PAC-E Series Numerical Protection Relays

TECHNICAL SPECIFICATIONS(V1.20)

PAC-E100ST(IE)
(Over Current & Earth Fault Relay)

PNC Technologies Co., Ltd.


PAC-E100ST (Over Current & Earth Fault Relay)

1. General Data
1.1 Power Supply
Input Voltage 110~220 VAC±20 %, 50/60 Hz, 80~300 VDC
19~130 VDC
Power Consumption less than 15 VA

1.2 Current Input


Nominal Frequency 50/60 Hz
Phase CT Secondary 5 A or 1A
Ground CT Secondary 5 A or 1A
Input Range 0.1~250 A(5 A rated), 0.01~50 A(1 A rated)
Burden less than 0.5 VA per phase
Current Withstand 1 sec at 100 times rated
, 2 sec at 20 times rated
, continuous at 3 times rated

1.3 Contact Input


Number 1(for TCS), 7(configurable)
Voltage Range 250 VDC maximum
On/Off Voltage Level
Control Voltage 24/48 VDC 110~220 VDC
On Level  19 V  80 V
Off Level  14 V  60 V

Recognition Time less than 10 msec

1.4 Contact Output


Number 3 NO, 2 NO/NC, configurable
Make and Carry 16 A continuous, 250 VAC
30 A, 0.5 sec, 125 VDC, resistive load
Breaking Capacity 5 A, L/R of 25 msec, 125 VDC

1.5 Communication Interface


Front Panel USB RS-232, 38400 bps (fixed), ModbusRTU protocol
Rear Panel 2 Galvanic isolated RS-485, 300~57600 bps
COM1 : ModbusRTU/DNP3.0/ IEC60870-5-103
COM2 : ModbusRTU(for remote setting)

1.6 HMI
LEDs Run, System Error, Trip, Pickup
Local, Remote, CB open, CB Close, 79 active,
6 Programmable LEDs
Keys Local, Remote, Open, Close, Reset, Menu,
Enter, 79 enable
LCD 3P+I0 current RMS can be displayed on single page.

2
PAC-E100ST (Over Current & Earth Fault Relay)

1.7 Type Test


Insulation IEC 60255-5, ANSI/IEEE C37.90.0
Oscillatory Transient IEC 60255-22-1, ANSI/IEEE C37.90.1
Surge Immunity IEC 60255-22-5 class Ⅳ
Fast Transient IEC 60255-22-4 class Ⅳ, ANSI/IEEE C37.90.1
Electrostatic Discharge IEC 60255-22-2 class Ⅲ
RFI Susceptibility IEC 60255-22-3 class Ⅲ, ANSI/IEEE C37.90.2
Vibration IEC 60255-21-1 class Ⅱ
Shock IEC 60255-21-2 class Ⅱ
Seismic IEC 60255-21-3 class I, IEC60068-3-3
Humidity(non-condensing) 56days, 93 %, +40 °C, IEC60068-2-78

1.8 Environmental
Carrying and Storage -30 °C~+75 °C
Operating Temperatures -25 °C~+70 °C
Altitude up to 2000 m

3
PAC-E100ST (Over Current & Earth Fault Relay)

2.Protection
2.1 Definite Time Overcurrent(50_1,50_2,50N_1,50N_2)
Setting
Pickup Current(50_1,50_2) 0.50~100.00 A, 0.05 step*)
Pickup Current(50N_1,50N_2) 0.05~100.00 A, 0.05 step *)
Operating Delay 0.00~300.00 sec, 0.01 step
Dropout Delay 0.00~1.00sec, 0.01 step(valid only for 50N_1 and 50N_2)

Accuracy
Pickup Current 2 % of setting value or 70 mA
Operating Time 3 % or ±35 msec of setting value, @ 2xpickup current
Dropout Level 96~98 % of pickup current
Dropout Time less than 40 msec

Information
Pickup 50_1_PKP_A, 50_1_PKP_B, 50_1_PKP_C, 50_1_PKP_OR
50_2_PKP_A, 50_2_PKP_B, 50_2_PKP_C, 50_2_PKP_OR
50N_1_PKP, 50N_2_PKP
Operation 50_1_OP_A, 50_1_OP_B, 50_1_OP_C, 50_1_OP_OR
50_2_OP_A, 50_2_OP_B, 50_2_OP_C, 50_2_OP_OR
50N_1_OP, 50N_2_OP
*)
for 1A rated, all value divided by 5

2.2 Inverse Time Overcurrent(51,51N)


Setting
Pickup Current(51) 0.50~100.00 A, 0.05 step*)
Pickup Current(51N) 0.05~100.00 A, 0.05 step*)
Time Multiplier 0.01~10.00, 0.01 step
Operating Delay 0.00~300.00 sec, 0.01 step
(Definite Time)
Dropout Delay 0.00~1.00sec, 0.01 step(valid only for 51N)

Trip Characteristic Curve


IEC 60255-3, ANSI/IEEE, KEPCO

 
 
 
  TM sec 
K
T  L
 C
 G  
    1 
  GS  
T : Trip time in second
K,C,L,M : Constants
G : Current input
GS : Pickup current setting
TM : Time multiplier
Curve K L C
IEC Normal Inverse 0.14 0.02 0.00
IEC Very Inverse 13.50 1.00 0.00
IEC Extremely Inverse 80.00 2.00 0.00
IEC Long Inverse 120.00 1.00 0.00
ANSI Inverse 8.9341 2.0938 0.17966

4
PAC-E100ST (Over Current & Earth Fault Relay)

ANSI Short Inverse 0.2663 1.2969 0.03393


ANSI Long Inverse 5.6143 1 2.18592
ANSI Moderately Inverse 0.0103 0.02 0.0228
ANSI Very Inverse 3.922 2 0.0982
ANSI Extremely Inverse 5.64 2 0.02434
ANSI Definite Inverse 0.4797 1.5625 0.21359
KEPCO Normal Inverse 0.11 0.02 0.42
KEPCO Very Inverse 39.85 1.95 1.08
Trip time for G/Gs ≥20 are identical to those for G/Gs = 20.

Accuracy
Pickup Current 2 % of setting value or 70 mA
Operating Time 3 % or ±35 msec of setting value
Dropout Level 96~98 % of pickup current
Dropout Time less than 40 msec for instantaneously reset setting

Information
Pickup 51_PKP_A, 51_PKP_B, 51_PKP_C, 51_PKP_OR, 51N_PKP
Operation 51_OP_A, 51_OP_B, 51_OP_C, 51_OP_OR, 51N_OP
*)
for 1A rated, all value divided by 5
2.3 Negative Phase Sequence Overcurrent (46)
Setting
Pickup Current 0.50~100.00 A, 0.05 step*)
Operating Delay 0.00~180.00 sec, 0.01 step

Accuracy
Pickup Current Accuracy 2 % of setting value or 70 mA
Operating Time Accuracy 3 % or ±35 msec of setting value, @ 2xpickup current
Dropout Level 96~98 % of pickup current
Dropout Time less than 40 msec

Information
Pickup 46_PKP
Operation 46_OP
*)
for 1A rated, all value divided by 5

2.4 Undercurrent (37)


Setting
Pickup Current 0.10~5.00 A, 0.05 step*)
Operating Delay 0.00~180.00 sec, 0.01step

Accuracy
Pickup Current Accuracy 2 % of setting value or 70 mA
Operating Time Accuracy 3 % or ±35 msec of setting value, @ 0xpickup current
Dropout Level 102~104 % of pickup current
Dropout Time less than 40 msec

Information
Pickup 37_PKP_A, 37_PKP_B, 37_PKP_C, 37_PKP_OR
Operation 37_OP_A, 37_OP_B, 37_OP_C, 37_OP_OR
*)
for 1A rated, all value divided by 5

5
PAC-E100ST (Over Current & Earth Fault Relay)

2.5 Thermal Overload (49)


Setting
K-Factor for IEC 60255-8 0.10~4.00, 0.01 step
Time Constant(τ) 1.0~999.9 min, 0.1 step
Thermal Alarm 50~100 %, 1 step

Trip Characteristic Curve(for I/k•IN <= 8)


- With pre-load -Without pre-load
 I   I 2

2
   I 2 
   P      
  k  I N   k  I N     k  I N  
t    ln  2
[min] t    ln  2 [min]
  I     I  
    1    k  I   1 
  k  IN    N  

t : Trip time
τ : Temperature rise time constant
I : Load current
IP : Pre-load current
k : Setting factor
IN : Nominal current
Thermal State Calculation
2
 I 
 m1     1  exp( t /  )   m  exp( t /  )
 k  IN 
θ being calculated every 100ms
I means True RMS

Accuracy
Pickup Current Accuracy 2 % of setting value or 70 mA
Operating Time Accuracy 10 % or ±2 sec of setting value
Dropout Level 98~100 % of thermal trip setting

Information
Alarm 49_ARM
Trip 49_TRIP

2.6 Auto-Reclosing(79)
Setting
Shot Number 1~5, 1 step
Prepare Condition EasyLogic Operand
Cycle Start Condition EasyLogic Operand
Prepare Time 0.05~200.00 sec, 0.01 step
Discriminating Time 0.01~5.00 sec, 0.01 step
Reclaim Time 0.01~350.00 sec, 0.01 step
1st ~ 5th Shot Delay 0.01~300.00sec, 0.01 step

Command
CB Close Command 79_CLS_CMD
CB Final Trip Command 79_OPN_CMD

6
PAC-E100ST (Over Current & Earth Fault Relay)

Information
Auto-Reclosing Ready 79_READY
Auto-Reclosing In Progressing 79_IN_PROG
Auto-Reclosing Fail(Final Trip) 79_FAIL

Reclosing Cycle 1st Delay 79_DELAY_1


Reclosing Cycle 2nd Delay 79_DELAY_2
Reclosing Cycle 3rd Delay 79_DELAY_3
Reclosing Cycle 4th Delay 79_DELAY_4
Reclosing Cycle 5th Delay 79_DELAY_5

2.7 Circuit Breaker Failure(50BF)


Setting
Trip Relay TS1, TS2, TS3, TS4
Pickup Current(CB Closed) 0.50~5.00 A, 0.05 step*)
Operating Delay(Trip Timer) 0.00~60.00 sec, 0.01 step

Accuracy
Pickup Current 3 % of setting value
Operating Time ±20 msec of setting value
Dropout Time less than 40 msec, after trip relay reset

Information
Operation 50BF_OP
*)
for 1A rated, all value divided by 5

2.8 Cold Load Pick-up(COLD_LD)


Setting
Current Detection Level 0.50~2.50 A, 0.05 step*)
OP Delay 0~18000 sec, 1 step
Reset Delay 0~18000 sec, 1 step
Pickup Multiplier 1.00~10.00, 0.01 step

During Cold Load Pickup is operating, all overcurrent protection(50_1, 50_2, 51, 50N_1,50N_2,51N,46)
pickup values are multiplied by Pickup Multiplier setting value.

Accuracy
Pickup Current 3 % of setting value

Information
Pickup COLD_LD_PKP
Operation COLD_LD_OP
*)
for 1A rated, all value divided by 5

2.9 Inrush Detection(I2/I1)


Setting
2nd Harmonic of I2/I1 10~100 % , 1 step
Minimum Current(at least one phase) 0.50~2.50 A, 0.05 step*)
Operating Delay 0.00~60.00 sec, 0.01step
Reset Delay 0.00~60.00 sec, 0.01 step

7
PAC-E100ST (Over Current & Earth Fault Relay)

2nd Harmonic Measuring Time 1/2 cycle

Accuracy
Pickup Current 3 % of setting value
Operating Time ±20 msec of setting value
Dropout Time less than 40 msec

Information
Operation I2/I_OP
*)
for 1A rated, all value divided by 5

3.Control
3.1 Circuit Breaker Control
Setting
Trip Pulse Time 0.1~5.0 sec, 0.1 step
Close Pulse Time 0.1~5.0 sec, 0.1 step
3.2 Setting Group
Number of Setting Group 4
Manual Setting Group Change Command(KeyPad), Communication
Auto Setting Group Change DI function Setting

Auto)
1) If one of DI is set to ”SG SEL0”, then Setting Group change range are 0~1.
2) If 2 DIs set to ”SG SEL0” and ”SG SEL1”respectively, then Setting Group change range are 0~3.
3) If only 1 DI is set to ”SG SEL1”, then Setting Group changing function is blocked(Error)

Manual)
If auto changing is blocked(no settting), manual changing is valid.

3.3 EasyLogic
Contact Output, Programmable LED, 4 User Logic
Logic OR8(8 input OR)
, HALF-OR8(Non inverting 4 input & inverting 4 input OR)
, AND8(8 input AND)
, HALF-AND8(Non inverting 4 input & inverting 4 input AND)
Logic Input Input1~8, refer to < PAC-E100S Logic Input >
Reset Type Self(latched until delay timer is expired)
, Manual(latched until reset is issued)
Reset Input refer to < PAC-E100S Logic Input >
Self Reset Delay 0.00~60.00sec(0.01sec step)

*Conditional automatic reset for LED Last fault only is annuciated.

Contact Input
Function General Input
, CB Open
, CB Close
, Annunciator Reset
, SG SEL0(Setting Group Select 0)
, SG SEL1(Setting Group Select 1)

8
PAC-E100ST (Over Current & Earth Fault Relay)

Logic Design (Contact Output & LED)


Input#1
Input#2
Input#3
Input#4 Reset Type
Input#5
Input#6 = Self Contact Out
Input#7
Input#8 #1 ~ #5
Input#1
Input#2
Input#3
Input#4 0.00 ~ 60.00
Input#5
Input#6
Input#7
Input#8
LED#1~#6
Input#1
Input#2
Reset Type
Input#3
Input#4 = Manual User Logic
Input#5
Input#6
Input#7
#1~#4
Input#8
Input#1
S Q
Input#2
Input#3
Input#4
Input#5 R
Input#6
Input#7
Input#8
Setting
Logic Input

<PAC-E100S Logic Input>


Input Group Input Description
L_OFF Logic ‘0’
Logic
L_ON Logic ‘1’
Command ANN_RESET Annunciator reset by RESET key or communication
CB_OPEN_CTL CB Open Control(Local or Remote)
CB control
CB_CLOSE_CTL CB Close Control(Local or Remote or Auto-Reclosing)
CONT_IN 1 Contact input1 status
Contact inputs … …
CONT_IN 7 Contact input7 status
CONT_OUT 1 Contact output1 status
Contact outputs … …
CONT_OUT 5 Contact output5 status
U_LOGIC1 User logic1 status
User logics … …
U_LOGIC4 User logic4 status
SYS_ERR Self-diagnosis error is occurred
Monitor TCS_ALM Trip circuit supervision alarm is occurred
CB_MON_ALM CB wear monitor alarm is occurred
PROT_PKP_OR Any protection element is picked up
PROT_OP_OR Any protection element is operated
50_1_PKP_OR At least 1 phase of 50_1 is picked up
50_1_PKP_A Phase A of 50_1 is picked up
50_1_PKP_B Phase B of 50_1 is picked up
50_1_PKP_C Phase C of 50_1 is picked up
Protection elements
50_1_OP_OR At least phase of 50_1 is operated
50_1_OP_A Phase A of 50_1 is operated
50_1_OP_B Phase B of 50_1 is operated
50_1_OP_C Phase C of 50_1 is operated
50_2_PKP_OR At least 1 phase of 50_2 is picked up
50_2_PKP_A Phase A of 50_2 is picked up

9
PAC-E100ST (Over Current & Earth Fault Relay)

50_2_PKP_B Phase B of 50_2 is picked up


50_2_PKP_C Phase C of 50_2 is picked up
50_2_OP_OR At least phase of 50_2 is operated
50_2_OP_A Phase A of 50_2 is operated
50_2_OP_B Phase B of 50_2 is operated
50_2_OP_C Phase C of 50_2 is operated
51_PKP_OR At least 1 phase of 51 is picked up
51_PKP_A Phase A of 51 is picked up
51_PKP_B Phase B of 51 is picked up
51_PKP_C Phase C of 51 is picked up
51_OP_OR At least phase of 51 is operated
51_OP_A Phase A of 51 is operated
51_OP_B Phase B of 51 is operated
51_OP_C Phase C of 51 is operated
50N_1_PKP 50N_1 is picked up
50N_1_OP 50N_1 is operated
50N_2_PKP 50N_2 is picked up
50N_2_OP 50N_2 is operated
51N_PKP 51N is picked up
51N_OP 51N is operated
37_PKP_OR At least 1 phase of 37 is picked up
37_PKP_A Phase A of 37 is picked up
37_PKP_B Phase B of 37 is picked up
37_PKP_C Phase C of 37 is picked up
37_OP_OR At least phase of 37 is operated
37_OP_A Phase A of 37 is operated
37_OP_B Phase B of 37 is operated
37_OP_C Phase C of 37 is operated
49_ALARM 49 is alarmed
49_OP 49 is operated
46_PKP 46 is picked up
46_OP 46 is operated
79_READY 79 ready
79_IN_PROG 79 is in progressing
79_FAIL 79 is failed
50BF_OP 50BF is operated
COLD_LD_PKP Cold load pickup is picked up
COLD_LD_OP Cold load pickup is operated
I2/I_OP 2nd harmonic Inrush condition is operated

10
PAC-E100ST (Over Current & Earth Fault Relay)

4. Monitoring
4.1 Self-Diagnosis
Memory After power-on reset, RAM pattern test error
Setting When power-on reset or setting is changed,
Non-volatile memory setting is checked.
Setting value is out of boundary
Total check-sum Error
A/D Converter A/D running counter stop
, A/D reference input is out of boundary
Auto-Calibration Each analog input calibration factor is out of boundary
, Ttotal check-sum error
4.2 Trip Circuit Supervision(TCS)
Only One DI is used for TSC.
TCS DI Input is checked every 10 msec.
If consecutive check is failed after expiring timer, TCS fail annunciation is reported.
After TSC fail is cleared, the failure annunciation is reset automatically

Setting
Time setting 0.02 ~ 600.00sec, 0.01 step

4.3 CB wear monitor


This is alarm function which is operated when at least 1 phase of 3 phase accumulated data of CB
wear monitor is reached alarm level(ALARM setting).
The user should set the breaker maintenance curve with 3 piont paired value of interrupted
current vs allowed operation. CB_MON_%x accumulated value are integrated every time breaker
open/close operation. The each phase interrupted current are captured at 1.5 cycle after the trip
conatact output is activated.
Because CB_MON_%x are saved non-volatile memory, the accumulated value are kept during
relay power off or ‘FUNCTION’ is disabled. The accumulated value can clear in ‘COMMAND’
menu in front panel or via communication.

11
PAC-E100ST (Over Current & Earth Fault Relay)

Breaker maintenance curve

Setting
1. FUNCTION ENABLED, Whether function use or not
DISABLED
2. LOW kA 0.00~650.00 kA Current at low current point CB
3. LOW CNT 0~65000 - Allowed operation at low current point maintenance
4. MID kA 0.00~650.00 kA Current at middle current point curve setting
5. MID CNT 0~65000 - Allowed operation at middle current point
6. HIG kA 0.00~650.00 kA Current at high current point
7. HIG CNT 0~65000 - Allowed operation at high current point
8. ALARM 0.0~100.0 % Alarm level

Metering
CB_MON_%A CB wear monitor A phase accumulation % value( ~250.0%)
CB_MON_%B CB wear monitor B phase accumulation % value( ~250.0%)
CB_MON_%C CB wear monitor C phase accumulation % value ( ~250.0%)
CB_MON_ALM 3 phase alarm logic OR of CB wear monitor
CB_MON_ALM_A A phase alarm of CB wear monitor
CB_MON_ALM_B B phase alarm of CB wear monitor
CB_MON_ALM_C C phase alarm of CB wear monitor

12
PAC-E100ST (Over Current & Earth Fault Relay)

5. Measurement
Current
Phase, Ground Current RMS
Input Range 0.5~250 A*)
Accuracy ±2 %(0.5~1 A), ±0.5 %(1~6 A) *)

Sequence Current
Positive/Negative/Zero Sequence Current RMS

Harmonic Current
2nd Harmonic Current A/B/C

Frequency
Range 40 Hz~70 Hz, Phase A Current
Accuracy ±0.03 Hz at Nominal current input
*)
for 1A rated, all value divided by 5

6. Record
6.1 Events(Including Fault Report)
Storage Capacity Max 700 events with 1 msec time resolution
Data System reset
, Annuciator reset
, Setting changed
, Clear event record
, Clear waveform recording
, Protection pickup/operate/release etc.
Analog input information(current rms) are recorded when a protection element triggered.

6.2 Fault Report


Storage Capacity The latest 50 faults with occurred time.

6.3 Waveform
Storage Capacity Max 16sec@50Hz
Record Type(block*cycle) 16*50, 8*100 or 4*200(16*1s, 8*2s or 4*4s@50Hz)
Trigger Position 0 ~ 99%
Trigger Source Protection trip
, Change of contact input status
Data Current sample(IA, IB, IC, IN)
, Contact input/Output status
, Enabled protection status

6.4 CB Trip Counter


Trip counter is accumulated in non-volatile memory after only protection trip is issued.
Trip Counter range are 0 to 65535, free running(roll-over).
This counter can be edited by local front key operation.

13
PAC-E100ST (Over Current & Earth Fault Relay)

7.Communication
7.1 USB
Front Panel USB232, 38400 (fixed), ModbusRTU

7.2 RS-485
2 Galvanic isolated RS-485
BPS 300~57600
Protocol COM1 : ModbusRTU , DNP3.0 or IEC60870-5-103
COM2 : ModbusRTU(fixed)
Connection
Num COM1 Num COM2

1 -- 1 --
2 RS485_DATA- 2 RS485_DATA-
3 RS485_DATA+ 3 RS485_DATA+
4 -- 4 --
5 RS485_COM 5 RS485_COM
6 -- 6 --
7 -- 7 --
8 -- 8 --
9 -- 9 --

8.PC Software
Relay setting upload and download.
Event upload from relay and save to file.
Waveform upload from relay and analysis in PC supported.

14
PAC-E100ST (Over Current & Earth Fault Relay)

9. Mounting and Dimensions

Panel Mounting, Draw-out type

<Dimensions of PAC-E100ST>

Rear Terminal Block


PAC-E100ST
No Description No Description No Description No Description
30 TCS_COM 21 TCS_P 11 IA+ 1 IA-
31 DI1_COM 22 DI1_P 12 IB+ 2 IB-
32 DI2_COM 23 DI2_P 13 IC+ 3 IC-
33 DI3~7_COM 24 DI3_P 14 IN+ 4 IN-
34 DI4_P 25 DI5_P 15 TS1_COM 5 TS1_NO
35 DI6_P 26 DI7_P 16 TS2_COM 6 TS2_NO
36 PWR+ 27 PWR+ 17 TS3_COM 7 TS3_NO
37 PWR- 28 PWR- 18 TS4_COM 8 TS4_NO
38 SURGE 29 SURGE 19 TS5_COM 9 TS4_NC
20 TS5_NO 10 TS5_NC

15
PAC-E100ST (Over Current & Earth Fault Relay)

<Dimensions of PAC-E100ST(IE)>

Rear Terminal Block


PAC-E100ST(IE)
No Description No Description No Description No Description
30 TCS_COM 21 TCS_P - - - -
31 DI1_COM 22 DI1_P - - - -
32 DI2_COM 23 DI2_P - - - -
33 DI3~7_COM 24 DI3_P - - - -
34 DI4_P 25 DI5_P 15 TS1_COM 5 TS1_NO
35 DI6_P 26 DI7_P 16 TS2_COM 6 TS2_NO
36 PWR+ 27 PWR+ 17 TS3_COM 7 TS3_NO
37 PWR- 28 PWR- 18 TS4_COM 8 TS4_NO
38 SURGE 29 SURGE 19 TS5_COM 9 TS4_NC
20 TS5_NO 10 TS5_NC

16
PAC-E100ST (Over Current & Earth Fault Relay)

10. External Connection Diagram

PAC-E100ST(IE) C B A
15
TS1_COM
5 PAC_E100ST(IE )
TS1_NO
16
TS2_COM
6 IA
TS2_NO
17
TS3_COM IB
7 Rogowski coil CT
TS3_NO
8 IC or LPCT
TS4_NO
18
TS4_COM 8Pin Modular Jack
9
TS4_NC
TS5_NO 20
19
TS5_COM PAC_E100ST
10
TS5_NC 11
IA 1
21 12
TCS_P
30 IB 2
TCS_COM 22
DI1_P 13
31
DI1_COM IC 3
23 14
DI2_P
32
DI2_COM IN 4
24
DI3_P
34
DI4_P
25
DI5_P
35 27,36
DI6_P AC/DC 110~220V POWER+
28,37
DC 19~130V
29,38
POWER-
26 SURGE
DI7_P
DI3~7_COM 33
GROUND
BUS
COM1 COM2
RS485 RS485
USB RS-232
DB-9 DB-9
Front
Rear Rear

<External Connection Diagram of PAC-E100ST>

11.Ordering Information
Power Supply 125 VDC/110 VAC or 250 VDC/220 VAC
24/48 VDC
CT Rated Secondary 1 A or 5 A
Language English, Turkish

17
PAC-E100ST (Over Current & Earth Fault Relay)

DISPLAY STATUS CONTACT INPUT CONT IN1 ~ 7


Top CONTACT OUTPUT CONT OUT1 ~ 5
USER LOGIC USER LOGIC1~4
- IA,IB SELF DIAGNOSIS MEMORY, SETTING, AD CONVERTER,
IC,IN measure CALIBRATION, TRIP CIRCUIT, CB MONITOR
- P#] : Active COM COM1~2, Tx/Rx Counter display
Setting Group PROTECTION IOC1(50_1), IOC2(50_2), TOC(51), IOCG1(50N_1),
- R#] : Reclosing IOCG2(50N_2), TOCG(51N), THERMAL(49), UC(37),
Counter NSOC(46), AREL(79), CBFAIL(50BF), COLD LD,INRUSH
(during reclosing
MEASURE CURR(IA), CURR(IB), CURR(IC), CURR(IN),SEQ(I0), SEQ(I1), SEQ(I2),
in progress )
THERMAL,FREQUENCY, TRIP COUNT, CB_MON%
RECORD EVENT
WAVEFORM
SYSTEM INFO. Version Display

SETTING SYSTEM POWER SYSTEM FREQUENCY, PHS CT RATIO,


GND CT RATIO
WAVEFORM TYPE, TRIG.POS, TRIG.SRC
CB CONTROL TRIP PULSE, CLOSE PULSE
TCS FUNCTION, DELAY
CB MONITOR FUNCTION, LOW kA, LOW CNT, MID kA, MID CNT,
HIGH kA, HIGH CNT, ALARM
COM1 FUNCTION, SLAVE ADDR, BPS, PROTOCOL
COM2 FUNCTION, SLAVE ADDR, BPS, PROTOCOL
DNP3.0 TX DELAY, LINK CONFIRM, LINK RETRY,LINK
TIMEOUT, SBO TIMEOUT,WR TIME INT, COLD RESTART
CONTACT INPUT CONT IN1 ~ 7
LOGIC, INPUT1~8,
CONTACT OUTPUT CONT OUT1 ~ 5
RESET TYPE, INPUT,DELAY
LED LED1 ~ 6 LOGIC, INPUT1~8,
RESET TYPE, INPUT,DELAY
USER LOGIC USER LOGIC LOGIC, INPUT1~8,
1~4 RESET TYPE, INPUT,DELAY
PASSWORD
PROTECTION1 FUNCTION, PICKUP, DELAY, BLOCK
IOC1(50_1)
PROTECTION2
PROTECTION3 IOC2(50_2) FUNCTION, PICKUP, DELAY, BLOCK
PROTECTION4 TOC(51) FUNCTION, CURVE, PICKUP, MULTIPLIER,
**: Active setting DT DELAY, BLOCK
group IOCG1(50N_1) FUNCTION, PICKUP, DELAY, DROP DELAY, BLOCK
IOCG2(50N_2) FUNCTION, PICKUP, DELAY, DROP DELAY, BLOCK
TOCG(51N) FUNCTION, CURVE, PICKUP, MULTIPLIER,
DT DELAY, DROP DELAY, BLOCK
THERMAL(49) FUNCTION, K-FACTOR, TIME CONS, ALARM,
BLOCK
UC(37) FUNCTION, PICKUP, DELAY, BLOCK
COMMAND CONT OUT TEST
NSOC(46) FUNCTION, PICKUP, DELAY, BLOCK
EVENT CLEAR
AREL(79) FUNCTION, SHOT NUM, PRE CON,
WAVE CLEAR START CON, PREPARE TIME, DISCRIM TIME,
THERMAL CLEAR 1ST DLY TIME, 2ND DLY TIME, 3RD DLY TIME,
4TH DLY TIME, 5TH DLY TIME, BLOCK
TRIP CNT EDIT
CBFAIL(50BF) FUNCTION, TRIP RELAY, PICKUP, DELAY,
CB MON CLEAR BLOCK
COLD LD FUNCTION, PICKUP, OP DELAY, RST DELAY,
CHANGE SG
OC PKP MUL, BLOCK
PANEL TEST INRUSH(I2/I1) FUNCTION, I2/I1, MIN I1, OP DELAY,
RST DELAY, BLOCK

18