Conexión c) Yyn0

1. Corrientes de falla

Fallas de los buses


BUS Fault 1 Fault 2 Fault 1 Current Mag Fault 1 Current Ang Fault 2 Current Mag Fault 2 Current Ang
1 3PB SLG 11982.86 -73.07 13649.20 -76.11
1 LL DLG 10238.12 -162.88 16279.42 99.32
2 3PB SLG 9747.07 -86.42 0.00 -94.80
2 LL DLG 8424.31 -176.35 0.00 90.00
3 3PB SLG 5024.20 -86.97 0.04 -91.57
3 LL DLG 4342.25 -176.90 0.02 88.34
4 3PB SLG 7676.33 -81.69 0.00 -96.12
4 LL DLG 6637.28 -171.64 0.00 0.00
5 3PB SLG 5552.51 -79.75 0.00 -96.68
5 LL DLG 4803.03 -169.71 0.00 -82.87
6 3PB SLG 13053.30 -88.33 15037.41 -91.09
6 LL DLG 11299.74 -178.31 17683.45 85.11
7 3PB SLG 13053.32 -88.33 15037.46 -91.09
7 LL DLG 11299.76 -178.31 17683.54 85.11

2. Factores de sobretensión

Factores de sobretension BUS2 23kV


Falla Phase Volt A(pu) Phase Volt B (pu) Phase Volt C (pu) Phase Ang A Phase Ang B Phase Ang C
DLG 0.99 0.49294 0.49 -10.29 169.74 169.69
SLG 0.00 1.80 1.80 10.91 -154.80 145.20

1) Definir la clase de conexión a tierra en cada sistema: 115 kV, 46 kV, 23 kV y 4.16 kV.

3. Conexión a tierra
BUS Voltaje (kV) Conexión a tierra
BUS 1 115 Efectiva a tierra
BUS 2 23 No Efectiva a tierra
BUS 3 46 No Efectiva a tierra
BUS 4 23 No Efectiva a tierra
BUS 5 23 No Efectiva a tierra
BUS 6 4.16 Efectiva a tierra
BUS 7 4.16 Efectiva a tierra