Sei sulla pagina 1di 110

PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX.

ETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI PLANNED COMPLETION DATE: 20
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
MAIN SUMMARY CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: LV ROOM - GROUND

CIRCUIT FEEDER DB NO.


SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
1C, mm2
F/S MCCB MCB R-PH kW Y-PH B-PH TOTAL
kW kW kW
SWA/ PVC 2/4X1C
mm2
ISO ACB
INCOMER BY DEWA

OUTGOING
LV PANEL 4P 2500 SET AT 0.8 65 XLPE BY DEWA 2x1Cx150 438.63 431 422.52 1314.14

NOTE(S): 1 ALL TRANSFORMERS SHALL HAVE LV INTEGRAL METERING AT LV SIDE


2 ALL TENANT METERS ARE DEWA SUBMETERS TO THE MAIN LV INTEGRAL METER

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 438.6 431 422.5 1314.1
MAX. DEMAND LOAD (3 PH) 1051.31 kW TOTAL CONNECTED LOAD (3 PH)

CT-METER LOAD (3PH) ……………kW


Type of Meter (Rating of Incomer): (1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A (1 Phase) (3 Phase)
AGE CIRCLE, DUBAI PLANNED COMPLETION DATE: 2016

M - GROUND

Proposed kWh Metering REMARKS


1-PH (1) 3-PH (2) 3-PH (3) CT (4)

90 1 2400/5A CT

90 1
1314.14 kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: LV PANEL CLIENT: SARHANK KADER
PLOT NO. JVC14VMRA002
FED FROM: TRANSFORMER CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: LV ROOM - GROUND

CIRCUIT FEEDER DB SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
NO. 1C, mm2
F/S MCCB MCB R-PH Y-PH B-PH TOTAL KW
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm2
mm2
ISO ACB

INCOMER-1 4P 2500 SET AT 0.8 65 XLPE BY DEWA 2x1Cx150 438.63 431.00 422.52 1314.14

INCOMER-2 4P 2500 SET AT 0.8 65 XLPE MOB. GEN. PROVISION

OUTGOING

SMDB-LL X 500 50 XLPE 2x4Cx150 2Cx70 71.2 75.73 74.43 221.37

ESMDB-LL X 200 50 FIRE RATED 4Cx95 1Cx50 32.97 31.39 31.19 95.55

SMDB-RETAIL X 80 50 XLPE 4Cx35 1Cx16 11.8 11.8 11.8 35.4

SMDB-GF X 125 50 XLPE 4Cx50 1Cx25 19.42 16.66 16.71 52.79

SMDB-1F X 350 50 XLPE 4Cx240 1Cx120 55.81 55.07 52.4 163.28

SMDB-2F X 350 50 XLPE 4Cx240 1Cx120 55.81 55.07 52.4 163.28

SMDB-3F X 350 50 XLPE 4Cx240 1Cx120 55.81 55.07 52.4 163.28

SMDB-4F X 350 50 XLPE 4Cx240 1Cx120 51.11 48.25 49.56 148.93

SMDB-5F X 350 50 XLPE 4Cx240 1Cx120 53.69 51.95 51.62 157.26

DB-SS X 32 50 XLPE 2Cx10 1Cx10 1 1

FIRE PUMP X 250 50 FIRE RATED 4Cx150 1Cx70 30 30 30 112

CAPACITOR BANK X 1000 50 XLPE 3x4Cx240 3x1Cx120

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 438.63 431 422.52 1314.14
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 1051.31 kW TOTAL CONNECTED LOAD (3 PH) 1314.14

CT-METER LOAD (3PH) ……………kW


Type of Meter (Rating of Incomer): (1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A
CLIENT: SARHANK KADER

Proposed kWh Metering REMARKS

DEMAND MAXIMAM 1-PH (1) 3-PH (2) CT (4)


FACTOR DEMAND LOAD
Kw

1 2400/5A CT METER

E&M
INTERLOCKED

0.8 177.1

0.8 76.44 WITH ATS TO GEN

0.8 28.32 3

0.8 42.23 5

0.8 130.62 17

0.8 130.62 17

0.8 130.62 17

0.8 119.14 16

0.8 125.81 15

0.8 0.8

0.8 89.6 ELS+ALARM IN CP

400KVAR-
MULTISTEP

90 1

kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF:
SMDB-LL CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM

CIRCUIT FEEDER DB SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
NO. 1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm²
mm²
ISO ACB

INCOMER X 500 (N/A) XLPE 2x4Cx150 2Cx70 32.97 31.39 31.19

OUTGOING

ESMDB-MECH@BF X 80 25 XLPE 4Cx25 1Cx16 8.3 8.3 8.3

EDB-LL1@B1 X 32 25 XLPE 4Cx10 1Cx10 3.53 1.55 1.6

ESMDB-MTR X 32 25 XLPE 4Cx10 1Cx10 3 3 3

CENTRAL BATTERY X 32 25 XLPE 4Cx10 1Cx10 1.5 1.5 1.5

EDB-LL2@GF X 32 25 XLPE 4Cx10 1Cx10 1.9 2.3 1.5

DB-LL3@1F X 32 25 XLPE 4Cx10 1Cx10 1.14 1.14 1.14

DB-LL4@4F 32 25 XLPE 4Cx10 1Cx10 1.2 1.2 1.75

ESMDB-MECH@RF X 80 25 XLPE 4Cx25 1Cx16 12.4 12.4 12.4

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 32.97 31.39 31.19
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 76.44 kW TOTAL CONNECTED LOAD (3 PH)

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
DB REF:

Proposed kWh Metering REMARKS

TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)

95.55 0

24.9

6.68

4.5

5.7

3.42

4.15

37.2

95.55 0

95.55 kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: ESMDB-MECH@BF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: BASEMENT FLOOR ELECTRICAL ROOM

CIRCUIT FEEDER DB SP TP RATING - AMPS Fault Duty kA PVC XLPE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
NO. 1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH TOTAL KW 1-PH (1)
kW kW kW
SWA/ PVC 2/3/4C mm²

ISO ACB

INCOMER X 63 (N/A) FIRE RATED 4Cx25 1Cx16 8.3 8.3 8.3 24.9

OUTGOING

JOCKEY PUMP X 32 25 FIRE RATED 4Cx6 1Cx6 1 1 1 3

SUMP PUMP-1 (D) X 32 25 XLPE 4Cx6 1Cx6 0.7 0.7 0.7 2.1

SUMP PUMP-1 (S/BY) X 32 25 XLPE 4Cx6 1Cx6

SUMP PUMP-2 (D) X 32 25 XLPE 4Cx6 1Cx6 0.7 0.7 0.7 2.1

SUMP PUMP-2 (S/BY) X 32 25 XLPE 4Cx6 1Cx6

TRANSFER PUMP (D) X 32 25 XLPE 4Cx6 1Cx6 1.5 1.5 1.5 4.5

TRANSFER PUMP (S/BY) X 32 25 XLPE 4Cx6 1Cx6

EXAF-1 X 32 25 FIRE RATED 4Cx10 1Cx10 2.2 2.2 2.2 6.6

EXAF-2 X 32 25 FIRE RATED 4Cx10 1Cx10 2.2 2.2 2.2 6.6

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 8.3 8.3 8.3 24.9
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 19.92 kW TOTAL CONNECTED LOAD (3 PH) 24.9

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
CLIENT:

Proposed kWh Metering REMARKS

3-PH (2) 3-PH (3) CT (4)

100mA ELS+ALARM

100mA ELS+ALARM

100mA ELS+ALARM

100mA ELS+ALARM

100mA ELS+ALARM

100mA ELS+ALARM

100mA ELS+ALARM

DUAL SPEED STARTER+300mA ELCB

DUAL SPEED STARTER+300mA ELCB

kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
DB REF: SMDB-LL CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM

CIRCUIT FEEDER SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
DB NO. 1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm²
mm²
ISO ACB
INCOMER X 500 (N/A) XLPE 2x4Cx150 2Cx70 71.2 75.73 74.43

OUTGOING
DB-LL1@BF X 40 25 XLPE 4Cx16 1Cx16 2.04 3.45 2.15

DB-LL2@GF X 63 25 XLPE 4Cx25 1Cx16 6.19 6.33 6.25

DB-LL3@1F X 80 25 XLPE 4Cx35 1Cx16 12.32 11.59 11.92

DB-LL4@4F X 80 25 XLPE 4Cx35 1Cx16 5.08 4.63 4.38

SMDB- MECH@RF X 300 35 XLPE 4Cx185 1Cx95 45.57 49.73 49.73

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 71.2 75.73 74.43
SMDB CONNECTED TO : MDB…………………
MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 177.1 kW TOTAL CONNECTED LOAD (3 PH)

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
W Proposed kWh Metering REMARKS
TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)

221.37 0

7.64 BF

18.77 GF

35.83 1,2 & 3

14.09 4,5 & RF

145.04

221.37 0

221.37 kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-RETAIL
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM

CIRCUIT FEEDER SP TP RATING - AMPS PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
DB NO. 1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH TOTAL KW 1-PH (1)
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm²
mm²
ISO ACB

INCOMER X 80 (N/A) XLPE 4Cx35 1Cx16 11.8 11.8 11.8 35.4

OUTGOING

DB-RETAIL 01 X 40 XLPE 4Cx16 1Cx16 3.4 3.4 3.4 10.2

DB-RETAIL 02 X 40 XLPE 4Cx16 1Cx16 3.4 3.4 3.4 10.2

DB-RETAIL 03 X 40 XLPE 4Cx16 1Cx16 5 5 5 15

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. 11.8 11.8 11.8 35.4


SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 28.32 kW TOTAL CONNECTED LOAD (3 PH) 35.4

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
Proposed kWh Metering REMARKS

3-PH (2) 3-PH (3) CT (4)

1 65m²

1 65m²

1 102m²

kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-GF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM

CIRCUIT FEEDER DB SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
NO. 1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH TOTAL KW
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm²
mm²
ISO ACB

INCOMER X 125 (N/A) XLPE 4Cx50 1Cx25 19.42 16.66 16.71 52.79

OUTGOING

DB-F/GF01 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.51 3.96 11.22

DB-F/GF02 X 40 25 XLPE 4Cx10 1Cx10 4.11 3.75 3.38 11.24

DB-F/GF03 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.58 3.91 11.24

DB-F/GF04 X 40 25 XLPE 4Cx10 1Cx10 3.55 4.11 3.58 11.24

DB-F/GF05 X 40 25 XLPE 4Cx16 1Cx16 5.19 5.07 5.24 15.51

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 19.42 16.66 16.71 52.79
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 70% DIVERSITY 36.95 kW TOTAL CONNECTED LOAD (3 PH) 52.79

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
CLIENT:

Proposed kWh Metering REMARKS

1-PH (1) 3-PH (2) 3-PH (3) CT (4)

kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-1F TYPICAL FOR
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL SMDB-2F & 3F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: TYPICAL FLOOR EL ROOM

CIRCUIT SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
FEEDER DB NO. 1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH
SWA/ PVC 2/4X1C 2/3/4C mm² kW kW kW
ISO ACB mm²
INCOMER X 350 (N/A) XLPE 4Cx240 1Cx120 55.81 55.07 52.4

OUTGOING
DB-F101 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81
DB-F102 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81
DB-F103 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81
DB-F104 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81
DB-F105 X 40 25 XLPE 4Cx10 1Cx10 3.65 4.13 3.58
DB-F106 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81
DB-F107 X 40 25 XLPE 4Cx16 1Cx16 3.51 2.85 2.9
DB-F108 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.61 3.41
DB-F109 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.61 3.41
DB-F110 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.61 3.41
DB-F111 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.58 3.91
DB-F112 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.58 3.91
DB-F113 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61
DB-F114 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61
DB-F115 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61
DB-F116 X 40 25 XLPE 4Cx10 1Cx10 4.11 3.75 3.38
DB-F117 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.15 2.61

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 55.81 55.07 52.4
SMDB CONNECTED TO : MDB…………………
MAX. DEMAND LOAD (3 PH) AT 70% DIVERSITY 114.3 kW TOTAL CONNECTED LOAD (3 PH)

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A (1 Phase) (3 Phase)
REF: SMDB-1F TYPICAL FOR CLIENT:

W Proposed kWh Metering REMARKS

TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)

163.28 17

9.07 1
9.07 1
9.07 1
9.07 1
11.36 1
9.07 1
9.26 1
9.07 1
9.07 1
9.07 1
11.24 1
11.24 1
9.07 1
9.07 1
9.07 1
11.24 1
9.17 1

163.28 17

163.28 kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-4F CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 4th FLOOR EL ROOM

CIRCUIT FEEDER DB NO. SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm²
mm²
ISO ACB

INCOMER X 350 (N/A) XLPE 4Cx240 1Cx120 51.11 48.25 49.56

OUTGOING

DB-F401 X 40 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79

DB-F402 X 40 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79

DB-F403 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.28 3.74

DB-F404 X 40 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79

DB-F405 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.38 4.11

DB-F406 X 40 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79

DB-F407 X 40 25 XLPE 4Cx16 1Cx16 4.21 3.44 3.51

DB-F408 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.28 3.74

DB-F409 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61

DB-F410 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61

DB-F411 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61

DB-F412 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61

DB-F413 X 40 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79

DB-F414 X 40 25 XLPE 4Cx10 1Cx10 3 2.26 3.74

DB-F415 X 40 25 XLPE 4Cx10 1Cx10 3 2.26 3.74

DB-F416 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.1 2.59

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 51.11 48.25 49.56
SMDB CONNECTED TO : MDB…………………
MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 119.14 kW TOTAL CONNECTED LOAD (3 PH)

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A (1 Phase) (3 Phase)
CLIENT:

Proposed kWh Metering REMARKS

TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)

148.93 16

9 1

9 1

9.07 1

9 1

11.24 1

9 1

11.17 1

9.07 1

9.07 1

9.07 1

9.07 1

9.07 1

9 1

9 1

9 1

9.1 1

148.93 16

148.93 kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-5F
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 5th FLOOR EL ROOM

CIRCUIT FEEDER SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
DB NO. 1C, mm²
F/S MCB R-PH Y-PH B-PH
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm²
mm²
ISO
INCOMER X 350 (N/A) XLPE 4Cx240 1Cx120 53.69 51.95 51.62

OUTGOING
DB-F501 X 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79
DB-F502 X 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79
DB-F503 X 25 XLPE 4Cx10 1Cx10 3.75 3.38 4.11
DB-F504 X 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79
DB-F505 X 25 XLPE 4Cx16 1Cx16 3.85 3.5 3.74
DB-F506 X 25 XLPE 4Cx10 1Cx10 3.05 2.61 3.41
DB-F507 X 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61
DB-F508 X 25 XLPE 4Cx10 1Cx10 4.11 3.75 3.38
DB-F509 X 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61
DB-F510 X 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61
DB-F511 X 25 XLPE 4Cx10 1Cx10 2.8 3.41 2.79
DB-F512 X 25 XLPE 4Cx10 1Cx10 3 2.59 3.41
DB-F513 X 25 XLPE 4Cx10 1Cx10 3 2.59 3.41
DB-F514 X 25 XLPE 4Cx10 1Cx10 3.1 2.26 3.74
DB-GYM X 25 XLPE 4Cx25 1Cx16 8.4 8.48 7.43

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 53.69 51.95 51.62
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 125.81 kW TOTAL CONNECTED LOAD (3 PH)

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A (1 Phase) (3 Phase)
, DUBAI DB REF: SMDB-5F

W Proposed kWh Metering REMARKS


TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)

157.26 15

9 1
9 1
11.24 1
9 1
11.09 1
9.07 1
9.07 1
11.24 1
9.07 1
9.07 1
9 1
9 1
9 1
9.1 1
24.31 1

157.26 15

AD (3 PH) 157.26 kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI CLIENT: SARHANK KADER
PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: ROOF FLOOR ELECTRICAL ROOM DB REF: SMDB-MECH@RF

CIRCUIT FEEDER SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
DB NO. 1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH TOTAL KW
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm²
mm²
ISO ACB

INCOMER X 300 (N/A) XLPE 4Cx185 1Cx95 45.57 49.73 49.73 145.04

OUTGOING

FAHU-01 X 80 25 XLPE 4Cx25 1Cx16 10.07 10.07 10.07 30.22

CU/FAHU-01-CP X 250 35 XLPE 4Cx150 1Cx70 31.2 31.2 31.2 93.6

BOOSTER PUMP (D) X 20 25 XLPE 4Cx6 1Cx6 0.5 0.5 0.5 1.5

BOOSTER PUMP (D) - STBY X 20 25 XLPE 4Cx6 1Cx6

GEF X 20 25 XLPE 4Cx6 1Cx6 0.4 0.4 0.4 1.2

SW POOL EQPT X 40 25 XLPE 4Cx16 1Cx16 3.4 3.4 3.4 10.2

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 45.57 49.73 49.73 145.04
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 116.03 kW TOTAL CONNECTED LOAD (3 PH) 145.04

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A (1 Phase) (3 Phase)
CLIENT: SARHANK KADER

Proposed kWh Metering REMARKS

1-PH (1) 3-PH (2) 3-PH (3) CT (4)

300mA ELCB+Y/D STARTER IN CP

300mA ELCB+UVR+ART+CONTACTOR IN CP

100mA ELCB

100mA ELCB

300mA ELCB

kW
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: ROOF FLOOR ELECTRICAL ROOM DB REF: ESMDB-MECH@RF

CIRCUIT FEEDER SP TP RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW
DB NO. 1C, mm²
F/S MCCB MCB R-PH Y-PH B-PH TOTAL KW
kW kW kW
SWA/ PVC 2/4X1C 2/3/4C mm²
mm²
ISO ACB

INCOMER X 80 (N/A) XLPE 4Cx35 1Cx16 12.4 12.4 12.4 37.2

OUTGOING

SEF X 32 25 FIRE RATED 4Cx6 1Cx6 1.5 1.5 1.5 4.5

MAF X 32 25 FIRE RATED 4Cx6 1Cx6 1.5 1.5 1.5 4.5

LIFT-1 X 40 25 XLPE 4Cx16 1Cx16 3.35 3.35 3.35 10.05

LIFT-2 X 40 25 XLPE 4Cx16 1Cx16 3.35 3.35 3.35 10.05

LIFT CONTROL X 25 25 XLPE 4Cx6 1Cx6 0.7 0.7 0.7 2.1

GSM X 32 25 XLPE 4Cx6 1Cx6 2 2 2 6

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 12.4 12.4 12.4 37.2
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 29.76 kW TOTAL CONNECTED LOAD (3 PH) 37.2

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A (1 Phase) (3 Phase)
Proposed kWh Metering REMARKS

1-PH (1) 3-PH (2) 3-PH (3) CT (4)

300mA ELS+ALARM

300mA ELS+ALARM

300mA ELCB

300mA ELCB

kW
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: DB-SS
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: ELECTRICAL SUB-STATION

RATING OF RATING OF SL NO CIR NO MCB CCT ECC ROOM/ AREA CONNECTED LOADS/POINTS
INCOMER ELCB RTG IN Wire Wire
Amps Size Size
mm2 mm2
LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
Fan S/O S/O
32A SPN ISOL 40A,4P 1 C1 10 2.5 2.5 SUBSTATION 6
100mA ELCB-
1 2 C2 SPACE
3 C3 SPACE
40A,4P 4 C4 20 4 4 SUBSTATION 2
30mA ELCB-
2
5 C5 SPACE
6 C6 SPACE

SUB TOTAL
CABLE SIZE: 2C, 10 mm² XLPE/SWA/PVC/CU + TOTAL 1.00 kW
LE, DUBAI DB REF: DB-SS

ATION

WATT UNIT Load Per Circuit WATT REMARKS


R Y B

100 600

200 400

SUB TOTAL 1,000 0 0


PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: DB-LL1@BF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: BASEMENT FLOOR ELECTRICAL ROOM

RATING OF INCOMER RATING OF SL NO CIR NO MCB CCT ECC ROOM/ AREA CONNECTED LOADS/POINTS WATT UNIT
ELCB RTG IN Wire Size Wire Size
Amps mm2 mm2
LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
Fan S/O S/O
40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PARKING(1-14 & 27-45)+FAN RM 8 50
100mA ELCB-
1 2 Y1 10 2.5 2.5 PARKING(15-72) 8 50

3 B1 10 2.5 2.5 DRIVEWAY+RAMP(GF-BF) 12 50

4 R2 10 2.5 2.5 STAIR-01 (BF-RF) 13 50

5 Y2 10 2.5 2.5 LIFT SHAFT (BF-RF) 7 20

6 B2 SPACE

40A,4P 7 R3 10 2.5 2.5 DRIVEWAY+RAMP(BF-GF) 14 50


100mA ELCB-
2 8 Y3 SPACE

9 B3 10 2.5 2.5 STAIR-02 (UG-RF) 15 50

40A,4P 10 R4 20 4 4 LIFT SHAFT+PARKING 4 200


30mA ELCB-
3 11 Y4 SPACE

12 B4 20 4 4 PARKING 3 200

40A,4P 13 R5 SPACE
100mA ELCB-
4 14 Y5 32 6 6 LIFT LOBBY CU (B1-01) 1 2400

15 B5 20 4 4 LIFT LOBBY FCU (B1-01) 1 170

SUB TOTAL

CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,


16mm² PVC/CU GY ECC TOTAL 7.61
CLIENT:

Load Per Circuit WATT REMARKS

R Y B

400

400

600

650

140

700

750

800

600

2,400 UVR+ART+CONT

170

2,550 2,940 2,120


PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: DB-LL2@GF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV RM PAGES: 1/2

RATING OF INCOMER RATING OF SL NO CIR NO MCB CCT ECC ROOM/ AREA CONNECTED LOADS/POINTS
ELCB RTG IN Wire Wire Size
Amps Size mm2
mm2

LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU


Fan S/O S/O

63A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 CORRIDOR-GF 6


100mA ELCB-
1 2 Y1 10 2.5 2.5 FOOT PATH+STAIR LOBBY+WM 7

3 B1 10 2.5 2.5 ENT+LIFT LOBBY+RETAIL CORR 15

4 R2 10 2.5 2.5 SERV RMS+TOILETS+PASSAGE 1/14

5 Y2 10 2.5 2.5 PARKING-GF 5

6 B2 10 2.5 2.5 LV RM+GEN RM 8

40A,4P 7 R3 10 2.5 2.5 MAIN ENT+RETAIL ENT 7


100mA ELCB-
2 8 Y3 SPACE

9 B3 10 2.5 2.5 DRIVEWAY-GF 7

40A,4P 10 R4 20 4 4 SERV RMS+RETAIL CORR 3


30mA ELCB-3
11 Y4 20 4 4 CORRIDOR+ENT 4

12 B4 20 4 4 PARKING-GF 3

13 R5 SPACE

14 Y5 20 4 4 DISABLED TOILET WH 1

15 B5 20 4 4 LV RM+GEN RM 2

40A,4P 16 R6 20 4.0 4.0 ENT LOBBY CU (GF-09) 1


100mA ELCB-
5 17 Y6

18 B6

40A,4P 19 R7 20 4 4 CORRIDOR FCU (GF-10) 1


100mA ELCB-
6 20 Y7 20 4 4 ENT LOBBY FCU (GF-09) 1

21 B7 SPACE

40A,4P 22 R8 32 6 6 GARBAGE RM CU (GF-11) 1


100mA ELCB-
7 23 Y8 SPACE

24 B8 20 4 4 GARBAGE RM FCU (GF-11) 1

SUB TOTAL

CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,


16mm² PVC/CU GY ECC TOTAL 12.86
CLIENT:

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

20 120

50 350

20 300

20/50 720

50 250

50 400

20 140

50 350

200 600

200 800

200 600

1200 1200

200 400

3600 1,200 UVR+ART+CONT

1,200

1200

400 400

330 330

2200 2,200 UVR+ART+CONT

100 100

SUB TOTAL 5,380 4,130 3,350

12.86
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: DB-LL2@GF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV RM PAGES: 1/2

RATING OF INCOMER RATING OF SL NO CIR NO MCB CCT ECC ROOM/ AREA CONNECTED LOADS/POINTS
ELCB RTG IN Wire Wire Size
Amps Size mm2
mm2
LTG EX. 13A SH W/H W/M ISO CCU FCU CU
Fan S/O S/O
63A TPN ISOL 40A,4P 25 R9 20 4 4 TEL RM FCU (GF-13) 1
100mA ELCB-
8 26 Y9 20 4 4 TEL RM CU (GF-13) 1

27 B9 SPACE

40A,4P 28 R10 20 4 4 LV RM FCU (GF-14) 1


100mA ELCB-
9 29 Y10 SPACE

30 B10 20 4 4 LV RM CU (GF-14) 1

40A,4P 31 R11 20 4.0 1.0 GARBAGE COMPACTOR 1


100mA ELCB- A TP X 4.0 X 4.0
10
Y11

B11

40A,4P 32 R12 20 4 4 CORRIDOR CU (GF-10) 1


100mA ELCB-
11 Y12

B12

SUB TOTAL

CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,


16mm² PVC/CU GY ECC TOTAL 18.77
CLIENT:

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

140 140

1700 1700 UVR+ART+CONT

170 170

2400 2400 UVR+ART+CONT

1500 500 TPN ISOL

500

500

5700 1900 UVR+ART+CONT

1900

1900

SUB TOTAL 6,190 6,330 6,250

18.77
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 1st FLOOR ELECTRICAL ROOM PAGES: 1/2
DB REF: DB-LL3@1F

RATING OF RATING OF SL NO CIR NO MCB CCT ECC ROOM/ AREA CONNECTED LOADS/POINTS WATT UNIT
INCOMER ELCB RTG IN Wire Size Wire Size
Amps mm2 mm2
LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
Fan S/O S/O

80A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-1F 17 20


100mA ELCB-
1 2 Y1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-2F 17 20

3 B1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-3F 17 20

4 R2 10 2.5 2.5 SERVICE RMS+STAIR LOBBY-1F 11 50

5 Y2 10 2.5 2.5 SERVICE RMS+STAIR LOBBY-2F 11 50

6 B2 10 2.5 2.5 SERVICE RMS+STAIR LOBBY-3F 11 50

40A,4P 7 R3 20 4 4 CORR+STORE+TEL RM-1F 5 200


30mA ELCB-
2 8 Y3 20 4 4 CORR+STORE+TEL RM-2F 5 200

9 B3 20 4 4 CORR+STORE+TEL RM-3F 5 200

40A,4P 10 R4 20 4 4 CORRIDOR FCU (F-18)-1F 1 330


100mA ELCB-
3 11 Y4 SPACE

12 B4 20 4 4 CORRIDOR FCU (SE-18)-2F 1 330

40A,4P 13 R5 20 4 4 CORRIDOR FCU (F-19)-1F 1 400


100mA ELCB-
4 14 Y5 20 4 4 CORRIDOR FCU (SE-19)-2F 1 400

15 B5 SPACE

40A,4P 16 R6 20 4.0 4.0 CORRIDOR CU (SE-18)-2F 1 3600


100mA ELCB-
5 17 Y6

18 B6

40A,4P 19 R7 20 4.0 4.0 CORRIDOR CU (SE-19)-2F 1 5700


100mA ELCB-
6 20 Y7

21 B7

40A,4P
100mA ELCB-
22 R8 20 4 4 CORRIDOR FCU (TH-19)-3F 1 400

7 23 Y8 SPACE

24 B8 20 4 4 CORRIDOR FCU (TH-18)-3F 1 400

SUB TOTAL

CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,


16mm² PVC/CU GY ECC TOTAL 17.23
Load Per Circuit WATT REMARKS

R Y B

340

340

340

550

550

550

1,000 RING

1,000 RING

1,000 RING

330

330

400

400

1,200 UVR+ART+CONT

1200

1200

1,900 UVR+ART+CONT

1900

1900

400

400

6,120 5,390 5,720


PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 1st FLOOR ELECTRICAL ROOM PAGES: 2/2
DB REF: DB-LL3@1F

RATING OF RATING OF SL NO CIR NO MCB CCT ECC ROOM/ AREA CONNECTED LOADS/POINTS WATT UNIT
INCOMER ELCB RTG IN Wire Size Wire Size
Amps mm2 mm2
LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
Fan S/O S/O

80A TPN ISOL 40A,4P 25 R9 20 4.0 4.0 CORRIDOR CU (TH-19)-3F 1 5700


100mA ELCB-
8 26 Y9

27 B9

40A,4P 28 R10 20 4.0 4.0 CORRIDOR CU (TH-18)-3F 1 5700


100mA ELCB-
9 29 Y10

30 B10

40A,4P 31 R11 20 4.0 4.0 CORRIDOR CU (F-18)-1F 1 3600


100mA ELCB-
10 32 Y11

33 B11

40A,4P 34 R12 20 4.0 4.0 CORRIDOR CU (F-19)-1F 1 3600


100mA ELCB-
11 35 Y12

36 B12

SUB TOTAL

CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,


16mm² PVC/CU GY ECC TOTAL 35.83
Load Per Circuit WATT REMARKS

R Y B

1,900 UVR+ART+CONT

1900

1900

1,900 UVR+ART+CONT

1900

1900

1,200 UVR+ART+CONT

1200

1200

1,200 UVR+ART+CONT

1200

1200

12,320 11,590 11,920


RATING OF INCOMER RATING OF SL NO CIR NO
MCB RTG IN Amps
CCT Wire Size
ECC mm2 ROOM/ AREA CONNECTED LOADS/POINTS WATT UNIT Load Per CircuitWATT
ELCB Wire
Size R
mm2

LTG EX FAN 13A S/O SH S/O W/M IND SKT KIT HD ISOL FCU CU

80A TP N IS OL 40A,4P 1 R1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-4F 15 20 300


100mA ELCB-
1 2 Y1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-5F 14 20

3 B1 10 2.5 2.5 ROOF 7 50

4 R2 10 2.5 2.5 SERVICE RMS-4F 5 50 250

5 Y2 10 2.5 2.5 SERVICE RMS-5F 4 50

6 B2 10 2.5 2.5 ROOF 10 50

40A,4P 7 R3 10 2.5 2.5 EL RM+LIFT LOBBY+ROOF 6 50 300


100mA ELCB-
2 8 Y3 10 2.5 2.5 GSM RM+ROOF 7 50

9 B3 SPACE

40A,4P 10 R4 20 4 4 CORR+TEL RM-4F 4 200 800


30mA ELCB-3
11 Y4 20 4 4 CORR+TEL RM-5F 4 200

12 B4 20 4 4 ROOF 2 200

13 R5 20 4 4 SIGNAGE 1 700 700

14 Y5 20 4 4 ROOF 3

15 B5 20 4 4 ROOF 2

40A,4P 16 R6 20 4 4 CORRIDOR FCU (4F-17)-4F 1 330 330


100mA ELCB-
4 17 Y6 SPACE

18 B6 20 4 4 CORRIDOR FCU (4F-18)-4F 1 330

40A,4P 19 R7 20 1.0 4.0 CORRIDOR CU (4F-18)-4F 1 3600 1200


100mA ELCB-
5 20 Y7

21 B7

40A,4P 22 R8 20 1.0 4.0 CORRIDOR CU (5F-17)-5F 1 3600 1200


100mA ELCB-
6 23 Y8

24 B8

SUB TOTAL 5,080

CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,


TOTAL 14.09
16mm ² PVC/CU GY ECC

PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI CLIENT: SARHANK KADER

PLOT NO. JVC14VMRA002

FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 4th FLOOR ELECTRICALPARGOEOSM: 1/2 DB REF: DB-LL4@4F
Load Per CircuitWATT REMARKS

Y B

280

350

200

500

350

800

400

SPN ISOL

600

400

330

UVR+ART+CONT

1,200

1,200

UVR+ART+CONT

1,200

1,200

4,630 4,380

CLIENT: SARHANK KADER

DB REF: DB-LL4@4F
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI CLIENT: SARHANK KADER

PLOT NO. JVC14VMRA002

FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 4th FLOOR ELECTRICALPARGOEOSM: 2/2 DB REF: DB-LL4@4F

RATING OF INCOMER RATING OF SL NO CIR NO


MCB RTG IN Amps
CCT Wire Size
ECCmm2
Wire ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS WATT UNIT Load Per CircuitWATT
ELCB
R

LTG EX FAN 13A SH W/M IND SKT KIT HD ISOL FCU CU


S/O S/O

80A TPN ISOL 40A,4P


100mA ELCB-
25 R9 SPACE

7 26 Y9 20 4 4 CORRIDOR FCU (5F-18)-5F 1 400

27 B9 20 4 4 CORRIDOR FCU (5F-17)-5F 1 400

40A,4P 28 R10 20 4.0 1.0 CLEANING CRADLE-1 1 1200 400


100mA ELCB- A TP X 4.0 X 4.0
8 29 Y10

30 B10

31 R11 20 4.0 1.0 CLEANING CRADLE-2 1 1200 400


A TP X 4.0 X 4.0
32 Y11

33 B11

40A,4P 34 R12 20 4.0 1.0 CLEANING CRADLE-3 1 1200 400


100mA ELCB- A TP X 4.0 X 4.0
9 35 Y12

36 B12

37 R13 20 4.0 1.0 CLEANING CRADLE-4 1 1200 400


A TP X 4.0 X 4.0
38 Y13

39 B13

40A,4P 40 R14 20 4.0 1.0 CORRIDOR CU (4F-17)-4F 1 3600 1200


100mA ELCB- A TP X 4.0 X 4.0
10 41 Y14

42 B14

40A,4P 43 R15 20 4.0 1.0 CORRIDOR CU (5F-18)-5F 1 5700 1900


100mA ELCB- A TP X 4.0 X 4.0
11 44 Y15

45 B15

SUB TOTAL 9,780


CLIENT: SARHANK KADER

DB REF: DB-LL4@4F

Load Per CircuitWATT REMARKS

Y B

400

400

TP IND SKT

400

400

TP IND SKT

400

400

TP IND SKT

400

400

TP IND SKT

400

400

UVR+ART+CONT

1,200

1,200

UVR+ART+CONT

1,900

1,900

9,730 9,480
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: BASEMENT FLOOR ELECTRICAL ROOM DB REF: EDB-LL1@BF

RATING OF
INCOMER
RATING OF
ELCB
SL NO CIR NO MCB RTG IN Amps
CCT Wire ECC
Size mm ²
ROOM/ AREA
Wire Size mm ² CONNECTED LOADS/POINTS

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 EL RM+PARKING(15-72) 9


100mA ELCB-1 2 Y1 10 2.5 2.5 DRIVEWAY+RAMP(GF-BF) 13
3 B1 10 2.5 2.5 PARKING(1-14 & 27-45) 6
4 R2 10 2.5 2.5 LIFT LOBBY 4
5 Y2 10 2.5 2.5 UG PUMP RM 4
6 B2 10 2.5 2.5 DRIVEWAY+RAMP(BF-GF) 12
40A,4P 7 R3 SPACE
30mA ELCB- 8 Y3 20 4 4 UG PUMP RM 2
2
9 B3 20 4 4 EL RM+LIFT LOBBY+FAN RM 3
10 R4 20 4 4 CCTV CAMERA (2NOS.) 2
11 Y4 20 4 4 CCTV CAMERA 1
12 B4 20 4 4 CCTV CAMERA 1
40A,4P 13 R5 20 4 4 UG PUMP RM CU (B2-01) 1
100mA ELCB-3 14 Y5 20 4 4 UG PUMP RM FCU (B2-01) 1
15 B5 SPACE

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

OOR ELECTRICAL ROOM DB REF: EDB-LL1@BF

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

50 450
50 650
50 300
20 80
50 200
50 600

200 400
200 600
100 200
100 100
100 100
2800 2800 UVR+ART+CONT
200 200

3,530 1,550 1,600


6.68
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM DB REF: EDB-LL2@GF

RATING OF
INCOMER
RATING OF
ELCB
SL NO CIR NO MCB RTG IN Amps
CCT Wire ECC
Size mm² ²
ROOM/ AREA
Wire Size mm
CONNECTED LOADS/POINTS

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD ISOL FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PARKING-GF 4


100mA ELCB-1 2 Y1 10 2.5 2.5 CORRIDOR-GF 5
3 B1 10 2.5 2.5 DRIVEWAY-GF 7
4 R2 SPACE
5 Y2 10 2.5 2.5 ENT+LIFT LOBBY+RETAIL CORR 11
6 B2 SPACE
40A,4P 7 R3 20 4 4 ENTRY GATE BARRIER 1
100mA ELCB-2 8 Y3 SPACE
9 B3 20 4 4 EXIT GATE BARRIER 1
40A,4P 10 R4 20 4 4 CCTV CAMERA (2NOS.) 2
100mA ELCB-3 11 Y4 20 4 4 CCTV CAMERA (3NOS.) 3
12 B4 20 4 4 CCTV CAMERA (2NOS.) 2
13 R5 SPACE
14 Y5 SPACE
15 B5 20 4 4 CCTV CAMERA (3NOS.) 3
40A,4P 16 R6 20 4 4 CORRIDOR+RECP-GF 1/2
30mA ELCB- 17 Y6 20 4 4 MFACP 1
4
18 B6 20 4 4 RECEPTION 12U CABINET 1
19 R7 SPACE
20 Y7 20 4 4 MAIN TEL RM 2
21 B7 SPACE

SUB TOTAL
CABLE SIZE: 4C, 10 mm² XLPE/SWA/PVC/CU + TOTAL 5.75 kW
1C, 10 mm² PVC/CU GY ECC
E CIRCLE, DUBAI

OR LV ROOM DB REF: EDB-LL2@GF

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

50 200
50 250
50 350

50 550

500 500 SPN ISOL

500 500 SPN ISOL


100 200 @H/L
100 300
100 200

100 300
200/400 1,000 RING
400 400 MFACP
200 200 12U CAB

400 800

SUB TOTAL 1,900 2,300 1,550


.75 kW
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 1st FLOOR ELECTRICAL ROOM DB REF: EDB-LL3@1F

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-1F 17


100mA ELCB-1 2 Y1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-2F 17
3 B1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-3F 17
40A,4P 4 R2 20 4 4 CCTV CAMERA (3NOS.)-1F 3
100mA ELCB-2 5 Y2 20 4 4 CCTV CAMERA (3NOS.)-2F 3
6 B2 20 4 4 CCTV CAMERA (3NOS.)-3F 3
40A,4P 7 R3 20 4 4 MOTORIZED DAMPER-1F 1
100mA ELCB-3 8 Y3 20 4 4 MOTORIZED DAMPER-2F 1
9 B3 20 4 4 MOTORIZED DAMPER-3F 1
10 R4 20 4 4 MOTORIZED DAMPER-1F 1
11 Y4 20 4 4 MOTORIZED DAMPER-2F 1
12 B4 20 4 4 MOTORIZED DAMPER-3F 1
40A,4P 13 R5 20 4 4 EL RM-1F 1
30mA ELCB- 14 Y5 20 4 4 EL RM-2F 1
4
15 B5 20 4 4 EL RM-3F 1

SUB TOTAL
CABLE SIZE: 4C, 10 mm² XLPE/SWA/PVC/CU + TOTAL 3.42 kW
1C, 10 mm² PVC/CU GY ECC
E CIRCLE, DUBAI

ECTRICAL ROOM DB REF: EDB-LL3@1F

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

20 340
20 340
20 340
100 300 @H/L
100 300
100 300
50 50 @H/L
50 50
50 50
50 50
50 50
50 50
400 400
400 400
400 400

SUB TOTAL 1,140 1,140 1,140


.42 kW
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 4th FLOOR ELECTRICAL ROOM DB REF: EDB-LL4@4

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-4F 16


100mA ELCB-1 2 Y1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-5F 15
3 B1 10 2.5 2.5 ROOF 7
40A,4P 4 R2 20 4 4 CCTV CAMERA (3NOS.)-4F 3
100mA ELCB-2 5 Y2 20 4 4 CCTV CAMERA (3NOS.)-5F 3
6 B2 20 4 4 CCTV CAMERA (1NO.)-RF 1
7 R3 20 4 4 CCTV CAMERA (1NO.)-RF 1
8 Y3 20 4 4 CCTV CAMERA (1NO.)-RF 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 MOTORIZED DAMPER-4F 1
100mA ELCB-3 11 Y4 20 4 4 MOTORIZED DAMPER-5F 1
12 B4 20 4 4 MOTORIZED DAMPER-RF 1
13 R5 20 4 4 MOTORIZED DAMPER-4F 1
14 Y5 20 4 4 MOTORIZED DAMPER-5F 1
15 B5 20 4 4 MOTORIZED DAMPER-RF 1
40A,4P 16 R6 20 4 4 EL RM-4F 1
30mA ELCB- 17 Y6 20 4 4 EL RM-5F 1
4
18 B6 20 4 4 EL RM-RF 1
19 R7 SPACE
20 Y7 SPACE
21 B7 20 4 4 GSM RM-RF 2

SUB TOTAL
CABLE SIZE: 4C, 10 mm² XLPE/SWA/PVC/CU + TOTAL 4.19 kW
1C, 10 mm² PVC/CU GY ECC
EIRAH VILLAGE CIRCLE, DUBAI

N: 4th FLOOR ELECTRICAL ROOM DB REF: EDB-LL4@4F

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

20 320
20 320
50 350
100 300 @H/L
100 300
100 100
100 100
100 100

50 50 @H/L
50 50
50 50
50 50
50 50
50 50
400 400
400 400
400 400

400 800

1,220 1,220 1,750


.19 kW
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F/GF01 1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 BED RM 3
2
6 B2 20 4 4 LIV/DIN 2/1
7 R3 SPACE
8 Y3 20 4 4 12U CABINET 1
9 B3 20 4 4 LAUNDRY 1
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 SPACE
100mA ELCB-4 14 Y5 20 4 4 PANTRY FCU 1
15 B5 SPACE
40A,4P 16 R6 20 4.0 4.0 CU 1
100mA ELCB-5 17 Y6
18 B6

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
LLAGE CIRCLE, DUBAI

RTMENT ENTRANCE DB REF: DB-F/GF01 1BHK

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

50/100 250
20/50/100 210
20/100 260
200 400
200 600
200/400 800

200 200
1000 1,000
1200 1200
200 200

400 400

5700 1900 UVR+ART+CONT


1900
1900

3,750 3,510 3,960


11.22
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F/GF02 1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 12U CABINET 1
8 Y3 20 4 4 LAUNDRY 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
RCLE, DUBAI

NTRANCE DB REF: DB-F/GF02 1BHK

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

20/50/100 210
20/50/100 250
20/100 280
200 600
200 400
200/400 800
200 200
1000 1,000

1200 1,200
200 200

5700 1900 UVR+ART+CONT


1900
1900

400 400

4,110 3,750 3,380


11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F/GF031BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 PASSAGE+LIV/DIN 2/1
2
6 B2
7 R3 20 4 4 LAUNDRY 1
8 Y3 20 4 4 BED RM 3
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

NTRANCE DB REF: DB-F/GF031BHK

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

20/50/100 250
20/100 280
20/50/100 210
200 400
200/400 800

1000 1,000
200 600
200 200
200 200

1200 1,200
5700 1900 UVR+ART+CONT
1900
1900

400 400

3,750 3,580 3,910


11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F/GF04 1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 BED RM 3
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 LAUNDRY 1
8 Y3 20 4 4 12U CABINET 1
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- 11 Y4 20 4 4 BATH WH 1
3
12 B4 20 4 4 PANTRY (FRIDGE) 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F/GF04 1BHK

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

20/50/100 250
20/50/100 210
20/100 280
200 400
200 600
200/400 800
1000 1000
200 200

1200 1,200
200 200
5700 1900 UVR+ART+CONT
1900
1900

400 400

3,550 4,110 3,580


11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F/GF05 2BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 BED RM1+BATH 2/1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/3
4 R2 10 2.5 2.5 BED RM2+BATH 2/1/1 1
5 Y2 SPACE
6 B2 SPACE
40A,4P 7 R3 20 4 4 PANTRY 2
30mA ELCB- 8 Y3 20 4 4 BED RM1 3
2
9 B3 20 4 4 LIV/DIN 2/1
10 R4 20 4 4 BED RM2 3
11 Y4 20 4 4 BATH1 WH 1
12 B4 20 4 4 PANTRY (FRIDGE) 1
40A,4P 13 R5 20 4 4 BATH2 WH 1
30mA ELCB- 14 Y5 20 4 4 12U CABINET 1
3
15 B5 20 4 4 LAUNDRY 1
40A,4P 16 R6 SPACE
100mA ELCB-4 17 Y6 20 4 4 PANTRY FCU-1 1
18 B6 20 4 4 FCU-2 1
19 R7 20 4.0 4.0 CU 1
20 Y7
21 B7
40A,4P 22 R8 20 4.0 4.0 CU 1
100mA ELCB-5 23 Y8
24 B8
SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F/GF05 2BHK

Load Per Circuit REMARKS


WATT UNIT WATT
R Y B

20/50/100 250
20/50/100 210
20/100 380
20/50/100 210

200 400
200 600
200/400 800
200 600
1200 1,200
200 200
1200 1,200
200 200
1000 1,000

330 330
330 330
3800 1,267 UVR+ART+CONT
1,267
1,267
3800 1,267 UVR+ART+CONT
1,267
1,267
5,193 5,073 5,243
15.51
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(101,102,103,104 & 10

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 BED RM 3
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 LAUNDRY 1
8 Y3 20 4 4 12U CABINET 1
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- 11 Y4 20 4 4 BATH WH 1
3
12 B4 20 4 4 PANTRY (FRIDGE) 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

TMENT ENTRANCE DB REF: DB-F(101,102,103,104 & 106)1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 250
20/50/100 210
20/100 280
200 400
200 600
200/400 800
1000 1000
200 200

1200 1,200
200 200
3600 1200 UVR+ART+CONT
1200
1200

330 330

2,850 3,410 2,810


9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI 1BHK
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F105

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/2 1


100mA ELCB-1 2 Y1 10 2.5 2.5 BED RM+BATH 3/1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 BED RM 3
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 LAUNDRY 1
8 Y3 20 4 4 12U CABINET 1
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- 11 Y4 20 4 4 BATH WH 1
3
12 B4 20 4 4 PANTRY (FRIDGE) 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI 1BHK

PARTMENT ENTRANCE DB REF: DB-F105

Load Per Circuit REMARKS


WATT UNIT WATT
R Y B

20/50/100 350
20/50/100 230
20/100 280
200 400
200 600
200/400 800
1000 1000
200 200

1200 1,200
200 200
5700 1900 UVR+ART+CONT
1900
1900

400 400

3,650 4,130 3,580


11.36
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB- F107 1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 5/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 PASSAGE+LIV/DIN 3/1
7 R3 SPACE
8 Y3 20 4 4 LAUNDRY 1
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 PANTRY (FRIDGE) 1
40A,4P 13 R5 20 4 4 BED BATH FCU 1
100mA ELCB-4 14 Y5 SPACE
15 B5 SPACE
16 R6 20 4.0 4.0 CU 1
17 Y6
18 B6

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

ENT ENTRANCE DB REF: DB- F107 1BHK

Load Per Circuit REMARKS


WATT UNIT WATT
R Y B

20/50/100 210
20/50/100 250
20/100 300
200 600
200 400
200/400 1,000 RING

1000 1,000
200 200
1200 1,200

200 200
300 300

3600 1200 UVR+ART+CONT


1200
1200

3,510 2,850 2,900


9.26
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF:
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB-F(108,109 & 110) 1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 PASSAGE+LIV/DIN 2/1
2
6 B2 20 4 4 BED RM 3
7 R3 20 4 4 LAUNDRY 1
8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 20 4 4 PANTRY FCU 1
18 B6

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI DB REF:

APARTMENT ENTRANCE DB-F(108,109 & 110) 1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 250
20/100 280
20/50/100 210
200 400
200/400 800
200 600
1000 1,000

200 200
200 200

1200 1,200
3600 1200 UVR+ART+CONT
1200
1200

330 330

3,050 2,610 3,410


9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF:
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB-F(111 & 112) 1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 PASSAGE+LIV/DIN 2/1
2
6 B2 SPACE
7 R3 20 4 4 LAUNDRY 1
8 Y3 20 4 4 BED RM 3
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI DB REF:

APARTMENT ENTRANCE DB-F(111 & 112) 1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 250
20/100 280
20/50/100 210
200 400
200/400 800

1000 1,000
200 600
200 200
200 200

1200 1,200
5700 1900 UVR+ART+CONT
1900
1900

400 400

3,750 3,580 3,910


11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(113,114,115) BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 12U CABINET 1
8 Y3 20 4 4 LAUNDRY 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(113,114,115) BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 210
20/50/100 250
20/100 280
200 600
200 400
200/400 800
200 200
1000 1,000

1200 1,200
200 200

3600 1200 UVR+ART+CONT


1200
1200

330 330

3,410 3,050 2,610


9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(116) BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 12U CABINET 1
8 Y3 20 4 4 LAUNDRY 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(116) BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 210
20/50/100 250
20/100 280
200 600
200 400
200/400 800
200 200
1000 1,000

1200 1,200
200 200

5700 1900 UVR+ART+CONT


1900
1900

400 400

4,110 3,750 3,380


11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F117 1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. 13A SH W/H W/M KIT CCU FCU CU


Fan S/O S/O HD
40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1
100mA ELCB-1 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/2 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 12U CABINET 1
8 Y3 20 4 4 LAUNDRY 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F117 1BHK

Load Per Circuit REMARKS

WATT UNIT WATT

R Y B

20/50/100 210
20/50/100 350
20/100 280
200 600
200 400
200/400 800
200 200
1000 1,000

1200 1,200
200 200

3600 1200 UVR+ART+CONT


1200
1200

330 330

3,410 3,150 2,610


9.17
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(401,402,404,406 & 413

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. 13A SH W/H W/M KIT CCU FCU CU


Fan S/O S/O HD
40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1
100mA ELCB-1 2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 BED RM 3
2
6 B2 20 4 4 LIV/DIN 2/1
7 R3 20 4 4 LAUNDRY 1
8 Y3 20 4 4 12U CABINET 1
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- 11 Y4 20 4 4 BATH WH 1
3
12 B4 20 4 4 PANTRY (FRIDGE) 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(401,402,404,406 & 413) 1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

100 200
20/50/100 210
20/100 260
200 400
200 600
200/400 800
1000 1000
200 200

1200 1,200
200 200
3600 1200 UVR+ART+CONT
1200
1200

330 330

2,800 3,410 2,790


9.00
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(403 & 408)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. 13A SH W/H W/M KIT CCU FCU CU


Fan S/O S/O HD
40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1
100mA ELCB-1 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 PASSAGE+LIV/DIN 2/1
2
6 B2 20 4 4 BED RM 3
7 R3 20 4 4 LAUNDRY 1
8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

RTMENT ENTRANCE DB REF: DB-F(403 & 408)1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 250
20/100 280
20/50/100 210
200 400
200/400 800
200 600
1000 1,000

200 200
200 200

1200 1,200
3600 1200 UVR+ART+CONT
1200
1200

330 330

3,050 2,280 3,740


9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(405)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 PASSAGE+LIV/DIN 2/1
2
6 B2 20 4 4 BED RM 3
7 R3 20 4 4 LAUNDRY 1
8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 20 4 4 PANTRY FCU 1
18 B6 SPACE

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

RTMENT ENTRANCE DB REF: DB-F(405)1BHK

Load Per Circuit REMARKS

WATT UNIT
R Y B

20/50/100 250

20/100 280
20/50/100 210
200 400
200/400 800
200 600
1000 1,000

200 200
200 200

1200 1,200
5700 1900 UVR+ART+CONT
1900
1900

400 400

3,750 3,380 4,110


11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F407 2BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 BED RM1+BATH 2/1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
4 R2 10 2.5 2.5 BED RM2+BATH+BALCONY 4/1/1 1
5 Y2 SPACE
6 B2 SPACE
40A,4P 7 R3 20 4 4 PANTRY 2
30mA ELCB- 8 Y3 20 4 4 BED RM1 3
2
9 B3 20 4 4 LIV/DIN 2/1
10 R4 20 4 4 BATH2 WH 1
11 Y4 20 4 4 BATH1 WH 1
12 B4 20 4 4 PANTRY (FRIDGE) 1
40A,4P 13 R5 20 4 4 BED RM2 3
30mA ELCB- 14 Y5 20 4 4 12U CABINET 1
3
15 B5 20 4 4 LAUNDRY 1
40A,4P 16 R6 20 4 4 BED RM2 BATH FCU 1
100mA ELCB-4 17 Y6 SPACE
18 B6 SPACE
19 R7 20 4.0 4.0 CU 1
20 Y7
21 B7

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

TMENT ENTRANCE DB REF: DB-F407 2BHK

Load Per Circuit REMARKS

WATT UNIT WATT


R Y B

100 200

20/50/100 210
20/100 280
20/50/100 250

200 400
200 600
200/400 800
1200 1,200
1200 1,200
200 200
200 600
200 200
1000 1,000
330 330

3700 1233 UVR+ART+CONT


1233
1233

4,213 3,443 3,513


11.17
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(409,410,411 & 412) 1BH

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 12U CABINET 1
8 Y3 20 4 4 LAUNDRY 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(409,410,411 & 412) 1BHK

Load Per Circuit REMARKS

WATT UNIT WATT

R Y B

20/50/100 210

20/50/100 250
20/100 280
200 600
200 400
200/400 800
200 200
1000 1,000

1200 1,200
200 200

3600 1200 UVR+ART+CONT


1200
1200

330 330

3,410 3,050 2,610


9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(414 & 415)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 LIV/DIN 2/1
2
6 B2 20 4 4 BED RM 3
7 R3 20 4 4 LAUNDRY 1
8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(414 & 415)1BHK

Load Per Circuit REMARKS

WATT UNIT WATT


R Y B

100 200

20/100 260
20/50/100 210
200 400
200/400 800
200 600
1000 1,000

200 200
200 200

1200 1,200
3600 1200 UVR+ART+CONT
1200
1200

330 330

3,000 2,260 3,740


9.00
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F416

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PANTRY 2 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 LIV/DIN 2/1
7 R3 20 4 4 12U CABINET 1
8 Y3 20 4 4 LAUNDRY 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

TMENT ENTRANCE DB REF: DB-F416

Load Per Circuit REMARKS


WATT UNIT WATT
R Y B

20/50/100 210

100 300
20/100 260
200 600
200 400
200/400 800
200 200
1000 1,000

1200 1,200
200 200

3600 1200 UVR+ART+CONT


1200
1200

330 330

3,410 3,100 2,590


9.10
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(501,502,504 & 511) 1B

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 BED RM 3
2
6 B2 20 4 4 LIV/DIN 2/1
7 R3 20 4 4 LAUNDRY 1
8 Y3 20 4 4 12U CABINET 1
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- 11 Y4 20 4 4 BATH WH 1
3
12 B4 20 4 4 PANTRY (FRIDGE) 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(501,502,504 & 511) 1BHK

Load Per Circuit REMARKS


WATT UNIT WATT
R Y B

100 200

20/50/100 210
20/100 260
200 400
200 600
200/400 800
1000 1000
200 200

1200 1,200
200 200
3600 1200 UVR+ART+CONT
1200
1200

330 330

2,800 3,410 2,790


9.00
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(503)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 PASSAGE+LIV/DIN 2/1
2
6 B2 20 4 4 BED RM 3
7 R3 20 4 4 LAUNDRY 1
8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 20 4 4 PANTRY FCU 1
18 B6 SPACE

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(503)1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 250

20/100 280
20/50/100 210
200 400
200/400 800
200 600
1000 1,000

200 200
200 200

1200 1,200
5700 1900 UVR+ART+CONT
1900
1900

400 400

3,750 3,380 4,110


11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(506)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 PASSAGE+LIV/DIN 2/1
2
6 B2 20 4 4 BED RM 3
7 R3 20 4 4 LAUNDRY 1
8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 20 4 4 PANTRY FCU 1
18 B6 SPACE

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(506)1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 250

20/100 280
20/50/100 210
200 400
200/400 800
200 600
1000 1,000

200 200
200 200

1200 1,200
3600 1200 UVR+ART+CONT
1200
1200

330 330

3,050 2,610 3,410


9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(506)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 PASSAGE+LIV/DIN 2/1
2
6 B2 20 4 4 BED RM 3
7 R3 20 4 4 LAUNDRY 1
8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 20 4 4 PANTRY FCU 1
18 B6 SPACE

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(506)1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 250

20/100 280
20/50/100 210
200 400
200/400 800
200 600
1000 1,000

200 200
200 200

1200 1,200
3600 1200 UVR+ART+CONT
1200
1200

330 330

3,050 2,610 3,410


9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F505 2BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 5/2
3 B1 10 2.5 2.5 BED RM1+BATH 2/1/1 1
4 R2 10 2.5 2.5 BED RM2+BATH+BALCONY 4/1/1 1
5 Y2 SPACE
6 B2 SPACE
40A,4P 7 R3 20 4 4 PANTRY 2
30mA ELCB- 8 Y3 20 4 4 LIV/DIN 2/1
2
9 B3 20 4 4 BED RM1 3
10 R4 20 4 4 BATH2 WH 1
11 Y4 20 4 4 PANTRY (FRIDGE) 1
12 B4 20 4 4 BATH1 WH 1
40A,4P 13 R5 20 4 4 BED RM2 3
30mA ELCB- 14 Y5 20 4 4 LAUNDRY 1
3
15 B5 20 4 4 12U CABINET 1
40A,4P 16 R6 SPACE
100mA ELCB-4 17 Y6 SPACE
18 B6 20 4 4 BED RM2 BATH FCU 1
19 R7 20 4.0 4.0 CU 1
20 Y7
21 B7

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

NTRANCE DB REF: DB-F505 2BHK

Load Per Circuit REMARKS

WATT UNIT WATT

R Y B

100 200

20/100 300
20/50/100 210
20/50/100 250

200 400
200/400 800
200 600
1200 1,200
200 200
1200 1,200
200 600
1000 1,000
200 200

330 330
3600 1200 UVR+ART+CONT
1200
1200

3,850 3,500 3,740


11.09
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(507,509 & 510)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 12U CABINET 1
8 Y3 20 4 4 LAUNDRY 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(507,509 & 510)1BHK

Load Per Circuit REMARKS


WATT UNIT WATT

R Y B

20/50/100 210
20/50/100 250
20/100 280
200 600
200 400
200/400 800
200 200
1000 1,000

1200 1,200
200 200

3600 1200 UVR+ART+CONT


1200
1200

330 330

3,410 3,050 2,610


9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(508)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2
40A,4P 4 R2 20 4 4 BED RM 3
30mA ELCB- 5 Y2 20 4 4 PANTRY 2
2
6 B2 20 4 4 PASSAGE+LIV/DIN 2/1
7 R3 20 4 4 12U CABINET 1
8 Y3 20 4 4 LAUNDRY 1
9 B3 SPACE
40A,4P 10 R4 20 4 4 BATH WH 1
30mA ELCB- 11 Y4 20 4 4 PANTRY (FRIDGE) 1
3
12 B4 SPACE
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 SPACE
18 B6 20 4 4 PANTRY FCU 1

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

MENT ENTRANCE DB REF: DB-F(508)1BHK

Load Per Circuit REMARKS

WATT UNIT WATT

R Y B

20/50/100 210
20/50/100 250
20/100 280
200 600
200 400
200/400 800
200 200
1000 1,000

1200 1,200
200 200

5700 1900 UVR+ART+CONT


1900
1900

400 400

4,110 3,750 3,380


11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F(512 & 513)1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1


100mA ELCB-1 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1
40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB- 5 Y2 20 4 4 LIV/DIN 2/1
2
6 B2 20 4 4 BED RM 3
7 R3 20 4 4 LAUNDRY 1
8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1
40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1
30mA ELCB- 11 Y4 SPACE
3
12 B4 20 4 4 BATH WH 1
40A,4P 13 R5 20 4.0 4.0 CU 1
100mA ELCB-4 14 Y5
15 B5
40A,4P 16 R6 SPACE
100mA ELCB-5 17 Y6 20 4 4 PANTRY FCU 1
18 B6 SPACE

SUB TOTAL
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²
PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

ENT ENTRANCE DB REF: DB-F(512 & 513)1BHK

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

100 200
20/100 260
20/50/100 210
200 400
200/400 800
200 600
1000 1,000

200 200
200 200

1200 1,200
3600 1200 UVR+ART+CONT
1200
1200

330 330

3,000 2,590 3,410


9.00
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE DB REF: DB-F514 1BHK

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD CCU FCU CU

40A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 PANTRY 2 1


100mA ELCB-1
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2

3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1

40A,4P 4 R2 20 4 4 PANTRY 2
30mA ELCB-
2 5 Y2 20 4 4 LIV/DIN 2/1

6 B2 20 4 4 BED RM 3

7 R3 20 4 4 LAUNDRY 1

8 Y3 SPACE
9 B3 20 4 4 12U CABINET 1

40A,4P 10 R4 20 4 4 PANTRY (FRIDGE) 1


30mA ELCB-
3 11 Y4 SPACE

12 B4 20 4 4 BATH WH 1

40A,4P 13 R5 20 4.0 4.0 CU 1


100mA ELCB-4
14 Y5

15 B5

40A,4P 16 R6 SPACE
100mA ELCB-5
17 Y6 20 4 4 PANTRY FCU 1
18 B6 SPACE

SUB TOTAL

CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²


PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

ENT ENTRANCE DB REF: DB-F514 1BHK

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

100 300

20/100 260

20/50/100 210

200 400
200/400 800

200 600

1000 1,000

200 200

200 200

1200 1,200

3600 1200 UVR+ART+CONT


1200

1200

330
330

3,100 2,260 3,740

9.10
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GYM ENTRANCE DB REF: DB-GYM

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD ISOL FCU CU

63A TPN ISOL 40A,4P 1 R1 10 2.5 2.5 GYM+BALCONY 2/8


100mA ELCB-1
2 Y1 10 2.5 2.5 FEM CHANGING+SHOWER 13
3 B1 10 2.5 2.5 GYM 8

4 R2 SPACE

5 Y2 10 2.5 2.5 M CHANGING+SHOWER+PLANT RM 16

6 B2 SPACE
40A,4P 7 R3 20 4 4 GYM 3
30mA ELCB-
2 8 Y3 20 4 4 MALE+FEMALE CHANGING 2

9 B3 SPACE

10 R4 20 4 4 MALE SHWR WH 1

11 Y4 20 4 4 FEMALE SHWR WH 1
12 B4 20 4 4 GYM 3

40A,4P 13 R5 SPACE
100mA ELCB-3
14 Y5 20 4 4 GYM FCU (5F-15) 1

15 B5 20 4 4 GYM FCU (5F-16) 1


40A,4P 16 R6 20 4.0 4.0 CU 1
100mA ELCB-4
17 Y6

18 B6

40A,4P 19 R7 32 4.0 1.0 SAUNA-MALE 1


100mA ELCB-5 A TP X 6.0 X 6.0
20 Y7
21 B7

22 R8 32 4.0 1.0 SAUNA-FEMALE 1


A TP X 6.0 X 6.0
23 Y8

24 B8

SUB TOTAL

CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm ²


PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

E DB REF: DB-GYM

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

50/100 900

50 650
100 800

50 800

400 1,200 RING

200 400

1200 1,200

1200 1,200
400 1,200 RING

330 330

330 330
3600 1200 UVR+ART+CONT

1200

1200

4050 1,350 TPN ISOL

1,350
1,350

4050 1,350 TPN ISOL

1,350

1,350

7,200 7,280 6,230


20.71
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GYM ENTRANCE DB REF: DB-GYM

RATING OF RATING OF SL NO CIR NO MCB RTGCCT


IN Amps
Wire ECC
Size mm2
Wire
ROOM/
Size mm2
AREA CONNECTED LOADS/POINTS
INCOMER ELCB

LTG EX. Fan 13A S/O SH S/O W/H W/M KIT HD ISOL FCU CU

63A TPN ISOL 40A,4P 25 R9 20 4.0 4.0 GYM CU (5F-15) 1


100mA ELCB-6
26 Y9
27 B9

SUB TOTAL

CABLE SIZE: 4C,16 mm² XLPE/SWA/PVC/CU + 1C, 16mm ²


PVC/CU GY ECC TOTAL
E CIRCLE, DUBAI

E DB REF: DB-GYM

WATT UNIT Load Per Circuit WATT REMARKS

R Y B

3600 1200 UVR+ART+CONT

1200
1200

8,400 8,480 7,430

24.31