QSN14 Series
365-400 kVA, 292-320 kWe Prime, 440 kVA, 352 kWe Standby
Specification Sheet
Latest Technology Product With Lowest Operating Cost And
Global Cummins® Platform Comprehensive Warranty
The Cummins® QSN14 series heavy-duty engine Highly reliable and durable product
and world class Stamford alternator powered diesel All elements are designed to work together to
generator set maximize efficiency even at part loads, offering the
Class defining Quantum engine technology with fully advantage of lowest operating costs.
integrated subsystems 500 Hours / 1 year service interval
Advanced in-cylinder technology to meet latest Industry acknowledged best-in-class comprehensive
emission norms without any after-treatment device warranty on the entire package including rubber
Smart aesthetic and superior finish components
Compact in size with optimum power to weight ratio
Single Source Power Assurance
Environment Friendly Power All the major components – the engine, alternator,
Class defining technology engine is designed to meet control system and canopy are designed,
stringent exhaust emission tests as per revised MoEF manufactured and tested by Cummins India.
norms, thus offering environment friendly power. Best and largest customer support network in India,
The Cummins® diesel generator sets are available with capable of providing round-the-clock service and
the lowest noise levels in its range spares support
All these things put together, Cummins® offers you
SINGLE SOURCE POWER ASSURANCE
Diesel Generator Set QSN14 Series Specification Sheet
Technical Data
Generator set specification
Model C365D5P C400D5P C440D5S
Duty Prime Prime Standby
Power Rating kVA / kWe 365/292 400/320 440/352
No. of Phases 3 3 3
Output Voltage and Frequency (V and Hz) 415 V, 50 Hz 415 V, 50 Hz 415 V, 50 Hz
Power Factor 0.8 (lagging) 0.8 (lagging) 0.8 (lagging)
Current (A) 508 556 612
RPM 1500 1500 1500
Engine Specification
Make Cummins® Cummins® Cummins®
Model QSN14-G1 QSN14-G2 QSN14-G3
MoEF Certified Power (hp) 448 487 531
Required Power for Rated kVA (hp) 440 475 522
Cooling Liquid Cooled (EG Liquid Cooled (EG Liquid Cooled (EG
Compleat 50:50) Compleat 50:50) Compleat 50:50)
Aspiration Turbocharged, Charge Air Turbocharged, Charge Air Turbocharged, Charge Air
cooled cooled cooled
No. of cylinders 6, In-line 6, In-line 6, In-line
Bore (mm) x Stroke (mm) 140 x 152 140 x 152 140 x 152
Compression ratio 16.5: 1 16.5: 1 16.5: 1
Displacement (litre) 14 14 14
Fuel High Speed Diesel High Speed Diesel High Speed Diesel
Fuel consumption @75% load with radiator and fan* 61.05 67.45 73.52
(litre/hr)
Fuel consumption @100% load with radiator and fan* 77.69 88 93.89
(litre/hr)
Performance class of generator set ISO 8528-5 G2 ISO 8528-5 G2 ISO 8528-5 G2
Starting system 24 V DC Electrical 24 V DC Electrical 24 V DC Electrical
Lube oil specification CI4+ 15W40 CI4+ 15W40 CI4+ 15W40
Lube oil sump capacity, High-Low level (litre) 36-28.4 36-28.4 36-28.4
Total lubrication system capacity (litre) 38.6 38.6 38.6
Lube oil consumption @ full load** (litre/hr) 0.08 0.09 0.10
Total coolant capacity (litre) 51 51 51
Exhaust pipe size (inch) 6 6 6
Total wet weight (Engine+Radiator)## (kg) 1706 1706 1706
Length x Width x Height (Engine) (mm) 1502 x 888 x 1219 1502 x 888 x 1219 1502 x 888 x 1219
Mean Piston speed (m/s) 7.5 7.5 7.5
Combustion air intake @100% load (±5%) (cfm) 954 1024 1059
Exhaust Temperature (°C) 475 491 492
Alternator Specification
Make Stamford (CGT) Stamford (CGT) Stamford (CGT)
Alternator frame HCI444F HCI544C HCI544C
Enclosure IP23 IP23 IP23
Voltage regulation (Max.) ±1% ±1% ±1%
Class of Insulation H Class H Class H Class
Winding Pitch 2/3 2/3 2/3
Stator Winding Double layer lap Double layer lap Double layer lap
Rotor Dynamically Balanced Dynamically Balanced Dynamically Balanced
Waveform distortion/ Total Harmonic Distortion No load < 1.5 %, Non No load < 1.5 %, Non No load < 1.5 %, Non
distorting balanced linear distorting balanced linear distorting balanced linear
load < 5 % load < 5 % load < 5 %
Maximum Unbalanced Load across phases# less than or equal to 25% less than or equal to 25% less than or equal to 25%
Telephonic Harmonic factor < 2% < 2% < 2%
* Fuel consumption data is based on diesel having specific gravity of 0.85 and conforming to IS:1460. Fuel consumption tolerance is +5%
** Oil consumption data is based on oil having specific gravity of 0.89 and meeting CI4+ API categories
#
With the condition that none of the phases exceeds its rated current
Diesel Generator Set QSN14 Series Specification Sheet
Genset Rating Length Width Height Wet Weight## Standard Fuel tank
Model (kVA) (mm) (mm) (mm) (kg) Capacity (litre)
C365D5P 365 5500 1900 2150 6165 450
C400D5P 400 5500 1900 2150 6250 450
C440D5S 440 5500 1900 2150 6250 450
##
Approximate weight
Authorised Representative