Sei sulla pagina 1di 1

Settings

Group / IED Value PC Value Unit Min Max


Parameter
Name
OEXPVPH: 1
MeasuredI L1L2
MeasuredU L2L3
Setting Group1
Operation On
IBase 2062 A 1 99999
UBase 10.50 kV 0.05 2000.00
V/Hz>> 120.0 %UB/f 100.0 200.0
V/Hz> 110.0 %UB/f 100.0 180.0
XLeak 0.000 ohm 0.000 200.000
TrPulse 2.000 s 0.000 60.000
tMin 2.000 s 0.000 60.000
tMax 3.00 s 0.00 9000.00
tCooling 3.00 s 0.10 9000.00
CurveType IEEE
kForIEEE 1 1 60
t1Tailor 7200.00 s 0.00 9000.00
t2Tailor 3600.00 s 0.00 9000.00
t3Tailor 1800.00 s 0.00 9000.00
t4Tailor 900.00 s 0.00 9000.00
t5Tailor 450.00 s 0.00 9000.00
t6Tailor 225.00 s 0.00 9000.00
AlarmLevel 60.0 % 50.0 120.0
tAlarm 5.00 s 0.00 9000.00

Project Responsible department Technical ref... Document kind Doc. designation

PLTU GORONTALO UNIT 2 N... ABB Ltd. AA1J1Q01A1


Repla... Created by Title Document id.
REG670
PLTU GORONTALO UNIT 2
Approved by Rev. Rel. date Lan
NEW USE.Substation.Voltage
Re Rel. Created Based 1/1
v.
Modification
date by on Level.Bay 0 11/12/2018 en