DATA SHEET FOR INSTRUMENT CABLE

Attached Number of Page(s) : Review / Approval

SIGN / STAMP
Page 1 + 6.

ReGulf ALLARA ENERGY TWENTY 20

A 14-10-19 Issued for ABS JOS / AKA DM JDA


IDC
Revision Date Description Prepared By Checked By Checked By Approved By Approved By
No.
PROJECT NO. 1019 PAGE 2 OF6
DOC NO. 1019-DPP-INS-DTS-0004 REV A
DOC. TITLE DATA SHEET FOR INSTRUMENT CABLES
TWENTY 20 DIRIO CENTRAL PROVINCE POWER
PROJECT
PLANT GAS PIPING SYSTEM
LOCATION PNG

Table-1
COMPOSITION -Single pair, Armoured cable, Flame retardant.
Type:-T2/INST.NIS/332-1/Pr/Ov/1.5/01

CORE:
1: Conductor: Stranded annealed copper, (class 2) according to IEC 60228
Temperature rating 90°C
Size 1.5 mm²
Identification: Black and white

2: Insulation: Flame retardant Cross Linked Polyethylene (XLPE). Formatted: Centered

CABLE: Cores are twisted together and covered with:


3: Fillers: Flame retardant moisture resistant material (manufacturer standard)
4: Cable shield: One drain wire and aluminum backed mylar tape.
Tape shall be helically wrapped with 25% overlap.
Aluminum tape shall be in continuous contact with a stranded tinned copper of
cross-section 0.50 mm² (7 x 0.30 mm)
5: Inner jacket: Flame retardant Polyvinyl Chloride
Color: Black
6: Armour: Galvanized spiral double carbon steel strips
7: Outer jacket: Flame retardant Polyvinyl Chloride cable as per IEC 60332 Formatted: Font: (Default) Calibri, Font color: Black, Pattern:
Minimum Oxygen Index-30% Clear

Temperature Index-250 °C
Color : Black
8 : Quantity 500 meters
PROJECT NO. 1019 PAGE 3 OF6
DOC NO. 1019-DPP-INS-DTS-0004 REV A
DOC. TITLE DATA SHEET FOR INSTRUMENT CABLES
TWENTY 20 DIRIO CENTRAL PROVINCE POWER
PROJECT
PLANT GAS PIPING SYSTEM
LOCATION PNG

Table-2
COMPOSITION -Multipair, Armoured cable, Flame retardant.
Type:-T2/INST.NIS/332-1/Pr/In&Ov/1.5/05

CORE:
1: Conductor: Stranded annealed copper, (class 2) according to IEC 60228
Temperature rating 90°C
Size 1.5 mm²
Identification: Black and white
Each core printed with pair number throughout the cable at equal distance
2: Insulation: Flame retardant Cross Linked Polyethylene (XLPE).

CABLE: Cores are twisted together into pairs (10 to14 twists/m) together and covered with:
3: Pair Screen : One drain wire and aluminum backed mylar tape.
Tape shall be helically wrapped with 25% overlap.
Aluminum tape shall be in continuous contact with a stranded tinned copper of
cross-section 0.50 mm² (7 x 0.30 mm)
4: Fillers: Flame retardant moisture resistant material (manufacturer standard)
5: Cable shield : One drain wire and aluminum backed mylar tape.
Tape shall be helically wrapped with 25% overlap.
Aluminum tape shall be in continuous contact with a stranded tinned copper of
cross-section 0.50 mm² (7 x 0.30 mm)
6: Inner jacket: Flame retardant Polyvinyl Chloride
Color: Black
7: Armour: Galvanized spiral double carbon steel strips
8: Outer jacket: Flame retardant Polyvinyl Chloride
Minimum Oxygen Index-30%
Temperature Index-250 °C
Color : Black
9. Quantity: 4 pair, 500 meters Formatted: Right: -0.9"
Note:-Requirement of 4 Pair
PROJECT NO. 1019 PAGE 4 OF6
DOC NO. 1019-DPP-INS-DTS-0004 REV A
DOC. TITLE DATA SHEET FOR INSTRUMENT CABLES
TWENTY 20 DIRIO CENTRAL PROVINCE POWER
PROJECT
PLANT GAS PIPING SYSTEM
LOCATION PNG

Table-3
COMPOSITION -Single triad, Armoured cable, Flame retardant.
Type:-T2/INST.NIS/332-1/Tri/In&Ov/1.5/01

CORE:
1: Conductor: Stranded annealed copper, (class 2) according to IEC 60228
Temperature rating 90°C
Size 1.5 mm²
Identification: Black - white and Red
2: Insulation: Flame retardant Cross Linked Polyethylene (XLPE).

CABLE: Cores are twisted together and covered with:


3: Fillers: Flame retardant moisture resistant material (manufacturer standard)
4: Cable shield: One drain wire and aluminum backed mylar tape.
Tape shall be helically wrapped with 25% overlap.
Aluminum tape shall be in continuous contact with a stranded tinned copper of
cross-section 0.50 mm² (7 x 0.30 mm)
5: Inner jacket: Flame retardant Polyvinyl Chloride
Color: Black
6: Armour: Galvanized spiral double carbon steel strips
7: Outer jacket: Flame retardant Polyvinyl Chloride
Minimum Oxygen Index-30%
Temperature Index-250 °C
Color : Black
8: Quantity: 500 meters
PROJECT NO. 1019 PAGE 5 OF6
DOC NO. 1019-DPP-INS-DTS-0004 REV A
DOC. TITLE DATA SHEET FOR INSTRUMENT CABLES
TWENTY 20 DIRIO CENTRAL PROVINCE POWER
PROJECT
PLANT GAS PIPING SYSTEM
LOCATION PNG

Table-4
COMPOSITION -Multi-triad, Armoured cable,Flame retardant.
Type:-T2/INST.NIS/332-1/Tri/In&Ov/1.5/10

CORE:
1: Conductor: Stranded annealed copper, (class 2) according to IEC 60228
Temperature rating 90°C
Size 1.5 mm²
Identification: Black - white and Red
Each core printed with triad number throughout the cable at equal
distance
2: Insulation: Flame retardant Cross Linked Polyethylene (XLPE).

CABLE: Cores are twisted into Triads-Triads twisted(10 to 14 twists/m) together and covered with:
Flame retardant moisture resistant material (manufacturer
3: Fillers: standard)
4: Cable shield : One drain wire and aluminum backed mylar tape.
Tape shall be helically wrapped with 25% overlap.
Aluminum tape shall be in continuous contact with a stranded
tinned copper of cross-section 0.50 mm² (7 x 0.30 mm)
5: Inner jacket: Flame retardant Polyvinyl Chloride
Color: Black
6: Armour: Galvanized spiral double carbon steel strips
7: Outer jacket: Flame retardant Polyvinyl Chloride
Minimum Oxygen Index-30%
Temperature Index-250 °C
Color : Black
8: Quantity: 6 Triad, 500 meters