Detailed Performance Summary For Encon - Ascendas

Project: ~Untitled3 03/07/2017


Prepared By: Balaji 09:56PM

PackagedChillerReport:DoNotEdit

Unit Information
Tag Name: Encon - Ascendas
Model Number: 30XW0552P
Condenser Type: Water Cooled
Nameplate Voltage: 400-3-50 V-Ph-Hz
Quantity: 1
Manufacturing Source: Shanghai, China
Refrigerant: R134a
Minimum Capacity: 15.00 %
Shipping Weight: 3312 kg
Operating Weight: 3025 kg
Unit Length: 3055 mm
Unit Width: 1008 mm
Unit Height: 1743 mm

Performance Information
Cooling Capacity: 546.5 kW
Heating Capacity: 646.3 kW
Total Unit Power: 101.9 kW
Cooling Efficiency (E.E.R.): 5.362 kW/kW
Heating Efficiency (C.O.P.): 6.341 kW/kW

Acoustics Information
A-Weighted Sound Pressure Level: 81 dbA

Evaporator Information
Fluid Type: Fresh Water
Fouling Factor: 0.0880 (sqm-K)/kW
Leaving Temperature: 6.70 °C
Entering Temperature: 13.70 °C
Fluid Flow: 18.62 L/s
Pressure Drop: 15.7 kPa

Condenser Information
Fluid Type: Fresh Water
Fouling Factor: 0.1760 (sqm-K)/kW
Leaving Temperature: 35.00 °C
Entering Temperature: 29.40 °C
Fluid Flow: 27.76 L/s
Pressure Drop: 36.3 kPa

Electrical Information
Unit Voltage: 400-3-50 V-Ph-Hz
Standby Power: 0.1 kW
Minimum Voltage: 360 Volts
Maximum Voltage: 440 Volts
Power Factor: 0.87

Electrical Electrical
Amps (Un) Circuit 1 Circuit 2
Max Unit Current 242.0
Draw (RLA)
Max Start Up 450.0
Current (ICF)
Nominal Unit 162.0
Current Draw (A)

Packaged Chiller Builder China Export 3.39l Page 1 of 3


Detailed Performance Summary For Encon - Ascendas
Project: ~Untitled3 03/07/2017
Prepared By: Balaji 09:56PM

Accessories and Installed Options


No Accessories or Installed Options selected

Packaged Chiller Builder China Export 3.39l Page 2 of 3


Detailed Performance Summary For Encon - Ascendas
Project: ~Untitled3 03/07/2017
Prepared By: Balaji 09:56PM

Load Line

Unit Performance (1)


Percent Full Load Cooling Capacity, % 100.00 90.00 80.00 70.00 60.00 50.00 40.00 30.00 20.00 10.00
Percent of Full Load Power, % 100.00 85.84 76.41 66.15 55.90 47.44 41.64 40.51 39.38 13.03
Unloading Sequence Default Default Default Default Default Default Default Default Default Default
Cooling Capacity, kW 546.5 491.8 437.2 382.5 327.9 273.2 218.6 163.9 109.3 54.6
Heating Capacity, kW 646.3 577.5 513.4 448.6 383.7 320.6 260.1 204.4 148.6 64.3
Total Unit Power, kW 101.9 87.5 77.9 67.4 57.0 48.4 42.4 41.3 40.1 13.3
Nominal Unit Current Draw (RLA) 161.2 139.1 125.1 110.4 95.8 83.2 74.3 72.5 70.7 -
Cooling Efficiency, kW/kW 5.36 5.62 5.61 5.67 5.76 5.65 5.15 3.97 2.72 4.11
Heating Efficiency, kW/kW 6.34 6.60 6.59 6.65 6.73 6.63 6.13 4.95 3.70 4.84
Evaporator Data
Fluid Entering Temperature, °C 13.70 12.99 12.29 11.59 10.89 10.19 9.49 8.80 8.10 7.40
Fluid Leaving Temperature, °C 6.70 6.70 6.70 6.70 6.70 6.70 6.70 6.70 6.70 6.70
Fluid Flow Rate, L/s 18.62 18.62 18.62 18.62 18.62 18.62 18.62 18.62 18.62 18.62
Fouling Factor, (sqm-K)/kW 0.0880 0.0880 0.0880 0.0880 0.0880 0.0880 0.0880 0.0880 0.0880 0.0880
Condenser Data
Fluid Entering Temperature, °C 29.40 29.40 29.40 29.40 29.40 29.40 29.40 29.40 29.40 29.40
Fluid Leaving Temperature, °C 35.00 34.40 33.85 33.29 32.72 32.18 31.65 31.17 30.69 29.96
Fluid Flow Rate, L/s 27.76 27.76 27.76 27.76 27.76 27.76 27.76 27.76 27.76 27.76
Fouling Factor, (sqm-K)/kW 0.1760 0.1760 0.1760 0.1760 0.1760 0.1760 0.1760 0.1760 0.1760 0.1760

(1) Compressor cycling is expected. Stated performances are average.

Sound pressure level measured in accordance with AHRI Standard 575. Sound pressure level is the free field sound data (the unit is placed in free field over a reflecting plane).
Outside the scope of AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-
P) and AHRI Standard 551/591 (SI).

Packaged Chiller Builder China Export 3.39l Page 3 of 3