Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Out-or-Phase Switching Voltages and which can appear across the circuit
breaker poles. Since the extinction of an
Their EKect on High-Voltage a-c arc will generally take place at a zero
of the current wave, the currents in each
phase of a balanced 3-phase circuit will
Circuit Breaker Performance not be interrupted at the same instant.
Therefore, the dynamic voltages which
are of interest for this investigation are:
W. M. LEEDS D. J. POVEJSIL 1. The dynamic voltage existing across one
FELLOW AIEE NONMEMBER AIEE open circuit breaker pole when the other two
poles are conducting.
2. The dynamic voltages existing across
THE possibility that transmission line the more probable conditions involving each of two open circuit breaker poles when
circuit breakers may be subjected to this unusually severe duty. the third pole is conducting.
as much as double normal line-to-ground This paper comprises an analytic study 3. The dynamic voltages existing across
voltage if opened during a system dis- of dynamic voltages to be expected at the each of three open circuit breaker poles.
turbance when sections on either side of terminals of a tie-line circuit breaker dur-
the circuit breaker are out-of-phase, has ing the separation of two parts of a system In order to calculate the dynamic
been recognized by manufacturers and 180 degrees out of phase. Transient voltages, it is necessary to define the
operating personnel for a long time. How- voltage crests have been investigated on following quantities.
ever, only a few isolated cases of trouble the analogue computer for a typical sys- Rl+jX,=R2+jX2=positive and negative
have been traced to this exceptional cir- tem under faulted and unfaulted condi- sequence impedances looking into network
cuit breaker duty, and therefore it has tions and the results are compared with from circuit breaker terminals
not been felt justifiable in circuit breaker oscillographic records obtained on an ac- Ro+jXo=zero-sequence impedance looking
specifications to insist on proven ability tual power system. Finally, high power into network from circuit breaker terminals
to handle double voltage interruptions.1 laboratory data obtained on modern high- E1 and E2=vector voltages to neutral on
Experience indicates that many circuit voltage circuit breakers opening fault each side of circuit breaker when all three
breakers have struggled through out-of- currents at twice normal voltage and poles are open
phase operations (which inherently in- higher are evaluated in the light of the El.= El-E2= vector voltage across circuit
volve only a fraction of the circuit break- maximum possible duty indicated by the breaker poles when all three poles are open
er's current interrupting capacity because analytic study.
It will be noticed that all quantities
of considerable line impedance) by con-
have been defined at the point of the cir-
tinuing to arc until separating parts of the Analytical Study cuit breaker location in the circuit. The
system have swung sufficiently in phase
purpose of this method of definition is to
again to permit interruption. For a sy7stem disturbance, the total re-
allow such factors as shunt loads and line
Nevertheless, there is evidence that this covery voltage across a circuit breaker at
capacitance to be taken into account
problem is becoming of greater impor- any point in the system can be considered without changing the fundamental ex-
tance because of the tremendous increase to consist of two components.
pressions. These factors are considered
in power concentration resulting from the 1. Dynamnic or normal frequency v-oltage in the calculation of E12, which depends
integration of large generating centers into component. upon:
gigantic interconnected power pools. 2. Transient component.
Circuit breaker intermpting capacities
now are required in the range from 3,500,- In the case of disturbances initiated by Paper 52-16, recommended by the AIEE Switch-
gear Committee and approved by the AIEE Tech-
000 to 10,000,000 kva, and the conse- switching, the magnitude of the transient nical Program Committee for presentation at the
AIEE Winter General Meeting, New York, N. Y.,
quences of faulty operation are likely to component is a function of the dynamic January 21-25, 1952. Manuscript submitted
become much more serious than hereto- voltage. Therefore, the first step in this October 24, 1951; made available for printing
November 20, 1951.
fore. study was the analytical determination of W. M. LEEDS and D. J. POVEJSIL are both with
These conditions justify a more de- the dynamic voltages which could exist Westinghouse Electric Corporation, East Pitts-
tailed inquiry into the actual condi- across the poles of a circuit breaker open- burgh, Pa.
tions to which tie line circuit breakers ing under completely out-of-phase condi- The authors are indebted to the Bonneville Power
Administration for the test data obtained during
may be subjected. Also, there is a nec- tions. special fault tests on their system made to deter-
essity for definite data to show that such An understanding of the operation of mine the magnitude of transient voltages which
could be obtained under out-of-phase conditions on
circuit breakers are capable of handling 3-pole circuit breakers is important in the an actual power system.
6)
v
Dynamic voltage across first pole to open
U
VW
(122)(210)=256 per cent
Dynamic voltage across second pole to
044 open=(110)(210)=231 per cent
Dynamic voltage across third pole to open =
lx/oH 61
210 per cent
C-
.E0,
This example shows that the dynamic
voltages across the circuit breaker poles
for completely out-of-phase conditions
in an effectively-grounded system are
LL considerably greater than double voltage,
the figure generally mentioned in dis-
cussions of out-of-phase switching duty.
This fact has been recognized by Hans
Thommen,2 who suggested an added
factor of 20 per cent to allow for shifting
of the neutral potential caused by cur-
rents flowing through the ground circuit.
The maximum values of dynamic
voltages occur on a completely un-
grounded system. If the system of
Figure 2 were ungrounded, the maximum
dynamic voltages would be
Dynamic voltage across first pole to open =
(1.50)(210)=315 per cent
Dynamic voltage across second pole to
open =(1.73)(210)=363 per cent
zX/OH Dynamic voltage across third pole to open =
I; 210 per cent
~%-0--- LINE A 6
GROUNDING
3 BC
LINE
TRANSFORMER
A
, A
PHASE SEQUENCE - A B C
OPENING SEQUENCE a A C B
Figure 3. Single-line diagram of general system used for analogue
Figure 2. Typical system used for example computer study
Therefore, it can be seen that the out- was represented was assumed to have no of transmission line on each side of the
of-phase switching problem is even more ground wires because it was expected that circuit breaker, the maximum recovery
acute for systems which are not effec- the most serious recovery voltages would voltage does not necessarily occur on the
tively grounded. (The region of "ef- occur for this case. first peak of the recovery voltage wave.
fective grounding" as defined by the The subtransient reactance of the gen- This phenomenon is shown by Figure 4,
AIEE is shown by the shaded portions of eration and the connected transformer and can ke explained by the fact that the
Figure 1; that is, Xo/X1 < 3, Ro/X, < 1. 3) capacity at each end of the line was as- asymmetry of the circuit causes a time-
At this point, it should be emphasized sumed to be 40 per cent on a 324-mega- phase difference in the reflected waves
that the Xo/Xl ratio which is used to as- volt-ampere base, and the voltages be- which reach the circuit breaker. A sub-
certain dynamic voltages during out-of- hind subtransient reactance were made sequent discussion in this paper will in-
phase switching is not the same as that equal to 100 per cent of nominal system terpret this result as it applies to circuit
used to calculate dynamic overvoltages voltage. The transformers were con- breaker performance.
during faults. This difference can be seen nected delta-Y, grounded on the high
by referring to Appendix I. During side. A synchronous switch, which could
faults, the X0/Xl ratio at the fault loca- be adjusted to interrupt each phase at a Table 1. Test Numbers 1, 2, 3, and 4 for
tion is equal to the parallel combination zero of the current wave, was used to Generator Voltages 180 Degrees Out of Phase
of the zero-sequence networks on each simulate the circuit breaker. Sending and Receiving End Transformers Neu-
side of the fault divided by the parallel Using the basic system shown in Figure trdl Solidly Grounded. Generdtion at Each
combination of the positive-sequence net- 3, an extensive series of tests were per- End Equivalent to 324 Megavolt-Amperes
works on each side of the fault. How- formed to determine the magnitude of the
ever, for calculations involving voltages recovery voltages which would occur Maximum Recovery
across open conductors, the proper X0/Xl upon the opening of the tie circuit breaker Voltage Across Pole
in Per Cent of
ratio is equal to the series combination of when the opposite ends of the system were Normal Line-to-
180 degrees out of phase. The type of Line Length, Neutral Peak
the zero-sequence networks on each side Miles First Maximum
of the opening divided by the series com- tests performed and the results obtained A B Phase Peak Peak
bination of the positive-sequence net- are summarized in Table I. The crest
works on each side of the opening. recovery voltage figures are expressed in Test Number 1. Grounded Transformer Bank at
Circuit Breaker Not Connected. Circuit Breaker
per cent of normal line-to-neutral peak Opening Sequence ABC
Analogue Computer Study voltage. 100 ..100 . A. 366 . 366
In addition to the tests outlined in (a) 100 ..100 . B . 360 . 360
100. .10..C . 310 . 310
The characteristics of the analogue Table I, other tests were performed to de- 100 ..150 . A. 336 . 336
(b) 100. .15. .B . 336 . 336
computer4 make it ideally suited to the termine the effects of various system 100 ..150 . . C 250 . 276
parameters. The results of all tests are 100 ..200 . A . 270 . 366
solution of practically all power system 100 ..200 . B . 246 . 348
transient problems. In most cases, the discussed in the following sections. 100. .20..C . 240 . 284
procedure for setting up a problem and Test Number 2. 100-Megavolt-Ampere Grounded
EFFECTS OF CIRCUIT BREAKER POSITION Transformer Bank Connected to "A" Line at
obtaining a solution is the same with the Circuit Breaker Location. Circuit Breaker Open-
ing Sequence =ABC
analogue computer as with the a-c net- The tests show that the highest re- 100 ..100 . A . 324 . 324
work calculator. However, for transient covery voltages appear when the system (a) 100 ..100 . B . 324 . . 324
studies it is more advantageous to use a is symmetrical, or approximately sym- 100 ..100 . C . 300 . 300
100 ..200 . A . 326 . 326
3-phase representation of the system metrical, about the circuit breaker. (b) 100 ..200 . B . 300 . 300
100 ..200 . C . 260 . 260
rather than the positive, negative, and (Tests 1(A) and 4(A).) On the basis of
Test Number 3. 100-Megavolt-Ampere Grounded
zero sequence network representation this observation, it may be concluded that Transformer Bank Connected to "B" Line at
which is commonly used in network cal- the maximum recovery voltages under Circuit Breaker Location. Circuit Breaker Open-
ing Sequence=ABC
culator studies. In this way the transient completely out-of-phase conditions are 100 ..200 . A . 246 . 340
voltages can be measured directly rather approximately equal to twice the volt- (a) 100 ..200. B . 282 . 320
100 ..200. C . 224 . 294
than as positive, negative, and zero se- ages which would appear across the cir-
Test Number 4. Same as Test Number I Except
quence components. cuit breaker poles if the circuit breaker that Generation at End of "A" Line is Increased to
The basic system studied on the ana- were switching a grounded 3-phase fault 1,000 Megavolt-Amperes
at the circuit breaker location. Further 100 ..100. A . 370 . 370
logue computer is shown in Figure 3. Two (a) 100 ..100 . B . 370 . 370
pi sections per phase were used to repre- proof supporting this conclusion is shown 100..100 .10.C . 330 . 330
later in the paper. 100. .150 . A . 350 . 350
sent each 100-mile section of 230-kv line (b) 100. .150 . B . 350 . 350
since it was found that additional pi sec- When the circuit is decidedly asym- 100 150 . C . 320 .
100. .200 . A . 340 .
320
370
tions mnade no appreciable difference in metrical about the circuit breaker loca- 100. .200 . B . 320 . 370
the recovery voltages. The line which tion, especially with regard to the length 100. .200 . C . 240 . 330
0 c xy
c o NEGATIVE
l NEGATIVE on
Ion
n n x ---
ZERO ZERO
on
on
A B
Figure 10. Sequence network connections
(A) One circuit bredker pole open (B) Two circuit bredker poles open
Referring to Table I, it is seen that the come the voltage unbalancing effect of part of this paper shows that during out-
maximum recovery voltage is 370 per cent the capacitance between the moving con- of-phase switching the neutral shift
of normal line-to-neutral voltage. Doub- tact cross-arm and the grounded tank, caused by ground return currents before
ling the results obtained for switching see Figure 9. the third phase clears may result in
grounded 3-phase faults on the Coulee- However, under out-of-phase switching dynamic voltages of as high as 2.5 times
Midway line and also the results from its conditions at a time when there are no normal. It is doubtful whether most
analogue yields 338 per cent and 380 per faults on the lines connected to either side present-day circuit breakers are capable
cent respectively. of the circuit breaker, the approximatelv of handling such an extreme condition
symmetrical location of potentials results consistently. However, considering the
Circuit Breaker Interrupting Ability in a fairly equal division of voltage be- low probability of encountering this
tween the halves of each circuit breaker theoretical maximum voltage, it may not
The short-circuit interrupting ability pole. In fact, it can be argued that if a be economical to make such performance
of a high-voltage circuit breaker is usu- circuit breaker with no voltage-dividing a definite specification which could in-
ally verified by single-phase fault tests at means has been tested successfully in the vrolve considerable additional cost to pro-
normal line-to-ground voltage either in a laboratory with at least 87 per cent of vide the necessary factors of safety in in-
high power laboratory or on a large power rated line-to-line voltage applied to one terrupting ability. Before coming to a
system. Since the first circuit breaker pole with one terminal grounded (in- conclusion on this point, it will be well to
pole to clear a 3-phase ungrounded fault stead of the actual 3-phase ungrounded consider the magnitude of the transient
on a system with grounded neutral will fault condition of two-thirds voltage overvoltages that could be encountered
have a dynamic recovery voltage of 1.5 above ground on one terminal of the first under the more pessimistic of out-of-
times line-to-neutral voltage, 86.6 per pole to clear and one-third voltage below phase switching condition.
cent of line-to-line voltage, (see Figure ground on the other terminal) then the
8) until the line-to-line fault which re- same circuit breaker should be capable of RATE OF RISE OF RECOVERY VOLTAGE
mains is cleared by the other two poles, handling the balanced out-of-phase condi- AND TRANSIENT VOLTAGE CRESTS
some further fault testing is often in- tion of approximately double line-to- It is well known that the criterion of a-c
cluded either at this voltage or even with neutral voltage across each circuit breaker arc interruption is based on building up
full line-to-line voltage across a single pole. To take a 230-kv circuit breaker as dielectric strength in the contact gaps
pole. an example, a single-pole test at 198 kv to immediately folloAing a current zero at
The situation at the present time and ground with a very conservative estimate such a rate that the voltage required for
probably in the future is that high power of 70 per cent 30 per cent voltage dis- breakdown is always above the rising re-
laboratories are not of sufficient capacity tribution between the two halves of the covery voltage. Therefore, a knowledge
to test the largest circuit breakers at circuit breaker would indicate that the in- of the transient voltage crest and the time
their full short-circuit interrupting rating terrupting units on the high side were to reach it is necessary in addition to the
even on a single-phase basis. However, capable of handling 139 kv which is ap- magnitude of the dynamic voltage in
the unit method of testing by which only proximately half of the out-of-phase order to establish the actual severity of
a subdivision of a circuit breaker is veri- voltage that might appear across the cir- the interrupting duty on a circuit breaker.
fied at a proportionately reduced voltage- cuit breaker. Traveling waves over the connecting
for instance, a half-pole tested at half W0here voltage division in a circuit transmission lines and the interaction of
line-to-neutral voltage-provides fault breaker is controlled, for instance by re- reflected waves make calculations of
currents of greater magnitude by appro- sistor units of a megohm or less, the per- transient voltage conditions during
priate changes in the test transformer formance under out-of-phase conditions switching very difficult. However, some
ratio. The validity of the unit method of might be checked up to double voltage by of the answers to typical situations have
testing, of course, depends on the effec- field tests at normal line-to-neutral volt- been indicated by the analogue computer
tiveness of shielding means or voltage- age but with one-half of the interrupting on which transient conditions of a system
dividing impedances in establishing an units shunted out. In fact, the sym- set up in miniature have been studied.
equal share of the recovery voltage across metrv of out-of-phase voltages, as just These show transient overshooting of as
each unit of the circuit breaker. discussed above, might make such a half- much as 60 per cent above the dynamic
The dead-tank circuit breaker pro- pole test also reasonably valid even for voltage crest. Under the most unfavor-
vides an unequal division of voltage dur- circuit breakers without voltage dividing able out-of-phase switching conditions
ing grounded fault conditions unless suit- impedances. within the limits of effective grounding
able compensation is provided to over- However, the analytic study in the first (RoIX1 <1 and XO/X1 <3), using a dy-
JANUARY 195-2 Leeds, Po-vejsil-Out-of-Phase Switching Vloltages 93
namic voltage factor of 130 per cent from resistors in the circuit breaker as part of Table Ill. High Power Laboratory Over-
the curves of Figure 1 (A), the peak of the the contact assembly. voltage Interrupting Tests
transient voltage could theoretically reach
1.3X2X1.6 or a little over four times HIGH POWER LABORATORY TESTS Inter-
rupted
Inter-
rupting
Single-Phase
normal line-to-ground crest voltage. On Test Test Voltage Current, Time,
A number of modern high-voltage cir- No. Ky X Normal Amperes Cycles
a 230-kv system this amplitude would be cuit breakers have been tested at double
230/V/3 X V/2 X4.16 = 780 kv, which ex- voltage and higher with quite satisfac- A. 138-kv 3,500-Megavolt-Ampere Circuit Breaker
ceeds by 30 per cent the crest voltage of tory results. Table III shows data taken 2-91303.. ..160 . 2.0 ....... 210.. 2.4
2-91304.... 160 . 2.0 ....... 1140 .. 2.4
the 425-kv 1-minute insulation test ap- from High Power Laboratory tests on 05....160 . 2.0 ....... 1060 .. 2.8
plied across the fully-open contacts of cir- typical circuit breakers from the 138-, 06.... 160 . 2.0 ....... 1160.. 2.9
2-91307... .160 . 2.0 ....... 3500 .. 2.8
cuit breakers for use on 230-kv systems 161-, and 230-kv voltage classes. Note 08... .160..... 2.0...... 2550 ......2.9
09....160 . 2.0 ....... 3300.. 2.6
with effectively grounded neutrals. This that on the 10,000-megavolt-ampere 230- 2-91310. ...160 . 2.0 ....... 4550 .. 2.9
emphasizes the extreme duty that is in- kv circuit breaker, the tests were carried 11 .... 160 ..... 2.0....... 6050 ..... 2.8
12 .... 160. 2.0. 4550 .. 2.7
dicated by these calculations. as high as 360 kv across a single-pole
B. 161-kv 10,000-Megavolt-Ampere Circuit
In some cases, the maximum voltage is unit, or 2.7 times normal line-to-ground Breaker
reached on a later crest than the first peak voltage, without damage to the inter- 2-95215.... 198. 2.1 ....... 95 . 2.5
16....198 . 2.1 ....... 105 . 2.5
of the transient recovery voltage, see rupters. The maximum crest voltage 17.... 198 . 2.1 ....... 80 . 2.3
Figure 4, which greatly lowers the prob- withstood on the recovery voltage tran- 2-95218.... 198. 2.1 ....... 250 . 2.4
19....198. 2.1 ....... 235 ... 2.3
ability of arc reignition since the proc- sient was in the neighborhood of 560 kv. 20.... 198 ..... 2.1 ....... 235......2.5
esses of deionization in the interrupter Although damping in the laboratory cir- 2-95221. ...198 . 2.1 . 1000 .. 2.6
22....198 . 2.1 . 1000 .. 2.6
will have had time to be practically com- cuit limited the overshooting to approxi- 23.... 198 . 2.1 . 1280 .. 2.6
pleted. Also, it has been shown that mately 20 per cent, the frequency oscilla- 2-95224... ..198 . 2.1 . 2600 .. 2.8
25 ... .198 ..... 2.1 ...... 2600 ..... 2.7
there are many factors in practice which tion was quite high, around 3,000 cycles, 26 ... .198 ..... 2.1 ...... 2900......2.5
compared to the 300- to 400-cycle oscilla- 2-95227... ..198 . 2.1 . 4400 .. 2.6
can reduce the magnitude of the transient 28.... 198 . 2.1 . 4600 .. 2.7
voltage that theoretically may appear tion encountered in the field. 29....198 . 2.1 . 6100 .. 2.7
across the terminals of a tie circuit breaker. C. 230-kv 10,000-Megavolt-Ampere Circuit
Breaker
For instance, unequal line lengths on Conclusions 2-100323. ..264 . 2.0 . 1500 . ..2.6
either side of the circuit breaker, unequal 2-100324. ..330 . 2.5 . 2050.. 2.5
25...330 . 2.5 . 1800 .. 2.9
generating capacity on the two ends of 1. An analytic study, supplemented 26...330 . 2.5 . 2050.. 2.8
the line, grounded transformers or heavy by measurements on the analogue com- 2-100327 ... 360 . 2.7 . 2250 .. 2.7
28...360 . 2.7 . 2000.. 3.0
loads in the vicinity of the circuit breaker, puter, has been made for the typical volt-
overhead ground wires, attenuation of age transmission systems under out-of-
traveling waves due to corona and other phase voltage conditions to determine with transient overshooting of approxi-
losses in the lines and iron losses in the magnitude of possible recovery voltages mately 25 per cent, opening fault currents
transformers, any and all of these may that may appear across opening tie-line up to, say, 25 per cent of the current in-
cut down the maximum value of the volt- circuit breakers. Even on effectively- terrupting capacity rating.
age. grounded systems, it appears that dy-
In addition, it is quite probable that namic voltages up to 2 to 2.5 times nor-
interruption under an out-of-phase con- mal plus 25 to 60 per cent transient over- Appendix 1. Calculation of
dition, which is an infrequent occurrence shoot are theoretically possible. These re- Dynamic Voltages
in itself, will usually occur when the dif- sults are in agreement with data from field
ference in-phase is much less than the full tests on the Bonneville Power Adminis- With one pole open, Figure 10, assume cir-
cuit breaker pole in phase a has cleared.
180 degrees. tration 230-kv system made for the pur- Then
At the present time, there are no test pose of indicating possible voltages under
specifications for circuit breakers covering completely out-of-phase conditions. Ia = 0
interrupting ability under out-of-phase 2. The presence of permanent faults Vxyb Vxyc 0
= =
voltage conditions. If the most unfavor- on a system under out-of-phase conditions since
able conditions indicated by this study as does not increase the magnitude of the Vxya Vxya,l + Vxya,2+ Vxya,o
=
theoretically possible, although extremely maximum recovery voltages on the circuit Vzxb a2 Vxya,i+a Vxya,2+ Vxya,o
=
unlikely, were taken as the basis of a breakers separating parts of the sys- Vxyc a Vzya,i+a2 Vxya,2+ Vzya,o
=
difficulties now experienced with present circuit breaker interrupting performance Ia,l -(Ia,2+Ia,o)
equipment. However, a reasonable test to checking the ability to handle higher These relations dictate the sequence net-
might be the interruption of moderate than normal recovery voltages encoun- work connections shown in Figure 10.
short-circuit currents up to, say, 25 per tered by tie-line circuit breakers under Employing Thevenin's Theorem, and de-
cent of rating at twice normal line-to- out-of-phase conditions. In view of the fining constants as was done in the text, the
ground voltage. The natural frequency relatively minor damage attributed to voltage across the open pole can be written:
of the recovery voltage transient should such relatively infrequent overvoltage in-
be not less than 300 cycles, with no more terrupting duty in service, it may be un- XI
Ey= 3E121 R021 2XI
economical to design for the theoretical ErV=El20R, +2R 2(1 2Xo
external circuit damping than enough to 2]
limit the overshooting to approximately maximum voltages indicated by this IXIo XI+e +X
25 per cent of normal crest. Additional study. Tests are suggested, however, up
damping could, of course, be provided by to at least double line-to-ground voltages For constant values of Exy/E,2 and Ru/X1,
94 Leeds, Povejsil-Out-of-Phase Switching Voltages JANUARY 1952
this equation can be rewritten in the form of AGES UP TO 400 Kv, Hans Thommen. Report 109, Transactions), volume 58, August 1939, pages 386-
a family of circles with radii equal to International Conference of Larch High Voltage 94.
Electric Systems (Paris, France), 1946.
6. PRACTICAL CALCULATION OF ELECTRICAL
3K V\11+(RI/Xl)1 2. STANDARD FOR NEUTRAL GROUNDING DEVICES.
AIEE Standard Number 32, 1947.
TRANSIENTS ON POWER SYSTEMS, R. D. Evans,
R. L. Witzke. Electrical Engineering (AIEE
4K2-9 Transactions), volume 62, November 1943, pages
3. ELECTRICAL TRANSMISSION AND DISTRIBUTION 690-96.
where K = Exv/E12, and centers at REFERENCE BOOK. Westinghouse Electric Corpo-
7. TRANSIENT PERFORMANCE OF ELECTRIC POWER
ration (East Pittsburgh, Pa.), 1950.
SYSTEMS (book), Reinhold Rudenberg. McGraw-
-2K2 2(R1/X1)K2 4. SYSTEM RECOVERY VOLTAGE DETERMINATION Hill Book Company, New York, N. Y., 1950.
4K2 -9' 4KI2_9 BY ANALYTICAL AND A-C CALCULATING BOARD 8. TRANSIENT RECOVERY VOLTAGES AND CIRCUIT-
METHODS, R. D. Evans, A. C. Monteith. Electrical BREAKER PERFORMANCE, R. C. Van Sickle. Elec-
Engineering (AIEE Transactions), volume 56, July trical Engineering (AIEE Transactions), volume 61,
References 1937, pages 695-703. November 1942, pages 804-13.
5. POWER-SYSTEMS TRANSIENTS CAUSED BY 9. TRANSIENTS IN POWER SYSTEMS (book), H. A.
1. PROBLEMS CONNECTED WITH THE RUPTURING SWITCHING AND FAULTS, R. D. Evans, A. C. Mon- Peterson. John Wiley and Sons, Inc., New York,
OF ALTERNATING CURRENTS AT VERY HIGH VOLT- teith, R. L. Witzke. Electrical Engineeiring (AIEE N. V., 1951.