Sei sulla pagina 1di 116

Flow Control

Weir Floway, Inc.


2494 S Railroad Ave
Fresno, CA 93706 USA

T +1 559 442 4000


F +1 559 442 3098
www.global.weir

INSTALLATION, OPERATION
MAINTENANCE MANUAL

&

MANUFACTURING DATA BOOK

TAG NO.: PO# 22959-SAL

CUSTOMER: FRESH EXPRESSS

SUPPLIER: THE BROWN COMPANY

PURCHASE ORDER NO.: 11513-889

FACTORY CUSTOMER ORDER NO.: 80621

80621IOM & 80621MDB, REV. 0

“Copyright © 2018, Weir Floway, Inc.

Weir Floway, Inc. (“the Company”) is the owner of the copyright and all confidential information in this document. The document may contain information that is private, confidential or
privileged. The document must not be copied in whole or in part, in any form or by any means, and the information in it must not be disclosed to any person, or used for any purpose other than
the specific purpose for which it has been provided, without the prior written consent of the Company.”
Flow Control
Weir Floway, Inc.
2494 S Railroad Ave
Fresno, CA 93706 USA

T +1 559 442 4000


F +1 559 442 3098
www.global.weir

Title: Installation, Operation Maintenance Manual & Manufacturing Data Book


Purchase Order No.: PO# 22959-SAL

Floway: 80621IOM & 80621MDB

Date Revision Description

06/22/2018 0 Initial Release.

“Copyright © 2018, Weir Floway, Inc. All Rights Reserved.”


Flow Control
Weir Floway, Inc.
2494 S Railroad Ave
Fresno, CA 93706 USA

T +1 559 442 4000


F +1 559 442 3098
www.global.weir

INSTALLATION, OPERATION MAINTENANCE MANUAL


&
MANUFACTURING DATA BOOK

CUSTOMER: FRESH EXPRESSS


SUPPLIER: THE BROWN COMPANY
PURCHASE ORDER NO.: 11513-889
FACTORY CUSTOMER ORDER NO.: 80621
Table of Contents

SECTION 1: PUMP
SERIAL NO.: 80621-1-1 / TAG NO.: PO# 22959-SAL

Description Drawing Number

CERTIFIED OUTLINE DRAWING 8062101COD, REV. 0


PUMP INSTALLATION, OPERATION AND MAINTENANCE MANUAL 2001299-VTP-IOM-EN
BOWL INSTALLATION, OPERATION AND MAINTENANCE MANUAL IM-106
PUMP GROUTING PROCESS 2001306_rev0

SECTION 2: PARTS LISTS

PARTS LIST WITH RECOMMENDED SPARES 8062101PL, REV. 0

SECTION 3: WARRANTY

WEIR FLOWAY, INC. – 1 YEAR WARRANTY FMSA 8.2.1, R00

SECTION 4: MANUFACTURING DATA

CERTIFIED PERFORMANCE TEST CURVE COVER SHEET 80621-1-1


PERFORMANCE TEST DATA PC# 39883
CERTIFIED PERFORMANCE TEST CURVE 80621-1-1-T1
PUMP TEST RECORD PC# 39883
NEWTON, GENERAL EQUATIONS 2 PAGES
NAMEPLATE F80621-1-1
HYDROSTATIC TEST REPORT (HEAD) 1 PAGE
HYDROSTATIC TEST REPORT (DISCHARGE CASE) 1 PAGE
HYDROSTATIC TEST REPORT (BOWL, PT# 548100-1052) 1 PAGE
HYDROSTATIC TEST REPORT (BOWL, PT# 548100-2052) 1 PAGE

“Copyright © 2018, Weir Floway, Inc.

Weir Floway, Inc. (“the Company”) is the owner of the copyright and all confidential information in this document. The document may contain
information that is private, confidential or privileged. The document must not be copied in whole or in part, in any form or by any means, and the
information in it must not be disclosed to any person, or used for any purpose other than the specific purpose for which it has been provided, without
the prior written consent of the Company.”

80621IOM & 80621MDB, REV. 0, DV, 06/21/18 Page 1 of 1


SECTION 1
FLOWAY® PUMPS
Vertical Turbine Pumps
Vertical Turbine Pumps
Installation, Operation, & Maintenance Manual

Copyright © 2014, Weir Floway, Inc.


Floway is a registered trademark of Weir Floway, Inc.
Weir Floway, Inc. (“the Company”) is the owner of the copyright and all confidential information in this
document. The document may contain information that is private, confidential or privileged. The document
must not be copied in whole or in part, in any form or by any means, and the information in it must not be
disclosed to any person, or used for any purpose other than the specific purpose for which it has been
provided, without the prior written consent of the Company.

Document Name: 2001299-VTP-IOM-EN


Revision 3 Issue Date: December 12, 2014
FLOWAY® PUMPS
Vertical Turbine Pumps
Vertical Turbine Pumps
Installation, Operation, & Maintenance Manual

Revision Page

Revision Description Reviewed By Approved By Date

0 Initial Release - - -

1 ERCO-1001843 DEB AW July 11, 2014

2 ERCO-1002047 DEB ASP October 3, 2014

3 ERCO-1002197 DEB FW December 12, 2014

Document Name: 2001299-VTP-IOM-EN Page i


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps
Table of Contents
1 Introduction ............................................................................................................................... 1
1.1 Scope of the Manual ........................................................................................................................................ 1
1.2 Intended Audience ........................................................................................................................................... 1
1.3 Disclaimer ........................................................................................................................................................ 1
1.4 Contact Information.......................................................................................................................................... 1
1.5 Glossary of Acronyms ..................................................................................................................................... 2

2 Safety.......................................................................................................................................... 3
2.1 Safety Symbols ............................................................................................................................................... 4
2.2 Mandatory Personal Protective Equipment ..................................................................................................... 4
2.3 Important Information....................................................................................................................................... 4
2.4 Intended Use.................................................................................................................................................... 7
2.5 Qualified Workers ............................................................................................................................................ 7
2.6 Markings and Approvals ................................................................................................................................. 8
2.7 Safety Equipment for the Pump ....................................................................................................................... 8
2.8 Fire Fighting ..................................................................................................................................................... 8
2.9 Emergency Procedures ................................................................................................................................... 8

3 General Information and Description ...................................................................................... 9


3.1 General Information ......................................................................................................................................... 9
3.2 Identification..................................................................................................................................................... 9
3.3 General Description ......................................................................................................................................... 9
3.3.1 Drivers ..........................................................................................................................................11
3.3.2 Discharge Head Assembly ...........................................................................................................11
3.3.3 Column Assemblies......................................................................................................................11
3.3.4 Bowl Assemblies ..........................................................................................................................11
3.3.5 Suction Vessel ..............................................................................................................................11

4 Pre-installation ........................................................................................................................ 12
4.1 Receiving and Unloading ............................................................................................................................... 12
4.2 Storage........................................................................................................................................................... 12
4.3 Uncrating and Cleaning ................................................................................................................................. 13
4.4 Lifting ............................................................................................................................................................ 13
4.4.1 Lifting Pump Components and Pump Assemblies....................................................................... 14
4.5 Installation Equipment and Tools ................................................................................................................... 17
4.6 Pre-installation Check List ............................................................................................................................. 17

5 Installation ............................................................................................................................... 19
5.1 General .......................................................................................................................................................... 19
5.2 Foundation ..................................................................................................................................................... 19
5.3 Suction Barrel Installation .............................................................................................................................. 20
5.4 Vertical Turbine Pump Installation for Wet Pit (Type VS1)............................................................................. 20
5.5 Vertical Turbine Can Pump Installation (Type VS6) ....................................................................................... 22
5.6 Hollow Shaft Driver Installation ...................................................................................................................... 24
5.7 Solid Shaft Driver Installation ......................................................................................................................... 27
5.8 Impeller Adjustment - General ....................................................................................................................... 29

Document Name: 2001299-VTP-IOM-EN Page ii


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps
5.9 Impeller Adjustment - Hollow Shaft Driver ..................................................................................................... 31
5.10 Impeller Adjustment - Solid Shaft Driver (thrust bearing in driver) ................................................................. 32
5.10.1 Adjustable Flanged Couplings ..................................................................................................... 32
5.11 Impeller Adjustment - Solid Shaft Driver (thrust bearing in pump) ................................................................. 32
5.12 Mechanical Seal............................................................................................................................................. 33
5.13 Packing Boxes ............................................................................................................................................... 33
5.14 Enclosing Tube Tension ................................................................................................................................. 33

6 Commissioning and Operation .............................................................................................. 34


6.1 Pre-starting Checks ....................................................................................................................................... 35
6.2 Initial Start-up ................................................................................................................................................ 36
6.3 Packing Box Adjustment ............................................................................................................................... 36
6.4 Lineshaft Lubrication...................................................................................................................................... 37

7 Maintenance ............................................................................................................................ 39
7.1 Periodic Inspection, Condition Monitoring, and Preventative Maintenance ................................................... 39
7.2 Packing Box Maintenance ............................................................................................................................. 40
7.2.1 Packing Box Greasing ................................................................................................................. 40
7.2.2 Replacing the Packing................................................................................................................. 40
7.3 Start-up with New Packing ............................................................................................................................. 41
7.4 Auxiliary Packing Box Maintenance............................................................................................................... 41
7.5 Mechanical Seal Maintenance ...................................................................................................................... 42
7.6 Impeller Readjustment ................................................................................................................................... 42
7.7 Pump Lubrication ........................................................................................................................................... 44
7.8 Driver and Auxiliary Equipment Maintenance ................................................................................................ 44

8 Repairs .................................................................................................................................... 45
8.1 General .......................................................................................................................................................... 45
8.2 Equipment and Tools ..................................................................................................................................... 46
8.3 Packing Box Repairs...................................................................................................................................... 46
8.4 Mechanical Seal Repairs ............................................................................................................................... 46
8.5 Disassembly................................................................................................................................................... 46
8.6 Inspection and Cleaning ................................................................................................................................ 49
8.7 Replacement Parts ........................................................................................................................................ 50
8.8 Lubrication ..................................................................................................................................................... 50
8.9 Assembly ....................................................................................................................................................... 51
8.10 Tension Nut Assembly and Adjustment ......................................................................................................... 52

9 Decommissioning and Disposal ............................................................................................ 53


10 Troubleshooting ...................................................................................................................... 55
11 Parts ........................................................................................................................................ 57
11.1 Ordering Parts................................................................................................................................................ 57
11.2 Stocking Spare Parts...................................................................................................................................... 57
11.3 Returning Parts .............................................................................................................................................. 57

12 Parts List ................................................................................................................................. 58

Document Name: 2001299-VTP-IOM-EN Page iii


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps
List of Figures
Figure 3-1:Major VTP Components................................................................................................................................ 10

Figure 4-1:Lifting Pumps from Horizontal to Vertical Position ........................................................................................ 15

Figure 4-2:Fabricated Head Lifting................................................................................................................................. 16

Figure 4-3:Cast Head Lifting .......................................................................................................................................... 16

Figure 4-4:Typical Clamping Fixture .............................................................................................................................. 16

Figure 4-5:Shaft Locking Plate ...................................................................................................................................... 18

Figure 5-1:Recommended Anchor Bolt Arrangement .................................................................................................... 20

Figure 5-2:Suction and Discharge Identification - Type VC Discharge Head................................................................. 23

Figure 5-3:Motor Guide Bushing Location ..................................................................................................................... 25

Figure 5-4:Hollow Shaft Driver Clutch ............................................................................................................................ 26

Figure 5-5:Driver Half Coupling Correctly Positioned..................................................................................................... 28

Figure 5-6:Types of Impellers......................................................................................................................................... 30

Figure 5-7:Adjustable Flanged Coupling for Solid Shaft Drivers .................................................................................... 32

Figure 7-1:Effect of Adjusting Semi-open Impellers ....................................................................................................... 43

Figure 8-1:Correct Positioning of Wrenches on Shafting ............................................................................................... 48

Figure 8-2:Enclosing Tube and Lineshaft....................................................................................................................... 49

Figure 8-3:Tension Nut Assembly .................................................................................................................................. 52

Figure 12-1:Adjustable Flanged Coupling ...................................................................................................................... 58

Figure 12-2:Type A - Enclosed Lineshaft ....................................................................................................................... 59

Figure 12-3:Type CF - Open Lineshaft........................................................................................................................... 60

Figure 12-4:Type F and VF - Open Lineshaft................................................................................................................. 61

Figure 12-5:Type AF - Open Lineshaft ........................................................................................................................... 62

Figure 12-6:Type A - Open Lineshaft ............................................................................................................................. 63

Figure 12-7:Type VU - Enclosed Lineshaft..................................................................................................................... 64

Figure 12-8:Injection Lubrication Arrangement .............................................................................................................. 65

Figure 12-9:Type VC ...................................................................................................................................................... 66

Figure 12-10:Type VC .................................................................................................................................................... 67

Document Name: 2001299-VTP-IOM-EN Page iv


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps
List of Tables
Table 1-1:Acronyms ......................................................................................................................................................... 2
Table 2-1:Safety Symbols ................................................................................................................................................ 4
Table 2-2:Personal Protective Equipment ........................................................................................................................ 4
Table 5-1:Shaft Diameter Turns ..................................................................................................................................... 31
Table 6-1:Recommended Lineshaft Oil .......................................................................................................................... 37
Table 6-2:Recommended Lineshaft Oil .......................................................................................................................... 37
Table 6-3:Recommended Greases ................................................................................................................................ 38
Table 7-1:Standard Type Box ......................................................................................................................................... 40
Table 7-2:Hi-pressure Type Box ..................................................................................................................................... 41

Table 8-1:Recommended Torque Values for Typical Fasteners.................................................................................... 51


Table 10-1:Troubleshooting Chart .................................................................................................................................. 55

Document Name: 2001299-VTP-IOM-EN Page v


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Introduction

1 Introduction
This IOM manual must be read thoroughly before installing or operating the pump. All instructions regarding
maintenance must be retained for reference.
The descriptions and instructions included in this manual cover the basic design of the equipment and
common deviations when possible. This manual does not cover all design details and variations nor does it
provide for every possible contingency which may be encountered. When information cannot be found in this
book, contact the nearest representative.
Do not operate this equipment other than in accordance with the instructions contained in this manual. This
equipment (or a prototype) has been shop tested and found satisfactory for the conditions for which it was
sold.
This equipment is capable of extended trouble-free operation when properly applied, installed and
maintained. These instructions present the basic information and methods required for proper installation,
operation and maintenance of vertical turbine pumps.

1.1 Scope of the Manual


This manual describes the installation, operation, and maintenance of Vertical Turbine Pumps. The manual
must be used as a reference only, in conjunction with any Weir Minerals product-specific information and
training.

1.2 Intended Audience


This manual is intended for:
• Weir Minerals service personnel.
• Personnel who have at least a basic level of trade/professional competency.
WARNING
PERSONNEL INJURY
The pump must be installed, operated, and maintained only by personnel who are trained
and have sufficient knowledge about the hazards that may occur during pump operation.

1.3 Disclaimer
Contact your local Weir Minerals representative for any assistance.
• This manual provides basic information about the product. The product purchased may contain
equipment variations to this manual.
• Operating conditions specified in the manual may vary to the operating conditions of the product
installed on-site.
• Illustrations shown in the manual are for reference only and may not match the specific product.

1.4 Contact Information


If you need any assistance, please contact your local Weir Minerals representative (www.weirminerals.com/
contacts/worldwide.aspx or visit www.weirminerals.com/Floway).

Document Name: 2001299-VTP-IOM-EN Page 1 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Introduction

1.5 Glossary of Acronyms

Acronym Description

ATEX Equipment for Potentially Explosive Atmospheres

EMC Electromagnetic Compatibility

ID Inside Diameter

IOM Installation, Operation, & Maintenance

ISO International Organization for Standardization

LOTO Lockout Tagout

MAWP Maximum Allowable Working Pressure

NPSHR Net Positive Suction Head Requirement

OD Outside Diameter

OEM Original Equipment Manufacturer

PED Pressure Equipment Directive

PPE Personal Protective Equipment

RMA Returned Material Authorization

SDS Safety Data Sheets

TIR Total Indicator Reading

TPI Threads Per Inch

VTP Vertical Turbine Pump


Table 1-1: Acronyms

Document Name: 2001299-VTP-IOM-EN Page 2 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Safety

2 Safety
DANGER
DANGER
Study this instruction manual carefully. Failure to follow the instructions can cause serious
personal injury, death, or property damage.
Legal requirements and local regulations may differ substantially with regard to particular safety requirements
and may be regularly modified by relevant authorities without notice. As a consequence, applicable laws and
regulations must be consulted to ensure compliance. The following cannot be guaranteed for its
completeness or continuing accuracy.
These instructions are intended to facilitate familiarisation with the product and its permitted use. Operating
the product in compliance with these instructions is important to help ensure reliability in service and avoid
risks. The instructions may not take into account local regulations. It is the responsibility of the purchaser of
the product to ensure such regulations are observed by all, including those installing the product. Always
coordinate repair activities with operations personnel and follow all plant safety requirements, applicable
workplace health and safety laws and regulations.
These instructions must be read prior to installing, operating, using and maintaining the equipment in any
region, worldwide. The equipment must not be put into service, until as a minimum, all the conditions relating
to workplace health and safety in the instructions, are met.
Information in these user instructions is believed to be reliable. In spite of all the efforts to provide correct and
necessary information, the content of this manual may appear insufficient and is not guaranteed as to its
completeness or accuracy.

Document Name: 2001299-VTP-IOM-EN Page 3 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Safety

2.1 Safety Symbols

Illustration Safety Tool Description

DANGER Indicates a hazard with a high level of risk which, if


DANGER not avoided, could result in death or catastrophic
equipment damage.

WARNING Indicates a hazard with a medium level of risk


WARNING which, if not avoided, could result in serious or
moderate injury, or serious equipment damage.

CAUTION Indicates a hazard with a low level of risk which, if


CAUTION not avoided, could result in moderate or minor
injury, or moderate equipment damage.

NOTICE Indicates important information for the user.


NOTICE

Table 2-1: Safety Symbols

2.2 Mandatory Personal Protective Equipment

Mandatory Personal Protective Equipment Description

Use the following personal protective equipment:


• Protecting Gloves
• Safety Vest
• Safety Shoes
• Safety Goggles
• Hard Hat
• Ear Plugs
• Safety Shield
Table 2-2: Personal Protective Equipment

2.3 Important Information

DANGER
PERSONNEL INJURY
The equipment supplied can cause serious personnel injury or death if mishandled or
misused. Extreme caution must be exercised during the handling and operation of the
equipment.

DANGER
TOXIC VAPOURS FROM PUMPAGE
Appropriate risk assessment must be made regarding the nature of the product in the
pump and necessary safety precautions put in place to protect from exposure to product
vapours.

Document Name: 2001299-VTP-IOM-EN Page 4 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Safety

DANGER
RISK ASSESSMENT
A comprehensive risk assessment of the installation site, pump equipment, and pumping
system must be completed prior to receiving the equipment. The risk assessment should
include but is not limited to the following: lifting procedures, pump equipment, system
piping, system valving, system operation and readiness, containment of pressurized fluid,
intake structures, electrical systems, hazardous materials and conditions, lock-out-tag-out
procedures, start-up and shutdown procedures, potential for reverse flow and/or reverse
pump rotation, water hammer, safety considerations for all personnel and public, and site
security including preventing access to the pump intake structure.

DANGER
PUMP SIGNAGE AND ACCESS
Do not allow anyone near the suction or open discharge of the pump during operation.
Pumps can create strong forces that will pin individuals. It is highly recommended to post
signage and restrict access to the pump suction and/or intake structure to prevent serious
injury or death.

DANGER
LOCKOUT-TAGOUT (LOTO)
• Prior to allowing any checking, maintenance, or other work on the equipment, all
hazardous energy sources (for example, electrical, mechanical, hydraulic, pneumatic,
etc.) must be isolated using an appropriate lockout-tagout procedure.
• Ensure that the intake and discharge openings are totally isolated from all potentially
pressurized connections and that they are, and can only be exposed to atmospheric
pressure.
• Drain the pump and isolate pipework before dismantling the pump. The appropriate
safety precautions must be taken when the pumped liquids are hazardous.
• Failure to follow appropriate LOTO procedures may result in serious personal injury or
death.

DANGER
GUARDS
Contact with rotating equipment can result in serious injury. Appropriate guards must be
installed at all times during operation. Any procedures requiring the removal of the
equipment guards must be performed by qualified personnel trained to perform such work.

DANGER
PERSONNEL INJURY FROM FALLS
Working at height may be required when working on equipment (for example, when
adjusting the impellers with a hollow shaft driver). Always wear appropriate PPE, such as a
safety harness and restraint system, when working at heights.

Document Name: 2001299-VTP-IOM-EN Page 5 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Safety

DANGER
VAPORIZATION
• Do not operate the pump at low or zero flow conditions, or under any circumstances that
causes the pumped liquid to vaporize.
• Personnel injury and equipment damage could result from the high temperature and
pressures created if the pumping liquid vaporizes.
• Low or zero flow conditions must be avoided under any circumstances for any significant
period of time (more than 1 minute) due to the risk of heat/vaporisation of pumped fluid in
the casing that may cause subsequent explosion.

DANGER
THERMAL SHOCK
Do not feed very hot liquid into a cold pump or very cold liquid into a hot pump. Thermal
shock may cause damage to the internal components and rupture the pump casing.

DANGER
LIFTING DEVICE SAFETY
• Lifting devices of adequate capacity must be used whenever they are required.
• Safe workshop practices must be applied during all assembly and maintenance work.
• Personnel must never work under suspended loads.

DANGER
DANGER
Unapproved parts, unapproved pump construction, and misapplication (for example, foot
valves, non-OEM parts, worn/damaged/corroded/obsolete parts, mis-assembly, excess
pressure, unapproved fluids, etc.) may result in serious personal injury or death. Only use
supplied equipment for its intended purpose.

WARNING
SHARP EDGES
• Before handling, identify work parts that could be hazardous due to sharp edges. All
metal components must be considered to have sharp edges.
• Pump components can have sharp or jagged edges. Handle parts carefully, to prevent
damage to slings or personal injury.

Document Name: 2001299-VTP-IOM-EN Page 6 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Safety

2.4 Intended Use


Vertical turbine pumps are built in a variety of designs and materials and for many applications/services. The
manufacturer’s IOM manual must be studied carefully and followed.
For the safety of operating personnel, note that the information contained in this manual applies only to the
fitting of genuine Floway parts and recommended spares.

DANGER
GENUINE OEM PARTS
• Genuine OEM parts and accessories are designed, tested and incorporated into the
products to help ensure they maintain continued product quality and performance in use.
• As Weir Floway does not test the parts and accessories sourced from other vendors, the
installation of such parts and accessories may adversely affect the performance and
safety features of the products.
• The failure to properly select, install or use authorized parts and accessories is
considered misuse. Damage or failure caused by misuse is not covered by our warranty.
• In addition, any modification of Weir Floway products or removal of original components
may impair the safety of these products in their use.

WARNING
SERIOUS PERSONAL INJURY AND EQUIPMENT DAMAGE
• Pump units must only be used for their intended purpose. Refer to the Certified Outline
Drawing and other contract documents for construction and application details.
• The pumps must not be operated beyond their design MAWPs (suction and discharge
sides), temperature limits and speed limits specified for the application. These limits are
dependent on the pump type, configuration and materials used. If there is any doubt
about the suitability of the product for the intended application, contact Weir Floway,
referencing the serial number.
If the conditions of service on the purchase order are going to be changed (for example liquid pumped,
temperature or duty), it is requested that the user seek the manufacturer’s written agreement before start-up.

2.5 Qualified Workers


All personnel involved in the assembly, installation, operation, maintenance, inspection, and
decommissioning of pump equipment must be qualified to carry out the work involved. If the personnel in
question do not already possess the necessary knowledge and skill, appropriate training and instruction must
be provided.
If required, the operator may engage the manufacturer/supplier to provide applicable training.
Always coordinate repair activities with operations and workplace health and safety personnel, and follow all
plant safety requirements and applicable workplace health and safety laws and regulations.

Document Name: 2001299-VTP-IOM-EN Page 7 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Safety

2.6 Markings and Approvals

WARNING
EXPLOSIVE ATMOSPHERES
Prior to installing any equipment, determine the hazardous area classification and any
other requirements applicable to the specific location and confirm all equipment has the
required certifications.
It is a legal requirement that machinery and equipment put into service within certain regions of the world
must conform to the applicable marking directives and standards such as CE marking directives covering
machinery and, where applicable, low-voltage equipment, EMC, PED, and ATEX.
Where applicable, the directives and any additional approvals cover important workplace health and safety
aspects relating to machinery and equipment and the satisfactory provision of technical documents and
workplace health and safety instructions.
To confirm the applying approvals, and if the product is CE marked, check the serial number plate markings
and the certification.

2.7 Safety Equipment for the Pump


Do not operate the pump without properly installed seal and coupling guards in place. If guards are removed
during maintenance or gland adjustment, they must be replaced prior to operating the pump.

WARNING
ROTATING PARTS
Personnel injury or illness may result from contact with rotating parts, seal leakage or spray
from the rotating shaft.

WARNING
GLAND ADJUSTMENT
During gland seal adjustment the fixed guard needs to be removed while the pump is
operational. When the guard is removed, the rotating shaft is exposed. Additional safety
management measures must be implemented to manage this specific hazard and only
suitable trained and qualified personnel must work on gland adjustment. The guard must
be replaced when adjustment is complete.
For auxiliary equipment, standard workplace health and safety precautions must be followed and appropriate
instruction manuals consulted before and during installation, operation, adjustment, and maintenance.

2.8 Fire Fighting


A number of possible emissions or leakage of hazardous substances may be possible depending on the
product being pumped. Ensure you are familiar with site and local procedures and requirements.

2.9 Emergency Procedures


Ensure you are familiar with site and local procedures and requirements. If there is an emergency, follow site
and local procedures.

Document Name: 2001299-VTP-IOM-EN Page 8 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps General Information and Description

3 General Information and Description


3.1 General Information
Floway Pump's standard practice is to ship close coupled pumps assembled. Where long pump lengths,
shipping limitations, handling limitations and headroom limitations prevent complete assembly, we will ship
the pump sub-assembled. It is the responsibility of the installer to ask for assistance should it be required to
properly assemble and install the pump.
The duration of satisfactory service obtained from the equipment, in part, depends on proper installation and
maintenance.
This instruction manual provides basic guidelines for installation, operations and maintenance of the
equipment and other safety precautions required for personnel. Due to the many variations and custom
designed units it is impossible to cover every design variation or contingency which may arise. However, the
basic information contained herein will answer most questions.

3.2 Identification
• Should questions arise concerning the pump equipment, the complete pump serial number will be
required for identification. The pump serial number is stamped on metal nameplates affixed to the
discharge head and bowl assemblies.
• The driver has a separate nameplate attached to it.
• When requesting information on the driver, both the driver serial number and pump serial number must
be provided.

3.3 General Description


The major components of vertical turbine pumps include:
• Driver
• Discharge Head Assembly
• Column Assembly (when used)
• Bowl Assembly (with strainer as applicable)
• Suction Vessel (when used)

Document Name: 2001299-VTP-IOM-EN Page 9 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps General Information and Description

Refer to Figure 3-1 for one possible variant. Pumps less than 30 feet in length are typically shipped fully
assembled and ready for installation. The drivers, couplings and strainers (when used) are shipped
separately to prevent damage.

1. Driver (electric driver


illustrated)
2. Discharge Head Assembly
3. Column Assembly
4. Bowl Assembly
5. Strainer

Figure 3-1: Major VTP Components

Document Name: 2001299-VTP-IOM-EN Page 10 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps General Information and Description

3.3.1 Drivers
A variety of drivers can be used; however, electric motors are most common. In this manual, electric motor
drivers are grouped into two categories:
1. Hollow Shaft Drivers: where the pump shaft extends through a tube in the center of the motor shaft and
is connected to the driver by a clutch assembly at the top of the driver.
2. Solid Shaft Drivers: where the motor shaft is solid and projects below the driver mounting base. This
type of driver requires an adjustable coupling to connect to the pump.

3.3.2 Discharge Head Assembly


• The discharge head supports the driver, column, and bowl assemblies in addition to providing a
discharge connection (the type VU discharge connection is located on one of the column pipe sections
below the discharge head).
• A shaft sealing arrangement is located in the discharge head to seal the rotating shaft where it passes
from the stationary housing (liquid chamber). Typically, the shaft seal is either a mechanical seal
assembly or a packing box.

3.3.3 Column Assemblies


Column assemblies are of two basic types, either of which can be used on vertical turbine pumps:
1. Open Lineshaft Construction: utilizes the liquid being pumped to lubricate the lineshaft bearings.
2. Enclosed Lineshaft Construction: has an enclosing tube around the lineshaft and utilizes oil, grease or
injected liquid (usually clean water) to lubricate the lineshaft bearings (not used on barrel pumps).
Column assemblies consist of the following:
• Column Pipe: which connects the bowl assembly to the discharge head and carries the pumped liquid
to the discharge head. Column pipe is either threaded or flanged.
• Shaft: which connects the bowl shaft to the driver; and may contain bearings if required for the
particular unit.
• Enclosing Tube (if applicable): surrounds the lineshaft to contain the supplied lubrication.

NOTICE
Some units do not require a column assembly, as the bowl assembly is connected directly
to the discharge head.

3.3.4 Bowl Assemblies


The bowl assembly consists of the following:
• Impellers rigidly mounted on the bowl shaft which rotate and impart energy to the fluid.
• Bowls to contain the increased pressure and direct the fluid.
• Suction bell or case which directs the fluid into the first stage impeller.
• Bearings located in the suction bell (or case) and each bowl.
A separate instruction manual is available which provides construction details and repair instructions for
Floway bowl assemblies.

3.3.5 Suction Vessel


The suction vessel may consist of a barrel with or without suction fitting, to connect to customers piping
arrangement, or a storage tank with suitable opening to mount the pump.
Whatever the arrangement may be, it must provide:
• Adequate support for the unit
• A means of supplying the pump with liquid

Document Name: 2001299-VTP-IOM-EN Page 11 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Pre-installation

4 Pre-installation
DANGER
LIFTING DEVICE SAFETY
• Use mechanical lifting devices to lift heavy or awkward components.
• Lifting devices must be in good condition, certified, and tagged.
• Lifting devices of adequate capacity must be used whenever they are required.
• Personnel must never work under suspended loads.

DANGER
LIFTING POINT SAFETY
Check that the lifting lugs are in suitable condition for lifting, before lifting pump parts.

4.1 Receiving and Unloading


When receiving the shipment, extreme care must be taken while unloading.
• Use a forklift or crane to unload the equipment.
• Do not drop the unit, or any parts, as damage can cause trouble in assembly and operation of the units.
• Inspect the unit for signs of transit damage before beginning to uncrate or placing in storage. If damage
is evident notify the local transporting company agent before uncrating and file a claim with the agent.

4.2 Storage

NOTICE
These provisions are applicable to Weir Floway pump components only. For the
appropriate storage procedures for non-Weir items (for example, drivers, mechanical
seals, auxiliary equipment, etc.), refer to specific requirements from the manufacturer.
• If the unit is to be stored prior to installation, carefully select a storage space where the unit will not be
subjected to excess moisture, extreme weather conditions, corrosive fumes, or other harmful conditions.
• Carefully inspect the unit and clean the rust spots on the machined surfaces with a fine emery cloth.
• Coat machined surfaces with a rust preventative.
• Protect the pump from any dust, dirt, or debris from entering the unit. Wrap all openings with a heavy
gauge polyethylene and tape tightly to seal.
• If the unit is stored for a long period of time it should be periodically inspected and cleaned as required.
• Contact the factory for special long term storage (greater than 4 months) requirements for the unit
supplied.

Document Name: 2001299-VTP-IOM-EN Page 12 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Pre-installation

4.3 Uncrating and Cleaning


If the unit appears undamaged proceed to uncrate following the instructions given below:

CAUTION
DEFLECTION OF THE PUMP
To prevent deflection of the pump components, take appropriate precaution to prevent the
weight of the pump from resting on the suction bell or case, when lifting to vertical position.
Refer to Figure 4-1 on page 15.
• Clean all the parts of any dirt, packing material or other foreign matter.
• Flush the pump inside and outside with clean water or a fluid compatible with pumpage. If the pump is
for potable water, a lightly chlorinated flush may be recommended.
• Clean all machined surfaces as these are coated with a rust preventative before shipment, which must
be removed.
• Remove any rust spots found on the machined surfaces with a fine emery cloth.
• Clean all threaded connections and any accessory equipment.
NOTICE
Parts and accessories may be placed inside shipping containers or attached to skids in
individual packages. Inspect all containers, crates and skids for attached parts before
discarding.

4.4 Lifting

DANGER
LIFTING DEVICE SAFETY
• Use mechanical lifting devices to lift heavy or awkward components.
• Lifting devices must be in good condition, certified, and tagged.
• Lifting devices of adequate capacity must be used whenever they are required.
• Personnel must never work under suspended loads.

DANGER
LIFTING POINT SAFETY
Check that the lifting lugs are in suitable condition for lifting, before lifting pump parts.

WARNING
LIFTING EXPERIENCE
All lifting and rigging must be performed by qualified and experienced personnel who are
familiar with safe lifting practices and requirements. A lifting plan should be established and
followed to ensure safe lifting of all equipment.

WARNING
PERSONAL INJURY
To avoid personal injury, all components and assemblies greater than 30 lbs. (14 kg)
should be lifted using mechanical methods.

Document Name: 2001299-VTP-IOM-EN Page 13 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Pre-installation

WARNING
LIFTING DRIVERS AND AUXILIARY EQUIPMENT
Refer to the manufacturer’s instruction manual for proper lifting techniques of all drivers
and auxiliary equipment. Driver lifting locations must only be used to lift the driver. Do not
use the driver lifting locations to lift the assembled pump and driver.

4.4.1 Lifting Pump Components and Pump Assemblies


Refer to the certified outline drawing for approximate pump assembly weights.
Pump components and assemblies must only be lifted from the appropriate locations. If there is any doubt
regarding proper lifting methods and locations, contact your nearest manufacturer’s representative.

WARNING
PERSONAL INJURY AND EQUIPMENT DAMAGE
Never lift any assemble by the bowl shaft or lineshaft. This can result in damage to the
shaft and personal injury.
• Cans/Barrels must be lifted using appropriate lifting devices attached to the mounting plate.
• Discharge heads are fitted with lifting lugs suitable to support the entire weight of the pump. Typically
two or more lifting lugs are supplied, a minimum two point lifting method is required (refer to Figure 4-2
on page 16 for fabricated heads and Figure 4-3 on page 16 for cast heads).
• Column and bowl assemblies must be lifted using an appropriate clamping fixture. The fixture must
positively lock to the item being lifted and have adequate strength to support the assembly’s weight. A
common fixture design employs beams and threaded rods that can be fastened around the assembly
(refer to Figure 4-4 on page 16). When clamping to threaded column, the upper column coupling must
be fully installed to provide a stop for the lifting clamp placed below the coupling. If the column is
supplied with optional lifting lugs, those may be used to lift the assembly.
WARNING
PERSONNEL INJURY
• Clamping fixtures that do not positively lock to the assembly being lifted may come loose
and cause personal injury. Always ensure the clamping fixture is of an appropriate design
to support the load and has secure means to lock onto the assembly being lifted.
• Do not lift bowl assemblies by placing lifting devices through the flange bolt holes, the
cast bowl flange holes may break through and result in dropping the load and personal
injury.
Lift devices (straps, chains, etc.) attached to the pump must not exceed a 45 degree angle to the vertical
position. Exceeding this angle could overload the lifting location (refer to Figure 4-2 on page 16).
When lifting an assembled pump, it must be supported at minimally two locations. When lifting to the vertical
position, use the discharge head lifting lug locations to lift the pump assembly (refer to Figure 4-1 on page
15). For pump units over 40 ft in length, the pump shall be assembled during installation vertically in place
over the mounting location.
If the unit is supplied with a separate motor stand (that is, a component bolted between the driver and
discharge head), do not lift the entire pump unit from the motor stand. The motor stand lifting lugs are for
lifting the motor stand assembly only.

Document Name: 2001299-VTP-IOM-EN Page 14 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Pre-installation

≤ 40 ft

Figure 4-1: Lifting Pumps from Horizontal to Vertical Position

(for pump lengths up to 40 feet)

Document Name: 2001299-VTP-IOM-EN Page 15 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Pre-installation

Max. lift angle


from vertical Lifting devices must pass
shall not through center opening of
exceed 45° top plate and wrap around
lifting lugs cast into the
vertical ribs

Figure 4-2: Fabricated Head Lifting Figure 4-3: Cast Head Lifting

Figure 4-4: Typical Clamping Fixture

Document Name: 2001299-VTP-IOM-EN Page 16 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Pre-installation

4.5 Installation Equipment and Tools


Do not attempt installation without proper equipment. The following list covers the major equipment and tools
required for installation:
1. Mobile crane capable of hoisting and lowering the weight of the pump or motor (refer to Figure 4-1 on
page 15).
2. Cable sling for attaching to the pump and motor lifting eyes (refer to Figure 4-1 on page 15).
3. Ordinary hand tools such as end wrenches, socket set, screw drivers, allen wrenches, etc.
4. Wire brush, scraper and fine emery cloth.
5. Thread sealing compound, light machinery oil and a thread lubricant.
6. Tank or barrel flange gasket and flange bolts & nuts (Can Pumps).

4.6 Pre-installation Check List


For proper and timely installation, complete the following checks before starting the installation procedure:
1. Check the pump serial number with the number on the packing slip to ensure that the correct unit is
installed.
2. Check the driver horsepower and speed indicated on the driver nameplate and the horsepower and
speed indicated on the pump nameplate (located on the discharge head) to ensure they agree.

NOTICE
A slight difference between the nominal speeds (RPM) shown on the driver and pump
nameplates are permissible. However, the difference must not be more than 1% to 2%.

3. For electric motor driven units, make sure the voltage and frequency on the motor nameplate agree with
the service available. Also, ensure the horsepower/voltage rating of the control panel, starter, and/or
VFD agree with the horsepower/voltage rating of the motor.
4. Check the depth of the sump or barrel against the pump length to ensure there is no interference.
5. Check bottom of the pump. Sleeve-type mechanical seal units shipped completely assembled are
supplied with a shaft locking plate which must be removed and replaced with a pipe plug (plug is
required only on grease packed suction bearings) prior to installation (refer to Figure 4-5 on page 18).

Document Name: 2001299-VTP-IOM-EN Page 17 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Pre-installation

Figure 4-5: Shaft Locking Plate

NOTICE
Shaft type seals are shipped separately and are not installed in the seal housing. A tag is
supplied indicating that the seal is not installed. Lock down plate is not supplied for units
which have no seals installed.

6. Check the proposed minimum liquid level in the sump against the pump length; the bottom stage of the
pump must be submerged at all times and satisfy the minimum required submergence and NPSHR.
7. Clean the sump and piping system before installing the pump.
8. Check the installation equipment to ensure it can safely handle the equipment.
9. Check the pump connections (bolts, nuts, etc.) for tightness. These are properly tightened before
leaving the factory. However, some connections can become loose during transit.
10. For hollow shaft drivers, check the clutch size against the shaft size that must pass through the clutch.
Sometimes the shaft size coming through the discharge head is different from the shaft size going
through the driver (ensure the clutch is checked against to correct shaft).
11. For solid shaft drivers, check the motor shaft size against the driver half coupling bore size. Also check
all keys.

Document Name: 2001299-VTP-IOM-EN Page 18 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

5 Installation

WARNING
PERSONAL INJURY
The pump must be installed, operated and maintained only by personnel who are trained
and have sufficient knowledge about the hazards that may occur during such work.

5.1 General
This is a precision piece of equipment and must be treated as such. Proper installation is necessary to obtain
maximum service life from the pump. To ensure proper alignment, three items are very important during
installation:
1. All machined mating surfaces (such as the mating flanges of the pump and driver) must be clean and
free of burrs and nicks. These surfaces must be cleaned thoroughly with scraper, wire brush and emery
cloth if necessary, and any nicks or burrs must be removed with a fine file.
2. Exterior strain must not be transmitted to the pump. The most common cause of trouble in this respect is
forcing the piping to mate with the pump. It is recommended that flexible connectors are installed in the
piping adjacent to the pump when possible. This is especially critical on type VU (underground
discharge) units where the discharge could be several feet below the supporting structure and a
relatively small strain can cause misalignment.
3. All threads must be checked for damage and repaired if necessary. If filing is required, remove the part
from the pump if possible, or arrange a rag to catch all the filings so that they do not fall into other parts
of the pump. Clean all threads with wire brush and cleaning solvent. Ends of shafts must be cleaned and
any burrs removed since alignment depends on the shaft ends butting squarely. Lubricate all screwed
connections with a thread lubricant suitable for steel. Use an anti-galling compound such as !
“Never- Seez” on stainless and monel mating threads.

CAUTION
EQUIPMENT DAMAGE
Apply thread lubricant sparingly to male shaft threads only when making up shaft
connections. Do not allow excess lubricant to get in between the ends of the shaft.

5.2 Foundation
• The foundation may be constructed out of any material which can afford permanent, rigid support to the
discharge head and can absorb the expected stress that may be encountered during service.
• It is recommended that concrete foundations have anchor bolts installed in sleeves twice the diameter of
the bolt to allow alignment with the holes in the mounting plate as illustrated in Figure 5-1 on page 20,
however, sleeves are not required and anchor bolts may be directly installed in concrete.

Document Name: 2001299-VTP-IOM-EN Page 19 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

"D"
1
2 1. Anchor Bolt (diameter “D”)
8
2. Nut
3 3. Grout
4
4. Floor
5. 4 x "D" Square Plate
6. 2 x "D" Sleeve Diameter
7. Opening for Pump
8. Mounting Plate (sole plate,
7 discharge head, or barrel plate)
10 x "D"

6
5
1 1/2" min

1/4" fillet welds


(all around)
Figure 5-1: Recommended Anchor Bolt Arrangement

5.3 Suction Barrel Installation


If a suction barrel has been furnished with the pump it must be mounted to a firm foundation. The suction
vessel must provide permanent, rigid support to the pump and motor. It is recommended that concrete
foundations have anchor bolts installed in sleeves twice the diameter of the bolt to allow alignment with the
holes in the mounting plate, however, sleeves are not required and anchor bolts may be directly installed in
concrete. Level the pump mounting surface, then grout and anchor in place.

5.4 Vertical Turbine Pump Installation for Wet Pit (Type VS1)

DANGER
LIFTING DEVICE SAFETY
• Use mechanical lifting devices to lift heavy or awkward components.
• Lifting devices must be in good condition, certified, and tagged.
• Lifting devices of adequate capacity must be used whenever they are required.
• Personnel must never work under suspended loads.

DANGER
LIFTING POINT SAFETY
Check lifting lugs are in suitable condition for lifting, before lifting pump parts.

CAUTION
DAMAGE TO THE PUMP
Clean the sump and piping of all abrasive particles and loose debris before starting
installation, to avoid any damage to the pump.
1. Position the lifting equipment so it will center over the foundation opening.
2. If a soleplate is used, level the mounting surface then grout and anchor in place.

Document Name: 2001299-VTP-IOM-EN Page 20 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

3. Clean the pump discharge flange.

NOTICE
• All machined surfaces are coated with rust preventative prior to shipment. This must be
completely removed along with any paint overspray or rust which might be on the
machined faces.
• The faces must be scraped and wire brushed first.
• Use fine emery cloth to remove any stubborn spots.

CAUTION
EQUIPMENT DAMAGE
Be particularly careful not to damage any piping which may extend down, along the column
and/or bowl assembly. This piping (when used) must not be crushed. If damaged, remove
and replace it.
4. Lift the pump, mount the strainer if required and lower slowly into the sump. Guide the pump as it is
being lowered and watch for any obstructions or binding of the pump. Stop lowering the unit when still a
few inches off the foundation.
5. Rotate the pump until the discharge flange faces the proper direction for alignment with piping. Align the
anchor bolt holes.
6. Slowly lower the pump onto the foundation (or sole plate if applicable).
7. Install the mounting bolts or nuts. Do not tighten at this stage.

CAUTION
EQUIPMENT DAMAGE
Excessive nozzle loads must not be imposed on the pump. All piping must be carefully
aligned and supported to prevent excessive nozzle loads.

CAUTION
EQUIPMENT DAMAGE
It is strongly recommended that flexible connectors (dresser couplings or equivalent) be
installed in the piping immediately adjacent to the pump.
8. Connect the system piping to the pump, if required, shift the pump slightly on the foundation to facilitate
alignment.

WARNING
PERSONNEL INJURY
• Always ensure proper tightening of all piping connections to the pump.
• Ensure the required gaskets and/or o-rings are installed.
• Poor connections may result in leakage.
• Leakage of hazardous or high pressure pumpage may result in personnel injury.
9. Tighten the discharge flange bolting. Ensure that the flanges mate face to face without applying
excessive force.
10. Tighten the mounting bolts (grout and anchor if no sole plate).

Document Name: 2001299-VTP-IOM-EN Page 21 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

5.5 Vertical Turbine Can Pump Installation (Type VS6)

DANGER
LIFTING DEVICE SAFETY
• Use mechanical lifting devices to lift heavy or awkward components.
• Lifting devices must be in good condition, certified, and tagged.
• Lifting devices of adequate capacity must be used whenever they are required.
• Personnel must never work under suspended loads.

DANGER
LIFTING POINT SAFETY
Check lifting lugs are in suitable condition for lifting, before lifting pump parts.
1. Position the lifting equipment so it will center over the suction vessel mounting flange (refer to “Suction
Barrel Installation” on page 20).

CAUTION
DAMAGE TO THE PUMP
Clean the suction vessel and piping of all abrasive particles and loose debris before
installation, to avoid any damage to the pump.
2. Clean the suction vessel mounting flange, oil lightly, and position the gasket. Clean the pump mounting
flange and oil lightly.

NOTICE
• All machined surfaces are coated with rust preventative prior to shipment. This must be
completely removed along with any paint overspray or rust which might be there on the
machined faces.
• The faces must be scraped and wire brushed first.
• Use fine emery cloth to remove any stubborn spots.

NOTICE
• Type VC can pumps have the suction nozzle located on the discharge head.
• Type AF, CF, VF and VFR can pumps have the suction nozzle located on the suction
vessel.
3. Clean the pump discharge flange (and suction flange wherever applicable).

CAUTION
EQUIPMENT DAMAGE
Be particularly careful not to damage any piping which may extend down along the column
and/or bowl assembly. This piping (when used) must not be crushed. If damaged, remove
and replace it.
4. Lift the pump, mount the strainer if required and lower slowly into the suction vessel. Guide the pump as
it is being lowered and watch for any obstructions or binding of the pump. Stop lowering the unit when
still a few inches off the mounting flange.
5. Rotate the pump until the discharge flange faces the proper direction for alignment with piping. Align the
mounting flange bolt holes.

Document Name: 2001299-VTP-IOM-EN Page 22 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

NOTICE
• Type VC discharge heads have both suction and discharge flanges. Therefore, it is
important to make sure that the suction piping is connected to the suction side of the
pump.
• A flow arrow is located on the side of the suction pipe to help identify the correct
orientation.
• Figure 5-2 on page 23 is provided to enable field identification in case the flow arrow is
not visible.
6. Check the mounting flange gasket to ensure it is in the correct position. Some pumps may be supplied
with O-rings in lieu of a gasket.
7. Slowly lower the pump onto the mounting flange.
8. Install the mounting bolts or nuts. Do not tighten at this stage.
3

1. Discharge Connects to Inner Pipe


Located in Center of Head
2. Suction Connects to Outer Annulus
3. Driver Mounting Flange
2 1

Suction Discharge

Figure 5-2: Suction and Discharge Identification - Type VC Discharge Head

CAUTION
EQUIPMENT DAMAGE
Excessive nozzle loads must not be imposed on the pump. All piping must be carefully
aligned and supported to prevent excessive nozzle loads.

CAUTION
EQUIPMENT DAMAGE
It is strongly recommended that flexible connectors (dresser couplings or equivalent) be
installed in the piping immediately adjacent to the pump.
9. Connect the system piping to the pump, if required, shift the pump slightly on the mounting flange to
facilitate alignment.

Document Name: 2001299-VTP-IOM-EN Page 23 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

WARNING
PERSONNEL INJURY
• Always ensure proper tightening of all piping connections to the pump.
• Ensure the required gaskets and/or o-rings are installed.
• Poor connections may result in leakage.
• Leakage of hazardous or high pressure pumpage may result in personnel injury.
10. Tighten the discharge (and suction, if applicable) flange bolting. Ensure that the flanges mate face to
face without applying excessive force.
11. Tighten the mounting flange bolting.

5.6 Hollow Shaft Driver Installation

DANGER
LIFTING DEVICE SAFETY
• Use mechanical lifting devices to lift heavy or awkward components.
• Lifting devices must be in good condition, certified, and tagged.
• Lifting devices of adequate capacity must be used whenever they are required.
• Personnel must never work under suspended loads.

DANGER
LIFTING POINT SAFETY
Check lifting lugs are in suitable condition for lifting, before lifting pump parts.

WARNING
CONSULT DRIVER IOM MANUAL
Consult the driver IOM for all safety, installation, operation, maintenance and other product
information.

NOTICE
• All machined surfaces are coated with rust preventative prior to shipment. This must be
completely removed along with any paint overspray or rust which might be there on the
machined faces.
• The faces must be scraped and wire brushed first.
• Use fine emery cloth to remove any stubborn spots.
1. Clean the driver mounting flange on the discharge head and remove any burrs or nicks on the register
and mounting face. Oil lightly.
2. Remove the driver clutch.
3. Clean the driver mounting flange and remove any burrs or nicks on the register and mounting flange. Oil
lightly.
4. Some electric motors are supplied with a lower guide bushing installed at the bottom of the motor to
stabilize the shaft at this point (also called a steady bushing). Some motor manufacturers mount this
guide bushing before shipping while others will ship the guide bushing separately with instructions for
field mounting. If applicable, mount the guide bushing to the motor (refer Figure 5-3 on page 25).

Document Name: 2001299-VTP-IOM-EN Page 24 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

Lower guide bushing located


inside holllow shaft at bottom
of motor
Figure 5-3: Motor Guide Bushing Location

5. Raise and center the driver over the pump.


6. Lower carefully until about 1/4" above mounting flange.
7. Rotate the driver until the junction box on the motor or the input shaft on the gear drive is in correct
position.
8. Align bolt holes and insert bolts.
9. Lower carefully into place ensuring that the driver and pump registers mate correctly.
10. Tighten the mounting bolts.
11. Refer to the driver manufacturer’s instruction manual for specific product requirements regarding
installation and start-up procedures.

WARNING
PERSONNEL INJURY
Do not touch the rotating elements with hands to establish the direction of rotation. Visually
confirm the direction of rotation.

CAUTION
DAMAGE TO THE PUMP
Always check rotation before connecting the driver to the pump as reverse rotation while
the pump is connected can cause extensive damage to the pump.
12. Prior to installation of headshaft, check electric drivers for rotation. Establish electrical connections and
jog the motor briefly to check the rotation. Driver must rotate in counter clockwise direction when viewed
from the top end of the motor.
To change the direction of rotation on a three phase motor, interchange any two line leads.
13. Install the mechanical seal at this time, if the pump is so equipped and the mechanical seal was
shipped uninstalled. Refer to “Mechanical Seal” on page 33 for further details.

Document Name: 2001299-VTP-IOM-EN Page 25 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

14. Clean all the shaft threads (on top shaft and both ends of headshaft). Try the lineshaft coupling and
headshaft nut on their respective threads. These must thread on by hand. If not, clean up the threads
with a fine three cornered file. Check the ends of the shaft where they butt inside the lineshaft coupling.
Ends must be square and clean. Fit the gib key to both motor clutch and headshaft. The key must slide
smoothly in both keyways.

1
6
2

3 1. Headshaft
2. Headshaft Nut (adjusting nut)
4 3. Gib Key
5 4. Cap Screw
5. Clutch
6. Headshaft Nut Lock Screw

Figure 5-4: Hollow Shaft Driver Clutch

NOTICE
For units equipped with one piece headshaft (no lineshaft coupling between driver and
pump) steps 15 and 16 will not be applicable.

CAUTION
EQUIPMENT DAMAGE
Apply thread lubricant only to male shaft threads sparingly to avoid buildup between ends
of shaft which can cause misalignment.
15. Lubricate the top shaft threads and thread (left hand threads) the lineshaft coupling half way onto the top
shaft.
16. Lubricate the headshaft threads and lower the headshaft carefully down through the driver, and thread
into the lineshaft coupling. Shafts must butt against each other.

NOTICE
Headshaft must stand centered (long shafts may lean slightly from own weight; however,
they can be centered without effort) in the driver hollow shaft. If not, check the driver
mounting flange for improper mounting and re-clean the shaft ends coupled inside the
discharge head.
17. Install the clutch on the driver and ensure that it fits down properly.
18. Install pre-fitted gib key in the clutch and the shaft.
19. Thread adjusting the nut down (right hand threads) on the shaft until it bears against the clutch.
20. Refer to “Impeller Adjustment - General” on page 29 for impeller adjustment.
21. Adjust mechanical seal after adjusting impellers.

Document Name: 2001299-VTP-IOM-EN Page 26 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

5.7 Solid Shaft Driver Installation

DANGER
LIFTING DEVICE SAFETY
• Use mechanical lifting devices to lift heavy or awkward components.
• Lifting devices must be in good condition, certified, and tagged.
• Lifting devices of adequate capacity must be used whenever they are required.
• Personnel must never work under suspended loads.

DANGER
LIFTING POINT SAFETY
Check lifting lugs are in suitable condition for lifting, before lifting pump parts.

WARNING
CONSULT DRIVER IOM MANUAL
Consult the driver IOM for all safety, installation, operation, maintenance and other product
information.

NOTICE
• All machined surfaces are coated with rust preventative prior to shipment. This must be
completely removed along with any paint overspray or rust which might be there on the
machined faces.
• The faces must be scraped and wire brushed first.
• Use fine emery cloth to remove any stubborn spots.
1. Clean the driver mounting flange on the discharge head and remove any burrs or nicks on the register
and mounting face. Oil lightly.
2. Clean the headshaft threads. Lubricate the threads and try installing the adjusting nut (it should thread
on by hand easily, if not, clean up the threads with a fine three cornered file).
3. Clean the driver mounting flange and remove any burrs or nicks on the register and mounting flange. Oil
lightly.
a. Check the shaft diameter and projection against coupling and schematic provided.
b. If the dimensions are correct proceed to step 4.
c. If the dimensions are incorrect contact the nearest manufacturer's representative for assistance.
4. Install the driver half coupling on the driver shaft (refer to Figure 5-5 on page 28 and Figure 12-1 on
page 58 for coupling illustrations).
a. Place the straight key into the keyway. Ensure that the key is up far enough to clear the circular
groove cut around the shaft, near the end. Hand press the key into groove.
b. Slide the driver half coupling onto the motor shaft far enough to insert the split circular thrust ring into
the shaft groove. The coupling must be a tight fit to the driver shaft but not interference fit.
c. Install split circular thrust ring in the shaft groove. When properly positioned the motor half coupling
will slide down over the split circular key and hold it in position (refer to Figure 5-5 on page 28).

Document Name: 2001299-VTP-IOM-EN Page 27 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

1. Driver Shaft
2. Square Key
3. Split Circular Thrust Ring
4. Driver Half Coupling (fits over split
circular thrust ring and holds in place)
2
4

Figure 5-5: Driver Half Coupling Correctly Positioned

5. Install the mechanical seal at this time if the pump is so equipped and the mechanical seal was shipped
uninstalled. Refer to “Mechanical Seal” on page 33 for further details.
6. Install the pump half coupling onto the headshaft:
a. Slide the pump half coupling onto the shaft.
b. Install the key and push down to clear the threads.
c. Thread the adjusting nut (right hand threads) onto the shaft until the end of the shaft is even with the
top of the adjusting nut.
7. Center the motor over the pump and rotate to align the mounting holes and properly align the power
conduit box. For gear drives, rotate the input shaft into desired position.
8. Lower the driver carefully into place ensuring that the driver and pump registers mate correctly. Check
the shaft gap between the motor and pump shaft against the schematic provided.

CAUTION
EQUIPMENT DAMAGE
• If the discharge head or motor stand was supplied with jacking screws, the driver must be
manually aligned to the pump shaft prior to bolting it down. Failure to align the driver may
result in equipment damage. The driver shaft must be aligned to within 0.002" max. TIR
with respect to the precision machined ID on the pump's driver mounting plate.
• If jacking screws are not supplied, manual driver alignment is not required.
9. Bolt the driver to the discharge head.
10. Refer to the driver manufacturer’s instruction manual for specific product requirements regarding
installation and start-up procedures.

WARNING
PERSONNEL INJURY
Do not touch the rotating elements with hands to establish the direction of rotation. Visually
confirm the direction of rotation.

Document Name: 2001299-VTP-IOM-EN Page 28 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

CAUTION
DAMAGE TO THE PUMP
• Before jogging the motor make sure the coupling halves are not touching and the motor
shaft end is sufficiently clear of the pump shaft and adjusting nut, and the driver can
rotate freely without rotating the pump. The driver half coupling must be in proper position
as shown in Figure 5-5 on page 28 so that the split circular thrust ring does not come out.
• Always check rotation before connecting the driver to the pump as reverse rotation while
the pump is connected can cause extensive damage to the pump.
11. Check the electric driver for rotation at this time. Establish electrical connections and run the motor
briefly to check the rotation. Driver must rotate in counter clockwise direction when viewed from the top
end of the motor.
a. To change the direction of rotation on a three phase motor, interchange any two line leads.
b. To change direction of rotation on a two phase motor, interchange the leads of either phase.
12. For pumps using a spacer type coupling, bolt the spacer to the driver half coupling.
13. Thread the adjusting nut up until there is 1/8" gap between the nut and the spacer or driver half coupling
(refer to Figure 5-7 on page 32).

NOTICE
Adjusting nuts have drilled holes on the outside diameter for inserting handle of hex wrench
or round bar to facilitate adjustment.

14. Refer to “Impeller Adjustment - General” on page 29 for impeller adjustment.


15. Adjust mechanical seal after adjusting the impellers (refer to “Mechanical Seal” on page 33).

5.8 Impeller Adjustment - General


• Proper impeller adjustment positions the impeller inside the bowl assembly for maximum performance.
• The impellers must be raised slightly to prevent dragging on the bowls.
DANGER
PERSONNEL INJURY AND EQUIPMENT DAMAGE
Never operate the pump without properly adjusting the impellers. Operating the pump
without proper adjustment could result in catastrophic damage to the equipment and injury
to personnel from projectiles.
Impellers are of two basic types: enclosed and semi-open (also referred to as semi-enclosed). The type and
size of impeller, as well as the application, determine what the proper impeller adjustment must be. The type
of impellers installed in the pump can be determined from the pump nameplate or packing slip. If the second
letter of the pump type is K, it is an enclosed impeller and if the letter is O, then it is a semi-open impeller.
Hence DKM indicates enclosed impellers, while DOM indicates semi-open impellers (refer to Figure 5-6 on
page 30).

Document Name: 2001299-VTP-IOM-EN Page 29 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

Enclosed Type Impeller Semi-open Type Impeller

Figure 5-6: Types of Impellers

CAUTION
EQUIPMENT DAMAGE
The impellers must be completely down against the bowl seat when starting the impeller
adjustment. All dimensions and instructions given above are based on the assumption that
the impellers are seated. When pumps are subjected to suction pressure, the pressure
acting against the shaft tends to raise it. If the suction pressure is great enough it can raise
the shaft. Make sure the shaft is down when starting to adjust the impellers.
1. Enclosed Impellers: for proper impeller adjustment refer to the pump nameplate on the discharge head.
2. Semi-open Impellers: the adjustment of semi-open impellers is more critical than that of enclosed
impellers. A small change in the impeller setting impacts the pump performance considerably (refer to
Figure 7-1 on page 43).
If after making the below adjustment the pump does not deliver its rated capacity, the impellers can be
lowered one step at a time until the lowest possible adjustment is achieved without the impellers
dragging.
On the other hand, if the impellers appear to be dragging after the initial adjustment the unit must be
stopped and the impellers raised one step. Dragging the impellers will increase the pump power
considerably and can usually be heard and felt as increased vibration.

CAUTION
EQUIPMENT DAMAGE
Excessively dragging impellers during operation will result in equipment damage. If
dragging occurs, stop the pump and increase the impeller setting.

NOTICE
If semi-open impellers are raised and then adjusted down, a slight increase in the power
required will be noted due to the increased delivery of the pump. Do not confuse this with
the marked power increase when impellers are lowered enough to drag.
• For optimum performance the impeller must run within a few thousandths of an inch of the bowl seat.
The exact shaft adjustment varies according to variables of each installation.
• For close coupled units, a general rule of 0.015" plus 0.005" of adjustment for each 100 feet of
discharge head produced by the pump, plus 0.005" adjustment for each 10 feet of column assembly
will provide close to ideal adjustment.

Document Name: 2001299-VTP-IOM-EN Page 30 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

• Use the highest discharge head that the unit is expected to operate against to calculate the impeller
adjustment value.
• For example: a pump designed to operate at 400 feet discharge head but will also be operated
against a closed valve for short intervals at which time it will produce 500 feet of pump pressure,
therefore 5 x 0.005" = 0.025". For a unit with 20 feet of column assembly, the calculation would be: !
2 x 0.005 = 0.010". The initial adjustment would be 0.025" + 0.010" + 0.015" = 0.050".
Refer to Table 5-1 to determine how many turns or fraction of a turn is necessary for the shaft diameter
supplied. For example: a 1 11/16 - 10" TPI shaft will provide 0.100" adjustment per turn of nut. Therefore !
1/2 turn of the nut will provide the required 0.050" impeller setting in the previous example.

Shaft Diameter Headshaft Nut (thread/inch) Inches per Full Turn of Adjusting Nut

3/4" 16 TPI - R.H. 0.063


1" 14 TPI - R.H. 0.071
1 1/4" 12 TPI - R.H. 0.083
1 1/2" 12 TPI - R.H. 0.083
1 11/16" 10 TPI - R.H. 0.100
1 15/16" 12 TPI - R.H. 0.083
2 1/4" 12 TPI - R.H. 0.083
2 7/16" 12 TPI - R.H. 0.083
2 11/16" 12 TPI - R.H. 0.083
2 15/16" 10 TPI - R.H. 0.100
3 3/16" 8 TPI - R.H. 0.125
3 7/16" 8 TPI - R.H. 0.125
Table 5-1: Shaft Diameter Turns

5.9 Impeller Adjustment - Hollow Shaft Driver


Impeller adjustment when using hollow shaft driver is accomplished at the top of the driver by the following
procedure.
1. Remove the driver canopy.
2. Install the headshaft as outlined in “Hollow Shaft Driver Installation” on page 24 if not already in place.
3. Install the driver clutch as per the driver instruction manual and bolt into place.
4. Install the gib key, ensuring the top of the gib key pushes down below the top of the clutch. To prevent
interference with the headshaft nut, fit the gib key to both the motor clutch and the headshaft. The key
must slide in smoothly in the keyway.
5. Check the shaft position; the impellers must be fully seated against the bowls prior to adjusting the
impellers.
6. Thread the headshaft nut down (right hand threads) until the impellers are lifted off their seat and the
shaft rotates freely. When semi-open impellers are used, the correct determination of the point where
the impellers just barely clear their seat is very important for proper adjustment.
7. Adjust the impellers as outlined in “Impeller Adjustment - General” on page 29.
8. Lock the headshaft nut with the lockscrew inserted down through the holes in the headshaft nut and
threaded into the driver clutch.

CAUTION
DAMAGE TO THE PUMP AND THE DRIVER
Always ensure the headshaft nut is locked before starting the driver to avoid damage to the
pump and the driver.

Document Name: 2001299-VTP-IOM-EN Page 31 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

5.10 Impeller Adjustment - Solid Shaft Driver (thrust bearing in driver)


Impeller adjustment when using a solid shaft driver (with thrust bearing in driver) is accomplished with the
adjustable flanged coupling located below the driver.

13 1. Driver Half Coupling


1 2. Spacer Bolts
12 3. Lock Nuts
2 4. Coupling Bolts
11
5. Headshaft
3 6. Dowel Pin
10 7. Pump Key
8. Pump Half Coupling
9. Adjusting Nut
10. Spacer (optional)
11. Split Circular Thrust Ring
3 12. Driver Key
13. Driver Shaft
9

8
7
Measure impeller adjustment
4 here before tightening
6 coupling bolts
5

Figure 5-7: Adjustable Flanged Coupling for Solid Shaft Drivers

(illustrated with spacer)

5.10.1 Adjustable Flanged Couplings


1. Assemble the coupling on the pump and the driver as outlined in “Solid Shaft Driver Installation” on
page 27.
2. Back off the adjusting nut up the shaft (threads are right hand) until the nut bears firmly against the
spacer or driver shaft and the headshaft does not move down. This ensures that the impellers are all the
way down against their seat and in proper position for starting the adjustment.
3. Thread the adjusting nut down until proper impeller adjustment as outlined in “Impeller Adjustment -
General” on page 29 can be measured between the adjusting nut and spacer or driver half coupling as
shown in Figure 5-7 on page 32.
4. Slide the pump half coupling up the shaft and align the adjusting nut bolt holes with those in the pump
half coupling. Rotate the driver shaft until bolts can be inserted and tightened.
5. Tighten all the bolts. This will raise the impellers to correct operating position.

5.11 Impeller Adjustment - Solid Shaft Driver (thrust bearing in pump)


Impeller adjustment when using a solid shaft driver (with thrust bearing in pump) is accomplished using the
adjusting nut located on top of the pump’s thrust bearing.
1. Install the thrust bearing drive key, ensuring the top of the key pushes down below the top of the thrust
bearing clutch. To prevent interference with the adjusting nut, fit the key to both the clutch and the top
lineshaft. The key must slide in smoothly in the keyway.
2. Check the shaft position; the impellers must be fully seated against the bowls prior to adjusting the
impellers.
3. Thread the adjusting nut down (right hand threads) until the impellers are lifted off their seat and the
shaft rotates freely. When semi-open impellers are used, the correct determination of the point where
the impellers just barely clear their seat is very important for proper adjustment.
4. Adjust the impellers as outlined in “Impeller Adjustment - General” on page 29.

Document Name: 2001299-VTP-IOM-EN Page 32 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Installation

5. Lock the adjusting nut with the lockscrew(s) inserted down through the holes in the adjusting nut and
threaded into the thrust bearing clutch. Use all lockscrews supplied.

CAUTION
DAMAGE TO THE PUMP AND THE DRIVER
Always ensure the adjusting nut is locked before starting the driver to avoid damage to the
pump and the driver.
6. After the impeller adjustment is completed, the flexible driver coupling may be installed.

5.12 Mechanical Seal

CAUTION
DAMAGE DUE TO MECHANICAL SEAL TABS
• For pumps fitted with mechanical seals always follow the seal manufacturer’s instruction
manuals.
• Always remove the mechanical seal setting tabs prior to starting the pump.
• Failure to remove the tabs will result in damage to both the pump and the seal.
• Ensure that the set screws are tight before removing the setting tabs.
Separate instruction manuals are written covering installation and operation for various mechanical seal
arrangements. However, the following instructions are common to all seals:
1. Clean the seal cavity before installing the seal.
2. Clean the faces and registers of the seal housing and seal housing cover. Remove any burrs.
3. The shaft seal is a precision product. Treat it with care. Take appropriate care not to scratch or chip the
lapped faces of the runner or seat.
4. Leave any circulation lines in place and open, do not remove.
5. Impeller adjustment must be made prior to seal adjustment.

Refer to the seal manufacturer's instruction manual for proper installation, operation, and
maintenance.

5.13 Packing Boxes


Packing boxes are pre-packed at the factory and are typically factory installed. Do not tighten the packing
gland at this stage. Refer to “Packing Box Adjustment” on page 36 for further information.

5.14 Enclosing Tube Tension


The enclosing tube (enclosed line shaft design) tension is pre-adjusted at the factory before shipping;
therefore, additional adjustment is not required. Refer to assembly instructions in “Assembly” on page 51 in
case assembly or adjustment is required for any reason.

Document Name: 2001299-VTP-IOM-EN Page 33 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Commissioning and Operation

6 Commissioning and Operation

DANGER
PERSONNEL INJURY DUE TO PROJECTILES
The following items may cause catastrophic pump failure resulting in projectiles. The
guarding is only designed to prevent personnel contact with the shaft and may not stop
projectiles. Do not stand in the line-of-fire.
• Improperly tightened couplings and coupling fasteners. Always ensure proper shaft
coupling installation prior to starting equipment.
• Incorrect driver rotational direction may unscrew coupling or damage pump. Always
ensure correct driver rotational direction with the pump uncoupled.
• Starting pump while it is spinning backwards. Never start a pump while it is spinning
backwards. A non-reverse ratchet on the driver or special system design must be utilized
to protect against this scenario.
• Reverse runaway rotation. For pumps not equipped with a non-reverse ratchet, the
system shall be designed and controlled such that the pump unit does not exceed the
specified maximum reverse runaway speed for that particular application. This capability
is not typically offered on pump units and must be specified by the customer in their pump
specification. If a maximum reverse runaway speed is not specified on the pump’s
Certified Outline Drawing, the operator must assume the unit was not designed for
reverse rotation.
• Improperly adjusted impellers could cause the pump to seize and catastrophically fail.
Always confirm that the impellers are properly adjusted.
• Overheating of the thrust bearing due to overload, over-speed, poor lubrication, poor
cooling or damage may result in seizing of the thrust bearing. Always ensure proper
operation of the thrust bearing.

WARNING
SERIOUS PERSONAL INJURY AND EQUIPMENT DAMAGE
• Pump units must only be used for their intended purpose. Refer to the certified outline
drawing and other contract documents for construction and application details.
• The pumps must not be operated beyond their design MAWPs (suction and discharge
sides), temperature limits and speed limits specified for the application. These limits are
dependent on the pump type, configuration and materials used. If there is any doubt
about the suitability of the product for the intended application, contact Weir Floway,
referencing the serial number.

WARNING
PERSONNEL INJURY FROM HAZARDOUS PUMPAGE
• Prior to introducing hazardous pumpage to any system, always leak test the system and
check for loose fitting and acceptable sealing.
• For applications involving hazardous fluids, degradation of the equipment and resulting
leaks may occur over time due to normal corrosion and wear of containment vessels and/
or sealing components. Procedures must be utilized to inspect equipment in such
applications to detect problems before they cause hazardous leaks and to detect leaks if
they occur.

Document Name: 2001299-VTP-IOM-EN Page 34 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Commissioning and Operation

WARNING
HOT FLUIDS AND SURFACES
Fluids and surfaces may become hot during operation (for example, hot pumpage, pump
surfaces, thrust bearing surfaces, thrust bearing oil, driver oil, driver surfaces, packing
leakage, etc.). Appropriate safety measures and PPE must be utilized to prevent personnel
injury.

6.1 Pre-starting Checks


Do the following checks before starting the pump:

WARNING
PERSONNEL INJURY
Do not touch the rotating elements with hands to establish the direction of rotation. Visually
confirm the direction of rotation.
1. Rotate the pump shaft to make sure the pump is free and impellers are correctly positioned.
2. The shaft adjusting nut is properly locked into position.
3. The driver has been installed and lubricated in accordance with the manufacturer’s instructions
furnished with the driver.
4. Check the driver for proper rotation. If not, disconnect the pump from the driver before doing further
checks. The driver must rotate counter-clockwise when viewed from the top of the driver.
5. All connections to the driver and control equipment are in place.
6. All piping connections are tight, leak free, and have the required gasket or O-ring installed.
7. All anchor bolts are tight.
8. All bolting and tubing connections are tight (driver mounting bolts, flanged coupling bolts, seal housing
cover bolts, seal piping, etc.).
9. For pumps equipped with a packing box, make sure the gland nuts are only finger tight. Do not tighten
the packing gland before starting the pump.
10. For pumps equipped with mechanical seals, clean fluid must be put into the seal chamber. For pumps
under suction pressure this can be accomplished by bleeding all the air and vapor out of the seal
chamber and allowing the fluid to enter. For pumps not under suction pressure the seal chamber must
be flushed liberally with clean fluid to provide initial lubrication. Make sure the mechanical seal is
properly adjusted and locked into place.

NOTICE
After the initial start-up, pre-lubrication of the mechanical seal is usually not required, as
enough liquid will remain in the seal chamber for subsequent start-up lubrication.

11. For pumps equipped with enclosed lineshaft, lubricating fluid must be available and allowed to run into
the enclosing tube in sufficient quantity to thoroughly lubricate all lineshaft bearings.

Document Name: 2001299-VTP-IOM-EN Page 35 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Commissioning and Operation

6.2 Initial Start-up

WARNING
PERSONNEL INJURY
Personnel injury or illness may result from contact with rotating parts, seal leakage or spray
from the rotating shaft.
1. If the discharge line has a valve in it, it should be partially open for initial starting.
2. Start the lubrication liquid flow on enclosed lineshaft units.
3. Start the pump and observe for excess noise, vibration or any other difficulty. If any malfunctions occur,
stop the pump immediately and refer to “Troubleshooting” on page 55 for probable cause.
4. Ensure all air and gases are properly vented from the pump and system.
5. Open the discharge valve as desired.
6. Check the complete pump and driver for leaks, loose connections or improper operation.
7. If possible, leave the pump running for approximately half an hour on the initial start-up; this will allow
the bearings, packing or seals, and other parts to “run-in” and reduce the possibility of trouble on future
start-ups.

CAUTION
EQUIPMENT DAMAGE DUE TO PUMP BLOCKAGE
The standard unit is not designed to pump large amounts of abrasives or debris. If any
unexpected debris or abrasives are present in the discharge liquid and the pumpage does
not clear up, immediately shut down the unit and eliminate the source of abrasives and
debris.

6.3 Packing Box Adjustment

WARNING
RISK OF ENTRAPMENT
During gland adjustment, the guard needs to be removed. When the guard is removed, the
rotating shaft is exposed and may cause entrapment. Hence, only qualified personnel must
work on gland adjustment.
• It is important that the packing is not tightened too much on initial start-up to prevent overheating and
damage.
• New packing must be “run in” properly to prevent damage to the shaft and shortening of the packing life.
Refer to “Start-up with New Packing” on page 41 for further information.
• The packing box must be allowed to leak for proper operation. The appropriate quantity of leakage can
be determined by checking the temperature of the leakage. The temperature must be cool or lukewarm,
not hot. Leakage of 40 to 60 drops per minute is adequate.
• When adjusting the packing gland, bring both the nuts down evenly and gradually until the leakage is
reduced to the required quantity. Tighten the nuts only about half a turn at a time, at 20 to 30 minute
intervals to allow the packing to “run-in”.
• Under proper operation a set of packing will last a long time. Occasionally a new ring of packing will
need to be added to keep the box full. After adding two or three rings of packing, or when proper
adjustment cannot be achieved, the packing box should be cleaned completely of all old packing and
repacked.

Document Name: 2001299-VTP-IOM-EN Page 36 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Commissioning and Operation

6.4 Lineshaft Lubrication


1. Open Lineshaft Bearings: are lubricated by the pumped fluid. Close coupled units (less than 40 feet
long) usually do not require pre or post lubrication.
2. Enclosed Lineshaft Bearings: are lubricated by external liquid (usually oil or clean water) which is fed to
the tension nut by either a gravity flow or pressure injection system. The gravity flow system which
utilizes oil is the most common arrangement. The oil reservoir must be kept filled with good quality light
turbine oil (about 150 S.S.U. at operating temperature) and adjusted to feed 5 to 8 drops per minute.
Injection lubrication systems are designed for each installation. The injection pressure and quantity of
lubricating liquid varies. Refer to Figure 12-8 on page 65 for injection lubrication arrangement.

Refer to the certified outline drawing for requirements when the unit is designed for
injection lubrication.

Refer to Table 6-1 for turbine oils, that are recommended for enclosed lineshaft bearing lubrication under
normal operating conditions.

Manufacturer Trade Name of Oil

Amoco American Industrial 32

Exxon Teresstic 32

Mobil Oil Company DTE Light

Conoco Conoco 32

Shell Oil Company Tellus 32

Chevron Chevron GST68

Texaco Texaco Regal R&O 32

Phillips 66 Magnus 32

Unocal Unocal Turbine Oil 32


Table 6-1: Recommended Lineshaft Oil

Refer to Table 6-2 for turbine oil that is suitable for use where FDA approved lubricating oil is required for
USDA-Classification H1.

Manufacturer Trade Name of Oil

Chevron Chevron FM Lubricating Oil 32

Lyondell Petrochemical ARCO White Oil 32


Table 6-2: Recommended Lineshaft Oil

If none of the above oils are available, procure the oil with following specifications:
• Turbine type oil with rust and oxidation inhibitors added.
• Viscosity 145-175 S.S.U. at 100°F with 90 minimum viscosity index. ISO grade 32.
• Do not use detergent type oils.

Document Name: 2001299-VTP-IOM-EN Page 37 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Commissioning and Operation

Recommended greases for packing boxes and suction bearings are given in Table 6-3.

Union Oil Grades Other ARCO SHELL TEXACO MOBIL GULF EXXON CHEVR
Products Specs. ON

UNOBA EP NLGI Lithium Litholine Alvania Multifak Moloiux Gulfcrown Beacon Dur-Lith
Grease #1 & 2 Soap H-EP EP EP EP EP EP

MP NLGI GM, Ford, EP Moly Super Marfak Mobile Gulfex Multi- Multi-
Automotive #00 Chrysler Grease Duty All Grease Poly Purpose Motive
Grease Molybde- Grease Purpose Special Grease Grease
num
Disulfide
& Poly-
ethylene
Table 6-3: Recommended Greases

Document Name: 2001299-VTP-IOM-EN Page 38 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Maintenance

7 Maintenance
DANGER
LOCKOUT-TAGOUT (LOTO)
• Prior to allowing any checking, maintenance, or other work on the equipment, all
hazardous energy sources (for example, electrical, mechanical, hydraulic, pneumatic,
etc.) must be isolated using an appropriate lockout-tagout procedure.
• Ensure that the intake and discharge openings are totally isolated from all potentially
pressurized connections and that they are, and can only be exposed to atmospheric
pressure.
• Drain the pump and isolate pipework before dismantling the pump. The appropriate
safety precautions must be taken when the pumped liquids are hazardous.
• Failure to follow appropriate LOTO procedures may result in serious personal injury or
death.

WARNING
PERSONNEL INJURY
• The pump must be installed, operated and maintained only by the personnel who are
trained and have sufficient knowledge about the hazards that may occur during the pump
operation and maintenance.
• A comprehensive risk assessment shall be conducted prior to performing any
maintenance or repair work on the equipment.
• Refer to the requirements in the driver, seal, and other auxiliary equipment IOMs prior to
beginning work.

WARNING
PERSONNEL INJURY DUE TO HAZARDOUS MATERIALS
During disassembly, personnel may come in contact with hazardous materials. These
materials must be identified before disassembly, and the correct SDS must be made
available and appropriate safety management precautions put in place. Hazardous
pumpage must be purged and flushed from the pump prior to disassembly. Always wear
appropriate PPE.

WARNING
HOT FLUIDS AND SURFACES
Fluids and surfaces may become hot during operation (for example, hot pumpage, pump
surfaces, thrust bearing surfaces, thrust bearing oil, driver oil, driver surfaces, packing
leakage, etc.). Appropriate safety measures and PPE must be utilized to prevent personnel
injury.

Document Name: 2001299-VTP-IOM-EN Page 39 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Maintenance

7.1 Periodic Inspection, Condition Monitoring, and Preventative Maintenance


• Periodic inspections (ideally once a month) and preventative maintenance are recommended as the
best means of preventing breakdown and keeping maintenance costs at a minimum.
• Maintenance personnel should look over the entire installation with a critical eye, each time the pump is
inspected.
• A change in noise level, amplitude of vibration, or performance is an indication of a possible impending
trouble and must be investigated for probable causes.
• During inspection the pump and driver should be checked for performance and change in noise or
vibration level, loose bolts or piping, dirt and corrosion. It helps to develop a vibration trend analysis
based upon periodic vibration reading recordings. This helps determine changes in equipment condition
and optimum repair frequency.
• Variances from initial performance are an indication of changing system conditions, wear or impending
breakdown of the unit.
• Clean and repaint all areas that are rusted or corroded.

7.2 Packing Box Maintenance


Maintenance of the packing box will consist of greasing the box when required, tightening the packing gland
occasionally as the leakage becomes excessive, and installing new packing rings or sets as required.

7.2.1 Packing Box Greasing


• Under normal operation, once a month greasing of the packing box is typically adequate.
• Use good grade multipurpose grease such as Chevron Industrial Grease - Medium or Marfak
MULTIPURPOSE #2.

7.2.2 Replacing the Packing


• Remove the gland and old packing. If the box contains a lantern ring remove this and the packing below
it.
• Inspect the shaft or sleeve for score marks or rough spots. Ensure that the bypass holes (if required) are
not plugged.
• Repair or replace badly worn shaft or sleeve. If the wear is minor dress down until smooth and
concentric. Clean the box bore.
• Oil the inside and outside of the replacement rings lightly and install in the box, staggering joints 90°. Be
sure to replace lantern ring in proper position when used.
NOTICE
Formed replacement packing rings are recommended and are available from the factory.

Document Name: 2001299-VTP-IOM-EN Page 40 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Maintenance

• Replace the gland, tighten the nuts and make sure the gland enters the box squarely. Keep the packing
under moderate pressure for one minute to allow it to cold flow and adjust itself. Back off on the gland
until loose and the gland nuts are hand tight before starting the pump.

Shaft Size # Packing Rings Packing Ring Size Depth of Box O.D. of Packing

3/4 5 5/16 1 23/32 1 3/8

1 5 5/16 1 23/32 1 5/8

1 3/16, 1 1/4 5 3/8 2 1/16 2

1 1/2 5 3/8 2 1/16 2 1/4

1 11/16 5 7/16 2 13/16 2 5/8

1 15/16 6 3/8 2 13/32 2 3/4

2 1/4 6 3/8 2 3/4 3 1/16

2 7/16 6 3/8 4 3/4 3 1/4

Table 7-1: Standard Type Box

Shaft Size # Packing Rings Packing Ring Size Depth of Box O.D. of Packing

3/4 6 5/16 3 5/8 1 3/8

1 6 5/16 3 5/8 1 5/8

1 3/16, 1 1/4 7 3/8 4 5/8 2

1 1/2 7 3/8 4 5/8 2 1/4

1 11/16 7 7/16 4 7/8 2 5/8

1 15/16 8 3/8 4 7/8 2 11/16

2 1/4 6 1/2 4 3/4 3 1/4

2 7/16 6 1/2 4 3/4 3 1/2

2 11/16 7 1/2 4 1/2 3 3/4

Table 7-2: Hi-pressure Type Box

7.3 Start-up with New Packing


• Check that the bypass line (if used) is connected and packing gland is loose.
• Start the pump and allow it to run for 20 to 30 minutes; do not tighten the gland during this “run-in” period
even if leakage is excessive. If the leakage continues to be more than normal, adjust as outlined in
“Packing Box Adjustment” on page 36.
• If the new packing causes excess heating during run-in, flush the shaft and packing box area with cold
water or shut the pump down. Allow to cool if necessary.

7.4 Auxiliary Packing Box Maintenance


• Pumps equipped with mechanical seals may also be provided with an auxiliary packing box to restrict
leakage, should the mechanical seal fail.
• This packing gland must be left loose since under regular operation the packing is not cooled or
lubricated by the pumpage.
• This packing box arrangement is designed to help contain leakage past the mechanical seal in the event
of a seal failure. It is not designed as a primary seal and must not be used as such.

Document Name: 2001299-VTP-IOM-EN Page 41 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Maintenance

7.5 Mechanical Seal Maintenance

CAUTION
DAMAGE DUE TO MECHANICAL SEAL TABS
• For pumps fitted with mechanical seals always follow the seal manufacturer’s instruction
manuals.
• Always remove the mechanical seal setting tabs prior to starting the pump.
• Failure to remove the tabs will result in damage to both the pump and the seal.
• Ensure that the set screws are tight before removing the setting tabs.
Mechanical seals should not be readjusted unless there is a reason. Best results are obtained when the seal
is properly set at start-up and left that way. If the seal starts to leak after an extended operating period, some
readjusting can be done at that time. However, it is usually best to replace the seal during the next scheduled
maintenance cycle.
After impeller readjustment, seal leakage may occur due to improper seal adjustment or improper seating of
the seal parts.

If readjustment of the seal does not correct the problem, refer to the manufacturer’s
instruction manual for further information.

7.6 Impeller Readjustment


Typically, impellers do not require readjustment if properly set at initial installation. Almost no change in
performance can be obtained by minor adjustment of enclosed impellers; however, the positioning of semi-
open impellers has a definite effect on the performance of the pump. This characteristic is sometimes used to
adjust the output of the pump without valving. Figure 7-1 on page 43 illustrates the general effect of raising
semi-open impellers.
After extended operation, the sealing faces between the semi-open impellers and the bowl will wear causing
a reduction in performance. The pump performance can be brought back up to almost “as new” by proper
readjustment of the impellers. Refer to “Impeller Adjustment - General” on page 29 for proper adjustment
procedure.

NOTICE
Adjusting the impellers will change the mechanical seal setting unless the seal is loosened
from the shaft. It is recommended to first loosen the seal from the shaft, perform the
impeller adjustment, then reset the mechanical seal.

Document Name: 2001299-VTP-IOM-EN Page 42 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Maintenance

Figure 7-1: Effect of Adjusting Semi-open Impellers

Document Name: 2001299-VTP-IOM-EN Page 43 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Maintenance

Figure 7-1 on page 43 indicates the approximate effect of raising semi-open impellers from their ideal (a)
operating position. Raising the impellers increases the clearance between the impeller and the bowl seat and
reduces the performance accordingly. The chart is generic and not exact for any particular pump model since
each model reacts differently. 100% head and capacity are to be taken as the head and capacity of the pump
at the best efficiency point (BEP).
For example, if a particular pump delivers 250 gpm and 50' head at BEP, when impellers are properly
adjusted, raising the impellers 0.080" will reduce the capacity to approximately 181 gpm (72.5% of 250 gpm)
while maintaining 50' head or conversely, the pump will deliver 250 gpm at 37.5' head (75% of 50'). The
horsepower will be about 91.50% of the previous horsepower.

7.7 Pump Lubrication


Other than the packing box lubrication outlined in “Packing Box Greasing” on page 40 and lineshaft
lubrication outlined in “Lineshaft Lubrication” on page 37 the pump does not require further periodic
lubrication. The suction bearing should be repacked with grease when repairs are done on the bowl assembly
(it is not necessary to repack the suction bearing before bowl assembly repairs are required). Special pump
construction may allow for more lubrication options, reference the pump’s Certified Outline Drawing for such
features and details.

7.8 Driver and Auxiliary Equipment Maintenance


Drivers and auxiliary equipment require periodic maintenance.

Refer to the manufacturer’s instruction manual for proper installation, operation, and
maintenance.

Document Name: 2001299-VTP-IOM-EN Page 44 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Repairs

8 Repairs
DANGER
LOCKOUT-TAGOUT (LOTO)
• Prior to allowing any checking, maintenance, or other work on the equipment, all
hazardous energy sources (for example, electrical, mechanical, hydraulic, pneumatic,
etc.) must be isolated using an appropriate lockout-tagout procedure.
• Ensure that the intake and discharge openings are totally isolated from all potentially
pressurized connections and that they are, and can only be exposed to atmospheric
pressure.
• Drain the pump and isolate pipework before dismantling the pump. The appropriate
safety precautions must be taken when the pumped liquids are hazardous.
• Failure to follow appropriate LOTO procedures may result in serious personal injury or
death.

DANGER
LIFTING POINTS GIVING AWAY
Lifting points may be corroded and may not be fit for use. Always check for suitable
condition of lifting points and rigging prior to lifting equipment.

WARNING
PERSONNEL INJURY
• The pump must be installed, operated and maintained only by the personnel who are
trained and have sufficient knowledge about the hazards that may occur during the pump
operation and maintenance.
• A comprehensive risk assessment shall be conducted prior to performing any
maintenance or repair work on the equipment.
• Refer to the requirements in the driver, seal, and other auxiliary equipment IOMs prior to
beginning work.

8.1 General
• The repair of vertical turbine pumping units is best handled by an experienced pump service center.
• Weir Minerals has a worldwide network of service centers where skilled machinists and mechanics can
repair and rebuild any pump unit to “as-new” condition. For information regarding the nearest service
center, contact Weir Floway by email at, flowayparts@weirminerals.com.
• Eventually repairs will be required for the pump equipment. When maintenance checks, condition
monitoring, or other indications show that an overhaul is required, the necessary repairs should not be
delayed. Delay of repairs could lead to catastrophic failure, safety risks, and system down time.
• Major repairs typically consist of removal of the unit and disassembly to the point necessary for
replacement of worn out parts.
• Disassembly must be performed in a clean area with sufficient space to lay out the parts in order of
disassembly. Cleanliness during repairs is important as this is a close tolerance, high speed machine
and must be handled as such.

Document Name: 2001299-VTP-IOM-EN Page 45 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Repairs

8.2 Equipment and Tools


If bowl assembly repairs are anticipated, a separate manual is available giving detailed instructions for
disassembly and repair. Read this manual thoroughly before attempting repairs of the bowl assembly. When
requesting this manual from the factory the pump model must be given.

Required equipment and tools are as listed in “Pre-installation” on page 12 of this manual
and in the appropriate Pump Bowl Instruction Manual.

8.3 Packing Box Repairs


Packing box repairs can be done without removing the complete unit. Packing replacement as outlined in
“Replacing the Packing” on page 40 can be accomplished without disturbing the pump or driver. The packing
box bearing can be replaced if necessary by removing the driver and sliding the packing box off the shaft.

8.4 Mechanical Seal Repairs


• Mechanical seal repairs can be done without removing the complete unit.
• The mechanical seal assembly can be replaced by removing the spacer and pump half coupling on solid
shaft units (remove the thrust bearing if it is located in the pump). For hollow shaft units, remove the
headshaft and shaft coupling inside the discharge head.
• Replacement of the bearing located at the bottom of the seal housing requires removal of the driver in
order to get enough headroom.

8.5 Disassembly
Refer to “Parts List” on page 58 for part drawings and identification.

WARNING
PERSONNEL INJURY DUE TO HAZARDOUS MATERIALS
During disassembly, personnel may come in contact with hazardous materials. These
materials must be identified before disassembly, and the correct SDS must be made
available and appropriate safety management precautions put in place. Hazardous
pumpage must be purged and flushed from the pump prior to disassembly. Always wear
appropriate PPE.

WARNING
PERSONNEL INJURY
Threaded components typically require application of very high torques to disassemble (for
example, shaft couplings, threaded bowls, threaded columns, etc.). Always ensure the
tools and methods used for disassembly are appropriate for the forces/torques required.

CAUTION
MACHINED SURFACES
Protect all machined surfaces from burrs and scrapes as this can cause misalignment upon
reassembly.
1. Disconnect the electrical leads from the motor.
2. Loosen the mechanical seal from the shaft.
3. Disconnect the pump shaft from the driver:
a. Hollow Shaft Driver: remove the headshaft nut lockscrew, headshaft nut, gib key and the driver clutch.
Unscrew and remove the headshaft from the shaft coupling inside the discharge head.

Document Name: 2001299-VTP-IOM-EN Page 46 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Repairs

b. Solid Shaft Driver: Unbolt the driver coupling to lower the pump shaft. Remove coupling components
(driver half coupling may be left in place, ensure it is safely secured to the driver shaft).
4. Remove the bolts which attach the driver to the discharge head.
5. Lift the driver off the pump and set it on wooden supports. For solid shaft drivers ensure the supports are
high enough to clear the shaft and coupling half, which project beneath the motor mounting plate.
6. Disconnect the discharge (and suction, if applicable) piping from the pump.
7. Remove the anchor bolt nuts, or bolts from the mounting flange.
8. Lift the pump vertically until the pump suction clears the foundation, or the mounting flange. Remove the
mounting flange gasket if required.
9. Cover the opening in the foundation.
10. Lower the pump and position horizontally on a stable support in a suitable area for disassembly.

For any major repairs it is recommended to take the unit to a shop or any other clean area
which has smooth flooring and overhead lifting equipment.
11. For packing box, mechanical seal and enclosed lineshaft construction do the following:
a. Packing Box Construction: remove the slinger and the packing gland.
b. Mechanical Seal Construction: loosen seal cover fasteners and remove the seal housing cover.

For sleeve mounted mechanical seals, remove the seal and sleeve assembly along with
the cover.

Refer to the manufacturer's instruction manual for further mechanical seal details.

c. Enclosed Lineshaft Construction: remove the lockscrew and lubrication line and unscrew the tension
nut assembly. Threads are left hand.
12. Remove the fasteners which attach the packing box, tension plate or seal housing to the discharge
head.
13. Remove the packing box, tension plate or seal housing.

If type FF-2 or FF-9 mechanical seal is used, loosen the set screws which lock the seal
assembly to the shaft before removing the seal housing.!

Before proceeding further, make sure the discharge head and the bowl/column assembly
are supported independently of each other.!

14. Disconnect the bowl assembly or top column from the discharge head. This connection may be flanged
or threaded. If threaded, the thread will be right hand.
15. Remove the discharge head being careful not to damage the shaft.
16. Disconnect the column pipe (if present) at first joint below the top and remove from the shaft.

Document Name: 2001299-VTP-IOM-EN Page 47 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Repairs

17. For open lineshaft and enclosed lineshaft construction do the following:
a. Open Lineshaft Construction: each time a lineshaft coupling is exposed by removing a length of the
column pipe, the lineshaft and the coupling must be removed by holding the coupling and turning the
upper lineshaft in right hand direction (line shaft threads are left hand).

CAUTION
EQUIPMENT DAMAGE
• When using wrenches on shafting, always place the wrenches on the same side of the
shaft as illustrated in Figure 8-1 on page 48 to avoid excess side strain on shafting.
• Always position the wrench that will grip the shaft above the shaft coupling (that is, on the
upper shaft as viewed when the pump is in the vertical installed position). This must be
done to prevent scoring and burrs on the top ends of the shafting to allow bearings to
slide on/off freely.

Figure 8-1: Correct Positioning of Wrenches on Shafting

b. Enclosed Lineshaft Construction: each time a length of column pipe is removed the enclosing tube
and lineshaft must also be disassembled. Locate the joint (refer to Figure 8-2) and unscrew (left hand
threads) the enclosing tube from the lineshaft bearing (which acts as a bearing for the shaft and also
as an enclosing tube coupling). Leave the lineshaft bearing threaded into the enclosing tube not being
removed (to support the lineshaft). Slide the enclosing tube up to expose the lineshaft coupling and
uncouple as outlined in step 17(a) above.

Document Name: 2001299-VTP-IOM-EN Page 48 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Repairs

1. Column Pipe
2. Pipe Coupling
3. Enclosing Tube
4 4. Lineshaft Bearing
5. Lineshaft
6. Lineshaft Coupling

Figure 8-2: Enclosing Tube and Lineshaft

18. Disconnect each section of the column pipe one at a time and remove along with the shaft and
enclosing tube as applicable until all are removed.
19. Remove and place the bowl assembly in a clear area.

Continue disassembly as outlined in separate Pump Bowl Instruction Manual.

8.6 Inspection and Cleaning


• After disassembly, clean all components and examine thoroughly for physical defects, wear, corrosion
and damage.
• Check all bearing bores for total clearance over the shaft diameter. Replace all lineshaft bearings
indicating wear. The following indicates the maximum allowable diametrical clearance over existing
shaft diameter, in which case bearing must be replaced.
• 3/4" through 1 11/16" shaft - 0.020" clearance
• 1 15/16" through 2 7/16" shaft - 0.025" clearance
• 2 11/16" through 3 15/16" shaft - 0.030" clearance

Document Name: 2001299-VTP-IOM-EN Page 49 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Repairs

• It is recommended that bowl assembly bearings be replaced when pump bowl assembly is
disassembled, and measured diametrical clearance exceeds standard clearance indicated in bowl
repair manual (new bearings) by 0.004 maximum.
• Inspect shaft straightness. Each shaft should be straight to within 0.0005" TIR per foot of shaft length
(for example, 0.005" TIR over a 10ft shaft length).
To measure shaft straightness:
i Support the shaft on two precision rollers, each placed 1/4 of the shaft length in from both shaft
ends.
ii Rigidly mount a dial indicator to contact the shaft.
iii Slowly rotate the shaft on the rollers and record the TIR from the dial indicator.
iv Measure and record TIR readings at 1 ft increments along the shaft length.
If the shaft is not straight, it must be either straightened or replaced with a new shaft.
• Check all enclosed impeller to bowl running clearances. If the clearance exceeds the quantity of (Imp.
Ring OD in inches #12) thousandths of an inch, renewing the clearance should be considered to
achieve optimum pump efficiency. For example, if the impeller wear ring OD is 13 inches, the clearance
should be renewed if the impeller to bowl clearance is greater than 0.025" (13+12 = 25 thousands of an
inch).

8.7 Replacement Parts


Replace parts showing signs of damage, cracks or excessive wear. Use only genuine Floway parts for
replacements.

DANGER
GENUINE OEM PARTS
• Genuine OEM parts and accessories are designed, tested and incorporated into the
products to help ensure they maintain continued product quality and performance in use.
• As Weir Floway does not test the parts and accessories sourced from other vendors, the
installation of such parts and accessories may adversely affect the performance and
safety features of the products.
• The failure to properly select, install or use authorized parts and accessories is
considered misuse. Damage or failure caused by misuse is not covered by our warranty.
• In addition, any modification of Weir Floway products or removal of original components
may impair the safety of these products in their use.
Order replacement parts as indicated in “Parts” on page 57.

CAUTION
INSPECT PARTS
When repairing a pump which has been in service, it is important to inspect the physical
condition or strength of all parts such as fasteners, bowls, threads, pressure casings, etc.,
to ensure all parts that will be reused are in good condition and fit to perform in the specific
application.

8.8 Lubrication

Repack the suction bearing as outlined in Pump Bowl Instruction Manual.

Lubricate all bearings and impeller skirts with clean grease or oil acceptable for the application. Thoroughly
clean all threaded connections and flanges and coat with thread lubricant, oil, or pipe joint compound.

Document Name: 2001299-VTP-IOM-EN Page 50 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Repairs

8.9 Assembly
Before proceeding with assembly, thoroughly clean and check all the threads, registers and mating faces for
burrs. Deburr with file and emery cloth where required. Lubricate as given in “Lubrication” on page 50. Oil the
shafts lightly.
Proceed with assembly in reverse order of disassembly as outlined in “Disassembly” on page 46.

CAUTION
EQUIPMENT DAMAGE
Cleanliness and proper lubrication are extremely important as one small chip, burr or dry
bearing can result in equipment damage and require further repair.

Refer to Table 8-1 for recommended torque values of typical fasteners.


WTUAQC0%2CKE>D>'%.CE>'AC0K%
!*+"%&'(%,$.1
,-.%/0(%9%:"65;*<1
23+"%4"#564"*7 23+"%4"#564"*7% !"93%:&'(%3% %!"35%&'(,I%
!"#$%&'(%!) ,-%/0(%9,) 23+"%4"#564"*7%
/89%:"65%;%*%*69< /8*%:*65%;%36-<1 >?@ABC0>DE< :&'(%-%
!*+"%,-.%/0(%*1 !"93%:&'(%3% 4=*%:*65%;%36-<)
4=5:*%"6-%;%*%*69<) 4=":*%*6-%;%*%*65<) :*69%;%*<) >?@ABC0>DE<%
,-.!%/0(%*!% >?@ABC0>DE< !*+"%,$1%
!*+"%,-.%/0(9 !*+"%,-.%/0(9 257- /C'JFD%KE>>0
:*%*6-%;%*%*69<) ,-.%/0(9%:H"65<
:*%*65;*%*69< :*;*%*65< .FD>0%G;3##
23+"%4"#564"*7
4=9%:"65%;%*<
20FRCT%.CE>'AC0%QFN>
9""1%9931%9"3%
#-51%99"1%9"9 *#71%*#$1%*$+1%993 *#71%*#$1%*$+1%993 ""#1%#59 *$+1%9951%993 #-3
""#1%*$+
!UU'F[ASCE>%2CKE>D>'%.CE>'AC0%.AD(%]A>0N%4E'>DXEM%:UKA<
"#### 53### 73### -#### +#### *##### *"####
,F0E%KAL>;EM'>CNK6AD WF'?@>%\C0@>%:0JV;VE<
*65%;%9# 9 " 5 3 3 7 -
36*7%;%*- 5 7 - *# ** *9 *7
"6-%;%*7 $ *# *5 *$ 9# 99 9-
$6*7%;%*5 *# *7 9" 9- "* "3 53
*69%;%*" *7 95 "3 5" 5- 3" 7+
+6*7%;%*9 9" "3 3# 7* 7+ $$ *##
36-%;%** "9 5- 7+ -3 +3 *#7 *"-
"65%;%*# 37 -3 *99 *3* *7+ *-- 953
$6-%;%+ +* *"7 *+$ 959 9$" "#" "+5
*%;%- *"7 9#5 9+3 "7" 5#+ 535 3+*
*%*6-%;%$ *+" 9+# 5*+ 3*3 3-# 755 -"$
*%*65%;%$ 9$" 5#+ 3+* $9$ -*- +#+ **-*
*%"6-%;%7 "3$ 3"7 $$5 +3" *#$9 **+* *35-
*%*69%;%7 5$5 $** *#9- *973 *59" *3-* 9#33
*%36-%;%- 75+ +$" *5#7 *$"# *+5$ 9*7" 9-*9
*%"65%;%3 $5- **99 *79# *++5 9955 95+" "95*
*%$6-%;%- *#*- *39- 99#$ 9$*7 "#33 ""+3 55*"
9%;%5(3 **95 *7-7 95"7 9++- ""$" "$5$ 5-$9
,CK>N%FD%OP/%EM'>CNK%0@J'AQCE>N%RAEM%FA0(
2CKE>D>'K%RAEM%ADE>'S>NACE>%TA>0N%KE>KK%BC0@>K%SCT%J>%0AD>C'0T%ADE>'UF0CE>N%V'FS%ECJ0>(
WCJ0>%QFDECADK%X>D>'C0%EF'?@>%BC0@>K%VF'%U@SU%QFSUFD>DEK%JCK>N%FD%C%7#Y%U'>0FCN%EF%EM>%SCE>'AC0ZK%TA>0N%KE'>DXEM(%%
2F'%CUU0AQCEAFDK%'>?@A'ADX%C%MAXM>'%U'>0FCN1%EM>%'CEAF%FV%:N>KA'>N%U'>0FCNY%6%7#Y<%QCD%J>%S@0EAU0A>N%JT%ECJ0>%BC0@>K%EF%N>E>SAD>%EF'?@>(
WF'?@>%BC0@>K%CKK@S>%CN>?@CE>%EM'>CN%KE'>DXEM%CDN%>DXCX>S>DE%EF%U'>B>DE%KE'AUUADX%EM>%EM'>CNK(
2F'%EAXME>DADX%CDQMF'%JF0EK%>SJ>NN>N%AD%QFDQ'>E>1%NF%DFE%>[Q>>N%3##%0JV;VE(
Table 8-1: Recommended Torque Values for Typical Fasteners

Document Name: 2001299-VTP-IOM-EN Page 51 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Repairs

8.10 Tension Nut Assembly and Adjustment


Enclosed lineshaft units use a tension nut which is at the top of the enclosing tube and must be tightened for
proper operation. Refer to Figure 8-3 for general construction.
1. Clean all O-ring sealing surfaces including the groove in the tension plate and oil lightly.
2. After assembling the discharge head to the column, install the tension plate (ensure that both O-rings
are in place), and allow the O-ring to slide down outside of tube adjusting nipple. Lightly oil the outside of
the tube adjusting nipple prior to installation of tension plate.
3. Bolt the tension plate into place.
4. Slide the tension nut over the shaft and thread into inside of the tube adjusting nipple (left hand threads)
until the tension nut is snug against the tension plate. Continue to tighten the tension nut until the
lockscrew slot lines up with the “first” tapped hole in tension plate (1/4 turn maximum).

CAUTION
DO NOT OVER TIGHTEN THE TENSION NUT
It is necessary that the enclosing tube have tension on it which is accomplished by
tightening the tension nut. However, excess tightening can distort or break the tension nut.
Do not tighten more than 1/4 turn on close coupled pumps.
5. Install the lockscrew and tighten.
6. Proceed to complete the installation.

1. Headshaft
2. Lock Screw
6 3. Tension Plate
5 4. Tension Plate O-ring
5. Tube Adjusting Nipple
6. Tube Nipple O-ring
7. Tension Nut

Figure 8-3: Tension Nut Assembly

Document Name: 2001299-VTP-IOM-EN Page 52 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Decommissioning and Disposal

9 Decommissioning and Disposal


This section describes decommissioning and disposal of the complete pump unit.

DANGER
LOCKOUT-TAGOUT (LOTO)
• Prior to allowing any checking, maintenance, or other work on the equipment, all
hazardous energy sources (for example, electrical, mechanical, hydraulic, pneumatic,
etc.) must be isolated using an appropriate lockout-tagout procedure.
• Ensure that the intake and discharge openings are totally isolated from all potentially
pressurized connections and that they are, and can only be exposed to atmospheric
pressure.
• Drain the pump and isolate pipework before dismantling the pump. The appropriate
safety precautions must be taken when the pumped liquids are hazardous.
• Failure to follow appropriate LOTO procedures may result in serious personal injury or
death.

DANGER
LIFTING DEVICE SAFETY
• Lifting devices of adequate capacity must be used whenever they are required.
• Safe workshop practices must be applied during all assembly and maintenance work.
• Personnel must never work under suspended loads.

DANGER
LIFTING POINTS GIVING AWAY
Lifting points may be corroded and may not be fit for use. Always check for suitable
condition of lifting points and rigging prior to lifting equipment.

WARNING
PERSONNEL INJURY DUE TO HAZARDOUS MATERIALS
During disassembly, personnel may come in contact with hazardous materials. These
materials must be identified before disassembly, and the correct SDS must be made
available and appropriate safety management precautions put in place. Hazardous
pumpage must be purged and flushed from the pump prior to disassembly. Always wear
appropriate PPE.

WARNING
SHARP EDGES
• Before handling, identify work parts that could be hazardous due to sharp edges. All
metal components must be considered to have sharp edges.
• Pump components can have sharp or jagged edges. Handle parts carefully, to prevent
damage to slings or personal injury.

Document Name: 2001299-VTP-IOM-EN Page 53 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Decommissioning and Disposal

WARNING
RESALE OF PUMPS AND PARTS
Due to the highly engineered nature of vertical turbine pumps, Weir Floway does not
recommend reselling used pumps or pump parts. Potentially unsafe conditions could be
created by using pumps and pump parts in applications for which they are not intended for.
Furthermore, used parts may be unsafe and not fit for any use due to corrosion, wear, or
other damage.
To decommission and dispose of a pump unit, Weir Floway recommends the following steps:

NOTICE
For drivers, mechanical seals, and other auxiliary equipment, refer to the respective
manufacturer's IOM for further details regarding decommissioning and disposal.!

1. Flush the pump of all hazardous pumpage using the necessary safety precautions.
2. Isolate the pump electrically, hydraulically, and mechanically (reference LOTO warning).
3. Drain all equipment fluids such as driver oil, thrust bearing oil, etc.
4. Disconnect the pump electrically, hydraulically, and mechanically.
5. Remove the driver, seal, and all other auxiliary equipment.
6. Remove the pump unit.
7. Disassemble the pump unit as required for disposal.
8. Follow all applicable environmental, health, and safety regulations, laws, and requirements to dispose of
the equipment and any hazardous materials.

Document Name: 2001299-VTP-IOM-EN Page 54 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Troubleshooting

10 Troubleshooting
Refer to Table 10-1 for troubleshooting instructions.

Condition Probable Cause Remedy

Pump not running. 1 Motor overload protection contacts open. 1 Do the following:
a Incorrect control box. a Check nameplate for HP and
b Incorrect connections. voltage.
c Faulty overloads. b Check wiring diagram furnished with
starter.
d Low Voltage.
c Replace.
e Ambient temperature of control box or
starter too high. d Check voltage at pump side of
control box.
6 Blown fuse, broken or loose electric
connections. e Use ambient compensated relays.
7 Defective Motor. 6 Check fuses, relays or heater elements
for correct size and all electrical
8 Faulty control equipment.
connection.
9 Faulty switch.
7 Repair or replace.
10Pump binding.
8 Check all circuits and repair.
9 Repair or replace.
10Pull master switch, rotate pump by hand
to check. Check impeller adjustment or
disassemble the unit to determine the
cause.

Pump is running but 1 Line check valve backward. 1 Reverse check valve.
no fluid delivered. 2 Line check valve stuck. 2 Free the valve.
3 Unit running backwards. 3 Refer to “Hollow Shaft Driver Installation”
4 Lift too high for pump. on page 24, step 12.
5 Pump not submerged. 4 Check with performance curve.
6 Excessive amounts of air or gas. 5 Lower pump if possible or add fluid to
system.
7 Intake strainer or impeller plugged, or pump
in mud or sand. 6 Correct conditions.
8 Impeller(s) loose on shaft. 7 Start & stop pump several times or use
line pressure if available to back flush.
Pull pump and clean.
8 Pull unit and repair.

Reduced capacity. 1 Bypass open. 1 Check bypass valving.


2 Lift too high for pump. 2 Check performance curve.
3 Motor not coming up to speed. 3 Check voltage while unit is running.
4 Strainer or impellers partly plugged. 4 Start & stop pump several times or use
5 Scaled or corroded discharge pipe or leaks line pressure if available to back flush.
anywhere in system. Pull pump and clean.
6 Excessive amounts of air or gas. 5 Replace pipe or repair leaks.
7 Excess wear due to abrasives. 6 Suitable conditions.
8 Impellers not properly adjusted. 7 Replace worn parts.
9 Impeller(s) loose on shaft. 8 Refer to “Impeller Adjustment - General”
on page 29.
9 Pull the unit and repair.
Table 10-1: Troubleshooting Chart

Document Name: 2001299-VTP-IOM-EN Page 55 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Troubleshooting

Condition Probable Cause Remedy

Motor overloaded. 1 Line voltage not correct. 1 Check and correct.


2 Faulty equipment used to check. 2 Check equipment.
3 Specific gravity higher than design. 3 Correct specific gravity or re-evaluate
4 Operation at point on pump curve other than system.
design. 4 Check performance curve.
5 Motor speed too high. 5 Line voltage too high or incorrect
6 Impellers dragging. frequency.
7 Pump in bind. 6 Readjust.
7 Pull master switch, rotate pump by hand
to check. Disassemble the unit to
determine the cause.

Pump vibrating 1 Unit running backwards. 1 Refer to “Hollow Shaft Driver Installation”
excessively and 2 Pump breaking suction and pumping air. on page 24, step 12.
making noise. 2 Lower pump or reduce capacity or
3 Loose fasteners.
increase fluid level.
4 Badly worn motor or pump bearings.
3 Check all bolts, nuts, and re-tighten.
5 Impeller(s) loose on shaft.
4 Pull unit and repair.
6 Pump & motor shafts misaligned.
5 Pull unit and repair.
7 Stress due to piping misalignment.
6 Pull unit and repair.
7 Correct.

Excess wear 1 Abrasives. 1 Clean system.


2 Pump in bind. 2 Pull master switch, rotate pump by hand
3 Vibration. to check. Disassemble the unit to
determine the cause.
3 Determine cause and correct.

Corrosion 1 Impurities. 1 Analyze the fluid.


2 Corrosive liquid. 2 Change to corrosion resistant materials.
Table 10-1: Troubleshooting Chart (Continued)

Document Name: 2001299-VTP-IOM-EN Page 56 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts

11 Parts
DANGER
GENUINE OEM PARTS
• Genuine OEM parts and accessories are designed, tested and incorporated into the
products to help ensure they maintain continued product quality and performance in use.
• As Weir Floway does not test the parts and accessories sourced from other vendors, the
installation of such parts and accessories may adversely affect the performance and
safety features of the products.
• The failure to properly select, install or use authorized parts and accessories is
considered misuse. Damage or failure caused by misuse is not covered by our warranty.
• In addition, any modification of Weir Floway products or removal of original components
may impair the safety of these products in their use.

11.1 Ordering Parts


When ordering spare parts or replacement parts give the following details:
• Pump serial number (available on the nameplate of the unit)
• Pump model (available on the nameplate of the unit)
• Part descriptions with complete part numbers
• Quantity required for each part

11.2 Stocking Spare Parts


Spare parts to be stocked in inventory depend on the following:
• Service type
• Anticipated maintenance cycles
• Allowable down time
• Number of units
It is recommended to maintain a minimum inventory of the following components:
• One complete set of bearings
• Gaskets
• O-rings
• Packing (or Mechanical Seal)
• One spare of each moving part.

11.3 Returning Parts


The following points are to be kept in mind when returning any materials:
• All materials returned to the factory must be accompanied by a RMA number.
• An RMA number can be obtained directly from the factory or by contacting a local Dealer/District
Manager.
• The RMA form must be filled in completely and forwarded as instructed.
• Parts being returned under warranty claim must be submitted with a complete written report along with
the RMA form.
CAUTION
PREVENT TRANSIT DAMAGE TO THE EQUIPMENT
Material returned must be carefully packaged to prevent transit damage. Weir Floway
cannot be held responsible for parts damaged in transit.
For information regarding service and spare parts:
1. Contact your local Weir Minerals Floway Pumps representative.
OR
2. Contact us through email at flowayparts@weirminerals.com or visit www.weirminerals.com/Floway.

Document Name: 2001299-VTP-IOM-EN Page 57 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

12 Parts List
NOTICE
• Separate instruction manual available covering bowl assembly construction and parts list.
• Separate instruction manual available covering mechanical seal construction and parts
list.
• Construction of unit supplied may vary considerably from drawings.

13 3 4

12
1. Driver Shaft
5
2. Driver Key
3. Split Thrust Ring
4. Driver Half Coupling
5. Spacer
6. Adjusting Nut
12
7. Pump Half Coupling
8. Pump Key
9. Dowel Pin
6 10. Pump Shaft
11. Coupling Bolt
12. Lock Nut
7 13. Spacer Bolt

11 8

9
10

Figure 12-1: Adjustable Flanged Coupling

(illustrated with spacer)

NOTICE
Construction for coupling assembly less spacer is identical to that shown except that the
spacer, spacer bolts, and lock nuts are omitted.

Document Name: 2001299-VTP-IOM-EN Page 58 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

1. Headshaft Nut
34 1 2. Gib Key
2 3. Head Shaft
4. Shaft Coupling
5. Coupling Guard Assembly
6. Slinger
33 3
7. Tension Nut
32 8. Tension Nut Plug
9. Tension Nut Lockscrew
31 10. Stuffing Box Cap Screws
4 5 11. Tension Plate
30
6 12. Snap Button Hole Plug
13. Top Lineshaft
29 7 14. Top Adjusting Tube
28 15. Intermediate Column Pipe
8
16. Intermediate Line Shaft
27
9 17. 5 feet Enclosing Tube
18. Bottom Column Pipe
10 19. Column Pipe Coupling
20. Line Shaft Bearing
26 11 21. Shaft Coupling
22. Top Column Pipe
23. Tube Nipple O-ring
25 24. Pipe Plug
24 25. Stuffing Box O-ring
12 26. Discharge Head
23 27. Oil Line with Fittings
28. Nameplate with Drive Screws
13 29. Sight Feed Valve (Auto)
30. Solenoid Valve (O.L)
14 31. Oil Pot with Cover
32. Oil Pot Mounting Bracket
22
33. Driver Bolts and Nuts
15 34. Headshaft Nut Lockscrew

21 16

17
20

19

18

Figure 12-2: Type A - Enclosed Lineshaft

Document Name: 2001299-VTP-IOM-EN Page 59 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

31 1 1. Headshaft Nut
2 2. Gib Key
3 3. Headshaft
30
4. Coupling Guard Assembly
4 5. Motor Stand
29 5 6. Seal Cover Cap Screws
28 7. Seal Housing Cover
6
8. Discharge Head
7
27 9. Pipe Plug
8
10. Mounting Flange Bolts or
26 9 Studs
11. Mounting Flange Gasket
25 12. Suction Barrel
13. Suction Barrel Inlet
24 10 14. Bottom Column Pipe
23 15. Shaft Coupling
11 16. Intermediate Lineshaft
17. Intermediate Column
Pipe
22 18. Bearing Retainer
19. Column Pipe Coupling
21 12 20. Lineshaft Bearing
21. Lineshaft Sleeve
20
22. Top Column Pipe
19 23. Top Lineshaft
24. By-pass with Fittings
18 25. Seal Housing Plug
17 26. Mechanical Seal Assembly
16 27. Motor Stand Bolts and
15 Nuts
28. Seal Cover Gasket or
O-ring
29. Shaft Coupling
14 13 30. Driver Nuts and Bolts
31. Headshaft Nut Lockscrew

Figure 12-3: Type CF - Open Lineshaft

Document Name: 2001299-VTP-IOM-EN Page 60 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

32
31

30
1. Coupling Guard Assembly
1 2. Slinger
29 3. Packing Glands Studs and Nuts
28 2 4. Stuffing Box O-ring
3 5. Packing Rings
27 6. Pipe Plug
4 7. Mounting Flange Bolts or Studs
26 5
8. Mounting Flange Gasket
25 9. Suction Barrel
24 6 10. Suction Barrel Inlet (VF only)
11. Bottom Column Pipe
12. Shaft Coupling
23 7 13. Intermediate Lineshaft
14. Intermediate Column Pipe
22 8 15. Lineshaft Sleeve
16. Bearing Retainer
21 17. Column Flange Bolts
9 18. Column Flange Nuts
19. Lineshaft Bearing
20 20. Top Column Pipe
21. Top Column Flange Cap Screws
22. Stop Column Flange Gasket
19 23. Top Lineshaft
18 24. Stuffing Box Bearing
17 25. Stuffing Box
26. Discharge Head
16 27. Stuffing Box Cap Screws
15 28. Grease Zerk with Cover
14 29. Packing Gland
30. Nameplate with Driver Screws
13 31. Driver Nuts and Bolts
12 32. Driver Shaft

11 10

Figure 12-4: Type F and VF - Open Lineshaft

(illustrated with adjustable flange coupling without spacer and standard packing box)

Document Name: 2001299-VTP-IOM-EN Page 61 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

36 1. Driver Bolts and Nuts


1
2. Motor Stand
2 3. Coupling Guard Assembly
3 4. Motor Stand Bolts and Nuts
35 5. Slinger
4
34 5 6. Seal Housing Plug
6 7. Seal Cover Cap Screws
33 8. Seal Cover Gasket or O-ring
32 7
9. Seal Housing O-ring
31
8 10. Snap Bottom Hole Plug
30
29 9 11. Mounting Flange Bolts or Studs
10 12. Mounting Flange Gasket
28 13. Suction Barrel
27 11 14. Suction Barrel Inlet (AF only)
12 15. Bottom Column Pipe
26 16. Shaft Coupling
25 17. Intermediate Lineshaft
13 18. Intermediate Column Pipe
24
19. Column Flange Bolts
23 20. Bearing Retainer
22 21. Column Flange Nuts
22. Lineshaft Bearing
21 23. Lineshaft Sleeve
20 24. Top Lineshaft
19 25. Top Column Pipe
18 26. Top Column Flange Cap Screws
27. Throttle Bushing Seal
17 28. Pipe Plug
16 29. Seal Housing
30. Mechanical Seal Assembly
15
31. Discharge Head
14 32. By-pass with Fittings
33. Nameplate with Driver Screws
34. Seal Housing Cover
35. Adjustable Flanged Spacer Coupling
Assembly
36. Driver Shaft
24. Bottom Column Pipe

Figure 12-5: Type AF - Open Lineshaft

(illustrated with motor stand, spacer coupling, FF-2 seal and seal housing)

Document Name: 2001299-VTP-IOM-EN Page 62 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

1. Headshaft Nut
2. Gib Key
31 1 3. Headshaft
2 4. Shaft Coupling
5. Slinger
6. Packing Gland Studs and Nuts
3 7. Packing Gland
30 8. Grease Zerk (with Cover)
4 9. Stuffing Box Cap Screws
5 10. Stuffing Box
29 11. Discharge Head
6
28 12. Snap Button Hole Plug
7
27 8 13. Stuffing Box Bearing
26 14. Lineshaft Sleeve
9
15. Bearing Retainer
16. Column Pipe Coupling
25 10 17. Lineshaft Bearing
24 18. Intermediate Lineshaft
23
11 19. Intermediate Column Pipe
22 20. Shaft Coupling
12
21. Top Column Pipe
21 13 22. Pipe Plug
23. Packing Rings
24. Lantern Ring
25. Stuffing Box O-rings
26. By-pass with Fittings
27. Top Lineshaft
28. Nameplate with Driver Screws
29. Coupling Guard Assembly
30. Driver Bolts and Nuts
31. Headshaft Nut Lockscrew
20

19
18

17

16

15

14

Figure 12-6: Type A - Open Lineshaft

(illustrated with column and hi-pressure packing box)

Document Name: 2001299-VTP-IOM-EN Page 63 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

32 1
31 2
30 1. Headshaft Nut
2. Gib Key
29 3. Coupling Guard Assembly
3
4. Tension Nut
28 5. Tension Nut Lockscrew
4
6 Stuffing Box Cap Screws
27 5 7. Discharge Head
26 6 7 8. Top Column Flange Gasket
9. Tension Plate
10. Tube Nipple O-ring
11. Top Adjusting Tube
25 8
12. Underground Discharge Assembly
24 13. Column Gasket or O-ring
9
14. Bottom Column Pipe
10 15. 5 feet Enclosing Tube
16. Intermediate Column Pipe
23
11 17. Column Flange Bolts
22 18. Column Flange Nuts
19. Shaft Enclosing Tube
21 20. Lineshaft Bearing
21. Shaft Coupling
12 22. Top Column Pipe
23. Top Lineshaft
20 24. Top Column Flange Screws
19 25. Stuffing Box O-ring
26. Oil Line with Fittings
18 27. Nameplate with Drive Screws
28. Sight Feed Valve
13
29. Oil Pot with Cover
17 30. Oil Pot Mounting Bracket
31. Driver Bolts and Nuts
32. Headshaft Nut Lock Screw
3. Headshaft
16

15

14

Figure 12-7: Type VU - Enclosed Lineshaft

(illustrated with manually operated lubrication assembly)

Document Name: 2001299-VTP-IOM-EN Page 64 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

13

1
12

11 2

10 3

8 4

1. Packing Gland Studs and Nuts


2. Injection Type Stuffing Box
3. Injection Line
4. Discharge Head
5. Top Adjusting Tube
6
6. Tube Nipple O-ring
7. Stuffing Box O-ring
8. Tension Plate
9. Stuffing Box Cap Screws
5
10. Tension Nut Lockscrew
11. Packing Rings
12. Packing Gland
13. Headshaft

Figure 12-8: Injection Lubrication Arrangement

Document Name: 2001299-VTP-IOM-EN Page 65 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

33
1
32 2
31 3
30 1. Coupling Guard Assembly
4
2. Discharge Head
29 5
3. Slinger
6 4. Seal Cover Cap Screws
28
7 5. Seal Housing Cover
6. Seal Cover Gasket or O-ring
27
8 7. Seal Housing O-ring
26 8. Seal Housing
25 9. Mounting Flange Bolts or Studs
10. Mounting Flange Gasket
24 11. Suction Barrel
12. Bottom Column Pipe
13. Bearing Retainer
9
23 14. Column Flange Bolts
15. Column Flange Nuts
22 16. Lineshaft Bearing
21 10 17. Lineshaft Sleeve
20 18. Intermediate Lineshaft
19 19. Intermediate Column Pipe
20. Shaft Coupling
18
11 21. Top Column Pipe
17 22. Top Column Flange Gasket
16 23. Top Column Bolts and Nuts
24. Pipe Plug
15 25. Top Lineshaft
26. Seal Housing Bearing
14 27. Mechanical Seal Assembly
28. By-pass with Fittings
13 29. Seal Lock Collar with Set Screws
12 30. Nameplate with Drive Screws
31. Adjustable Flanged Spacer Coupling
Assembly
32. Driver Bolts and Nuts
33.Driver Shaft
24. Seal Lock Flush and Quench Pipe Plugs

Figure 12-9: Type VC

(illustrated with adjustable flanged coupling with spacer and mechanical seal)

Document Name: 2001299-VTP-IOM-EN Page 66 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Vertical Turbine Pumps Parts List

2
1. Motor Shaft Coupling
2. Thrust Stand
3 3. Thrust Bearing Assembly
4. Coupling Guard Assembly
4 5. Discharge Head
5 6. Slinger
6 7. Seal Cover Cap Screws
28 7 8. Seal Housing Cover
8 9. Seal Cover Gasket or O-ring
9 10. Seal Housing O-ring
10 11. Seal Housing
12. Mounting Flange Bolts or Studs
11 13. Mounting Flange Gasket
27
14. Suction Barrel
15. Bottom Column Pipe
12 16. Bearing Retainer
26 17. Column Flange Bolts
25 18. Column Flange Nuts
13 19. Lineshaft Bearing
24 20. Lineshaft Sleeve
23 21. Intermediate Lineshaft
22. Intermediate Column Pipe
22
23. Shaft Coupling
21 24. Top Column Pipe
14
25. Top Column Flange Gasket
20 26. Top Column Bolts and Nuts
19 27. Pipe Plug
18 28. Top Lineshaft

17

16

15

Figure 12-10: Type VC

(illustrated with TSO thrust bearing, motor stand, and flexible driver coupling)

Document Name: 2001299-VTP-IOM-EN Page 67 of 67


Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
Excellent
Weir Floway, Inc. Engineering
Solutions

Pump Bowls
IM-106 - 6" Thru 22" - Open Line Shaft Type

INSTRUCTION MANUAL FOR

INSTALLA
INSTALLATION, OPERA
ALLATION, TION AND MAINTENANCE
OPERATION

AND

LIST OF PARTS
PARTS

“Copyright © 2009, Weir Floway, Inc.


Weir Floway, Inc. (“the Company”) is the owner of the copyright and all confidential information in this document. The document may contain
information that is private, confidential or privileged. The document must not be copied in whole or in part, in any form or by any means, and the
information in it must not be disclosed to any person, or used for any purpose other than the specific purpose for which it has been provided, without
the prior written consent of the Company.”
TABLE OF CONTENTS

Page
WARRANTY ........................................................................................................ 2
TABLE OF CONTENTS ....................................................................................... 3
IMPORTANT NOTE ............................................................................................. 4
SECTION I GENERAL INFORMATION & DESCRIPTION .................................. 5
SECTION II DISASSEMBLY ................................................................................ 7
SECTION III INSPECTION AND REPAIR ............................................................ 12
SECTION IV ASSEMBLY .................................................................................... 14
SECTION V PARTS LIST .................................................................................... 16

3
IMPORTANT NOTE
IMPORTANT
F AILURE TO FOLLOW THESE INSTRUCTIONS MA
MAYY CAUSE SERIOUS PER-
SONAL INJURY OR PROPERTY DAMAGE. STUDY THIS INSTRUCTION
MANUAL.

The descriptions and instructions included in this manual cover the standard design of the equipment and any common
deviations when possible. This book does not cover all design details and variations nor does it provide for every possible
contingency which may be encountered. When information cannot be found in this book, contact the nearest
representative.

Do not operate this equipment other than in accordance with the instructions contained in this manual. This equipment
(or a prototype) has been shop tested and found satisfactory for the conditions for which it was sold.

The following instructions should be read completely before starting to install the pump. This equipment is capable of
extended trouble-free operation when properly applied, installed and maintained. These instructions present the basic
information and methods required for proper installation and maintenance of turbine pumps of the size and type indicated
on the front cover.

Floway Pumps standard practice is to ship close coupled pumps assembled. Where long pump lengths, shipping limitations,
handling limitations and headroom limitations prevent complete assembly, we will ship the pump subassembled. It is the
responsibility of the installer to ask for assistance should it be required to properly assemble and install the pump.

CAUTION: The equipment supplied can cause serious personal injur y or death
injury
if mishandled and extreme care is not exer cised in the operation of the
exercised
equipment. NO ONE SHOULD EVER BE ALLOWED NEAR THE SUCTION OR
OPEN DISCHARGE OF THE PUMP DURING OPERA TION
TION.. A double custody
OPERATION
lock should be installed on cir cuit breaker before anyone should be allowed
circuit
to do any checking, maintenance or other work on the equipment. If the unit is
supplied from the factor
factoryy with OSHA approved coupling guards they must
be kept installed at all times during operation to prevent injur y to personnel.
injury

4
SECTION I
GENERAL INFORMATION AND DESCRIPTION

I-1. GENERAL INFORMATION 2. Enclosed lineshaft construction wherein an enclosing


tube is placed over the lineshaft and lubricants are
There are two basic methods of lubricating the lineshaft supplied to the lineshaft bearings thru the enclosing
of turbine pumps which alters the bowl assembly tube. A SEPARATE INSTRUCTION MANUAL IS
arrangement accordingly. These are: AVAILABLE COVERING THIS CONSTRUCTION.

1. Open lineshaft construction uses the pumped fluid


for lubrication. The lineshaft and bearings are “open” to
the pumped fluid and depend on this fluid for bearing I-2. GENERAL DESCRIPTION
lubrication. This construction is often referred to as
“water lubricated” since water is the most common The bowl assembly consists of the following basic
lubricant. THIS MANUAL IS WRITTEN TO COVER components:
THIS TYPE CONSTRUCTION.
1. SUCTION CASE or SUCTION BELL - is the inlet of
the pump. The suction case is provided with tapered
threads for connecting a suction pipe or threaded
strainer to it. The suction bell has a flared entrance
and is preferred for sump applications; clip-on type
strainers are available for attaching to the bell. Both
case and bell house a grease packed bearing with a
sand collar over the top of the bearing to keep out
abrasives.

SUCTION BELL SUCTION CASE

FIG. I-2 TYPES OF BOWL SUCTION PIECES

2. BOWLS - Two types of bowl are used in bowl


assemblies - intermediate and top. A single stage
bowl assembly will utilize a top bowl only, this bowl
directs the fluid from the impeller into the discharge
case. A multiple stage assembly will contain one or
more intermediate bowls and one top bowl at the top
of the “stack”. All bowls contain an impeller mounted
on the shaft and a bearing lubricated by the fluid
being pumped. The top bowl (throttle) bearing on all
models except 18MK and 20MK will extend into the
bottom of the discharge case.
Fig. I-1. BOWL ASSEMBLY GENERAL CONSTRUCTION
OPEN LINESHAFT TYPE

5
3. IMPELLERS - Two types of impellers are available - 5. BOWL SHAFT - is a one piece shaft extending from
“semi-open” or “enclosed”. The arrangement of the the suction bell (or case) thru the intermediate and
bowl assembly is identical with either type requiring top bowls and thru the discharge case where it is
only that the intermediate bowls and suction bell (or connected by a threaded coupling to the lineshaft
case) be designed to provide sealing surfaces for the and hence to the surface mounted driver. The
type impeller used. impellers are mechanically connected to the
pumpshaft by means of tapered lock collets. The
pumpshaft is supported above and below each
impeller by bearings - extra long bearings being
employed at top and bottom.

I-3. CAUSES FOR REDUCED


PERFORMANCE

Before pulling the pump bowl from the well the Installa-
tion and Operation Manual should be reviewed for
causes of reduced performance not related to the
condition of the bowl assembly. Some of the possible
causes of reduced performance could be:

1. Incorrect lateral adjustment. (This is especially


critical with units utilizing semi-open impellers.)

2. Well conditions such as gas or air in the water.

SEMI-OPEN TYPE IMPELLER 3. Change in operating conditions such as increased


pumping water level or increased discharge head
requirements.

4. Slow motor speed due to overload, low voltage or low


frequency.

5. Incorrect direction of rotation.

6. Strainer clogged or suction “sanded in”.

7. Inadequate submergence of pump suction.

After the pump bowls have been pulled but before


sending to the shop for repairs, check the bottom
impeller for foreign material such as rocks or wood
chips. Also check the strainer for obstructions.

ENCLOSED TYPE IMPELLER

Fig. I-3. TYPES OF IMPELLERS

4. DISCHARGE CASE - is the connecting piece


between the top bowl and column pipe. All dis
charge cases contain a “Discharge Case Bearing” at
the top. The 18MK and 20MK units also contain a
second bearing at the bottom.

6
SECTION II
DISASSEMBLY

II-1. GENERAL

Floway bowl assemblies are designed for minimum main- In dismantling a bowl assembly for repair, it is advisable to
tenance; frequency of required maintenance will depend mark the parts so they may be re-assembled in the same
on severity of service, accumulate operating hours, and sequence.
care given the unit during operation. Periodic performance
checks are the best method of determining when repairs
should be made. A significant change in the sound of the
running pump or an increase in vibration may indicate the
need for repairs.

II-2. SHOP REQUIREMENTS

Shop area should be sufficient to lay the parts out in order


of disassembly. Parallel steel or wooden rails are recom-
HEAT TREAT - HARDEN &
mended for cradling the bowl assembly although repairs DRAW TO 45 - 48 ROCKWELL C
can be effected on a flat bench or floor area of sufficient
length to support the complete bowl assembly. The area
DIMENSIONS IN INCHES
should be kept clean through-out the repairs - remember PUMP
SHAFT
SIZE
this is a close toleranced, high speed machine and should A B C D E
be handled as such. 6LK, 6JK, 6JO 1 1.269
1.291
1.010
1.015
6 1.360
1.390
2
8JK, 8JO, 13/16 1.442 1.198 6 1.529 2 1/4
8XK, 8LK, 8FK 1.437 1.203 1.559
II-3. TOOLS 10XK, 10LK, 1.820 1.515 1.875
10DK, 10DO, 10HK 1 1/2 1.815 1.520 6 1/4 1.906 2 5/8
10FK, 12DK, 12DO, 2.072 1.698 2.125
A good mechanics tool box will supply most of the tools 12FK, 12LK 1 11/16 2.067 1.703 7 1/8 2.155 2 7/8
required. The following should be available: 14DK, 14DO, 14FK, 1 15/16 2.348 1.948 8 3/16 2.438 3 1/8
14LK 2.343 1.953 2.468
2.691 2.260 2.750
15DK, 16MK, 18MK 2 1/4 10 3 1/4
Hammers (both hard and soft), screwdriver, allen wrenches, 2.686 2.265 2.780
2.982 2.445 3.040
chain tongs, open or box wrenches, fine flat file, fine 20MK, 22BK 2 7/16 2.977 2.450 10 3.060 3 1/2
triangular file, emery cloth, wire brush.

II-4. SPECIAL TOOLS Fig. II-1. COLLET DRIVER DIMENSIONS

A collet driver for installing and removing the impeller lock


collets is the only special tool required for bowl assembly
repairs. This tool fits snugly over the shaft and is hand 1. Lay complete unit in horizontal position and
operated, the male end being used to seat the collet while block evenly.
the female end is used to knock the impeller off the collet.
2. Remove suction bell (or case) plug.

II-5. DISASSEMBLY - FLANGED PUMP BOWLS 3. Measure end play of shaft by pushing the shaft all the
way down and marking and then pulling all the way up
Figure II-2 illustrates the parts of flanged pump bowl until the impellers hit. Measure and record the
assemblies in sequence of disassembly. distance traveled. (______ inch end play.)

4. Remove shaft coupling. Threads are left hand.

CAUTION:Protect machined sur faces from


surfaces 5. Remove discharge case cap screws.
burrs and scrapes which could cause mis-alignment
on re-assembly. 6. Slide discharge case off shaft.

7
Fig. II-2. 10" and Larger Pump, Exploded View

8
1. Suction Plug
2. Shaft Coupling
3. Discharge Case Cap Screws
4. Discharge Case
5. Bowl Cap Screws
6. Top Bowl
7. Impeller Collet
8. Impeller
9. Intermediate Bowl
10. Suction Case (or Bell)
11. Sand Collar Set Screws
12. Sand Collar
13. Pumpshaft
14. Bowl Bearing
15. Throttle Bearing
16. Suction Bearing
17. Discharge Case Bearing (Top)
18. Discharge Case Bearing (Bottom)
19. Column Adaptor
20. Suction Adaptor

Fig. II-2 (cont.). 10" and Larger Pump, Exploded View

9
7. Remove bowl cap screws and slide top bowl
off shaft.
5. Loosen two set screws located 90 degrees
apart and slide sand collar off shaft.
NOTE: Do not allow weight of bowl to rest on
unsupported shaft.
6. Slide collet driver onto shaft - male end toward
impeller. Strike impeller collet sharply with collet
8. Slide collet driver onto shaft - female end toward
driver. Repeat as necessary to loosen.
impeller. Pull shaft up so that impeller is not against
bowl seat. Strike impeller sharply with collet driver.
7. Slide impeller off shaft.
Repeat as necessary to loosen impeller - pull shaft up
after each blow.
8. Place blade of screwdriver into the split in the
impeller collet to spread and slide off shaft.
9. Insert screwdriver into the split in the impeller collet
to spread and slide off shaft.
9. Remove cap screws from next intermediate bowl
flange and slide intermediate bowl off shaft.
10. Remove impeller .
10. Repeat steps 6 through 9 until all intermediate bowls
11. Repeat steps 7 through 10 until all intermediate bowls
and impellers have been removed.
and impellers have been removed.
11. Slide discharge case off shaft.
12. Slide suction bell (or case) off over bottom end
of shaft.
12. Slide discharge case off shaft.
NOTE: Do not remove sand collar unless the
shaft or sand collar are to be replaced. II-7. DISASSEMBLY
The sand collar left on the shaft will - THREADED PUMP BOWLS
automatically provide the proper impeller
location when assembling. The disassembly of threaded bowls will be identical to
the two methods outlined above except the discharge
13. If the sand collar is removed record the distance from case, intermediate bowls and suction bell (or case) are
the bottom of the shaft to the bottom of the sand connected by threaded joints rather than cap screws.
collar. (______”) The threads are right hand. A pair of chain tongs or
large pipe wrenches will be required for disassembly.
14. To remove sand collar loosen two set screws
located 90 degrees apart and slide sand collar NOTE: Tapping the casting while applying force
off shaft. to the chain tongs will help “break”
stubborn joints. Use a light hammer - do
II-6. ALTERNATE DISASSEMBLY METHOD not strike heavy blows.

Occasionally a bowl assembly will become “locked” due II-8. REMOVING BEARINGS
to foreign materials or seizure of parts in such a way
that the above method of disassembly cannot be used. All intermediate bowl bearings and throttle bearing are
The Floway pump bowl can also be disassembled from pressed into their respective bores and can be either
the suction end as follows: pressed out or machined on the inside diameter until the
wall is thin enough to collapse.
1. Follow steps 1 thru 4 above.
The suction bearing must be pressed out from the bottom
2. Remove suction bell (or case) cap screws. or machined on the inside diameter until the wall is thin
enough to collapse. See Figure II-3.
3. Slide suction bell (or case) off shaft.

4. Measure and record sand collar location in


relation to end of shaft. (_____”)

10
BEARING MUST
DISCHARGE CASE
BE REMOVED IN
BEARING
THIS DIRECTION

DISCHARGE
CASE

Fig. II-4. REMOVING DISCHARGE CASE BEARING

Fig. II-3. REMOVING SUCTION BEARING

The discharge case bearing must be pressed out from


the bottom or machined on the inside diameter until the
wall is thin enough to collapse on the 6" thru 16" sizes.
See Figure II-4. The top discharge case bearing on the
15DK, 18MK and 20MK units is threaded (LEFT hand)
and may be unscrewed; the bottom discharge case
bearing may be pressed out from either end on 18MK &
20MK.

11
SECTION III
INSPECTION AND REPAIR

III-1. INSPECTION AND CLEANING III-2. TROUBLE SHOOTING


After disassembly, all components of the bowl assembly
should be thoroughly cleaned and examined for physical TROUBLE SOURCES PROBABLE CAUSE REMEDY
defects. The following components should be inspected Replace shaft. Check
Crooked shaft. Bent in installation.
for wear, corrosion and damage: bushings.
Replace bearings and
Uneven wear on Misalignment of shafts.
straighten or replace
1. Impellers - check water passageways for signs of bearings. Crooked Shaft.
shaft.
damage from abrasion or corrosion, check impeller
Wear on bearings. Abrasive action. Replace bearings.
skirts against “as new” dimension shown in
Figure III-1. Apply wear rings
Wear on bowl seal and (Figure III-4) if damage
Abrasive action.
impeller skirt. to bowl and impeller
2. Shaft - check shaft for pitting and wear, “as new” not too great.
dimensions are shown in Figure III-1. Check for Wear on bowl vanes Replace bowls if wear
Abrasive action.
and outside wall. is excessive.
straightness - shaft must be straight within .005 total Wear on impeller Replace impellers if
Abrasive action.
indicator reading. vances and shroud. wear is excessive.

3. Bowls - check water passageways for signs of Fig. III-2. TROUBLE SHOOTING CHART
damage from abrasion or corrosion, check impeller
seat against “as new” dimension shown in
Figure III-1.
III-3. REPAIRS

4. Bearings - check all bearings for total clearance over Parts showing signs of damage, cracks or excessive wear
the shaft diameter. It is recommended that all should be replaced. Use only genuine Floway parts for
bearings indicting wear be replaced. The following replacements. Order replacement parts as indicated in
indicates suggested maximum diametrical clearance Section V.
over existing shaft diameter:

1" through 1-3/4" shaft - .020" clearance CAUTION: When repairing a bowl assembly that
1-15/16" through 2-7/16" shaft - .025" clearance
has been in service for several years, the physical
NO M IN AL
NO M IN AL
N O M INA L
DIAM ETRIC AL
condition or strength of all parts such as cap screws,
D IAM ETRICAL
PU M P SIZ E
SHAF T
D IAM ETR ICAL
CLEA RAN CE -
CLEAR AN CE -
C LEAR ANC E -
IM PELLER
AXIAL
CL EARAN C E
bowls and bowl threads must be carefully checked.
DIA. IM PEL LER
SH AF T O .D. TO SKIRT O .D . TO EN D P LAY
SKIR T O .D . TO
BEAR ING I.D .* W E AR R ING
BO W L SEAL I.D.

6LK 1 0.008 0.012 0.013


I.D .
1/4
CAUTION: When attempting to re-work any part
6JO
6JK
1
1
0.008
0.008 0.012 0.013
7/16
3/8
extreme care must be taken to maintain alignment of
8F K 1 3/16 0.008 0.012 0.013 3/8 mating parts and “as new” tolerances.
8JK 1 3/16 0.008 0.012 0.013 9/16
8JO 1 3/16 0.008 9/16
8LK 1 3/16 0.008 0.012 0.013 7/16
8X K 1 3/16 0.008 0.012 0.013 7/16 A. REPLACING BEARINGS
10LK 1 1/2 0.008 0.011 0.013 1/2
10X K 1 1/2 0.008 0.011 0.013 1/2 Replacement bearings are furnished “to size” for press
10D O
10D K
1 1/2
1 1/2
0.008
0.008 0.011 0.013
1/2
9/16
fitting into their respective bores with a .001" to .003"
10H K 1 1/2 0.008 0.011 0.013 7/8 interference fit, if the bearing bore is heavily scarred or
10FK 1 11/16 0.008 0.012 0.013 9/16
12LK 1 11/16 0.008 0.012 0.013 1/2 corroded the part should be replaced or reworked to
12D O 1 11/16 0.008 5/8
12D K 1 11/16 0.008 0.013 0.013 5/8 provide a true bore for the bearing.
12FK 1 11/16 0.008 0.016 0.016 1/2
14LK 1 15/16 0.008 0.013 0.013 5/8
14D O
14D K
1 15/16 0.008
1 15/16 0.008 0.016 0.016
3/4
7/8
B. REPLACING SHAFT
14FK 1 15/16 0.008 0.017 0.016 1 Shaft damage is usually best corrected by replacing the
15D K 2 1/4 0.008 0.015 0.017 7/8
16M K 2 1/4 0.008 0.015 0.015 9/16 shaft. If an attempt is made to re-build the shaft, the
18M K 2 1/4 0.008 0.017 0.018 5/8
20M K 2 7/16 0.009 0.018 0.018 3/4 O.D. must be held within the tolerance shown in Figure
22BK 2 7/16 0.008 0.017 0.018 1 1/4
T O LER A N C ES :
S H AF T D IAM ET ER = + .000 - .002
III-1 and straight within .005" total indicator reading.
B EAR IN G C LEAR A N C E = + .002
IM PELLER SK IR T T O BO W L (W IT H O U T W EAR R IN G S) = + .002
Due to the possibility of interim damage, replacement
IM PELLER SK IR T T O BO W L (W IT H W EAR R IN G S) = + .004 shafts should always be checked for straightness before
*B EAR IN G PR ES SED IN T O H O U SIN G
N O T E: D IM EN SIO N S SH O W N A R E F O R ST AN D AR D C O N ST R U C T IO N - installing.
S PEC IAL M AT ER IALS O R C O N S T R U C T IO N M A Y C AU S E T H ESE
T O C H AN G E

Fig. III-1. BOWL ASSEMBLY DIMENSIONS


AND TOLERANCES
12
C. REPAIRING ENCLOSED IMPELLER AND BOWL
SEAL SURFACES D. REPAIRING SEMI-OPEN IMPELLER SEAT
Enclosed impeller skirt and bowl seal surface wear can Semi-open impeller and bowl seat wear can be cor-
be corrected by installing wear rings if the damage is not rected by refacing the surfaces if the damage is not
excessive. This is usually accomplished by turning the excessive. Depending on the type and extent of wear it
impeller skirt to obtain a smooth surface and then boring may only be necessary to reface one surface. After
the bowl and installing wear rings on either, or both, refacing, the two surfaces must be parallel to each other
surfaces. If the original unit was furnished with either and concentric to the shaft centerline.
bowl or impeller (or both) wear rings, these should be
removed completely and replaced.

Fig. III-4. REPAIRING SEMI-OPEN IMPELLER SEAT

Fig. III-3. REPAIRING ENCLOSED IMPELLER AND


III-4. LUBRICATION
BOWL SEAL SURFACES
Re-pack suction bearing with insoluble grease such as
Marfax #2. Lubricate all bearings and impeller skirts
When wear rings are installed on the impeller it is
with clean grease or oil. Thoroughly clean all bolts,
recommended that a shrink fit be utilized - the interfer-
nuts, threaded connections, and flanges and paint with
ence should be heavy to prevent slippage, 0.010" on the
white lead and oil, or pipe joint compound.
smaller units and up to 0.015" to 0.020" on the larger
sizes. Sufficient heat is then applied to the wear ring to
expand it and allow the wear ring to drop over the
impeller.

When wear rings are installed in the bowl a .003" to


.005" press fit should be used. The wear ring can be
installed by carefully tapping into place. A wooden block
should be used to protect the wear ring.

13
SECTION IV
ASSEMBLY
Assembly of the unit is basically the reverse of disas- over a considerable length the shaft can usually be
sembly. Before proceeding with assembly, clean straightened by supporting on two blocks straddling
thoroughly and check all threads, registers and mating the crooked section and applying pressure to the
faces for burrs. Clean up with file where required. high side to deflect the shaft in the opposite
Lubricate as outlined in paragraph III-4. It is important direction. If the shaft has a sharp crook (dog-leg) it
that the lower sand collar and first impeller are properly is recommended that the shaft be replaced since the
located on the shaft since the shaft projection is deter- shaft will not always remain straight even if
mined by this. satisfactorily straightened.

CAUTION: Cleanliness and proper lubrica-


tion are very important since one small chip, burr or
one dry bearing can be cause for re-doing the whole
job.

Fig. IV-2. CHECKING SHAFT FOR STRAIGHTNESS


Assembly procedure is as follows:
4. Insert shaft into suction bearing, sliding in
The parts reference numbers refer to Figure II-2 (Pages 8 until the sand collar rests against the bearing
and 9). housing.

1. Locate sand collar on shaft and lock in NOTE: Semi-Open impeller pumps require a 1/8"
position with the two set screws. The sand spacer be inserted between the sand
collar should be located in the same position as collar and bearing housing.
found when disassembled and recorded (see
page 6). If the sand collar location was not recorded Install the tie down bolt (1/2" N.C.) thru the bottom of the
refer to Figure IV-1 for standard dimension. suction bell (or case) and thread into tapped hole in end
of shaft as illustrated in Figure IV-3. Tighten the tie
down bolt enough to hold the sand collar firmly against
the bearing housing or spacer. Do not tighten enough to
move sand collar on shaft.

10FK
8LK 14LK
6LK 12LK
8JO 10DO 14DO 16MK
BOWLS 6JK 8XK 10LK 10HK 10XK 12DO 15DK 20MK 22BK
8JK 10DK 14DK 18MK
6JO 12DK
8FK 14FK
12FK
SUCTION
3-9/16 4-3/32 3-3/4 5-1/4 5-7/8 7 3-27/32 5-7/8 6-3/4 9-1/4 9-1/16 10-1/16 10-5/32
BE LL
SUCTION
3-9/16 4-3/32 3-3/4 5-1/4 5-7/8 7 3-27/32 5-7/8 6-3/4 9-1/4 9-1/16 10-1/16
CASE

NOTE: Add 1/8" to above dimensions for all semi open


impeller pumps.
Fig. IV-3. LOCKING SHAFT FOR ASSEMBLY
Fig. IV-1. SAND COLLAR SETTING
5. Slip the first impeller over shaft and seat in
2. Check shaft closely for nicks or burrs - smooth with suction bell (or case).
emery cloth as required.
6. Open collet with screwdriver blade and slide over
3. Check shaft for straightness - shaft must be straight shaft and into tapered impeller bore.
within .005" total indicator reading. Figure IV-2
indicates a recommended method for checking shaft 7. Using the male end of the collet driver, drive the
straightness. If the shaft is not straight it must be collet securely into the tapered impeller bore.
straightened or replaced. If the deflection is gradual Remove collet driver.

14
8. Tighten the tie down bowl securely at this time. If 12. Slide discharge case over pumpshaft. Install and
the sand collar has been raised slightly off the tighten cap screws, or screw discharge case onto
bearing housing by installation of the first impeller top bowl if threaded.
this is O.K.
13. Remove tie down bolt installed in step 4 (and sand
9. Slide intermediate bowl onto shaft and mate collar spacer if used).
with suction bell (or case). On bolted bowl
assemblies rotate bowl to align ribs with ribs on 14. Grasp shaft and rotate by hand to check for binding,
suction bell (or case). also check and play by pulling all the way up and
measuring distance traveled. Check this against
10. Insert and uniformly tighten cap screws on end play recorded in paragraph II-5 or nominal
flanged bowls; use heavy chain tongs to tighten dimensions shown in Figure III-1.
threaded bowls. Recommended torque values are
shown in Figure IV-4 and IV-5. 15. If the suction bearing cavity was not packed with
grease previously this should be done now. After
FASTNER SIZE 1/4 5/16 3/8 7/16 1/2 9/16 5/8 3/4
greasing work shaft up and down several times to
TORQUE (FT.-LB.) 5.4 10 17 27 40 60 84 135 remove excess grease.
Torque values shown are for standard fasteners lubricated with a high
stress lubricant (graphite and oil, moly-disulphite, etc.).
NOTE: Remove enough grease so that plug will
Fig. IV-4. TORQUE VALUES FOR STANDARD not force shaft up when installed
FASTNERS (step 16).

6JO 8JK, 8JO, 16. Install suction bell (or case) plug and tighten.
BOWL SIZE 6LK 10HK
6JK 8LK, 8FK
TORQUE (FT.-LB.) 760 1000 1200 1600
Torque values shown are for standard fasteners
17. Screw column adaptor into place and tighten.
lubricated with a high stress lubricant (graphite and oil,
moly-disulphite, etc.).
18. Screw shaft coupling onto shaft.
Fig. IV-5. TORQUE VALUES FOR STANDARD
THREADED BOWLS 19. (Flanged bowls) Check bolts and nuts for tightness,
also check column adaptor and tube adaptor bearing
11. Repeat steps 6, 7, 8, 9 and 10 until all bowls are in for tightness.
place, including the top bowl (the top bowl is (Threaded bowls) Put one chain tong on column
easily identified by the extra long throttle bearing adaptor and the other on the suction bell (or case)
which projects out the top on all models except and check complete bowl assembly for tightness,
18MK and 20MK). also check tube adaptor bearing for tightness.

15
SECTION V
PARTS

VII-3. RETURNING PARTS


VII-1. ORDERING PARTS
All materials returned to the factory must be accompanied
When ordering spare or replacement parts the pump
by a Returned Material Authorization (RMA) number. An
serial number and size and type of pump must be given.
RMA number can be obtained directly from the factory or
This can be found on the nameplate furnished with the
through your local Dealer or local District Manager. The
unit. Give the complete name of each part as indicated on
RMA Form must be filled in completely and forwarded as
the applicable sectional drawing (Fig. V-1, V-2, or V-3) and
directed thereon. Parts being returned under warranty
the quantity required.
claim must have a complete written report submitted with
the RMA Form.

VII-2. STOCKING SPARE PARTS


CAUTION: Returned material must be carefully
Spare parts to be kept in inventory will vary according to packaged to prevent transit damage - factory cannot
service, field maintenance anticipated, allowable down assume any responsibility for parts damaged in tran-
time and number of units. A minimum inventory of one sit.
complete set of bearings, gaskets, “O” rings, and packing
(or Mechanical seal) and one spare of each moving part is
suggested.

Who to contact for spare parts

1. Contact local authorized Floway Dealer or Representative.

2. If unable to locate an authorized Representative, call Floway’s Factory Parts


Department for the name of the nearest local contact:
Fresno, CA (559) 442-4000

16
Bowl Assembly Parts List
6LK, 6JK, 6JO, 8LK, 8JK, 8JO, 8FK & 10HK Series

Shaft Coupling

Bowl Shaft

Discharge Case Bearing (Top)

Column Adaptor

Discharge Case

Throttle Bearing
Top Bowl
Impeller Collet
Impeller

Bowl Bearing
Intermediate Bowl
Impeller Collet
Impeller

Sand Collar Set Screw


Sand Collar
Strainer Clips Bowl Nameplate
Strainer Screws Suction Bell

Strainer Suction Bearing


Impeller Collet
Suction Plug Impeller

Suction Case
Sand Collar Set Screw
Sand Collar
Bowl Nameplate
Bowl Wear Ring Suction Adaptor
Suction Bearing
Suction Plug

17
BOWL ASSEMBLY PARTS LIST
8XK, 10XK, 10LK, 10DK, 10DO, 10FK, 12DK, 12DO,
12LK, 12FK, 14DK, 14DO, 14LK, 14FK, 16MK SERIES

Shaft Coupling
Bowl Shaft

Column Adaptor

Discharge Case Bearing (Top)

Discharge Case

Discharge Case Cap Screws


Throttle Bearing
Top Bowl

Impeller Collet
Impeller

Bowl Cap Screw

Bowl Bearing

Intermediate Bowl

Suction Bell

Bowl Nameplate

Sand Collar Set Screw


Strainer Clips Sand Collar
Strainer Screws
Suction Bearing

Strainer
Suction Plug
Suction Case
Bowl Nameplate
Sand Collar Set Screw
Sand Collar

Suction Bearing
Bowl Wear Ring
Suction Adaptor

Suction Plug

18
18
BOWL ASSEMBLY PARTS LIST
15DK, 18MK, 20MK SERIES

Shaft Coupling

Bowl Shaft

Column Adaptor
Discharge Case Bearing (Top)
Discharge Case
Discharge Case Bearing (Bottom)
Discharge Case Cap Screws

Bowl Bearing
Top Bowl
Impeller Collet
Impeller
Bowl Cap Screw
Bowl Bearing
Intermediate Bowl
Impeller Collet
Impeller

Sand Collar Set Screw


Sand Collar
Bowl Nameplate
Strainer
Screws Suction Bell

Suction Bearing
Suction Plug
Strainer Impeller

Sand Collar Set Screw


Sand Collar
Bowl Nameplate
Suction Case
Bowl Wear Ring Suction Adaptor
Suction Bearing
Impeller Wear Ring Suction Plug

19
Excellent
Weir Floway, Inc. Engineering
Solutions
2494 S. Railroad Avenue Tel: (559) 442-4000
P. O. Box 164 Fax: (559) 442-3098
Fresno California 93707
www.weirminerials.com

IM106 December 2003 20


PUMP GROUTING PROCESS|
2494 S. Railroad Ave.
P.O. Box 164
Fresno, CA 93707
Tel: (559) 442-4000
Fax: (559) 442-3098

PUMP GROUTING PROCESS

A good grout job is essential for a trouble-free installation. To have a successful


foundation support a non-shrink epoxy grout is required. Do not use ordinary sand,
cement and water mixture as this will shrink when the water evaporates leaving the
underside of the foundation plate insufficiently supported. It is important that the grout
have 100% contact with the underside of the mounting plate. This applies to all
installations whether a soleplate, barrel or discharge head is used.

Grouting of Soleplate, Barrel or Discharge Head:*

1. Thoroughly clean the underside of the plate that will be in contact with the grout
by removing all oil, dirt, grease or other foreign material. Chip the foundation in
the area beneath the plate to remove cement-rich laitance and expose the
aggregate. This will assure a strong concrete/epoxy grout bond. The foundation
must be clean and dry before pouring the grout.
2. Place leveling nuts on the anchor bolts prior to installing the soleplate. Install the
soleplate on the leveling nuts and adjust to its proper elevation (allowing for a
minimum grout thickness of 2”). Level the soleplate to within .002” per linear
foot. This can be accomplished by placing a machinist’s level on a clean,
machined surface on the part. Once the part is leveled install the nuts on the
anchor bolts and secure firmly, but do not tighten.
3. Next, build a trough around the soleplate exterior and interior. Blocking off an
area around each anchor bolt so it will be exposed and not encapsulated in grout
during the pour. This will prevent the grout from spreading toward the pit and
away from the pump.
4. When pouring the grout be absolutely certain that there is 100% contact between
the soleplate and the foundation and that there are no voids in the grout. Air
pockets will leave the soleplate with insufficient support and shorten the life of
the grout.
5. Once the grout has cured, backoff the exposed leveling nuts so the entire weight
of the unit is resting on the grout. Place a machinist’s level on the machined
surface of the plate and confirm that it is within tolerance.
6. If level within tolerance re-pack the area around the anchor bolt with grout. When
grout has cured tighten the anchor bolts to their specified torque value and
confirm level tolerance again.

* When describing the installation process the term soleplate will be used as a
generic to also describe the barrel and head.

Grouting the Pump Std. II 01/14/10


SECTION 2
PARTS LIST WITH RECOMMENDED SPARES
CUSTOMER: FRESH EXPRESSS
SUPPLIER: THE BROWN COMPANY
PURCHASE ORDER NO.: 11513-889
FACTORY CUSTOMER ORDER NO.: 80621
QUANTITY: 1 SERIAL NO.: 80621-1-1 DATE: 6/21/2018

RECOM.
QTY PART NUMBER DESCRIPTION MATERIAL SPARES
1 546531-2051 HEAD,A-10-125#x16.50xTHD-10-.25TP CL. 30 CI
1 101462-1051 PLUG PIPE 0.750 NPT SQ HD CL. 30 CI
1 542959-1130 PLUG SNAP BTN HLE 0.625 PLT. STL.
1 542959-2130 PLUG SNAP BTN HLE 1.000 PLT. STL.
1 549085-1006 NAMEPLATE "WARNING" 316 SS
1 547777-1006 NAMEPLATE UL/FM FIREPUMP - UL AND FM 316 SS
1 551597-006 NAMEPLATE,SMALL FLOWAY LOGO 316 SS
1 2001634-1006 NAMEPLATE,PUMP-LIFTING LUG WARNING 316 SS
14 101217-3006 SCREW DRIVE TYPE U #2 x 0.250 LG 316 SS
1 171000-129 GUARD,SCREEN,RAW-36x096x.040-.38SQ-ON.50 ALUMINUM
4 10001777-006-025 WASHER,FLAT-0.25_SAE 316 SS
4 100484-107-04 SCREW,CAP,HX-0.25-20NCx0.75 316 SS
1 305432-1014 RING,O-05.38IDx0.25RD BUNA-N *
8 100492-106-05 SCREW,CAP,HX-0.50-13NCx1.50 304 SS
2 548021-2145 PLUG,PIPE-0.25NPT_PUSH-IN TYPE PLASTIC
1 544723-6005 FITTING GRSE ZERK 1/8" NPT X 67 1/2 DEG STEEL
1 544723-7007 LUBRICAP #1087K11 RUBBER
1 546395-1051 BOX,STUFFING-5.38x1.50 CL. 30 CI
1 541830-1039 BEARING,SLV-1.50x1.88x3.00LG 932 BRZ *
5 549130-1000 RING,PACKING-1.50IDx0.38SQ-05.88LG ACRYLIC *
1 541781-102 GLAND,PACKING,SPLIT-1.50_NEW STYLE 316 SS
2 102504-107-06 STUD-0.38-16NCx2.50 316 SS
2 100885-222 NUT,HX-0.38-16NC 316 SS
1 549930-1017 SLINGER 1.500 x 3.500 x 0.250 NEOPRENE
1 544069-097-3250 SHAFT,DRIVER-T-150x32.50 416 SS
1 544087-174-2 NUT,ADJUSTING-VHS-1.50_6 HOLES 360 BRASS
1 542963-4086 KEY,GIB-0.38x0.38x2.00 1020 STL.
1 100368-106-12 SCREW,MACHINE,RD,HD,SLT-0.25-20NCx2.00 304 SS
1 542511-079-04213-279 COLUMN,THRD-10x.279Wx042.13LG-BUTT STL. PIPE
2 548831-1010 ASM,COL,PIPE-10.00BUTTx04'-11.50" ASSEMBLY
2 540208-1057 RETAINER,BEARING-10x3.00ID D.I.

J:/80000/80621/FINAL DATA/IOM MANUAL/PARTS LIST/8062101PL, REV.0_06-21-2018 DRAWING NO.: 8062101PL, REV.0


*= RECOMMENDED SPARES Page 1 of 3
DV
"Copyright @2018, Weir Floway, Inc. All Rights Reserved."
PARTS LIST WITH RECOMMENDED SPARES
CUSTOMER: FRESH EXPRESSS
SUPPLIER: THE BROWN COMPANY
PURCHASE ORDER NO.: 11513-889
FACTORY CUSTOMER ORDER NO.: 80621
QUANTITY: 1 SERIAL NO.: 80621-1-1 DATE: 6/21/2018

RECOM.
QTY PART NUMBER DESCRIPTION MATERIAL SPARES
1 542549-097-04475 SHAFT,LINE0-T-S0-150x044.75 416 SS
2 540011-701-06000 SHAFT,LINE0-T-S1-150x060.00 416 SS LS /
304 SS
2 540930-256 BEARING,TYPE-H-1.66x3.00x4.50LG S.B.R. *
1 542122-097-06050 SHAFT,BOWL1-T-C-150x225x060.50 416 SS
4 542568-097 COUPLING,SHAFT-THRD-1.50 416 SS
1 541244-1051 ADAPTER,COL-10NPSx12NPS CL. 30 CI
1 548106-1051 CASE,DISCH-15DK-O-12T CL. 30 CI
1 545611-1039 BEARING THROTTLE 2.250 x 2.750 x 7 932 BRZ *
1 545049-1039 BEARING DISCH CASE 2.250 X 3.500-12LH 932 BRZ *
2 101462-1051 PLUG PIPE 0.750 NPT SQ HD CL. 30 CI
12 100496-085-08 SCREW,CAP,HX-0.63-11NCx2.75 GR. BD
STL.
12 100889-150 NUT,HX-0.63-11NC GR. D STL.
1 548100-1052 BOWL,15DK-NO-INT-2.75-NO-SL CL. 30CIE
1 548100-2052 BOWL,15DK-BW-INT-2.75-NO-SL CL. 30CIE
2 548127-261 RING,WEAR,BOWL-08.09x08.56x1.44 954 BRZ *
1 549371-1039 BEARING,BRZ-2.25x2.75x05.00 932 BRZ *
24 100496-085-04 SCREW,CAP,HX-0.63-11NCx1.75 GR. BD
STL.
2 548103-1430M IMPELLER,15DKH-C-NO 903 BRZ
2 541277-1083 COLLET,IMP-2.25-STD_15DK,16DK,MK,18MK 1215 STL.
1 548104-2051 BELL,15DK-BW-FLG-STD-2.75-FLG CL. 30 CI
1 541279-097 COLLAR,SAND-2.25-3.00-1.38 416 SS
2 100611-107-02 SCREW,SET-HX-0.25-20NCx0.25-CUP_POINT 316 SS
1 542239-1039 BEARING,SUCTION-2.25x2.75x10.00 932 BRZ *
1 101472-3051 PLUG PIPE 2.500 NPT C'SUNK CL. 30 CI
1 544740-1001 NAMEPLATE PUMP BOWL BRZ. BRASS
2 101217-3130 SCREW DRIVE TYPE U #2 x 0.250 LG PLT. STL.
1 547769-1001 STRAINER CLIP ON 15 DK FIREPUMP BRASS
3 547957-1093 CLIP BSKT STRNR 1/8 X 1 X 2-3/8 316 SS
3 100484-107-04 SCREW,CAP,HX-0.25-20NCx0.75 316 SS

J:/80000/80621/FINAL DATA/IOM MANUAL/PARTS LIST/8062101PL, REV.0_06-21-2018 DRAWING NO.: 8062101PL, REV.0


*= RECOMMENDED SPARES Page 2 of 3
DV
"Copyright @2018, Weir Floway, Inc. All Rights Reserved."
PARTS LIST WITH RECOMMENDED SPARES
CUSTOMER: FRESH EXPRESSS
SUPPLIER: THE BROWN COMPANY
PURCHASE ORDER NO.: 11513-889
FACTORY CUSTOMER ORDER NO.: 80621
QUANTITY: 1 SERIAL NO.: 80621-1-1 DATE: 6/21/2018

RECOM.
QTY PART NUMBER DESCRIPTION MATERIAL SPARES
3 101225-144-06 WASHER,LOCK,EXT-TOOTH-0.25 410 SS
1 547799-4010 GAUGE PRESSURE 3.5 DIA 0-300 PSI-.25 NPT ASSEMBLY
1 46495K18 VALVE,BALL 0.25 NPT
1 9770K77 VALVE,SWING,CHECK-1.50x600PSI_CLASS_300
1 101413-1001 NIPPLE PIPE 0.250 NPT x 1.50 LG BRASS

J:/80000/80621/FINAL DATA/IOM MANUAL/PARTS LIST/8062101PL, REV.0_06-21-2018 DRAWING NO.: 8062101PL, REV.0


*= RECOMMENDED SPARES Page 3 of 3
DV
"Copyright @2018, Weir Floway, Inc. All Rights Reserved."
SECTION 3
Flow Control
Weir Floway, Inc.
2494 S Railroad Ave
Fresno, CA 93706 USA

T +1 559 442 4000


F +1 559 442 3098
www.global.weir

1 YEAR WARRANTY
SERIAL NUMBER(S): 80621-1-1
__________________ __________________ __________________
__________________ __________________ __________________
__________________ __________________ __________________

WEIR FLOWAY WARRANTS THE PRODUCT(S) LISTED ABOVE TO BE FREE OF DEFECTS IN WORKMANSHIP
AND MATERIALS.

If within 18 months from the date of shipment or 12 months after the product is first put into operation, whichever
comes first, Buyer discovers that any item listed above is defective and provides written notification within 30 days of
the earliest date which the alleged defect could have been discovered, Weir Floway shall remedy such non-
conformance by, at Weir Floway’s option, adjustment or repair or replacement of the item and any affected part of the
product(s) Ex-works factory.

Buyer shall assume all responsibility and expense for removal, reinstallation, and freight in connection with the
foregoing remedies. Equipment returned for warranty consideration will be subject to review and inspection by Weir
Floway authorized personnel prior to warranty disposition. The same obligations and conditions shall extend to
replacement parts furnished by Floway under warranty. Floway shall have the right of disposal of parts replaced by it.

THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO
EXPRESS & IMPLIED WARRANTIES OF MERCHANTABILITY, IMPLIED WARRANTY OF FITNESS FOR
PARTICULAR PURPOSE, AND CONSTITUTES THE ONLY WARRANTY BY WEIR FLOWAY WITH RESPECT TO
THE PRODUCT(S) LISTED ABOVE. THIS WARRANTY STATES BUYERS’S ONLY & EXCLUSIVE REMEDY
AGAINST WEIR FLOWAY RELATING THE PRODUCT(S) LISTED ABOVE.

Weir Floway and its suppliers shall have no obligation as to any product which has been improperly stored, handled,
or which has not been operated or maintained according to instructions from Weir Floway or supplier furnished
manuals.

Any controversy or claim arising out of or relating to the foregoing warranty, or the breach thereof, shall be settled by
arbitration in Fresno County, California, in accord with the Commercial Arbitration Rules of the American Arbitration
Association.

Page 1 of 1 FMSA 8.2.1, R00