PHASOR MEASUREMENT UNIT (PMU) WITH INBUILT GPS AND PDC (P847 Model B)
Tender Specification Quoted Specifications
ANALOG CURRENT MEASUREMENT INPUTS
Number of inputs: 4 (IA, IB, IC and IN) 4 x 3-phase set, or 12 individual

Rated Current: 1A/5A Current Rating: 1A or 5A as an order


option
Maximum Burden: ≤0.01VA@1A, ≤0.1VA@5A, <4 AC Current:
VA@42A Nominal burden per phase:
< 0.2 VA at In
Ac Voltage:
Nominal burden per phase:
< 0.02 VA at Vn
Measurement accuracy with 100% asymmetrical Typically +1%, but +0.5% between 0.2 –
current: Minimum 95 2In/Vn
Current: 0.05 to 3 In +1.0% of reading
Voltage:
0.05 to 2 Vn+1.0% of reading
Synchro Phasor Accuracy Magnitude: ±1.0% @ 25 °C + Synchro Phasor accuracy magnitude to
(± 20PPM/ °C) ≤14 A (5A) or ≤3.5 A (1A) ±1.2% @ 25 meet 1% TVE to the limits of C37.118.1-
°C, + (± 125PPM/ °C) >14 A (5A) or >3.5 A (1A) 2011
Synchro Phasor Accuracy Angle: ±0.5 degree @ 25 °C + Synchro Phasor accuracy Angle to meet
(± 20PPM/ °C) ≤14 A (5A), or ≤3.5 A (1A) ±0.8 degree 1% - .5°
@ 25 °C + (± 125PPM/°C) >14 A (5A) or >3.5 A (1A)
ANALOG VOLTAGE MEASUREMENT INPUTS: 3 (1 x 3-phase set or 3 x individual)
Number of inputs: 4(VA, VB, VC and VN)
Rated voltage: 57.7 V ac to 138.6 V ac (L-N) Voltage Rating: 110-120Vac the voltage
transformer inputs shall be rated for
100/120V ac and shall have a continuous
rating of 2 times the rated voltage. The
inputs shall have a short time thermal
withstand capability of 2.6 times the rated
voltage for 10 sec.
Measurement bandwidth (-3 dB), DC to 3 kHz 1648 * 50 = 82.4 kbps for a maximum
frame rate of 50 frames per second (TCP)
1648 * 60 = 98.88 kbps for a maximum
frame rate of 60 frames per second (TCP)
Sampling Rate:
82.4kbyte = 82400bytes = 659200 bits/sec
which is equal to 659.2khz
With the help of 659.2khz sampling rate
we can read or measure dc-3kHz input
signals
659200/3000=219 samples
Messages per second: 1, 2, 5, 10, 25, 50, 100, 200 for 10,25, or 50 per second for 50Hz
50Hz signal, 1, 2, 4, 5, 10, 12, 15, 20, 30, 60, 120, 240 for 10,12,15,30, or 60 per second for 60 Hz
60Hz signal
Built-in GPS option: GPS option replaces PPS fiber optic GPS Externally will be provided
input with a SMA antenna connector. Base precision <
45 nanoseconds
Substation Phasor Data Concentrator (sPDC) Phasor Data Concentrator (PDC)
Function:
Received multiple PMU streams
Phasor stream rate conversion
Phasor Stream time alignment
Cyber Security
NOTE: THE ABOVE QUOTED SPECIFICATIONS MEET WITH THE TENDER
SPECIFICATION.