Suspensions

Suspension Insulators
Ball and Socket Type

5 3/4"

10 3/4"

CATALOG REFERENCE NUMBER 8255 8256 8257 8258


ANSI CLASS (C29.2 - 1992) 52-3 52-3 52-3 52-5

CRITICAL DISTANCES, inches


Dry arcing distance 7 3/4 7 3/4 7 3/4 7 3/4
Leakage distance 11 13/16 11 13/16 11 13/16 11 13/16

MECHANICAL VALUES
Combined M & E strength, pounds 15000 18000 20000 25000
Mech, impact strength,inch.pounds 55 55 90 90
Routine proof test load, pounds 7500 9000 10000 12500
Time load test value, pounds 10000 12000 13500 15000
Maximum working load, pounds 7500 9000 10000 12500

ELECTRICAL VALUES, kV
Low-frequency dry flashover 80 80 80 80
Low-frequency wet flashover 50 50 50 50
Critical impulse flashover, positive 125 125 125 125
Critical impulse flashover, negative 130 130 130 130
Low-frequency puncture voltage 110 110 110 110

RADIO INFLUENCE VOLTAGE DATA


Low-frequency test voltage, RMS to ground 10 10 10 10
Maximum RIV at 1000 kHz, µV 50 50 50 50

Note 1: ANSI 70 gray is standard. Brown available by request


Note 2: The insulators can be requested with extra hot-dip galvanized layer in caps and bolts for contaminated areas
Note 3: The insulators can be requested with zinc sleeve ball bolt for contaminated areas
Note 4: Part numbers 8256 and 8257 comform to ANSI Class 52-3 specifications. However they carry higher strength
rating than that required by standard
Suspension Insulators
Clevis Type

1/2"

5/8"

11/16"

5 3/4" 11/16"

11/16"

10 3/4"

CATALOG REFERENCE NUMBER 8265 8267


ANSI CLASS (C29.2- 1992) 52-4 52-4

CRITICAL DISTANCES, inches


Dry arcing distance 7 3/4 7 3/4
Leakage distance 11 13/16 11 13/16

MECHANICAL VALUES
Combined M & E strength, pounds 15000 20000
Mech, impact strength,inch.pounds 55 90
Routine proof test load, pounds 7500 10000
Time load test value, pounds 10000 13500
Maximum, working load, pounds 7500 10000

ELECTRICAL VALUES, kV
Low-frequency dry flashover 80 80
Low-frequency wet flashover 50 50
Critical impulse flashover, positive 125 125
Critical impulse flashover, negative 130 130
Low-frequency puncture voltage 110 110

RADIO INFLUENCE VOLTAGE DATA


Low-frequency test voltage, RMS to ground 10 10
Maximum RIV at 1000 kHz, µV 50 50

Note 1: ANSI 70 gray is standard. Brown available by request


Note 2: The insulators can be requested with extra hot-dip galvanized layer in caps and bolts for contaminated areas
Note 3: Part numbers 8265 and 8267, can be requested with zinc sleeve ball bolt for contaminated areas
Note 4: Part number 8267 comform to ANSI Class 52-4 specifications. However it carry higher strengh rating than that
required by standard
Guy Strains
Guy Strain
Insulators

2 7/8"
2 1/2"
3" 2 1/8"
4 1/4"
3 1/2" 2 1/2" 1 3/4"
2 1/4"
1 3/4"

5/8" 7/8"

8502-70 8504-70

3 1/2"

3 3/8"
2 3/8"
4 1/2"
2 3/8"
6 3/4"
4 1/16"
5 1/2" 2 5/8"
3 1/8"

1" 1"

8506-70 8451-70

CATALOG REFERENCE NUMBER 8502-70 8504-70 8506-70 8451-70


ANSI CLASS (C29.4-1989 rev. 2002) 54-1 54-2 54-3 54-4
CRITICAL DISTANCES, inches
Leakage distance 1 5/8 1 7/8 2 1/4 3
MECHANICAL VALUES, pounds
Tensile strength 10000 12000 20000 20000
ELECTRICAL VALUES, kV
Low-frequency dry flashover 25 30 35 40
Low-frequency wet flashover 12 15 18 23
Note: ANSI 70 gray is standard. Brown available by request

|
Pins
Low - Medium Voltage Pin
Insulators
3 3/8"
3 3/8”
2 1/4"
2 1/4”
R 6/10" R 1 7/10”
3 1/2"
2 1/4"
R 5/8"
R9/16" R 9/16”

R 5/8" 3 3/4”
3 3/4" 1 1/2"
3 1/4" 1 1/2"

3 3/4" 4 3/4" 4 3/4”

6188R-70 6184R-70 6184RA-70


4"
2 7/8"
4"
RF 1"
2 7/8"
R 1"

RF 9/16"

R 9/16"

4 7/8" 2"
4 3/8" 1 3/4"

5 19/32" 7"

6183R-70 7061R-70

CATALOG REFERENCE NUMBER 6188R-70 6184R-70 6184RA-70 6183R-70 7061R-70


ANSI CLASS (C29.5-1984 rev. 2002) 55-2 55-3 55-3 55-4 55-5
CRITICAL DISTANCES, inches
Dry arcing distance 3 3/8 4 1/2 4 1/2 5 6 1/4
Leakage distance 5 7 7 9 12
Minimum pin height 4 5 5 5 6
MECHANICAL VALUES, pounds
Cantilever strength 2500 2500 2500 3000 3000
ELECTRICAL VALUES, kV
Typical application voltage 7.2 11.5 11.5 13.2 15
Low-frequency dry flashover 45 55 55 65 80
Low-frequency wet flashover 25 30 30 35 45
Critical impulse flashover, positive 70 90 90 105 130
Critical impulse flashover, negative 85 110 110 130 150
Low-frequency puncture voltage 70 90 90 95 115

RADIO INFLUENCE VOLTAGE DATA


Low-frequency test voltage, RMS to ground, kV 5 10 10 10 15
Maximum RIV at 1000 kHz, µV 50 50 50 50 100
Note 1: ANSI 70 gray is standard. Brown or white available by request
Note 2: Conductive Glaze - applied to head, side wire grooves and pin hole of one-piece units
Note 3: Neck Sizes - “C” & “F” conform to industry standards
Note 4: Pin Hole Sizes - Standard 1” to 15 kV and ref. 320275R-70, 1 3/8” for the rest of 23 kV & 35 kV units

|
High Voltage Pin
Insulators
4 5/8”

3 1/2”

4 3/4" R 3/4”
3 1/2"
R 1" R 9/16”
R 5/8"

5 3/4”
2”
5 1/2" 2 1/4"

8 3/8"

320275R-70 8248R-70
5 1/8”

4” 5 1/4”
4”
R 3/4”
R 3/4”
R 9/16”
R 9/16”

2”

2”

9”

10435R-70 8190R-70

CATALOG REFERENCE NUMBER 320275R-70 8248R-70 10435R-70 8190R-70


ANSI CLASS (C29.5-1984 rev. 2002 / C29.6-1996 rev. 2002) 55-6 56-1 56-2 56-3
CRITICAL DISTANCES, inches
Dry arcing distance 8 7 8 1/4 9 1/2
Leakage distance 15 13 17 21
Minimum pin height 7 1/2 6 7 8
MECHANICAL VALUES, pounds
Cantilever strength 3000 2500 3000 3000
ELECTRICAL VALUES, kV
Typical application voltage 23 23 23 34.5
Low-frequency dry flashover 100 95 110 125
Low-frequency wet flashover 50 60 70 80
Critical impulse flashover, positive 150 150 175 200
Critical impulse flashover, negative 170 190 225 265
Low-frequency puncture voltage 135 130 145 165
RADIO INFLUENCE VOLTAGE DATA
Low-frequency test voltage, RMS to ground, kV 22 15 22 30
Maximum RIV at 1000 kHz, µV 100 100 100 200
Note 1: ANSI 70 gray is standard. Brown available by request
Note 2: Conductive Glaze - applied to head, side wire grooves and pin hole of one-piece units
Note 3: Neck Sizes - “C” & “F” conform to industry standards
Note 4: Pin Hole Sizes - Standard 1” to 15 kV and ref. 320275R-70, 1 3/8” for the rest of 23 kV & 35 kV units