Exchanger E-35307/08
Discipline
Prepared Checked Project
Rev. Issue date Revision description Approved
by by Approved by
by
B1 28-Jun-18 For Review SSW SP
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528
Subject: Exchanger E-35307/08 Sheet 2+1 OF 50+29
Index Sheet
Issue B1 Date Date Date Date .
Date
Made/Revised by SW 28-Jun-18
Checked by SP 28-Jun-18
Approved
INDEX SHEET
Page Revision
S.N. DESCRIPTION No. REMARKS
B1
1 Cover Sheet 1 x
2 Index Sheet 2 x
3 General
3.1 General Description 3 x
3.2 Design Basis Assumptions 3 x
3.3 Material Used / Properties 4 x
3.4 Reference Codes / Drawings 4 x
4 Design Input
4.1 Design Input- E-35307/08 6 x
4.2 Foundation layout view 7 x
END OF DOCUMENT 30 x
END OF DOCUMENT
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
3.0 General
The scope of this document is to provide design calculation for foundation,supporting exchanger
E35307/08 at grade level. The equipment is supported on 2 saddles which are supported on pedestal
and isolated foundation. Preliminary loading as received from Mechanical is considered for foundation
design.
For location of equipement, refer Navis snap shot below. Due to overlapping of exchanger foundation
with Equipment Supporting Structure foundation. It is proposed to combine this foundation into a
mat foundation. For Euipment supporting Structure loading refer document NL8528C050003.
Design of foundation is carried out by means of Mat 3D software using EN code provisions.
The foundation is designed for serviceability and strength purpose.
Serviceability check
The stability and safe bearing capacity of foundations are checked for unfactored load combinations
Strength design
Pedestal and foundation design is done based on forces taken from factored load combinations
E35307/08
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
Loading Factors :
Codes :
EN 1990 - Euro code 0 Basis of structural design
EN 1991 - Euro code 1_(Part-1) General actions_Densities, Self-weight, Imposed
loads for buildings
EN 1992 - Euro code 2 Design of concrete structures
Client Specifications:
Petronas Technical Design Standards (PTS).
Reference Documents :
Design Basis Civil Design Basis S-350028-35-40-0006/B1
Soil Report Geotechnical Assessment Report NL8528CP02-Soil
Report 2
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
EL = 02100 D = 2.00 GC X
EL = 00600
EL = 00000 (FGL)
a
EL = -01400
e2 e1
E F
S
Equipment
Supporting
Structure
Foundation
Pedestal
Exchanger
Pedestal
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 9+5 OF 50+27
Design Input .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 10+5 OF 50+27
Design Input .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 11+8 OF 50+22
Load Calculations- At Fixed/Sliding Ends .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
5.1 Primary Load Cases : Primary Load cases considered for this calculation are as below :
Erection, Ee = 256.00 kN
Operating, Eo = 279.00 kN (Actual load is 535 Kn, 535-256 = 279)
Test, Et = 343.00 kN (Actual load is 599 Kn, 599-256 = 343)
Bundle Pull, Bp = 0.00 kN (Not applicable)
Above loads are converted into saddle reactions based on the CG of vessel (Sliding & Fixed)
For current case, CG is considered to be located at centre.
Piping Forces, Pp
Thermal Expansion, TL
Wind Transverse, WT
Wind Londitudinal, WL For load description refer section 5.2
Live Load on Platform, LL
Seismic Transverse, WT
Seismic Londitudinal, WL
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 12+8 OF 50+22
Load Calculations- At Fixed/Sliding Ends .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 13+8 OF 50+22
Load Calculations- At Fixed/Sliding Ends .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
5.2.4) Bundle Pull Load : (As informed by Mechanical, current exchanger has closed ends on both
Horizontal Force, HXF = 1 x Bp faces, hence no bundle pull load is applicable
= 1x0
= 0.00 kN Mx
Mz X
Moment, MZF = HXF x h
= 0 x 1.5
= 0.00 kN-m Z
Therefore Vertical Force on Fixed & Sliding Sides (Push Pull force due to moment)
-VF = VS = MZF / E
Mz
= 0 / 3.5
= 0.00 kN FORCE X
S Y F
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 14+8 OF 50+22
Load Calculations- At Fixed/Sliding Ends .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
S Y F
Z
FORCE
X
A A
HZS HZF
Y
S F
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 16+8 OF 50+22
Load Calculations- At Fixed/Sliding Ends .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Z
WIND
therefore
v(ze) = sqrt( 2 x 0.88 / 0.0125)
= 11.87 m2/s
therefore
Reynold Number, Re = 2 x 11.87 / 0.000015
= 1.58E+06
WIND
Vs VF
S E F
Wind Pressure, qp = 0.88 kN/m2
Wind Force, WL = Cf x qp x A
= 1.2 x 0.88 x 6.49
= 6.85 kN
Fixed Side Force, HXF = WL (Considering 70% wind force on fixed saddle)
= 4.795 kN
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 18+8 OF 50+22
Load Calculations- At Fixed/Sliding Ends .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Slide Side Force, HXF = WL (Considering 30% wind force on slide saddle)
= 2.055 kN
Vertical Force on Fixed & Sliding Sides (Push Pull force due to moment)
-VF = VS = MZF / E
= 10.28 / 3.5
= 3 kN
Sr No Platform El Length (m) Width (m) Area (sqm) UDL (kN/m2) Remark
1 0 0 5kN/sqm
2 0 0
Total 0
5.3.0) Seismic load
SEISMIC BASE SHEAR CALCULATION AS PER UBC 1997 FOR STATIC FORCE METHOD
V = 60.31% W
However Code indicates that total design base shear need not exceed:
V = 17.05% W
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet 19+8 OF 50+22
Load Calculations- At Fixed/Sliding Ends .
Issue B1 Date 0 Date 0 Date Date Date
Made/Revised by SW 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Another requirement is that total design base shear cannot be less than,
V = 1.65% W
b hp
h1
Z
a B
D L D d h
φ
Strap
Beam
L = 1.90 m INCREASE THE SPACING
min 3.5*F
F = 0.56 m
a = 0.60 m
b = 1.50 m
h = 0.75 m pacing min 2*F+0.1
h1 = 0.65 m
hp = 4.375 m
diameter of bar, db = 25.00 mm
Clear Cover = 125.00 mm
d = 0.75-(125/1000)-(25/1000/2)
0.61 m
A = 3.40 m
B = 1.00 m
D = 0.75 m
Paving Thickness = 0.15 m
Density of concrete = 25 kN/m2
Density of soil = 18 kN/m2
Density of water = 10 kN/m2
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet
22 OF 50 .
Foundation design calculations
Issue #REF! Date 0 Date 0 Date Date Date
Made/Revised by SW #REF! 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet
23 OF 50 .
Foundation design calculations
Issue #REF! Date 0 Date 0 Date Date Date
Made/Revised by SW #REF! 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
0 0
6.2.1) ULS Load Combination : Max Loads on Top of Pilecap from 5.4.2
Where : c = compression
t = tension
d = design
tr = transversal
rep = representative
F = load
R = resistance
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet
24 OF 50 .
Foundation design calculations
Issue #REF! Date 0 Date 0 Date Date Date
Made/Revised by SW #REF! 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet
25 OF 50 .
Foundation design calculations
Issue #REF! Date 0 Date 0 Date Date Date
Made/Revised by SW #REF! 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
V1 = Fy + ɣg * W
Hx1 = Fx
Hz1 = Fz
Mx1 = Mx + Fz x h
Mz1 = Mz + Fx x h
Hence 2 Nos 556 Diameter Piles are O.k (ø 556/640 Vibro piles (CPT 501C, Tip Level -23.5m))
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet
26 OF 50 .
Foundation design calculations
Issue #REF! Date 0 Date 0 Date Date Date
Made/Revised by SW #REF! 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Hence, the strap beam is safe, detail design to be done in foundation R/F calculation of V1510
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet
27 OF 50 .
Foundation design calculations
Issue #REF! Date 0 Date 0 Date Date Date
Made/Revised by SW #REF! 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
0
Subject: Exchanger E-35307/08 Sheet
28 OF 50 .
0
Issue #REF! Date 0 Date 0 Date Date Date
Made/Revised by SW #REF! 0 30-Dec-99 0 30-Dec-99
Checked by SP 28-Jun-18 0 30-Dec-99 0 30-Dec-99
Approved 0 30-Dec-99 0 30-Dec-99 0
0.0 0
The output of all design efforts have been finally converted in the form of design drawings.
Drawing List is attached herewith for ready reference:
No. Load Combination Load Elem Soil Mat App Axial Tot Axial Buoyant
Weight Weight Weight Load Load Load
kN kN kN kN kN kN
Note: Stability ratio values greater than 100 are displayed as 100.
Note: Sliding factor of safety value greater than 100 is displayed as 100.
Note: Sliding factor of safety value greater than 100 is displayed as 100.
No. Load Location Shear Shear Allowable Location Shear Shear Allowable
Combination Crit Sect Crit Sect Stress Stress Near Supp Near Supp Stress Stress
m kN N/sq mm N/sq mm m kN N/sq mm N/sq mm
No. Load Location Shear Shear Allowable Location Shear Shear Allowable
Combination Crit Sect Crit Sect Stress Stress Near Supp Near Supp Stress Stress
m kN N/sq mm N/sq mm m kN N/sq mm N/sq mm
AT A CRITICAL SECTION
Note: Allowable shear stress with enhancement may apply depending on the shear section location.
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
O
D
EN
Project No. Document / Item Reference
Plant/Area Ref: SRU Train 3
NL8528 0
BDD 86/1 Plant / Area Ref. : TSM - Transfer Tower Structure 18-3166 18-3166-00 / S.05 / 1104 / A4
Where ,
Cf = Force coefficient
For Karachi, Pakistan V = 50 m/sec (180 km/hr) (As per standard design criteria)
Velocity Pressure qz = 0.613 kz kzt kd V2 I (N/m2; V in m/sec) eq. 6-1, ASCE 7-02
BDD 86/1 Plant / Area Ref. : TSM - Transfer Tower Structure 18-3166 18-3166-00 / S.05 / 1104 / A4
Distribution:
BDD 86/1 Plant / Area Ref. : TSM - Transfer Tower Structure 18-3166 18-3166-00 / S.05 / 1104 / A4
Distribution:
Wind load acting on the structure is applied as a Nodal load at beam-column junction.
Thus,
[ Design wind pressure ] x [Effective projected area normal to wind of all the elements meeting at node.]
= Projected area of all elements normal to wind / Area enclosed by frame boundary
This exercise has been done for all the individual frames.
Wind load acting on all Equipments / Piping etc. is applied as given by client.