Sei sulla pagina 1di 4

UL

®
Okotherm CIC Fire Resistant Cable R

Type TC Cable
Multiple Tinned or Nickel Coated Copper Conductors 90°C Dry Rating

Nickel coated or tinned coated copper • Sunlight resistant.


A conductors, Okotherm CIC fire resis-
tant thermoset silicone insulation, • Flame Retardant - passes the
color or number coded fiber glass Vertical Tray Flame Test
B braid, cabled conductors, cable tape, requirements of UL 1277.
Okoclear® TP (TPPO) jacket.
• Passes the IEEE 1202-1991 verti-
C Tinned Coated Copper cal tray flame test.
or Nickel Coated Copper
D • Conforms with "LS" limited smoke
Okotherm Thermoset requirements of UL 1277 (3 or
E Silicone more Type RHH insulated conduc-
ICEA S-73-532, Method tors).
F 3,4 or 5.
• 90°C continuous rating.
Fiber Glass Braid
• 130°C emergency overload
Black Okoclear TP rating.
(TPPO)
• 250°C short circuit rating.
UL 1277, ICEA S-73-532 (NEMA WC • Quality control inspected to meet
57), ICEA S-95-658 (NEMA WC70), or exceed applicable industry
ASTM B-33 & B-355 standards.
• Jacket resistant to moisture and
IEC 60331, UL 1277, IEEE 1202 most chemical atmospheres.
• Thermal stability at elevated
Okotherm CIC 600 volt power & con- temperatures.
trol cables are used in systems where,
in the event of a fire, circuit integrity is • Easy to install and terminate.
required in order to maintain a process • Mechanically rugged.
or to safely shut down the process.
Fire resistance is determined by com- • Fire Resistant - qualified to
pliance to the IEC 60331 circuit 2000°F for 3 hours per IEC 60331.
integrity fire test. Okotherm CIC ca-
bles maintain circuit integrity based on
qualification to the IEC standard
60331 for all temperatures and times
up to and including 2000°F for three
hours. When exposed to the fire
source, the Okotherm CIC insulation
becomes an electrically insulating ce-
Tinned or Nickel Coated Copper
Conductors
ramic-like ash that is capable of
Okotherm (Silicone) Thermoset maintaining the operating voltage.
Insulation
Fiberglass Braid - Coded per ICEA
Okotherm CIC power & control
Glass Fillers cables may be installed in dry loca-
Cable Tape tions, as an aerial cable on a
Black Okoclear TP (TPPO) Jackett messenger and in any approved
raceway.
Okotherm CIC Fire Resistant Cable
Type TC Cable
600V Power & Control Tray Cable

=
202-17-3452 14 (7X) 2 45 0.48 0.18 124 147 15 15
202-17-3453 14 (7X) 3 45 0.51 0.20 142 165 15 15
45
202-17-3454 14 (7X) 4 60 0.59 0.27 202 226 15 15
202-17-3455 14 (7X) 5 60 0.64 0.32 238 277 15 15
202-17-3457 14 (7X) 7 60 0.70 0.39 297 336 15 14
202-17-3459 14 (7X) 9 60 0.81 0.52 345 384 15 14
202-17-3462 14 (7X) 12 45 80 0.95 0.71 497 561 12 10
202-17-3469 14 (7X) 19 80 1.10 0.95 696 776 12 10
202-17-3487 14 (7X) 37 80 1.46 1.67 1256 1399 10 8
202-17-3552 12 (7X) 2 45 0.52 0.21 154 177 20 20
202-17-3553 12 (7X) 3 60 0.59 0.27 205 229 20 20
45
202-17-3554 12 (7X) 4 60 0.64 0.32 254 293 20 20
202-17-3555 12 (7X) 5 60 0.69 0.37 301 340 20 20
202-17-3557 12 (7X) 7 60 0.75 0.44 380 419 20 17
202-17-3559 12 (7X) 9 80 0.92 0.67 479 543 20 17
202-17-3562 12 (7X) 12 45 80 1.03 0.83 636 716 15 12
202-17-3569 12 (7X) 19 80 1.20 1.13 905 985 15 12
202-17-3587 12 (7X) 37 80 1.60 2.01 1655 1798 12 10
202-17-3652 10 (7X) 2 60 0.60 0.28 211 235 30 30
202-17-3653 10 (7X) 3 60 0.63 0.31 261 300 30 30
10 (7X) 4 45 60 0.69 0.37 327 366 30 28
202-17-3654
202-17-3655 10 (7X) 5 60 0.75 0.44 389 428 30 28
202-17-3657 10 (7X) 7 60 0.82 0.53 499 563 28 24
202-17-3659 10 (7X) 9 45 80 1.00 0.69 627 691 28 24
202-17-3662 10 (7X) 12 80 1.12 0.99 836 916 28 17

Visit Okonite's web site, www.okonite.com, for the most up to date dimensions.
Okotherm CIC Fire Resistant Cable
Type TC Cable
600V Power & Control Tray Cable

=
202-16-3403 14 (7X) 14 0.58 0.26 206 230 15 15
202-16-3503 12 (7X) 3 45 12 60 0.62 0.30 254 278 20 20
202-16-3603 10 (7X) 10 0.66 0.34 322 361 30 30
112-16-3503 8 (133X) 10 60 0.78 0.48 447 486 55 50
112-16-3603 6 (133X) 3 60 8 80 0.89 0.62 625 689 75 65
112-16-3703 4 (133X) 8 80 0.97 0.74 783 847 95 85

112-16-3803 2 (7X) 3 60 6 80 1.10 0.95 1110 1190 130 115


112-16-3903 1 (19X) 6 1.27 1.27 1415 1521 150 130
112-16-3913 1/0 (19X) 6 1.36 1.45 1681 1797 170 150
3 80 80
112-16-3923 2/0 (19X) 6 1.45 1.65 2006 2149 195 175
112-16-3943 4/0 (19X) 4 1.67 2.19 2949 3126 260 230
112-16-3953 250 (37X) 95 4 110 1.93 2.93 3609 3875 290 255
112-16-3963 350 (37X) 95 3 110 2.15 3.63 4782 5182 350 310
3
112-16-3973 500 (37X) 95 2 110 2.43 4.64 6497 7056 430 380
112-16-3983 750 (61X) 110 1 140 2.92 6.70 9608 10370 535 475

(1) - Uninsulated, save metal as phase conductor


* Max flame temp 1000°C

Visit Okonite's web site, www.okonite.com, for the most up to date dimensions.

= area for calculation of cable tray fill in The ampacities shown apply to open runs of cable, installation
accordance with NEC Section 392.22. in any approved raceway, direct burial in the earth, or as aerial
cable on a messenger. Derating for more than three current
(1) are based on Table 310.15(B)(16) of the National carrying conductors within the cable is in accordance with
Electrical Code for conductors rated 90°C, in a multi-conductor NEC Section 310.15(B)(3)(a).
cable, at an ambient temperature of 30°C (86°F). The 75°C
column is provided for additional information. The ampacities shown also apply to cables installed in cable
tray in accordance with NEC Section 392.80.
THE OKONITE COMPANY
C/12110413 Ramsey, New Jersey 07446

Potrebbero piacerti anche