Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
The ABC’s of
Synchronous Motors
1 1
USA-EM200SYN42 - 05/12
www.electricmachinery.com www.electricmachinery.com
TheThe ABC’s
ABC’s of of Synchronous Motors
Power Factor
Synchronous Motors
In drawing
The Greeks had atheworddiagram, the reactance drop—
for it —SYNCHRONOUS is subtracted
”syn” a prefix2.5
meaning “with,” and “chronos” a word denoting time.
from the terminal voltage to obtain the internal voltage
A synchronous motor literally operates “in time with” or “in sync with” the power supply.
Peak p = 2.5
2
and the direction of the quadrature and direct axes. Peak i = 1.77 (℘2 x 1.25)
The modern synchronous
The internal voltagemotorsets theis alevel
double-duty
of flux inmotor. It is a highly
the motor, 1.5 efficient means of converting alternating current
Peak e = ℘2 E RMS
electrical energy
which, into mechanical
in turn, sets the mmf power. Also (ampere-turns
required it can operate at either1 leading, unity, or in rare cases at lagging power
Average Power = 1.25
= V x I x P.F.
factor, or
providing the function of a synchronous
magnetizing current). The current flowing in thecondenser for power
0.5factor correction.
armature winding produces an mmf called armature 0
In the synchronous
reaction. Themotor,
portion,theinbasic magnetic
line with field isaxis,
the direct obtained
must by –0.5
direct current excitation rather than through the air-gap
from the armature, as is the case with induction
be added (or subtracted, for lagging P.F.) to the mmf,motors. Comparatively large air-gaps are used, making practicable the
manufacture, eventhein internal
producing relativelyvoltage.
low horsepower
Since theratings of low speed synchronous motors.
field winding
–1 In all low speed ratings and in
V = 1.00
motorswinding
of equivalent horsepower.
can supply the required mmf. –2 p, i, e are instantaneous values
A synchronous
If the dc ismotor can bethe
increased, applied to voltage
internal any loadwill
which can be successfully driven by a NEMA Design B squirrel-cage
increase,
motor. and
However, there are certain types of loads for which
since the terminal voltage is fixed by the connected the synchronous motor is especially well suited. The correct
application of synchronous
system, the internal motors results
drop must in substantial
increase. savings in2.5several ways:
The result
of this is shown in Figure 9 where the line current is 2 Average Power = 1.0
t 0.5
en
Curr Et
id re 0
atu θ idxd
Arm iqxq
–0.5 I = 1.25 Power returned to system
Quadrature δ Ed
P.F.∠
Axis –1 V = 1.00
–1.5 Figure 6a
Two-Reaction Diagram
(Leading Power Factor) –2
Note that the current in phase with the voltage represents 2.5
Average Power = 1.0
the load and is unchanged, but a magnetizing component 2
Peak i = √2/0.8
has been added. This component flows to the line to try 1.5
Peak e = √2
to raise the system voltage. The motor has a leading 1 Average Power = 1
= V x I x P.F.
power factor. 0.5
The magnitude of the current and voltages is held constant for Quadrature
Quadrature Axis
iq
Internal Drop
Axis Current
id
iqxq
nt
e
for each in Figure 5a, 6a and 7a. Note that for lagging power urr
Current
eC
atur δ
factor, the current phasor lags the voltage phasor and the Quadrature A
rm Load Angle
instantaneous current passes through zero after the voltage. Axis Internal Voltage Ed
MMF due to (voltage due to field excitation)
Internal Volts
Two-Reaction Diagram
Direct Axis (Unity Power Factor)
Figure 8
8
2 The ABC’s of Synchronous Motors The ABC’s of Synchronous Motors 3
www.electricmachinery.com www.electricmachinery.com
2
and the direction of the quadrature and direct axes. Peak i = 1.77 (℘2 x 1.25)
The internal voltage sets the level of flux in the motor, 1.5
Peak e = ℘2 ERMS
on the rotor poles is in line with the direct axis, dc in this –1.5 Figure 5a
EM synchronous motors are designed and built STATOR … consists of the stationary magnetic parts,
–1.5 Figure 6a
including the core and winding which operate off the
to industry standards Two-Reaction Diagram
(Leading Power Factor) –2
alternating current power supply to provide a rotating
ANSI, IEC, IEEE andAxisNEMA standards help both manufacturer magnetic field.
Direct Figure 9
and user by providing definitions and suggested values.
ROTOR … consists of the rotating active parts, and includes
They are
Notecontinually updated
that the current to incorporate
in phase the latest
with the voltage trends
represents 2.5
the spider, the field-pole windingAverage and the amortisseur
in machine use. Although these standards are
the load and is unchanged, but a magnetizing component gradually 2
Power = 1.0
the exciter
Peak e = √2 or directly through collector rings and brushes;
NEMA provide the standards for synchronous motors
to raise the system voltage. The motor has a leading in the
they
1 interlock magnetically through the air-gap and = V x revolve
Average Power = 1
United power
States,factor.
whereas IEC standards provide the guidelines I x P.F.
The conversion of electrical energy to mechanical energy in Once the synchronous motor is synchronized, the field poles
a motor is accomplished by magnetic fields. In the previous on the rotor are in line with the rotating magnetic poles of the
section, it was explained how magnetic poles are formed when stator. If dc is applied to the rotor pole windings, the rotor can
current flows in coils placed around the stator gap bore. As supply the necessary ampere turns to generate the flux which
explained, these poles rotate around the stator. When voltage produces the internal motor voltage. Thus, the field current
is applied to a motor, an armature current flows to provide the can replace part or all of the magnetizing current. In fact, if
necessary magnetic push (mmf or ampere turns) to produce a more dc field current is supplied, the increased flux will try
flux which, in turn, produces a voltage (back emf) that opposes to increase the line voltage. To increase the line voltage, the
the applied voltage. This mmf is a magnetizing current. It is motor will supply ac magnetizing current to all “magnets” on
loss-less, except for the i2r in the winding and any core loss the system to increase their magnetic flux. This is leading
due to the changing flux in the iron. The magnetic energy is power factor.
transferred from the line to the motor and back again each
The synchronous torque developed is roughly proportional to
half cycle. The net power is zero, and the power factor is zero.
the angle of lag (load angle) of the motor rotor with respect to
The power factor of a synchronous motor is controllable within the terminal voltage, which, at full load, is in the area of 20 to
its design and load limits. It may operate at unity, leading, or 30 electrical degrees. If a restraining force is applied to the
in rare cases, lagging power factor and may be used to modify motor shaft, it will momentarily slow down until a torque is
the power factor of the system to which it is connected. A developed equal to the applied restraint. The motor will then
simplified explanation of phasor relationships will describe continue to operate at synchronous speed.
what takes place under various load and excitation conditions.
Figure 8 shows a somewhat simplified phasor diagram for a
Phasors are vectors that represent the relationship between unity power factor motor connected to a large system such
voltages or currents. The phasor length represents the that the terminal voltage is fixed. Since synchronous machines
magnitude and, as it is allowed to rotate counterclockwise have poles and interpole spaces, a system of phasors represent
about the origin, the projection on the x axis is the instantaneous each of the “direct” (in line with the pole) and “quadrature”
value. axes (interpole).
Figures 5, 6 and 7 show the instantaneous voltage, current and Terminal Direct Axis Internal Drop
power (V times I) for unity, leading and lagging power factors. Voltage Et idxd
The magnitude of the current and voltages is held constant for Quadrature
Quadrature Axis
iq
Internal Drop
Axis Current
id
iqxq
nt
for each in Figure 5a, 6a and 7a. Note that for lagging power rre
Current
Cu
re
atu
factor, the current phasor lags the voltage phasor and the Quadrature Arm
δ
Load Angle
instantaneous current passes through zero after the voltage. Axis Internal Voltage Ed
MMF due to (voltage due to field excitation)
Internal Volts
Two-Reaction Diagram
Direct Axis (Unity Power Factor)
Figure 8
84
4 The ABC’s of Synchronous Motors
www.electricmachinery.com
The conversion of electrical energy to mechanical energy in Once the synchronous motor is synchronized, the field poles
a motor is accomplished by magnetic fields. In the previous on the rotor are in line with the rotating magnetic poles of the
section, it was explained how magnetic poles are formed when stator. If dc is applied to the rotor pole windings, the rotor can
current flows in coils placed around the stator gap bore. As supply the necessary ampere turns to generate the flux which
explained, these poles rotate around the stator. When voltage produces the internal motor voltage. Thus, the field current
is applied to a motor, an armature current flows to provide the can replace part or all of the magnetizing current. In fact, if
necessary magnetic push (mmf or ampere turns) to produce a more dc field current is supplied, the increased flux will try
flux which, in turn, produces a voltage (back emf) that opposes to increase the line voltage. To increase the line voltage, the
the applied voltage. This mmf is a magnetizing current. It is motor will supply ac magnetizing current to all “magnets” on
loss-less, except for the i2r in the winding and any core loss the system to increase their magnetic flux. This is leading
due to the changing flux in the iron. The magnetic energy is power factor.
transferred from the line to the motor and back again each
The synchronous torque developed is roughly proportional to
half cycle. The net power is zero, and the power factor is zero.
the angle of lag (load angle) of the motor rotor with respect to
The power factor of a synchronous motor is controllable within the terminal voltage, which, at full load, is in the area of 20 to
its design and load limits. It may operate at unity, leading, or 30 electrical degrees. If a restraining force is applied to the
in rare cases, lagging power factor and may be used to modify motor shaft, it will momentarily slow down until a torque is
the power factor of the system to which it is connected. A developed equal to the applied restraint. The motor will then
simplified explanation of phasor relationships will describe continue to operate at synchronous speed.
what takes place under various load and excitation conditions.
Figure 8 shows a somewhat simplified phasor diagram for a
Phasors are vectors that represent the relationship between unity power factor motor connected to a large system such
voltages or currents. The phasor length represents the that the terminal voltage is fixed. Since synchronous machines
magnitude and, as it is allowed to rotate counterclockwise have poles and interpole spaces, a system of phasors represent
about the origin, the projection on the x axis is the instantaneous each of the “direct” (in line with the pole) and “quadrature”
value. axes (interpole).
Figures 5, 6 and 7 show the instantaneous voltage, current and Terminal Direct Axis Internal Drop
power (V times I) for unity, leading and lagging power factors. Voltage Et idxd
The magnitude of the current and voltages is held constant for Quadrature
Quadrature Axis
iq
Internal Drop
Axis Current
id
iqxq
nt
for each in Figure 5a, 6a and 7a. Note that for lagging power rre
Current
Cu
re
atu
factor, the current phasor lags the voltage phasor and the Quadrature Arm
δ
Load Angle
instantaneous current passes through zero after the voltage. Axis Internal Voltage Ed
MMF due to (voltage due to field excitation)
Internal Volts
Two-Reaction Diagram
Direct Axis (Unity Power Factor)
Figure 8
2
and the direction of the quadrature and direct axes. Peak i = 1.77 (℘2 x 1.25)
The internal voltage sets the level of flux in the motor, 1.5
Peak e = ℘2 ERMS
which, in turn, sets the mmf required (ampere-turns 1 Average Power = 1.25
= V x I x P.F.
or magnetizing current). The current flowing in the 0.5
armature winding produces an mmf called armature 0
reaction. The portion, in line with the direct axis, must –0.5
be added (or subtracted, for lagging P.F.) to the mmf, V = 1.00
–1
producing the internal voltage. Since the field winding (unity P.F.) i = 1.25
on the rotor poles is in line with the direct axis, dc in this –1.5 Figure 5a
t 0.5
en
urr
id ureC Et 0
at θ idxd
Arm iqxq
–0.5 I = 1.25 Power returned to system
Quadrature δ Ed
P.F.∠
Axis –1 V = 1.00
–1.5 Figure 6a
Two-Reaction Diagram
(Leading Power Factor) –2
Note that the current in phase with the voltage represents 2.5
Average Power = 1.0
the load and is unchanged, but a magnetizing component 2
Peak i = √2/0.8
has been added. This component flows to the line to try 1.5
Peak e = √2
to raise the system voltage. The motor has a leading 1 Average Power = 1
= V x I x P.F.
power factor. 0.5
E
LIN
O
representing minimum ac input and point
TOR
FAC
B representing the input at the desired
40
WER
excitation value. The power factor at
LAG LEAD
UNITY PO
that excitation is CO ÷ DB.
C D
0
0 25 50 75 100 125 150
% OF FULL LOAD .8 P.F. EXCITATION
Load Hrs
“V” Curves MWH P.F. kW kVAR kVA Load Rating
(Est)
T1 Office 77 0.92 194 400 -170 435 435 T1=1000
It is generally assumed that the line voltage will
T2 Pumps 587 0.72 335 1750 -1687 2431 2431 T2=2000
be substantially constant, and it is apparent from
the preceding discussion that load, excitation, line T3 Air 235 0.82 335 700 -489 854 854 T3=1500
amperes, and power factor are closely related. T4 Mill 1347 0.88 464 2900 -1565 3295 - -
This relationship is readily expressed by a family T4 Proposed 335 0.81 335 1000 -724 1235 4522 T4=4000
of characteristic curves known from their shape Overall - 0.824 - 6750 -4635 8188 - -
as “V” curves. These are represented in Figure 10.
Note that for each curve the power is constant and
the excitation is varied to give different magnetizing
Plant Loading and Power factor (synchronous motor proposed)
currents.
Monthly Averages Calculated Transformer
The minimum value of line amperes for each
load condition is at 1.0 or unity power factor. As Load Hrs
MWH P.F. kW kVAR kVA Load Rating
excitation is decreased, the line current will increase (Est)
and the motor will operate at lagging power factor. T1 Office 77 0.92 194 400 -170 435 435 T1=1000
If excitation is increased from the 1.0 power factor T2 Pumps 587 0.72 335 1750 -1687 2431 2431 T2=2000
condition, the line current will again increase, but T3 Air 235 0.82 335 700 -489 854 854 T3=1500
now the motor will operate under a leading power T4 Mill 1347 0.88 464 2900 -1565 3295 - -
factor condition.
T4 Proposed 335 .8 335 1000 750 1250 4522 T4=4000
For any load, the power factor will be the ratio Overall - 0.906 - 6750 -3161 7453 - -
of minimum line amperes at that load to the line
amperes at the excitation value under consideration. Figure 12
For leading power
To operate at 1.0 power factor for maximum factor LEADING
efficiency, set the excitation for minimum ac line synchronous
motors, leading
current. kVARs indicates
kVARs fed kW
to the system, kVAR
where as
induction motors
always absorb kVA
kVARs from the
system.
LAGGING
10
8 The ABC’s of Synchronous Motors
www.electricmachinery.com
kW = kWH/H
Motor rated kVA = 0.746 x HP 100
0.7 P.F. MOTOR
Eff. x P.F.
If the proposed expansion is an induction motor, the overall power 80
factor will be less than 0.9. This will result in additional charges
by the power company. Note that transformer T4 in Figure 11 60
0.9 P.F. MOTOR
will be overloaded.
40
If the addition is a 0.8 leading P.F. synchronous motor, the total 1.0 P.F. MOTOR
kW will be the same, but the kVAR will be less, and the overall 20
Of the five torques, only the first two are significant during
In some cases motor torques are expressed in foot-pounds; however,
starting and accelerating, and only their characteristics
they are usually expressed as a percentage of full load torque.
will be discussed here.
A synchronous motor has many important torques that determine the
The amortisseur windings
ability of the motor to start, accelerate, pull its connected load into step,
and operate it through anticipated peak loads within its design limits. These windings develop most of the starting and
accelerating torque in motors of this type. This winding
These torques may be described as:
consists of a partially distributed cage winding, with
1. Starting torque or breakaway torque. bars imbedded in the pole faces and short circuited at
This is the torque developed at the instant of starting at zero speed. each end by end rings. Varying the number, location and
resistance of these bars will have a substantial effect on
2. Accelerating torque. the torque and on the kVA input. In some cases a double
This is the motor torque developed from stand-still to pull-in speed cage, consisting of one row of shallow bars and one
minus the load torque. row of deepset bars, is used. These may be separate,
or they may have common end rings as circumstances
3. Pull-up torque. will dictate. Typical amortisseur windings are illustrated
This is the minimum torque developed between stand-still and the in Figure 15.
pull-in.
4. Pull-in torque.
This is the torque developed during the transition from slip speed 500 4
to synchronous speed and generally is defined at 95% speed. 3 kVA CURVES
6. Pull-out torque.
This is defined as the maximum steady state torque developed 200
by the motor, for one minute, before it pulls out of step due to 4
overload. 100 3
2
1 TORQUE CURVES
0
0 25 50 75 100
10
12 The ABC’s of Synchronous Motors % SYNCHRONOUS RPM
www.electricmachinery.com
Torque comes from the action of the flux produced by the stator.
Getting more torque requires more flux and, therefore, more iron.
More torque also results in more inrush. For any given motor, the As the rotor comes
effective resistance and reactance of the cage winding are the up to speed, the slip
principal factors in determining motor torques. Typical starting frequency decreases
and accelerating torques and their associated kVA values are and, with it, the
shown in Figure 16. impedance of the deep
cage. This permits
The double cage motor was developed to give essentially constant more of the induced
pull-up torque. The shallow cage has high resistance and low current to flow through the deep-set, low-resistance bars,
reactance, while the deep cage has low resistance and high resulting in high torques at speeds near pull-in. Figure
reactance. At standstill, slip frequency equals line frequency, and 17 illustrates the resultant torques using this type of
the high reactance of the deep cage forces most of the induced construction.
current to flow through the shallow cage, high resistance bars,
resulting in high starting torque. Ideal applications for double cage windings are those where
the load is uniformly high during the entire accelerating
period. Disadvantages include saturation, due to the
number of cage bars in the pole head, and stress due to the
differential thermal expansion in bars that are close together.
Double cage motors are relatively uncommon.
TORQUE FROM UPPER CAGE
Figure 16 (left) Curves show starting torque and starting kVA of
synchronous motors using various types of amortisseur winding
TORQUE RESULTANT - DOUBLE CAGE constructions. For any given motor, the effective resistance and
TORQUE
0 50 100
% SYNCHRONOUS SPEED
100
NEGATIVE
ROTATING
COMPONENT
600 hp. 900 rpm motor and a throttled centrifugal fan
80 load. The total motor and load WK2 (inertia) is given as
0 50 100 29770 lb.ft.2.
% SYNCHRONOUS SPEED PULL-IN TORQUE
60
12
14 The ABC’s of Synchronous Motors
www.electricmachinery.com
much heat as possible into the pole body and also that 20
TORQUE OF FAN
H = 0.231 x 29,770 x (855)2 = 5020 kW seconds result of accelerating the inertia, and of overcoming the load torque.
(1000)2 Since all of the torque developed by the motor must either accelerate
inertia or overcome load torque, and since slip loss is a function of this
H is expressed in per unit by dividing the above by rated kW torque and of slip, it is readily possible to determine this energy input.
(rated horsepower x 0.746). Interestingly, two times H in
Referring again to the motor and load characteristics covered by Figure
per unit is the accelerating time if the accelerating torque
20 and Figure 21, we can proceed as follows:
is equal to rated torque. Applying this to our example:
H = 11.2 and the average accelerating torque is 76%. Slip loss = 0.746 x TM x S x HP x t,
Accelerating time (t) = 11.2/0.76 x 2 = 29.5 seconds. in kilowatt seconds
TM = % motor torque
Some types of loads, such as ball mills, have very low
S = % slip
inertia values, but their load torque may approach
that developed by the motor if the rate of acceleration t = Time at that torque
and the accelerating torque is low. Large fans Note that slip loss is proportional to average slip and to average
may have both high inertia values and appreciable total motor torque (not net accelerating torque) for each 10% speed
torque requirements. In such cases, it is desirable to interval considered. As shown in Figure 21, total loss in the rotor is
determine the total energy input to the rotor, both as a 6400 kW seconds.
100 0
The ABC’s of Synchronous Motors
Torque 98 2
% SYNCHRONOUS RPM
Since it was previously determined that the loss due to accelerating the
inertia was 5020 kW seconds, we now determine the additional loss due 96 4
% SLIP
to the load is 6400 - 5020 = 1380 kW seconds.
In some cases the speed of the driven unit will differ from that of the driving 94 6
motor, because of belting or gearing arrangements. All WK2 values used
in determining accelerating time or energy absorption must be effective 92 8
values referring to the motor speed.
(rpm2)2
Effective WK12 = Wk22 x
(rpm )2 90 10
1 0 20 40 60 80 100
Effective WK 2 = WK2 referred to the RATIO LOAD Wk2 TO NORMAL LOAD Wk2
1
motor shaft rpm
Wk22 = Inertia of driven machine Figure 22 Relationship between load inertia and minimum
in lb. ft.2 @ rpm slip for pulling into step of a specific synchronous motor.
2
rpm2 = Speed of load shaft in
C HP
revolutions per minute S= x
rpm WK2
rpm = Motor shaft speed in
1
revolutions per minute
S = Slip in % of synchronous speed
WK2 = Inertia of motor rotor plus load inertia
Pull-in Torque
C = Constant taking into account such factors as
efficiency, power factor, etc.
The pull-in point (when a synchronous motor changes from
induction to synchronous characteristics and operation) is usually The relationship between slip and inertia in a given motor is
the most critical period in the starting of a synchronous motor. The shown by the curve in Figure 22. The larger the inertia the
torques developed by the amortisseur and field windings become higher the speed required to achieve synchronization.
zero at synchronous speed. They cannot pull the motor into step,
so the reluctance torque and the synchronizing torque (resulting Load Inertia
from exciting the field windings with direct current) take over.
Since load inertia is so important in determining the speed to
Reluctance Torque which the motor must accelerate before pull-in is possible,
NEMA has established normal load WK2 values. These are
Any magnetic object tends to align itself in a magnetic field so covered by the formula:
that the magnetic reluctance is at a minimum. There are as many
1.15
positions of a salient pole rotor within the rotating stator magnetic 3.75 x HP
Normal load WK2 =
field as there are poles. Below synchronous speed, a pulsating
( rpm /1000)
2
Synchronizing Torque We may designate as “inertia factor” the ratio of actual load
WK2 to normal load WK2. This varies over a wide range. Typical
When excitation is applied, definite polarity is developed in the values are shown in Figure 24.
rotor poles. If the slip is low enough, the attraction between
unlike poles in the rotor and the stator will lock the rotor into NEMA defines pull-in torque as the maximum constant torque
step with the rotating stator magnetic field. Neglecting the under which the motor will pull its connected inertia load into
influence of reluctance torque, the value of slip from which the synchronism at rated voltage and frequency, when excitation is
motor will pull into step may be expressed as follows: applied. This is sometimes referred to as “load” pull-in torque.
14
16 The ABC’s of Synchronous Motors
www.electricmachinery.com
Figure 22, pull-in can be affected at 8% slip with normal load 450 RPM
WK2. However, with an inertia factor of 100, the motor must 10
600 RPM
reach 99.2% of synchronous speed on the cage winding before
5
the motor will pull into step on application of excitation. A motor 900 RPM
will therefore have a much higher “load” pull-in torque when 1200 RPM
driving a load having a low inertia factor than with a load having 2
1800 RPM
a high inertia factor.
1
0 500 1000 2000 3000 4000 5000
It is rarely possible for the motor manufacturer to shop test the RATED HORSEPOWER
pull-in torque of a motor under actual load conditions. As a
practical substitute, the motor torque developed at 95% speed Figure 23 Curves show the relationship between rated horsepower,
(“nominal” pull-in torque) is used as a design and test point to speed and normal load WK2 for synchronous motors.
The load pull-in torque value (indicated in column 6) for 1. Type of load
chippers is merely friction and windage as shippers must be 2. Horsepower
3. RPM
started, accelerated, and synchronized unloaded. 4. Assumed inertia factor
5. Maximum slip from which motor will pull-in, in percent
In some cases, in order to obtain an adequate rate of 6. Load torque required at pull-in
acceleration, it will be desirable to design for higher nominal 7. Nominal pull-in torque
pull-in torque values than those shown in column 7 of Figure 26. Figure 26
Frequently, where it has been difficult for the motor to pull into
step on application of excitation, raising the applied excitation
voltage will facilitate pull-in. FREQUENCY OF FIELD-DISCHARGE CURRENT
60 CYCLES 30 CYCLES 6 CYCLES
MOTOR SYNCHRONIZED
3 CYCLES
if the excitation is applied at the proper interval of the field INDUCED FIELD CURRENT
discharge current wave, it will readily build up to a maximum INDUCED FIELD CURRENT
Excitation applied here
value, being assisted by the field discharge current, thus
Excitation applied here
pulling the rotor into step promptly and with a minimum of
line disturbance. Improved synchronization can be obtained
by proper timing of field application.
2.0 2.5
Figure 28b Stator Current. Rotor pulls into synchronism with minimum stator current. (Note: Pulsations of current after synchronism are
oscillations due to very large flywheel effect of the load.)
16
18 The ABC’s of Synchronous Motors
www.electricmachinery.com
magnetic
flux in δ electrical
air-gap degrees
d
90° 180°
0°
32°
S S' N
ROTOR
The ABC’s of Synchronous Motors 19
www.electricmachinery.com
200
TRANSIENT TORQUE
125
100
0
0 2 4 6 8 10 12 16
TIME IN CYCLES
Figure 30 Transient pull-out torque of a synchronous motor. Synchronous motors 3000 HP at 164 RPM with DPG enclosures driving a
This torque is influenced by reactance of the motor windings. dual pinion ball mill at an iron ore mine.
18
20 The ABC’s of Synchronous Motors
www.electricmachinery.com
Figure 31
Pulsations in total torque
due to reluctance
~20% variations in magnetic
circuit at 95% speed; 6 Hz.
or .167 sec./cycle.
.167 sec.
3 cycles
~20%
Figure 32
Pulsations in total torque
due to reluctance
variations in magnetic
.042 sec. circuit at 80% speed; 24
Hz. or .042 sec./cycle.
12 cycles
100
Figure 33
Typical speed-torque curve
showing average torque.
MOTOR %
TORQUE
95
0
0 25 50 75 100
% SYNCHRONOUS SPEED
As will be noted from the application section, the starting (zero Extreme care must then be taken in analysis of the
speed) torques required of salient-pole industrial synchronous system’s capacity, torque requirements, starting kVA,
motors range from 40% to 200%. and starting method.
The required pull-in torque depends upon the load torque and the Full-voltage starting, due to its simplicity, should be used
total inertia. As covered in the previous section, the nominal pull- wherever possible. Most systems can stand dips of up
in torque is the actual torque the motor develops at 95% speed. to 20%. System capacities are usually expressed as
MVA short circuit capacity. A quick approximation of the
The starting kVA depends on both the starting torque and the voltage dip during starting can be made by converting
nominal pull-in torque. For a given starting torque, the starting the motor inrush to MVA as follows:
kVA of a synchronous motor in percent of the full-load kVA will SCMVA = System short circuit capacity
increase with an increase in the ratio of nominal pull-in torque to in MVA
starting torque. Figure 34 shows some typical values. MMVA = (% of motor inrush/100) x
(motor kVA/1000)
% Starting Torque % Nominal Pull-in Torque % Starting kVA MVA = motor starting kVA
Motor kVA = HP x 0.746/(P.F. x Eff.)
80 60 355 % dip = MMVA x 100/(SCMVA) + MMVA)
80 80 410
In some cases, a reduction in starting kVA is necessary
80 100 470
to limit voltage dip. Line diagrams for various reduced
Figure 34
kVA starting methods are illustrated in Figure 35.
The starting kVA of synchronous motors often taxes the capacity Figure 36 shows motor voltage, line kVA and motor torque
of the generating or distribution system to which it is connected. relationships for various methods of
Full-voltage starting should always be used Line kVA is reduced approximately as the Line kVA is reduced approximately as the
unless (1) limited capacity of power systems square of the motor terminal voltage, as motor terminal voltage, but torque is reduced
makes reduced kVA starting necessary, or (2) is the motor torque. Closed transition as the square of the voltage. The starter
torque increments are required in starting. autotransformer starters avoid the line has the advantage of simplicity and closed
surges experienced with earlier open- transition switching.
transition switching.
Type of Starting Motor Voltage in % of Full Voltage Line kVA in % of Full Voltage kVA Motor Torque in % of Full Voltage Torque
Full Voltage 100 100 100
"Reduced
78 60 60
Voltage "
Reactor 60 60 36
Figure 36
20
22 The ABC’s of Synchronous Motors
www.electricmachinery.com
starting. Figure 37 shows full voltage starting kVAs for 1.0 P.F.
motors at high and low speeds.
To show what is required of the control, consider the starting 1. Provide a discharge path for the current induced in the field
of a synchronous motor. The ac breaker closes, applying three of the motor during starting, and open this circuit when
phase voltage to the stator winding. The stator winding has excitation is applied.
been wound to form a number of magnetic poles
2. Apply field excitation positively when
the motor reaches an adequate speed.
This excitation should be applied with
Field discharge resistors such polarity that maximum torque
will be obtained at the time of pull-in.
1 2 3
FDR
“SYNC-RITE”™
DC TO CONTROL 3 PHASE
EXCITER FIELD UNIT 6 SCR-2 AC
4 5 D10
ROTATING EQUIPMENT
Figure 39
Control Circuit
If the rotor does not synchronize, it will slip a pole; the induced
The control circuit keeps the SCR-1 from firing until the field voltage will oppose the exciter voltage causing the current
induced field current frequency is very low, representing a close to go to zero, turning SCR-1 off. SCR-2 is turned on only at a
approach to synchronous speed, and then fires the rectifier SCR- voltage higher than the exciter voltage so it will not be on when
1 at the proper time and applies excitation to the synchronous SCR-1 is on.
motor field. At the same time, the field discharge resistor is
Occasionally, a lightly loaded motor will synchronize without
removed from the circuit. This is done by the inherent operating
excitation being applied. This is due to the reluctance torque.
characteristics of silicon controlled rectifier SCR-2. This
Reluctance torque results from the magnetic circuit having less
frequency sensitive part of the control circuit assures that field
reluctance when the poles line up with the stator flux. The EM
excitation is applied at the proper pull-in speed for successful
design includes a “zero slip” circuit to apply excitation in these
synchronizing and at the proper polarity to give maximum pull-in
situations.
torque with minimum line disturbance.
While this may seem complex, it has proven to be a highly
The control circuit operates to remove excitation should the
reliable system.
motor pull out of step due to a voltage step or excessive
mechanical load. On the first half cycle after pull-out, the Features of the brushless exciter
induced field voltage causes the net field current to pass through
zero, turning SCR-1 off, automatically removing excitation. 1. No brushes, no carbon dust problems, no brush
SCR-2 operates to connect the field discharge resistor back maintenance.
in to the circuit. During this time, the motor operates as an
induction motor. When conditions permit, field is then reapplied 2. No commutator or slip rings to resurface.
as during starting.
3. Completely automatic field application at the best angle for
In Figure 39, the voltage from the exciter-rectifier is blocked sure synchronization.
by SCR-1 until the point of synchronization. The field has an
4. Removal of excitation and application of field discharge
alternating voltage causing current to flow first through SCR-2
resistor in the event of out of step operation and automatic
and the discharge resistor. On the next half cycle, current flows
resynchronization.
through the diode and discharge resistor. The control circuit
waits until the frequency drops to the preset value, indicating 5. No sparking. Can be used in hazardous areas.
the rotor is at an adequate speed. Then, after a North pole on
the stator is in the right position to be attracted to what will be 6. No field cubicle with FDR and field contactor to maintain.
a South pole on the rotor, it triggers SCR-1 to apply excitation.
Synchronous motors can handle any load which can be A few general rules may be established as a preliminary guide
driven by a NEMA design B squirrel-cage motor. Whether in selection of synchronous vs. induction motors, but specific
they should be used for any specific application is a matter of local conditions must govern:
some investigation. A rough rule of thumb is that synchronous
motors are less expensive than squirrel-cage motors if the 1. If especially low starting kVA, controllable torque or
rating exceeds 1 HP per rpm. However, that considers only adjustable speed are desired, a synchronous motor and
initial cost and does not take into account: slip coupling may be used.
1. Higher efficiency of the synchronous motor. 2. At 3600 rpm, synchronous motors are sometimes used
from 10,000-20,000 HP. Above that range they are the
2. Power factor improvement of the synchronous motor. only choice.
These two factors become important at speeds below 500 3. At 1800 rpm, motors show an advantage above 1000 HP.
rpm where induction motor characteristics leave much to be From 2000-10,000 HP, synchronous motors are used if
desired. On the other side of the balance are these: power factor improvement is especially important. Above
15,000 HP, they are the only choice.
3. Necessity for excitation source and field control means for
the synchronous motors. 4. Induction motors for operation below 500 rpm have
lower efficiency and a lower power factor. Synchronous
4. Relatively low torque/kVA efficiency in starting. motors are built at unity or leading power factor and with
good efficiencies at speeds as low as 72 rpm. For direct
5. Slightly greater maintenance cost, especially with motors
connection in ratings above 1000 HP and in speeds below
with slip rings and brushes.
500 rpm, the synchronous motor should be the first choice
for compressors, grinders, mixers, chippers, etc.
Leading power factor motors are slightly less efficient than unity
power factor motors, but they do double duty. Their application
depends on the necessity for power factor correction.
26
24 The ABC’s of Synchronous Motors
www.electricmachinery.com
20,000 SYNCHRONOUS
15,000
10,000
HORSEPOWER
7,500
EITHER
SYNCHRONOUS
OR INDUCTION
5,000
2,000
1,000 INDUCTION
500
3600 1800 1200 900 720 600 514 450 400 360 327 300
RPM
Synchronous motors for air and gas compressors and 5. Minimum floor space requirement.
vacuum pumps
6. Low maintenance cost.
Air and gas compressors and vacuum pumps may be
reciprocating, rotary or centrifugal. Synchronous motors Motors designed for direct connection to reciprocating
may be used with any of these types. Detailed application compressors are usually engine type or single bearing
information follows: construction. The stator is mounted on soleplates set in
the foundation. A special case is the flange-mounted motor
Reciprocating compressors and vacuum pumps in which the stator frame is mounted on a flange on the
compressor frame. In either case, torque requirements are
Many more synchronous motors are direct connected to usually within the range of normal design, low speed motors.
reciprocating compressors than are applied to all other types See Figure 41.
of loads combined. Factors contributing to this are:
The torque values may be exceeded for certain compressors
1. Low starting and pull-in torque requirement of unloaded and vacuum pumps; the manufacturer should be checked for
reciprocating compressors. specific values.
2. Elimination of belt, chain and gear drives. NEMA Recommended Torques Torques in % of Full-Load Torque
for Reciprocating Compressors Starting Pull-in Pull-out
3. High efficiency of low speed synchronous motors direct Air or Gas - Starting Unloaded 40 30 150
connected to compressors. Vacuum Pumps - Starting Unloaded 40 60 150
Current pulsation
A reciprocating compressor has a varying torque requirement will tend to have a natural period of oscillation. The
per revolution, depending on number of cylinders, crank angle, common pendulum is a good example.
etc. As discussed previously, the angle of rotor lag and the
amount of stator current vary with torque. There will be a cyclic The natural frequency of this oscillation in a synchronous
pulsation of the load current during each revolution. This in motor is determined by the formula:
itself is not too objectionable, but excessive current pulsation
may result in appreciable voltage variation and thus affect
NF = 35200
N
√ Pr x Hz
WK2
lights or other devices sensitive to voltage change.
NF = Natural frequency in oscillations per minute
Present standards limit current pulsation to 66% of rated N = Synchronous speed in revolutioins per minute.
full-load current, corresponding to an angular deviation of Pr = Synchronizing power
approximately 5% from a uniform rotative speed. The current Hz = Line frequency in CPS
pulsation is the difference between maximum and minimum WK2 = Flywheel effect in foot pounds squared
values expressed in percent of full-load current. Figure 42 It is assumed there is no effective damping and the motor
shows an actual oscillogram of current input to a synchronous is connected to an infinite system. This natural frequency
motor driving an ammonia compressor. should differ from any forcing frequency by at least 20%.
In some cases, step unloading of compressors involving Compressor factor
successive unloading of various cylinder ends is used. This
introduces additional irregularity into the crank effort and Neglecting inertia and damping forces, a single cylinder,
usually increases the current pulsation. double-acting or a two cylinder, single-acting compressor
will have a crank effort diagram similar to Figure 43. A
Natural frequency two cylinder, double-acting or a four cylinder, single-
acting crank effort diagram is illustrated in Figure 44.
Any system having mass in equilibrium and having a force
tending to return this mass to its initial position, if displaced,
ONE REVOLUTION
IN FOOT POUNDS
TORQUE
Figure 43
Crank effort diagram for a one
cylinder, double-acting compressor,
or two cylinder, single-acting
compressor.
0 180 360
26
28 The ABC’s of Synchronous Motors DEGREES
www.electricmachinery.com
200
ONE REVOLUTION
IN FOOT POUNDS
TORQUE
Figure 44
Crank effort diagram for a two
cylinder, double-acting compressor,
or four cylinder, single-acting
compressor.
Centrifugal fans, blowers and compressors differ from reciprocating The term “centrifugal” may be applied to radial-flow, mixed-
units in that the pressure developed is a function of the density of flow or axial-flow pumps. In all cases, energy is added to the
the air or gas handled, the speed of the impeller, and of restriction to flowing liquid by means of pressure differences created by
flow. The gas is accelerated in passing through the rapidly rotating vanes of a rotating impeller or propeller. The radial-flow pump
impeller, this velocity being converted into pressure in the volute discharges the liquid at right angles to the shaft, the mixed-
casing surrounding the impeller. flow discharges it at an angle, and the axial flow propels the
liquid in an axial direction.
Units operating at pressures above 30 psi are called compressors.
For pressures above 100 psi, multi-stage compression is commonly Hydraulically, the difference is fundamentally one of the
used. These units are especially suited for high volume at low “specific speed” used in the design. Mathematically, it is
pressure. NEMA recommended torques are shown in Figure 47. shown by this formula:
30
28 The ABC’s of Synchronous Motors
www.electricmachinery.com
mills may be gyratory, cone, hammermill, or roll type. c. Casing filled, discharge open 5-40 100 150
Pumps, centrifugal, radial impeller – starting with:
Rod mills may also be used as secondary grinders. A a. Casing dry 5-40 15 150
rod mill consists of a steel shell lined with wear-resistant b. Casing filled, discharge closed 5-40 40-60 150
material and rotated about a horizontal cylinder axis. The c. Casing filled, discharge open 5-40 100 150
mill uses steel rods 2 to 5 inches in diameter running the Pumps, mixed flow - starting with:
length of the mill. As the mill rotates, the tumbling action a. Casing dry 5-40 15 150
of the rods causes grinding. b. Casing filled, discharge closed 5-40 82-125 150
c. Casing filled, discharge open 5-40 100 150
Final grinding, possibly down to a material which will Pumps, reciprocating - starting with:
pass through a 200 mesh screen or finer, is usually a. Cylinders dry 40 30 150
done in a ball mill. This is similar to a rod mill except b. By-pass open 40 40 150
that steel balls tumble over the material to be crushed. c. No by-pass (three cylinder) 150 100 150
Figure 49
Autogenous mills use the crushed rock to grind itself to
powder. See Figure 50 for NEMA recommended torques Torques in % of Full-load Torque
Application
for the various types of mills. Starting Pull-in Pull-out
Gyratory (unloaded) 100 100 250
Synchronous motors for pulp and paper mills Cone (unloaded) 100 100 250
Hammermill (unloaded) 100 80 250
One of the largest power consuming industries is that of Roll crusher (unloaded) 150 100 250
processing wood and wood products in the manufacture Rod mill - ore 160 120 175
of paper and pulp. Ball mill - ore 150 110 175
Ball mill - rock or coal 150 110 175
Although alternative fibers may be used in relatively small Figure 50
quantities in the manufacture of pulp and paper, by far the
largest source is wood. Paper may be made either by the NEMA Recommended Torques in % of Full-load Torque
groundwood or chemical process. The application table Torques Starting Pull-in Pull-out
Refiners (unloaded) 50 50-100 150
and recommended NEMA torques shown in Figure 51
Conical (Jordan) disc 50 50 150
cover the usual synchronous motor applications in paper Chippers - empty (1) 60 50 250
mills, most of which are common to both processes. Grinders (unloaded)
Magazine 50 40 150
Paper mills are large users of synchronous motors for Pocket (unloaded) 40 30 150
pumps, refiners, chippers and other equipment. Vacuum pumps (Hytor) 60 100 150
(1) These are high-inertia loads and motor torque requirements can not be determined from load value
alone. WK2 values must be known to permit proper motor application.
Figure 51
To overcome this, a slip clutch (eddy current drive) is As technology has advanced over the latter third of the twentieth century,
sometimes used. Electric Machinery manufactures a the ability to change the frequency of the incoming line power — and thus,
magnetic drive for this use. Here the motor runs at rated to control the speed of “constant speed” motors — has become a reality.
speed and the magnetic drive slips, allowing the load to run This has led to adjustable speed drives for pumps, fans, compressors and
at a lower speed. At the lower speed the output and the other loads, yielding higher operational efficiencies, lower wear rates, softer
torque required are reduced. Although the torque is reduced, starting, lower starting currents, and even quieter operation as machines
the motor still runs at rated speed, so the HP is down in run at reduced speeds. See Figure 54 and compare it with Figure 53 to
proportion to the torque. There is some slip loss in the slip see potential efficiency improvements with adjustable frequency vs. eddy
clutch. This type of variable speed drive is declining in use. current drive.
30
32 The ABC’s of Synchronous Motors
www.electricmachinery.com
100 100
% Rated Shaft Horsepower
50 50
Throttling
losses saved by Throttling VFD
25 using magnetic Eddy current drive 25 losses saved by input power
drive input power required using VFD required
T x constant RPM T x variable RPM
(speed squared curve) (speed cubed curve)
0 0
0 25 50 75 100 0 25 50 75 100
% Rated Output % Rated Output
Figure 53 Power into eddy current drive is product of Figure 54 Power into variable frequency drive is the product of
torque required and constant input rpm. With an the torque required and the output rpm. With a load as in
unthrottled fan or pump, the torque requirement is nearly Figure 53, the input varies as the speed cubed.
a direct function of speed squared, thus, input power
varies as the output speed squared.
CURRENT FLOW
BRUSHLESS DC MOTOR
ELECTRONIC
+
DC
SUPPLY COMMUTATOR
CONVERTER
MOTOR
AC
BREAKER
HIGH
VOLTAGE
SUPPLY POWER
FLOW
TRANSFORMER
–
Figure 55 Load commutated variable frequency drive (6-pulse).
Speed 4 6 2
C-A
A
As with any thyristor circuit, once a thyristor is turned on, the C-A
current must be reduced to zero before the thyristor returns to the BA
non-conducting state. With an excited synchronous motor as the CB
load, the commutation is accomplished using the open circuited
winding to generate opposing voltages in the machine. (Figures 56 C
and 57.) To provide reliable operation at low speeds, encoders are
sometimes used to indicate the instantaneous position of the rotor 1 3 5
to the control so that succeeding thyristors can be turned on at the
proper instant. Variations in technologies also exist which use no 1 3 5
encoders, but work by sensing the back voltages from the machine. Figure 56 Load Current Path (C-A)
The six-step approach, while the simplest, is not the smoothest. The C-B CB
pulsations associated with the finite progression of magnetic fields C-B C
around the stator are reflected in torque pulsations and magnetic
noise. Care must be exercised to avoid critical frequencies in the
motor shaft and other elements which could respond to pulsations 1 3 5
set up by the inverter action. In some cases, special couplings must 1 3 5
be applied to avoid premature failures. The six-step approach is Figure 57 Load Current Path (C-B)
commonly used for horsepower in the 500-2500 range, sometimes A smoother-acting system can be assembled by taking
up to 6000 HP. Refer to Figure 60. advantage of the 30° difference between the secondary
voltages in wye and delta connected transformers. Using
this motor and transformer combination, a twelve-step
inverter can be applied.
34
32 The ABC’s of Synchronous Motors
www.electricmachinery.com
above, but the steps now are at 30° intervals rather than at
60°, as in the six-step inverter. Another significant advantage T2'
the wye and delta secondaries; they do not appear in the T1'-T3'
incoming power to the twelve step converter. The result is 2. -T3 5. 2. -T2
-T3
T1'-T3'
3. 6. 3. -T3
-T3
T1'-T3'
T2-T3 T3-T2 T1 T1-T3 T1' T1-T3
T2 -T3 -T2 T3
T1 T1
Υ T2 T2
T3 T3
1 3 5 5 3 1
Winding example of 6 pulse machine Both windings used on 12 pulse machine
Current Out
Current In
Current In
Degrees
120 X X T1 T3 SCR's
transformers between the inverter and the motor, but the 180 X X T2 T3 Switch Every
motor is frequently wound with a dual winding to isolate 240 X X T2 T1 60°
300 X X T3 T1
the outputs of the two inverter sections. The two separate
360 X X T3 T2
windings are shifted 30 electrical degrees. Each part of
the motor stator actually sees a six-step progression, but 30 X X T1 T2 X X T1' T2'
the rotor sees the twelve-step sum of the two inputs to the 60 X X T1 T2 X X T1' T3'
90 X X T1 T2 X X T1' T3'
machine. The twelve-step approach is typically used for 120 X X T1 T3 X X T2' T3'
12 Pulse Dual Winding
horsepowers of 2000 and larger, even up to 50,000. 150 X X T2 T3 X X T2' T3' SCR's
180 X X T2 T3 X X T2' T1' Switch Every
Current-limiting functions are often employed during 210 X X T2 T1 X X T2' T1' 30°
240 X X T2 T1 X X T3' T1'
starting, keeping currents to values considerably under 270 X X T3 T1 X X T3' T1'
normal locked rotor values. The current limit is adjustable 300 X X T3 T1 X X T3' T2'
and is set as a function of the amount of torque required. 330 X X T3 T2 X X T3' T2'
360 X X X T3 T2 X T1' T2'
Available starting torque, when operating with an LCI, is more
Figure 62 SCR firing sequence for 6 pulse and 12 pulse drive.
like the maximum operating torque of the motor, since it is
The ABC’s of Synchronous Motors 33
35
www.electricmachinery.com
Cooling the machine may be by use of an integral fan if the load is variable
torque and is not expected to operate at speeds below about 50% for
Current in Delta/Delta and Delta/WYE Transformers extended periods. If a constant torque load is being driven, however,
Fourier Series: and particularly if the speed will be less than 50% rated, external cooling
fans must be employed. Often, the motor will be oversized to lessen the
Itotal = 2 √ 3 Id (cos θ − 1∕11 cos 11θ + 1∕13 cos 13θ
π
effects of reduced cooling at lower speeds.
- 1∕23 cos 23θ + 1∕25 cos 25θ —)
Sometimes present in the output supplied to the motor from the LCI are
Figure 63 Sine wave simulation of VFD output.
common mode voltages which may impose higher-than-usual stresses
to ground from the machine winding. Accordingly, it is necessary to
provide groundwall insulation with 1.3 to 1.8 times the normal dielectric
strength compared to ordinary machines when the unit is to be operated
from an inverter.
34
36 The ABC’s of Synchronous Motors
www.electricmachinery.com
Figure 64
By-Pass and LCI
Contactor are
interlocked to be
mutually exclusive.
LCI
DRIVE
The exciter design must differ from conventional designs We have seen that the motors used with inverters are much
in that conventional exciters extract energy from the the same as those which are applied only at line voltages
rotating shaft, whereas, that source would be such a and frequencies; the major differences being in two-
variable factor — even approaching zero at very low winding stators for the twelve-step inverter applications,
speeds — the energy must be transmitted to the rotor possible heavier ground-wall insulation, cooling, and three
by another means. Exciter designs for these motors use phase exciter stator windings, plus torsional considerations
three-phase ac excitation on the stator, applied so the and, possibly, provisions for supersynchronous operation
rotating field is counter-rotating to the rotor. In a very real which affects the mechanical facets of the design as well
sense, it is a rotating transformer with an air gap in the as the electrical. However, these are but refinements to
magnetic circuit, and all of the power developed in the the machine to adapt it to a special application.
rotor comes from the excitation source. The exciter may
Advances in technology, bringing about such equipment
or may not have the same number of poles as the motor;
as the Load Commutated Inverter, continue to open new
however, the frequency in the rotor circuit is not critical,
doors of opportunity for application of that old, reliable
since it is rectified.
workhorse of industry, the Synchronous Motor.
An advantage of the LCI drive which has not been
Synchronous motors fill an important place in industry.
discussed is the ability to run at supersynchronous speed
They are usually associated with loads of major importance.
(higher than the synchronous speed of a machine with
A corresponding degree of care in their applications is well
the same number of poles when connected to the line). If
advised and worth the extra effort.
this kind of operation is planned, it must be kept in mind
that centrifugal forces are a function of the square of
Now deceased, Gerry Oscarson was the original author of this special issue of the EM Synchronizer.
He held Electrical Engineering degrees from the University of Minnesota. Specializing in electric power
apparatus, Mr. Oscarson was directly associated with the industrial application of motors, generators, and
controls. For many years, he was Chief Application Engineer of the Electric Machinery Manufacturing
Company. The ABC series of EM Synchronizers are Gerry’s work. These remain as standard references
for industrial plants around the world, and are often used as texts by engineering schools.
Jack Imbertson
Jack Imbertson holds an Electrical Engineering degree from the University of Minnesota. While at EM,
he held the positions of Design Engineer, Programmer, Manager of Synchronous Machines, and Manager
of Turbo Generators. He has been active in IEEE and was a past chairman of the IAS section. He also
served as a member of the ANSI C50 standards committee on synchronous machines.
Since retirement, he has taught electro-mechanics at the University of Minnesota and does some
consulting.
Ben Imbertson
Ben Imbertson holds a Bachelors degree in Electrical Engineering from the University of Minnesota and
is a registered Professional Engineer. While at EM, he worked as a Control Design Engineer, Control
Engineering Section Head, and Principal Engineer-Control Products.
His EM experience included applications in synchronous and induction motor control, generator control,
as well as adjustable-speed drives. His post EM experience has been in similar areas.
Ben’s writing has appeared in several EM publications including the Synchronizer, “The ABC’s of Motor
Control.”
Steve Moll
Steve Moll is presently Senior Marketing Representative with Electric Machinery. He holds a Bachelor
of Electrical Engineering degree from the University of Minnesota.
His experience at EM includes Senior Design Engineer where he worked with motor and generator
controls, as well as high voltage switchgear and controls for gas turbine driven generators. In his
present position, his area of specialty is application and marketing of 2-pole turbine driven generators.
He has significant experience with synchronous and induction motors as well.
36
38 The ABC’s of Synchronous Motors
www.electricmachinery.com
Notes
WEG Electric Corp. offers the following products, and more! With a full range
of IEC/NEMA Global Certifications and a full line of products, WEG can supply
the right solution for your needs anywhere in the world. To learn more about
WEG’s products and solutions or to locate a Distributor near you, please call
1-800-ASK-4WEG or visit www.weg.net/us.
Low Voltage Motors, Variable Frequency Drives Custom Panels
Single and 3-Phase, 1/8 – 700HP Low Voltage 1/4 to 2500HP, 230V – 480V Custom configured to your specification.
General Purpose Motors Medium Voltage 500-8000HP NEMA 1, 12, 3R, 4 and 4X cabinets
Explosion Proof Motors Multi-pump systems Quick delivery of preconfigured drives
Crusher Duty Motors NEMA 4X and soft starters
IEC Tru-Metric Motors Dynamic braking resistors UL 508 certified
Pump Motors including JP/JM Line and load reactors Low Voltage (230-460)
P-Base Pump Motors Plug and play technology Made in the U.S.A.
Oil Well Pumping Motors Network communications: Profibus-DP,
Pool & Spa Motors DeviceNet, Modbus-RTU Generators
Brake Motors PLC functions integrated Brushless Synchronous Generators for diesel gen-
Compressor Duty Motors Complete line of options and accessories sets up to 4,200kVA
Farm Duty Motors Hydro-generators up to 25,000kVA
Poultry Fan Motors Soft Starters Turbo-generators up to 62,500kVA
Auger Drive Motors 3-1500HP
IEEE 841 Motors Oriented start-up Power Transformers
Stainless Steel Wash Down Motors Built-in bypass contactor Built and engineered in North America
Saw Arbor Motors Universal source voltage (230-575V, Voltages < 500kV
Cooling Tower Motors 50/60Hz) Ratings 5-300MVA
Commercial HVAC Motors Network communications: Profibus-DP, Station class, oil filled, round core, copper windings
Pad Mounted Motors DeviceNet, Modbus-RTU Special configurations and designs available!
Vector Duty Motors Complete Line of options and accessories Ask your WEG Sales Representative for details.
MV Soft-starter 3.3kV, 4.16kV: up to Designed, built, and engineered to ANSI standards.
Large Electric Motors 3500HP, Withdrawable Power Stacks, & 8x
Low Voltage 3-phase motors up to PT100 Temperature monitoring Custom Solution Package Sales
2,500HP WEG can package any of its products for ease of
Motors up to 150,000HP and 14,400 V Controls sale! Enjoy a single point of contact for the entire
Wound Rotor Systems (including starters) Mini – Contactors package of products and assistance from quote
up to 70,000HP and 13,200V IEC Contactors through after-sales support. Ask your WEG Sales
Synchronous Motors up to 70,000HP and Thermal Overload Relays Representative for details.
13,200V Manual Motor Protectors
Explosion proof motors (Ex-d) up to Molded Case Circuit Breakers Magnetic Drives
1,500kW and 11kV Smart Relays
Ex-n, Ex-e, Ex-p motors Enclosed Starters: combination & non- Ratings range from 300-1800 rpm and 200-2700
combination, HP. Simple air-cooled design requires no auxiliary
Pushbuttons & Pilot Lights cooling and are available in horizontal and vertical
Timing & Motor Protection Relays constructions. No torque pulsations or harmonic
Terminal Blocks pollution eliminates the need of filters. Suitable for
pump and fan applications by matching equipment
speed to meet flow demands.
USA-EM200SYN42