Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1.0 SCOPE:
The intent of this calculation is to determine the following for WTG SwitchYard
1.1 : Size of earth strip
1.2 : Number of earth electrodes
1.3 : Earth Resistance
The entire earthing system will be designed in accordance with relevant Indian Standard specifications and with the requirements of
Indian Electricity Rules and Acts 1956 and IEEE Standard 80.
2.1 : IEEE Standard 80 - 1986 - AC Substation Grounding
2.2 : IS 3043 - 1987 - Code of Practice for Earthing
3.1 : Material used for Earth electrode : Copper clad steel electrode
3.2 : Material used for Earth grid conductor : Mild Steel (GI)
3.3 : Type of Joints in Earth Grid : Welded
5.0 Data
5.1 Short circuit Current for conductor sizing Is = 18 kA
5.2 System Short circuit current If = 18000 Amps
5.3 Current Division Factor considered Sf = 1
5.4 Short circuit Current through earthing electode Ig = 18 kA
5.5 Type of earthing Conductor = GI
5.6 Specific density of Material (GI Steel) SW = 8.386 gm/cm3
5.7 Specific Heat of conductor (GI Steel) SH = 0.112 cal/gm/ºc
5.8 Thermal Capacity Factor Tcap = 3.930 J/cu.cm/ºc As per IEEE Std 80
5.9 Reference temperarure for Material constants Tr = 20 ºc
5.10 Resistivity of earthing Material(GI Steel) ρr = 20.1 µΩcm As per IEEE Std 80
5.11 Thermal Co-officient for resistivity (GI Steel) αr 0.0032 /ºc As per IEEE Std 80
5.12 Fault Current withstand Capacity by Conductor tc = 1 s
5.13 Type of Joint Welded
5.14 Maximum Allowable Temperature for Welded joints for GI steel Tm = 419 ºc As per IEEE Std 80
5.15 Ko (1/αr)-Tr = 293 ºc As per IEEE Std 80
5.16 Ambient Temperature Ta = 50 ºc
5.17 Soil Resistivity P = 250 Ohm-m
5.18 Duration of Fault Clearing Time ts = 1 Seconds
I = A(0.1031513)
A = 269.46 sq.mm
In accordance with clause No. 10.3 of IS 3043, the dissipation of fault current at the earth conductors surface area, I is given by
Where,
I : Max. permissible current density at electrode surface in A/m2
P : Resistivity of Soil = 250 ohm-metre
t : Duration of fault current in second = 1 second
Therefore,
I= 478.77 A/ m2
To dissipate fault current of 18 kA, the total area of Earthing conductor required is worked out as below
Area = If/ I = 37.596 say 38 sq. mtr
14.2 mm diameter Copper clad Earth Electrodes with following length are provided for the following
Therefore, total area of buried earth conductor available for dissipation of 18kA fault current = 45.46 sq. mtr
It is seen from above that total area provided by 7 nos. Earth electrodes and grid conductors is adequate in order to dissipate
a fault current of 18 kA
8.1 The earth resistance for Earth Electrode is calculated based on the following formula (Cl. 9.2.2 of IS - 3043)
Where,
p = Resistivity of Soil = 250 ohm-mtr
L = Length of Earth Electrode in cm = 300 cm
d = Diameter of Earth Electrode in cm = 1.42 cm
N= No. of Electrodes = 7 nos.
Incase of Rocky area, replacement of Rocky/sandy soils with low resistivity Black cotton soil/ agricultural soil (appx. 50 Ohm-meter resistivity
to fill up a bore of 200x4000mm.
The most common formula for electrode with length L, Diameter D, developed by Prof.H.R.Dwight is
With considering to L= 3Meter and Diameter d= 0.0142mtr, the equation can be further simplified as unde
As a result of replacement of Rocky/Sandy soil with low resitivity black cotton soil and use of GEM material the above mentioned equation
can be further modified as under: -
R = 0.3312 * (0.40 * Gem material resistivity + 0.60 * Resistivity of Black cotton soil)
Appx. Theoretical value of earth resistance for a Grid having 7 no. of earth electrodes may be calculated using formula for resistance in
parallel:
Combined Earth resistance with 7 rods in parallel connection R1 = 1.421 Ohms
8.2 The earth resistane of GI strip forming the earth grid is calulated based on the following formula
R2 = (100 P/2∏L)* (Loge (2*L*L/ wt)) ohms …… from IS 3043 - Cl. No. 9.2.3, Pg no. 21
Where,
R2 = 0.802657 Ohms
Hence the combined resistane of WTG Yard considered with parallel connection of Copper bonded earth electrodes
earthing grid & foundation earthing conductor buried underground is given by
1/R = 1/R1 (Earth Electrode) + 1/R2 (earth mat of foundation and yard)
Where,
R =Combined earth resistane
R1 =Resistance of Copper bonded Electrodes
R2 = Resistance of 50X6 mm grid earthing
R = 0.5130 ohms
The above figure of 0.51 ohms is well within the permissible value of 2 ohms
9.0 CONLUSION:
9.3 Thus, resistance of earth grid is below 2 ohm which is less than the maximum allowable earth grid resisance
of 2 ohms for small substations & Yards