Sei sulla pagina 1di 51

Grid Connection of Wind Farms

Markus Pöller and Oscar Amaya/DIgSILENT GmbH

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Grid Connection

• Impact on thermal loading of lines/transformers


• Impact on voltage during normal operation
• Short circuit currents
• Power Quality Aspects
– Voltage dips because of WTG switching
– Voltage dips because of transformer inrush
– Continuous Flicker
– Harmonics
• Behaviour during grid faults/Fault ride through requirements

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Impact on Thermal Loading

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Options for network connection

HV
A Distributed/Embedded
B MV Substation
C
C HV Substation
MV

B
A

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Impact on Thermal Loading of Lines/Transformers

• Additionally required transmission lines must be planned based on


well defined scenarios, considering size and location of planned wind
farms.

• Load flow studies required for combinations of:


– Load level (High-/Low-load)
– Wind speed level (High-/Medium-/Low wind)

• For avoiding investments in new transmission lines which are only


required for a few hours per year, probabilities should be assigned to
the studied cases.

• Assessment of potential of dynamic line rating recommended because


of the good correlation of transmission line capacity and wind speed.

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Impact on Thermal Limits – Example

lod_70892..
lod_72882_1

lod_70892_1
lod_70962_1
lod_72802_1
BANTAM BAVIANSK GEELBEK KOUP ANTJIESK

2181WOLF

2181WOLF

2181WOLF
QUARY1_2 PIETM1_2 BANTM2_2 WHITH1_2 BAVIN1_2 GEELB1_2 RUITK1_2 KOUP1_2 GEMSB1_2 ANTJK1_2 BOTES_2 WELTV1_2

2181WOLF

2181WOLF
2,07

2,63

2,08

3,87
BOSKLOOF 2

0,51
2181WOLF
74,80 LEEUG1_2

2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF
22,49 11,41 11,17 9,96 12,93 11,05 13,16 9,64 14,20 24,09 21,81

Continued on lod_72852_1 lod_70682_1

Bacchus 132kV diagram


lod_72962_1 lod_72932_1 lod_70922_1 lod_70842_1 lod_70762_1 lod_70732_1

2181WOLF
2181WOLF

12,41
21,81
2181WOLF
74,80 LEEUG1_1

2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF

trf_70682..
22,49 11,41 11,17 9,96 12,93 11,05 13,16 9,64 14,20 24,09

BOSKLOOF 1

2181WOLF
12,40
QUARY1_1 PIETM1_1 BANTM1_1 WHITH1_1 BAVIN1_1 ANTJK1_1 BOTES_1 WELTV1_1
GEELB1_1 RUITK1_1 KOUP1_1 GEMSB1_1

To DROERIVIER

2181WOLF
11,45
LEEUG22

2181WOLF
11,45
2181WOLF
9,40

2181WOLF
lod_70686_1

9,40
LAIN132B1

LAIN132B2
LAIN132 WF

LAINGSBURG
LAIN WF Tr 1

WP51WOLF
2161WOLF
14,45
150 MW
14,45
WP51WOLF 2161WOLF M1311CH
6,00 6,12 28,11
LAIN33 WF

Wind Park SWART1 BUFPT1 LADIS13


LAIN WF Tr 2

trf_73002..

trf_74002..
LAIN0.69 WF Ladismith
SWART22 BUFPT22

Voltage Levels
Laingsburg WF
400, kV
lod_73006_1 lod_74006_1
220, kV
132, kV
66, kV
33, kV

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Impact on Thermal Limits – Example

2181WOLF

2181WOLF
QUARY1_2 PIETM1_2 BANTM2_2 WHITH1_2 BAVIN1_2

2181WOLF
GEELB1_2 RUITK1_2 KOUP1_2 GEMSB1_2 ANTJK1_2 BOTES_2

2181WOLF
2,07 km

2,63 km

2,08 km
3,36 %

6,05 %

0,95 %

2181WOLF
3,87 km
1,37 %

0,51 km
0,39 %
BOSKLOOF 2
2181WOLF
74,80 km
0,00 %

2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF
22,49 km 11,41 km 11,17 km 9,96 km 12,93 km 11,05 km 13,16 km 9,64 km 14,20 km 24,09 km
0,00 % 0,00 % 0,00 % 0,00 % 20,17 % 19,67 % 18,27 % 17,76 % 17,12 % 16,59 %

Continued on lod_72852_1

Bacchus 132kV diagram


lod_72962_1 lod_72932_1 lod_70922_1 lod_70842_1

2181WOLF
12,41 km
0,00 %
2181WOLF
74,80 km
110,86 %

2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF
22,49 km 11,41 km 11,17 km 9,96 km 12,93 km 11,05 km 13,16 km 9,64 km 14,20 km 24,09 km
111,37 % 112,44 % 115,48 % 115,69 % 22,62 % 20,68 % 20,32 % 17,88 % 17,53 % 16,33 %

BOSKLOOF 1

2181WOLF
120,99 %
12,40 km
QUARY1_1 PIETM1_1 BANTM1_1 WHITH1_1 BAVIN1_1 BOTES_1
GEELB1_1 RUITK1_1 KOUP1_1 GEMSB1_1 ANTJK1_1

To DROERIVIER

2181WOLF
11,45 km
20,83 %
off

2181WOLF
11,45 km
• 120% overload

22,97 %
2181WOLF
9,40 km
31,04 %

2181WOLF
31,04 %
9,40 km
LAIN132B1

LAIN132B2
LAIN132 W F

LAINGSBURG
180,00 MVA
86,01 %

WP51WOLF
km
15,72%%
2161WOLF
14,45km
150 MW

15,97
14,45
WP51WOLF 2161WOLF M1311CH
6,00 km 6,12 km 28,11 km
14,48 % 14,59 % 7,06 %
LAIN33 WF

Wind Park SWART1 BUFPT1 LADIS13


2,50 MVA
81,36 %

10,00 MVA

10,00 MVA
14,00 %

60,68 %
LAIN0.69 WF Ladismith
SWART22 BUFPT22

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Impact on Thermal Limits - Example

General mitigation options if thermal limits are exceeded:

• Build a new line


• Limit wind farm output to 80% during all times (80% of
rated output)
• Limit wind farm output in case of actual line failure (manual
or automatic inter-trip).
• Consider dynamic line rating systems.

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Violation of Thermal Limits – Cap Wind Farm Output

DIgSILENT
12,50

10,00

7,50

5,00

2,50

0,000

-2,50
0,500 1,500 2,500 3,500 4,500 5,500 6,500 7,500 8,500 9,500 10,50 11,50 12,50 13,50 14,50 15,50 16,50 17,50 18,50 19,50 20,50
x-Axis: Windpark Analysis: Wind Speed in m/s
Windpark Analysis: Probability in %

160,00

120,00
16.624 % 1454 h/year Y =120,000 MW

80,00

40,00

0,00

-40,00
0,03 20,03 40,03 60,03 80,03 100,03
x-Axis: Windpark Analysis: Cummulative Probability in %
Windpark Analysis: Generated Power in MW

High Load Plots Date: 7/23/2009


DIGSILENT Voltage at Laingsburg Wind Farm Connection Point PV-Curve Annex: 1 /3

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Violation of Thermal Limits – Cap Wind Farm Output

Not Delivered Energy depends on:


• Wind conditions (average wind speed)
• Site-specific aspects
• Power curve of turbines

Rough cost estimates (example):


• vw=7m/s:
– Energy not delivered around 5% of potential energy
– 150 MW wind-farm: 19 000MWh not delivered -> 23 750 000 R/year

• vw=8m/s:
– Energy not delivered around 7,5% of potential energy
– 150 MW wind-farm: 37 000 MWh not delivered -> 46 250 000 R/year

• Must be compared to annualized costs of required line upgrade

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Violation of Thermal Limits – Cap Wind Farm Output under
Contingency Situations

More cost effective solution:

• Limitation of wind farm output only in situations in which one circuit is


available (planned outage, unplanned outage)

• In case of minor overloads (below emergency rating):


– Manual action of system operator

• In case of major overloads (above emergency rating):


– Automatic inter-trip scheme

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Dynamic Line Rating - Potential

• Thermal loading of overhead lines depends on:


– Ambient temperature
– Wind speed -> correlation with wind generation

• Wind-generators:
– cut-in wind-speed: 2.5...4m/s, rated: 12...16m/s
– But: height, environment etc. must be considered too!

Ambient Line Rating expressed in MVA at 66 kV*


Temperature

Wind Speed = 0.5 m/s Wind Speed = 3.0 m/s Wind Speed = 5.0 m/s

30 ºC 22.6 39.9 49.5

35 ºC 16.5 32.9 41.5

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Impact on Voltage Variations

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations

• Distribution Grids: Considerable voltage variations for varying MW


because of low X/R ratios (large R)

• Transmission Grids: Substantially less voltage variations for varying


MW becaus of high X/R ratios (low R). Contingency cases are more
relevant.

• Mitigation Options:
– Q(P)-Characteristic (open-loop voltage compensation)
– Voltage control (voltage feed-back)

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations - Procedure

• Step 1 - System Operator: Identify required reactive power range at


connection point

• Step 2 – Wind farm planner: Design the reactive power capability for
complying with reactive capability requirements.

- Step 1 might be defined by a general Grid Code requirement -

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Example 1: Connection to Distribution/Subtransmission Grid

lod_70892..
lod_72882_1

lod_70892_1
lod_70962_1
lod_72802_1
BANTAM BAVIANSK GEELBEK KOUP ANTJIESK

2181WOLF

2181WOLF

2181WOLF
QUARY1_2 PIETM1_2 BANTM2_2 WHITH1_2 BAVIN1_2 GEELB1_2 RUITK1_2 KOUP1_2 GEMSB1_2 ANTJK1_2 BOTES_2 WELTV1_2

2181WOLF

2181WOLF
2,07

2,63

2,08

3,87
BOSKLOOF 2

0,51
2181WOLF
74,80 LEEUG1_2

2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF
22,49 11,41 11,17 9,96 12,93 11,05 13,16 9,64 14,20 24,09 21,81

Continued on lod_72852_1 lod_70682_1

Bacchus 132kV diagram


lod_72962_1 lod_72932_1 lod_70922_1 lod_70842_1 lod_70762_1 lod_70732_1

2181WOLF
2181WOLF

12,41
21,81
2181WOLF
74,80 LEEUG1_1

2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF 2181WOLF

trf_70682..
22,49 11,41 11,17 9,96 12,93 11,05 13,16 9,64 14,20 24,09

BOSKLOOF 1

2181WOLF
12,40
QUARY1_1 PIETM1_1 BANTM1_1 WHITH1_1 BAVIN1_1 ANTJK1_1 BOTES_1 WELTV1_1
GEELB1_1 RUITK1_1 KOUP1_1 GEMSB1_1

To DROERIVIER

2181WOLF
11,45
LEEUG22

2181WOLF
11,45
2181WOLF
9,40

2181WOLF
lod_70686_1

9,40
LAIN132B1

LAIN132B2
LAIN132 WF

LAINGSBURG
LAIN WF Tr 1

WP51WOLF
2161WOLF
14,45
150 MW
14,45
WP51WOLF 2161WOLF M1311CH
6,00 6,12 28,11
LAIN33 WF

Wind Park SWART1 BUFPT1 LADIS13


LAIN WF Tr 2

trf_73002..

trf_74002..
LAIN0.69 WF Ladismith
SWART22 BUFPT22

Voltage Levels
Laingsburg WF
400, kV
lod_73006_1 lod_74006_1
220, kV
132, kV
66, kV
33, kV

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations/Step 1 – Example 1: cosphi constant (=1)

DIgSILENT
X =150,000 MW
1,08
136.500 MW 1.074 p.u.
1.074 p.u. 1.070 p.u.
1.065 p.u.

58.375 MW
47.697 MW 66.198 MW 1.050 p.u. Y = 1,050 p.u.
1,05

1,02

0,99

0,96

0,93
7,50 47,50 87,50 127,50 167,50 207,50
x-Axis: Laingsburg WF: Active Power in MW
LAIN132 WF: Voltage in p.u. - Base Case
LAIN132 WF: Voltage in p.u. - Lain132kV_Laingsburg_Off
LAIN132 WF: Voltage in p.u. - Laingsburg_Boskloof_Off
LAIN132 WF: Voltage in p.u. - Laingsburg_Droerivier_Off

High Load Voltage Date: 7/24/2009


DIGSILENT Voltage at Laingsburg Wind Farm Connection Point PV-Curve Annex: 1 /2

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations/Step 1 – Example 1:
cosphi(P)-characteristic

DIgSILENT
X =150,000 MW
1,075

1.050 p.u. Y = 1,050 p.u.


1,050
1.044 p.u.
1.038 p.u.
1.037 p.u.

1,025

1,000

0,975

0,950
0,00 40,00 80,00 120,00 160,00 200,00
x-Axis: Laingsburg WF: Active Power in MW
LAIN132 WF: Voltage in p.u. - Base Case
LAIN132 WF: Voltage in p.u. - Lain132kV_Laingsburg_Off
LAIN132 WF: Voltage in p.u. - Laingsburg_Boskloof_Off
LAIN132 WF: Voltage in p.u. - Laingsburg_Droerivier_Off

High Load Voltage Date: 7/24/2009


DIGSILENT Voltage at Laingsburg Wind Farm Connection Point PV-Curve - cosphi(P)-characteristic Annex: 1 /2

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations- Example 1: Summary

• High voltages in case of cos(phi)=1

• Small voltage variations if cos(phi) adjusted to actually generated


power (absorbing vars for compensating increasing voltage)

• Voltage control (with voltage feed-back) at wind farm connection point


is possible but not required in this particular case because:
– Only small voltage steps in case of contingencies
– Only small voltage variations in case of different operational scenarios
(high/low load)
– No voltage stability issue

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Example 2: Large Wind Farms at Transmission Level

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage vs. Reactive Power – Voltage Stability

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations- Example 2: Summary

• Small Voltage Variations in function of active power variations (large


X/R ratios)

• High Voltage Variations in case of critical contingencies

• Voltage control (with voltage feed-back) at wind farm connection point


is required for maintaining voltage stability

• Required reactive power range can be determined by analyzing QV-


curves

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations/Step 2 – Wind Farm Design

• Wind farm design must consider reactive power requirements.

• Reactive power capability at grid connection point is limited by:


– Reactive power capability of wind turbine generators (WTGs)
– Thermal ratings of cables in the wind farm collector system.
– Voltage variations at the LV-nodes (voltage range of operation of WTGs)

• Requirement for additional reactive power compensation devices


(STATCOM, switched shunts) must be taken based on:
– Required reactive power capability
– Required dynamic performance of voltage/reactive power control.

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Reactive Power – Voltage Control

cos(phi)=0,95 cos(phi)=0,95
p

power factor limit

const var limit (recommended)

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations - Wind Farm Design

• Wind farm design must consider grid requirements

• Reactive power capability at grid connection point is limited by:


– Reactive power capability of wind turbine generators (WTGs)
– Thermal ratings of cables in the wind farm collector system.
– Voltage variations at the LV-nodes (voltage range of operation of WTGs)

• Requirement for additional reactive power compensation devices


(STATCOM, switched shunts) must be taken based on:
– Required reactive power capability
– Required dynamic performance of voltage/reactive power control.

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations – Wind Farm Planning Studies
PV
Uset=1,12
Windfarm Red Sunset Project: Example

DIgSILENT
DIGSILENT
CFE/GTZ/DIgSILENT Graphic: Red Sunset
Date: 7/27/2009
PowerFactory 14.0.513 Annex:

/115 kV

Trafo-Typ
0

Tr
/20 kV

NA2XS(F)2Y 1x185RM 12/20kV ir

NA2XS(F)2Y 1x185RM 12/20kV ir


3

2,50 km
S5

2,00 km
Shunt/Filter

S1
S8 S7 S6 max. no.: 3 S2 S3 S4
NA2XS(F)2Y 1x185RM 12/20kVNA2XS(F)2Y
ir 1x185RM 12/20kV
NA2XS(F)2Y
ir 1x185RM 12/20kV ir NA2XS(F)2Y
act. no.: 3 1x185RM 12/20kV
NA2XS(F)2Y
ir 1x185RM 12/20kV
NA2XS(F)2Y
ir 1x185RM 12/20kV ir
0,80 km 0,80 km 0,80 km 7,00 Mvar 1,00 km 1,00 km 1,00 km

NA2XS(F)2Y 1x185RM 12/20kV ir


LV-Trf

LV-Trf

LV-Trf

LV-Trf

LV-Trf

LV-Trf

LV-Trf

LV-Trf
Tr8

Tr7

Tr6

Tr5

Tr1

Tr2

Tr3

Tr4
0 0 0 0 0 0 0 0

0,80 km
S13
N2XS2Y 1x..

N2XS2Y 1x..
1,00 km

0,80 km
Line(3)

Line(4)
WTG 8 WTG 7 WTG 6 WTG 5 WTG 1 WTG 2 WTG 3 WTG 4

S16 S15 S14 S9 S11 S12


NA2XS(F)2Y 1x185RM 12/20kVNA2XS(F)2Y
ir 1x185RM 12/20kV
NA2XS(F)2Y
ir 1x185RM 12/20kV ir NA2XS(F)2Y 1x185RM 12/20kV ir NA2XS(F)2Y 1x185RM 12/20kV
NA2XS(F)2Y
ir 1x185RM 12/20kV ir
0,80 km 0,80 km 0,80 km 1,60 km 0,80 km 0,80 km
LV-Trf

LV-Trf

LV-Trf

LV-Trf

LV-Trf

LV-Trf

LV-Trf
Tr16

Tr15

Tr14

Tr13

Tr10

Tr11

Tr12
0 0 0 0 0 0 0

Windpark Analysis

WTG 16 WTG 15 WTG 14 WTG 13 WTG 10 WTG 11 WTG 12

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Voltage Variations – Wind Farm Design Studies

P [MW]
50

45

40

35

30

25

20

15

10

0
-30 -20 -10 0 10 20 Q [Mvar] 30
-5

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Short Circuit Contribution

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Short Circuit Contribution of Wind Farms

• Calculation of max. short circuit currents:

– Impact on short circuit ratings of existing components (substations,


CB-ratings, cable-/line ratings, transformers etc.)
– Impact on new components, inside the wind farm

• Calculation of min. short circuit currents:

– Verification of protection settings

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Short Circuit Contribution of Wind Farms

DIgSILENT
0,30

ip Fault Cleared

0,20

0,10

0,00

-0,10

-0,20

-0,30
-0,10 0,00 0,10 0,20 [s] 0,30
Tr2: Phase Current A/HV-Side in p.u.
Tr2: Phase Current B/HV-Side in p.u.
Tr2: Phase Current C/HV-Side in p.u.

Fault Current of DFIG with Crow-bar protection


GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Short Circuit Contribution - Modelling

• DFIG and WTGs with fully rated converter are devices with controlled
currents.

• DFIG is usually equipped with protection mechanisms (Crow-bar,


Chopper), which make short circuit behavior highly non-linear.

• Difficult to model for steady state short circuit analysis, which is


typically based on Thevenin-equivalents.

• No special consideration of WTGs given in IEC 60909.

• Proposed approach:
– „Equivalent Synchronous generator“ approach: Characterizing WTG short
circuit currents by subtransient and transient parameters.
– Approach suitable for planning studies but not for highly accurate studies.

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Power Quality

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Power Quality

• Impact on Flicker
– Continuous flicker
– Flicker following switching actions (WTGs, Inrush)

• Impact on Harmonics
– Harmonic injections
– Impact on harmonic impedance

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Continuous Flicker

Caused by
• Turbulences
• “Rotational sampling”:
turbulence variation across the rotor
• Tower Shadow
• Torsional oscillation
Applicable Standards:
• IEC 61000-3-6, IEC 61400-21
Mexican Grid Code: Pst<0,35
Plt<0,25

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Continuous Flicker - Example

DIgSILENT
4.00

2.00

-0.00

-2.00

-4.00

-6.00
-0.1000 14.041 28.182 42.323 56.465 [s] 70.606
Rotor-Turbulence: vt0

-3.20

-3.60

-4.00

-4.40

-4.80

-5.20
-0.1000 14.041 28.182 42.323 56.465 [s] 70.606
T3WT1: Total Active Power/HV-Side in MW

100

10

0.1

0.01

0.001
0.00 1.25 2.50 3.75 5.00 [Hz] 6.25
T3WT1: Total Active Power/HV-Side, Magnitude in MW

Turbulence, Electrical Power and Spectrum of a 5MW Variable Speed Turbine Plots(3) Date: 10/5/2003
DIgSILENT V0=13.6 m/s Annex: /1

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Flicker due to Switching Actions

• WTGs automatically synchronize to the grid if vw>vcutin

• Variable speed WTGs: Very smooth synchronisation


• Fixed speed WTGs: Considerable voltage dip. Mitigation: soft cut-in

• Wind farm energization causes more considerable voltage dips:


– Switching of WTG step-up transformers
– Switching of main transformer
– > only during wind farm energization, not repeting events.

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Switching of Fixed Speed Induction Generator

Typical start-up procedure

• Turbine pulls up the rotor to


ASM
0.9 ..1.1 nnominal
• Breaker is closed

Z’’n
IG’’ • Approximate Formula
V0 X’’ S rG
∆u = Z I = k i ' '
'' ''
n G
Sn

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Switching

DIgSILENT
6000.00 1.025

4000.00 1.000

2000.00 0.975

0.00 0.950

-2000.00 0.925

-4000.00 0.900

-6000.00 0.875
-0.05 -0.00 0.05 0.10 0.15 [s] 0.20 -0.05 -0.00 0.05 0.10 0.15 [s] 0.20
WG 315kW: Phase Current A in A 415V Machines: Voltage Phasor, Magnitude in p.u.
WG 315kW: Phase Current B in A
WG 315kW: Phase Current C in A

1.003 0.90

0.60
1.000

0.30
0.997

-0.00

0.994
-0.30

0.991
-0.60

0.988 -0.90
-0.05 -0.00 0.05 0.10 0.15 [s] 0.20 -0.05 -0.00 0.05 0.10 0.15 [s] 0.20
WG 315kW: Speed 415V Machines: Line-Line Phase Voltage A in kV
415V Machines: Line-Line Phase Voltage B in kV
415V Machines: Line-Line Phase Voltage C in kV

Wind Power Integration Training WG Date: 10/5/2003


DIgSILENT Asm cut-In, directly on line EMT-simulation Annex: 1 /1

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
With Soft Cut-In

DIgSILENT
200.00 1.0250

0.995
100.00

0.965

0.00

0.935

-100.00
0.905

-200.00 0.875
0.05 0.09 0.13 0.17 [s] 0.21 0.05 0.09 0.13 0.17 [s] 0.21
Motor 315kW: Phase Current A in A 415V Machines: Voltage Phasor, Magnitude in p.u.
Motor 315kW: Phase Current B in A
Motor 315kW: Phase Current C in A

1.0100 0.90

0.60
1.0040

0.30
0.998

-0.00

0.992
-0.30

0.986
-0.60

0.980 -0.90
0.05 0.09 0.13 0.17 [s] 0.21 0.05 0.09 0.13 0.17 [s] 0.21
Motor 315kW: Speed 415V Machines: Line-Line Phase Voltage A in kV
415V Machines: Line-Line Phase Voltage B in kV
415V Machines: Line-Line Phase Voltage C in kV

Wind Power Integration Seminar Motor Date: 10/5/2003


DIgSILENT Soft cut-in Annex: 1 /1

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Switching of Variable Wind Generators

SynM

DASM

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Connection of Variable Speed WTG

DIgSILENT
1.025

1.000

0.975

0.950

0.925

0.900
-0.00 0.02 0.04 [s] 0.06
Point of Interconnection: Voltage Phasor, Magnitude in p.u.

0.20

0.10

0.00

-0.10

-0.20
-0.00 0.02 0.04 [s] 0.06
PWM Grid Side: Current, d-Axis in p.u.
PWM Grid Side: d-Axis Current Reference in p.u.

0.04

0.02

0.00

-0.02

-0.04
-0.00 0.02 0.04 [s] 0.06
2-Winding Transformer: Phase Current A/HV-Side in kA
2-Winding Transformer: Phase Current B/HV-Side in kA
2-Winding Transformer: Phase Current C/HV-Side in kA

Wind Power Training Plots Date: 10/5/2003


DIgSILENT Cut-In of Variable Converter driven synchronous machine Annex: 1 /3

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Connection of Variable Speed WTG

DIgSILENT
1.025

1.000

0.975

0.950

0.925

0.900
-0.00 0.02 0.04 [s] 0.06
Point of Interconnection: Voltage Phasor, Magnitude in p.u.

0.20

0.10

0.00

-0.10

-0.20
-0.00 0.02 0.04 [s] 0.06
PWM Grid Side: Current, d-Axis in p.u.
PWM Grid Side: d-Axis Current Reference in p.u.

0.04

0.02

0.00

-0.02

-0.04
-0.00 0.02 0.04 [s] 0.06
2-Winding Transformer: Phase Current A/HV-Side in kA
2-Winding Transformer: Phase Current B/HV-Side in kA
2-Winding Transformer: Phase Current C/HV-Side in kA

Wind Power Training Plots Date: 10/5/2003


DIgSILENT Cut-In of Variable Converter driven synchronous machine Annex: 1 /3

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Harmonic and Inter-Harmonic Injections

Harmonic injections caused by:


• Power electronics converters
• modern PWM converters produce high order harmonics
• Saturation effects (Generator, Transformer)
Inter-Harmonic injections caused by:
• PWM with switching frequency different from multiples of network
frequency
Effect
• Voltage distortion depending on network impedance
• Resonance problems
Standards: IEC 61000-3-7, IEC 61400-21

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Self Commutated Converter

Udc Uac

U DC U AC

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Self Commutated PWM Converter

DIgSILENT
0.20

0.10

0.00

-0.10

-0.20
-0.00 0.02 0.04 0.06 [s] 0.08
2-Winding Transformer: Phase Current A/HV-Side in kA

0.15

0.12

0.09
1100.000 Hz
0.003 kA
0.06
1950.000 Hz 2050.000 Hz
0.004 kA 0.004 kA
900.000 Hz
0.004 kA
0.03

0.00
0.00 1280. 2560. 3840. 5120. [Hz] 6400.
2-Winding Transformer: Phase Current A/HV-Side, Magnitude in kA

Wind Power Training Currents Date: 10/5/2003


DIgSILENT PWM-converter Annex: 1 /4

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Impact on Harmonic Impedance

• Voltage source converters:


– define a path via the coupling reactance to earth for high frequency
harmonics.
– At low frequency harmonics: Controller transfer function needs to be
considered too.
• Effect:
– Shift of resonance frequencies (towards higher order).
– Increased harmonic damping

• Cable capacitance of wind farm-internal cables.


• Effect:
– Shift of resonance frequencies (towards lower order)
– Amplification of harmonic background distortion.

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Impact on Flicker and Harmonics - Summary

• Analysis of Flicker and Harmonics using IEC 61400-21 data sheet of a


typical variable-speed wind generator.

• Flicker generally low in case of large wind farms because Flicker-


relevant turbulences within a wind farm are only weekly correlated

• Harmonics of modern wind turbines (with IGBT-converters) very low.


Almost no harmonic current injections.

• WTGs can have a positive influence on harmonic impedance


characteristics (improved damping, increased resonance frequencies)

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Behaviour During Grid Faults – FRT Requirements

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Example: Converter Driven Synchronous Genenrator

DIgSILENT
1.20

1.00

0.80

0.60

0.40

0.20
0.00 0.20 0.40 [s] 0.60
HV: Voltage, Magnitude in p.u.
MV BusBar: Voltage, Magnitude in p.u.

60.00

40.00

20.00

0.00

-20.00
0.00 0.20 0.40 [s] 0.60
Cub_1\PCC PQ: Active Power in p.u.
Cub_1\PCC PQ: Reactive Power in p.u.

1.15

1.10

1.05

1.00

0.95

0.90
0.00 0.20 0.40 [s] 0.60
Generator: speed

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
FRT Requirements: Summary

Basic FRT-Requirements:

• WTGs must not disconnect in case of voltage dips

• WTGs must deliver active power shortly after a voltage dip

Advanced FRT-Requirements:

• WTGs must inject reactive current during a fault (voltage support,


protection excitation)

• WTGs must not absorb reactive power during voltage recovery

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany
Thank You

Markus Pöller Oscar Amay


mpoeller@digsilent.de o.amaya@digsilent.de

DIgSILENT GmbH
Heinrich-Hertz-Str. 9
72810 Gomaringen
www.digsilent.de

GTZ-TERNA Expert Workshop 2009: Grid and System Integration of Wind Energy, 10.11.2009-12.11.2009, Berlin/Germany

Potrebbero piacerti anche