltage shall be kept as low as approx. 1kV. Too high voltage applied effects that the
leakage current jumps onto the graphite layer and not voltage funnel can be detected.
By limiting the voltage, this effect can be prevented widely.
Conduit joints
showing the
leakage current
PVC condiut,
8-10m each
Cable with
ground/sheath fault
PVC condiut
Joints, point
of leakage to
Fig. 7.2.7; distribution of voltage funnels along the PVC conduit joints ground
Cable conduits are usually containing water or humidity inside. Therefore sheath faults can be
prelocated and pin-pointed.
The leakage current exits the nearby conduit joints and creates voltage funnels that can be located.
For pin-pointing it is important to use low current setting of. max. 30mA of pulsing current. This
enables to keep the signal only in the close area of the fault.
Too high current effects that the leakage current exits the conduit joints and creates voltage funnels
at every conduit joint over a long distance.