AIRTECH SYSTEMS INDIA PVT LTD.
502- 503, Satellite silver,Marol Naka ,Andheri East, Mum- 49
Tel: +91 22 28522270
Fax: +91 22 28592275
web: www.airtechsys.in - sales@airtechsys.in
Customer Armein Pharma Pvt. Ltd. Date 07/06/2019
To the k. a. of Adept consultants and Engineers Our Offer Armein Pharmaceuticals
Your Reference AHU-SL 13 MONSOON 6 ROWS Description
COOLING COIL - 102512_S_S 24T 6NR 1253A 2.1P 12NC
Geometry 102512_S_S Coil Length 1253 mm
Nr of Tubes per Row 24 Fin Pitch 2.10 mm
Nr of Rows 6 Nr of Circuits 12 Tube Shape Circular
Capacity 8.660 ton(ref.)
Sensible Capacity 5.714 ton(ref.)
Latent Capacity 2.946 ton(ref.)
Sensible/Total Capacity Ratio 0.6598
Quantity of Produced Water 14.95 kg/h
Exchange Surface 135.65 m²
Global Exchange Coefficient 22 W kg/(m² kJ)
DHML 10.12 kJ / kg
Fins Material / Tubes Material Aluminium / Copper
Fin Thickness 0.1000 mm
Coil Internal Volume 19.7 l
Tubes External Diameter 12.5 mm
Tubes Internal Diameter 11.8 mm
Number of skipped tube 0

AIR SIDE
Atmospheric Pressure / Altitude 1.01 / 0.00 bar A / m
Volumetric Air Flow 2620.0 cft/min
Mass Air Flow 5262 kg/h
Face Velocity on the Coil 255 ft/min
Inlet Air Density 1.18 kg/m³
Inlet Air Temperature 74.5 °F
Inlet Air Relative Humidity 56.30 %
Inlet Air Specific Humidity 10.10 g/kg AS
Inlet Air Enthalpy 49.44 kJ / kg
Outlet Air Temperature 50.4 °F
Outlet Air Relative Humidity 95.23 %
Outlet Air Specific Humidity 7.30 g/kg AS
Outlet Air Enthalpy 28.57 kJ / kg
Pressure Drop 41 Pa
Partial Exchange Coefficient 40 W/(m² K)
Fouling Factor 0.000000 (m² K)/W
Frost thickness 0.00 mm
FLUID SIDE
Fluid WATER (1 bar A)
Volumetric Fluid Flow 5.2 m³/h
Mass Fluid Flow 5199 kg/h
Fluid Velocity 3.61 ft/s
Inlet Fluid Temperature 7.0 °C
Outlet Fluid Temperature 12.0 °C
Total Pressure Drop Fluid Side 14.237 ftH2O
Partial Exchange Coefficient 4168 W/(m² K)
Fouling Factor 0.000000 (m² K)/W