Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
BEST PRACTICE
UNIT 230
RELIEF AND BLOWDOWN SYSTEM
10004.HTP.PRC.PRG
Rev. 0 – January 2008
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 2 of 93
INDEX
ACRONYMS 5
REFERENCE 92
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 4 of 93
For Main Utilities Best Practice reference shall be made to Eni E&P
internal document No. 10002.HTP.PRC.PRG.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 5 of 93
ACRONYMS
1.1 General
This document sets out the general guidelines for sizing and designing a
relief and blowdown system, for both on-shore and off-shore production
facilities, with particular attention to the flare sizing.
The principal elements of pressure relief systems are the individual
pressure relief devices, the flare piping system, the flare separator drum,
and the flare — including sealing devices, purge and steam injection for
smokeless burning.
Design of relief systems must comply with applicable state and federal
codes and laws as well as the requirements of the insurance covering the
plant or installation. State and federal regulations not only cover safety
but also environmental considerations such as air and water pollution and
noise abatement.
This section presents a convenient summary of relief, depressuring and
disposal systems information obtained from API 520 / 521 / 526 / 537 and
other sources.
outlet coincidental with a power failure. On the other hand, instrument air
failure during fire exposure may be considered single jeopardy if the fire
exposure causes local air line failures.
The consequences that may develop from any utility service loss,
whether local or plantwide, must be carefully evaluated. The normal utility
services that could fail and a partial listing of affected equipment that
could cause overpressure are given in Table 1.3.1.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 10 of 93
Even if fire is not usually the condition that may create the greatest
relieving requirements, it is the most common case.
Various empirical equations have been developed to determine relief
loads from vessels exposed to fire. Formula selection varies with the
system and fluid considered (see API 521, Section 5).
Jet fire is a fire created when a leak from a pressurized system ignites
and forms a burning jet. Jet fires can occur when almost any combustible
/ flammable fluid under pressure is released to atmosphere. Equipment
failure during a jet-fire is due to a localized and instantaneous
overheating without a significant pressure increase in the equipment (the
relief device set point isn’t often reached). This is due to the localized
nature of heating whereby the bulk fluid temperature might not increase
appreciably. Hence, a relief device might not prevent vessel failure from
jet fire impingement.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 11 of 93
Entrance of water or light hydrocarbons into hot oil, causing a great and
instantaneous expansion in volume, can cause system overpressure.
Normally, a pressure relieving device is not provided for this contingency.
Proper design and operation of the process system are essential in
attempts to eliminate this possibility.
When a large difference exists between the design pressure of the shell
and tube sides of an exchanger, provisions is required for relieving the
low pressure side (it could be required either on shell side or on tube
side). Because the test pressure is normally about 150% of the design
pressure, a “2/3 rule” is established from it. The rule is this: pressure relief
for tube rupture is not required where the low pressure exchanger side
(including upstream and downstream systems) is designed at or above
the 2/3 criteria. Because ASME changed the hydrostatic test pressure for
pressure vessels from the 150% design pressure to a new standard of
130% design pressure, the existing “2/3 rule” changed to a “10/13 rule”.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 12 of 93
As a general rule, the required relief capacity is based on twice the tube
cross section area, and the assumption that high pressure fluid can flow
through both the tube stub and the other end of the tube.
(c) Piping or vessels are blocked-in while they are filled with liquid at
near-ambient temperatures and are heated by direct solar
radiation.
Provisions are required for relieving the equipment. The capacity
requirement is not easy to determine. Since every application will be
relieving liquid, the required capacity of the thermal safety valve (TSV)
will be small; specifying an oversized device is, therefore, reasonable. A
3⁄4” ÷ 1” nominal pipe size (NPS 3⁄4 ÷ NPS 1) relief valve is commonly
used.
Proper selection of the set pressure for these relieving devices should
include a study of the design rating of all items included in the blocked-in
system. The TSV pressure setting should never be above the maximum
pressure permitted by the weakest component in the system being
protected.
3⁄4” ÷ 1” size is not adequate for long pipelines of large diameter in
uninsulated aboveground installations and large vessels or exchangers
operating liquid-full; in these cases, in order to evaluate the relief device
proper size, the following equation must be applied:
αV ⋅ φ
q= (1)
1000d ⋅ c
Where:
q volume flowrate at flowing temperature [m³/s]
αV cubic expansion coefficient for the liquid at the expected
temperature [1/°C]
φ total heat transfer rate [W]
d relative density referred to water (d = 1.00 @15.6°C)
c specific heat capacity of trapped fluid [J/kgK]
In the following is given a short summary for sizing the relief devices for
those equipment, such as pumps, compressors, atmospheric and low
pressure storage tanks, etc., which are not included in the API 520 and
API 521. This paragraph is also intended to give a brief description about
pressure safety valve operating in liquid service.
1.3.3.1 Pumps
Where:
pset Valve set pressure [bar]
pdelivery Pump delivery pressure [bar]
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 15 of 93
For valves sizing a flowrate value equal to the pump flowrate (or pump
maximum flowrate in case of pumps with variable motor) must be taken
into consideration.
Lines and equipment downstream a centrifugal pump have always a
design pressure equal to the pump shut-off pressure. Wherever this rule
is not applied, the piping and / or equipment downstream the pump shall
be protected with a relief device.
1.3.3.2 Compressors
1.3.3.3 Turbines
b) For all the equipments whose upper tangent line is higher than
10.5 m (or above the relief header upper tangent line), the
following considerations shall be applied:
b.1) If the equipment is inside a structure, the PSV shall be
positioned 1.5 m above the first level over the equipment upper
tangent line. This level is 3 m above the upper tangent line.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 17 of 93
b.2) If there isn’t a level over the equipment, the PSV shall have a
minimum elevation above the upper tangent line.
The pressure drop of the piping between protected equipment and its
relief valve shall not exceed 3% of the set pressure.
The inlet and outlet piping shall be installed without pockets to ensure
that liquid does not accumulate at the relief valve outlet or inlet.
Relief valves discharging to atmosphere should be located at the
maximum practical elevation to keep discharge piping (to safe location)
as short as possible. In case of multiple relief valves (including one
spare), each relief valve shall have an individual discharge pipe (see also
API 521).
Relief valves connected to a closed relief system shall be located above
the relief header. Relief valve outlet lines should be connected to the top
of the header, or at least so that the header cannot drain back into outlet
lines even with the header full of liquid. If the valves cannot be put above
the header, they shall be lined up to discharge into a local drain vessel.
Alternatively, if the problem of elevation is confined to a few valves, outlet
lines to the header shall be heat-traced from the relief valve to the highest
point of the line. Heat tracing isn’t permitted for relief valves which
discharge a medium which can leave a deposit.
Relief valve systems require periodic inspection and maintenance and
hence they should be easily accessible.
Because of a relief valve cannot depressurize a system but can only limit
the pressure rise to the set point during upset conditions, a dedicated
depressuring system is required to mitigate the consequences of a vessel
leak by reducing the leakage rate or to reduce the failure potential for
scenarios involving overheating (e.g. fire).
When metal temperature is increased due to fire or exothermic or
runaway process reactions, the metal temperature may reach a level at
which stress rupture could occur. This may be possible even though the
system pressure does not exceed the maximum allowable accumulation.
In this case, depressuring reduces the internal stress thereby extending
the life of the vessel at a given temperature.
In order to be effective, the depressuring system must depressure the
vessel such that the reduced internal pressure keeps the stresses below
the rupture stress. API 521 suggests depressurizing to 6.9 barg or 50% of
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 24 of 93
In large plants, in order to reduce the design blowdown flow rate, process
sectionalizing may be considered.
Process sectionalizing is a philosophy applied to split an installation into a
number of smaller fire zones. Potential fire areas shall be identified and
clearly shown on a plot plan. For process units, depending on the
drainage design of the plot, a typical fire area of 300 m² should be
assumed.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 27 of 93
pressure exceeds 30% to 50% of the set pressure due to subsonic flow
and/or physical responses to the high back pressure. Refer to API 520-I
for the effects of this back pressure.
in place when isolation block valves are used. Local jurisdictions may
have other requirements.
As per API 520 Part II, all the isolation valves located in relief system
piping shall meet the following requirements:
a) Valves shall be full bore.
b) Valves shall be suitable for the line service classification.
c) Valves shall have the capability of being locked or car sealed
open.
d) When gate valves are used, they should be installed with stems
oriented horizontally or, if this is not feasible, the stem could be
oriented downward to a maximum of 45° from the horizontal to
keep the gate from falling off and blocking the flow.
An isolation valve can be used either to isolate the individual relief valve
or to isolate a complete plant section. If isolation valves are used to
isolate relief valves, there is a basic difference between the need for an
inlet valve or for an outlet valve. An inlet valve is needed if the process
cannot be shut down, whereas an outlet valve is needed if the relief
header cannot be taken out of service. Thus a single relief valve (without
a spare) connected to a relief header which cannot be shut down will
have only an outlet isolation valve.
When isolation valves are installed in pressure relief valve discharge
piping, a means to prevent pressure build-up between the pressure relief
valve and the isolation valve should be provided (for example, a bleeder
valve), see Figure 1.6.1.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 31 of 93
Figure 1.6.1 – Typical pressure relief valve installation with an isolation valve.
Figure 1.6.2 – Typical pressure relief valve installation with 100% spare relieving
capacity and a three-way valve.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 33 of 93
Figure 1.6.3 – Typical pressure relief valve installation with 100% spare relieving
capacity.
Figure 1.6.4 – Typical interlocking System for pressure relief valves with atmospheric
discharge.
provided with single locks, while the inlet block valves shall have double
locks. As per atmospheric discharge, the piping between the upstream
block valve and the relief valve shall be fitted with a vent connection in
order to allow depressuring before the removal of the relief valve.
Each relief valve shall be provided with a unique key which fits Lock 1 of
its inlet block valve and the lock of its outlet block valve. The key of the
outlet block valve shall be retractable only when the outlet block valve is
locked open. The key of Lock 1 of the inlet block valve shall be
retractable only when the switch key is inserted in Lock 2 of the same
inlet block valve.
Each relief valve shall be provided with a single switch key which fits
Lock 2 of all inlet block valves. The switch key shall be retractable only
when the inlet block valve is locked open. This shall only be possible
when the key of Lock 1 is inserted in the lock. During operation, only the
inlet block valve of the installed spare S/R valve will be in the locked
closed position. All other block valves will be locked open. Locking open
the outlet block valve of the installed spare S/R valve (or its replacement
spool piece) prevents pressure build-up in case the inlet block valve
should leak.
The keys of the locks of the block valves of the relief valves in operation
will be trapped in Lock 1 of the inlet block valves. The switch key will be
trapped in Lock 2 of the closed inlet block valve of the spare valve. Since
the switch key is needed to unlock and close an inlet block valve, only
one block valve can be in the closed position at any time.
The key of Lock 1 of the inlet block valve of the spare valve shall be
stored in the control room which shall only be accessible to authorized
personnel.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 36 of 93
Figure 1.6.5 – Typical interlocking System for pressure relief valves with discharge to
a closed system.
Notice that also outlet valve could be subjected to a key interlock system:
in this case the key system could avoid to close outlet valve if the inlet
valve is open (that means that outlet valve could be closed only if the inlet
valve is closed; i.e. PSV in maintenance and an other PSV in service).
1.7.1 General
The type and height of the structures supporting flare or vent stacks
depend on the following operational and environmental aspects:
• Required availability of the flare and relief system;
• Acceptable heat radiation levels;
• Acceptable dispersion levels;
• Acceptable noise levels;
• Wind velocity.
There are three common stack support methods as shown in Figure
1.7.1.
The type selection is based on economical and operational grounds. A
brief structure description is given in the following.
1.7.5.1 Self-supported
Self-supported stacks are normally the most desirable. However, they are
also the most expensive because of greater material requirements
needed to ensure structural integrity. They are normally limited
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 40 of 93
These are the least expensive but require the largest land area due to the
guy-wire radius requirements. Typical guy-wire radius is equal to one-half
the overall stack height.
Utility / Pipe Flare: This is the simplest flare tip; this plain design has no
special features to prevent smoke formation, and consequently should
not be used in applications where smokeless operation is required unless
the gases being flared are not prone to smoking.
Flare tips of this style, as a minimum, should include a flame retention
device (to increase flame stability at high flowrates) and one or more
pilots (depending upon the diameter of the tip).
Smokeless Flare:
Steam Injection: Flare tips which use steam to control smoking are the
most common form of smokeless flare tip. The steam can be injected
through a single pipe nozzle located in the centre of the flare, through
a series of steam/air injectors, through a manifold located around the
periphery of the flare tip, or a combination of all three. The steam is
injected into the flame zone to create turbulence and/or aspirate air
into the flame zone via the steam jets. The amount of steam required
(see API 521, 5th Edition, Table 11) is primarily a function of the gas
composition, flowrate, and steam pressure and flare tip design.
Although steam is normally provided from a 100 to 150 psi (690-1034
kPa) supply header, special designs are available for utilizing steam
pressure in the range of 30 psi (2.07 kPa). The major impact of lower
steam pressure is a reduction in steam efficiency during smokeless
turndown conditions.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 42 of 93
⎛ W ⎞ z ⋅T
Mach = 3.23 ⋅ 10 −5 ⎜ ⎟ (6)
⎜ P ⋅d2 ⎟ k ⋅ MW
⎝ atm f ⎠
Where:
W Flow [kg/h]
Z Compressibility factor at flowing condition
T Temperature at vapour outlet [K]
df Flare diameter [m]
k Specific heat ratio, Cp/Cv
The flare stack height is generally based on the radiant heat intensity
generated by the flame. For flare radiation study, reference shall be made
to paragraph 1.11.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 46 of 93
Streams which are rich in hydrogen sulphide shall not be discharged into
a common HC flare or vent system unless it has been designed for this
purpose. This prevents the spreading of sour gas throughout the entire
main flare system and also avoids corrosion attack by hydrogen sulphide
and the subsequent accumulation of deposits of (pyrophoric) ferrous
sulphide.
These streams shall have a separate line-up, preferably a separate flare
stack equipped with a tip of the air pre-mix type. Alternatively, the gas
may be lined up to the bottom (downstream of the water seal) of the
hydrocarbon flare stack, but this should only be done if the hydrogen
sulphide rich flow constitutes a minor additional load.
The installation of a separate sour gas flare relief system implies
additional capital expenditure. From this point of view it is always better to
exclude such a system.
For a preliminary evaluation, the following factors should be considered
before deciding that a separate H2S flare relief system need to be
installed or not. Sour gas release can be tied into the HC flare system in
case of:
1) continuous HC release with an H2S content < 2% by volume;
2) intermittent HC release (only during startup and shutdown) with
an H2S content < 20% by volume, provided this stream is less
than 10% by volume of the total continuous HC release rate;
3) emergency HC release (e.g. PSV, emergency depressuring) with
an H2S content < 50% by volume.
When hydrogen sulphide rich gas has to be flared, incomplete
combustion can cause a hydrogen sulphide smell resulting in complaints
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 48 of 93
Gas streams from relief headers are frequently at or near their dewpoint,
where condensation may occur.
A knockout drum is usually provided near the flare/vent base, and serves
to recover liquid hydrocarbons, prevent liquid slugs, and remove liquid
particles. The knockout drum reduces hazards caused by burning liquid
that could escape from the flare stack.
As mentioned above, all lines downstream a relief/blowdown device
should be sloped toward the knockout drum to permit condensed liquid to
drain into the drum for removal. The locating of the flare/vent knockout
drum also needs to take into account radiation effect from the burning
flare/accidental ignition of the vent.
The economics of drum design may influence the choice between a
horizontal and a vertical drum. When a large liquid storage capacity is
desired and the vapour flow is high, a horizontal drum is often more
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 49 of 93
g ⋅ D ⋅ ( ρ L − ρV )
U d = 1.15 ⋅ (8)
ρV ⋅ C
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 50 of 93
Where:
Ud Maximum allowable vapour velocity for vertical vessels [m/s]
g Acceleration due to gravity, 9.81 m/s2
D Particle diameter [m]
ρL Liquid density [kg/m³]
ρV Vapour density [kg/m³]
C Drag coefficient determined using Figure 1.9.1
0.13 ⋅ 10 8 ⋅ D 3 ( ρ L − ρV )
C (Re) 2 =
µ2
µ Gas viscosity [cP]
The size of a vent stack is determined by the available pressure drop and
by any minimum velocity required to prevent hazardous conditions due to
combustible or toxic material at grade or working levels. Therefore, in
order to avoid the formation of flammable mixtures and to provide an
excellent dispersion, vent size is selected to have a discharge velocity of
at least 500 ft/s (152 m/s). Moreover, vent size should be checked to
ensure that sonic flow is not established.
The height of the vent stack is selected so that the concentration of
vapour at a point of interest is well below the lower flammable limit of the
vapour. Flammability consideration can be satisfied with 0.1 times to 0.5
times the lower flammable limit.
The radiant heat intensity for vent stacks should also be checked in the
event that a relieving vapour should ignite. This is done by the same
means used for flare stacks, and the same limits apply for radiant heat
intensity. Radiant heat levels sometimes take precedence over dispersion
in determining stack height.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 53 of 93
Another factor that must be taken into account when sizing a vent stack is
the noise level. Eni E&P internal standard, see doc. no
04927.PKG.MEC.SPC, suggests, in the worst operating conditions, the
noise level shall be no higher than 85 dB (A) for a radius of 50 m around
the base of the flares and property limits. For vent stack noise specific
calculation, see API 521, Section 7, Paragraph 7.3.4.3.
Table 1.11.2 – API 521 recommended design thermal radiation for personnel.
Flare system design and plant equipment layout should minimize the
need for operator attendance and equipment installed in locations of high
radiant heat intensity.
Personnel are commonly protected from high thermal radiation intensity
by restricting access to any area where the thermal radiation can exceed
6.31 kW/m2. The boundary of a restricted access area can be marked
with signage warning of the potential thermal radiation exposure hazard.
Personnel admittance to, and work within, the restricted access area
should be controlled administratively. It is essential that personnel within
the restricted area have immediate access to thermal radiation shielding
or protective apparel suitable for escape to a safe location.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 56 of 93
τ ⋅ F ⋅Q
D= (7)
4π ⋅ K
Where:
D Minimum distance from the epicentre of the flame to the object
being considered [m]
τ Fraction of the radiated heat transmitted through the atmosphere
F Fraction of heat radiated
Q Heat release [kW]
K Radiant heat intensity [kW/m²]
The wind tilts the flame in the direction the wind is blowing. As mentioned
above, assuming that a flame can be modelled by a single point source
for radiation, the wind effect is obtained from Figure 1.11.2, which relates
horizontal and vertical displacement of the flame to the ratio of lateral
wind velocity to stack velocity. A wind velocity ( u ∞ ) of 9 m/s (20 mph) is a
common assumption for most radiation calculations. The flame radiation
epicentre is located at the centre of a straight line drawn between the
flare tip and the end of the flame.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 58 of 93
Figure 1.11.2 - Approximate flame distortion due to lateral wind on jet velocity from
flare stack
Figure 1.11.4 – Flame centre for flares and ignited vents — Horizontal distance.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 60 of 93
Figure 1.11.5 – Flame centre for flares and ignited vents — Vertical distance.
• General:
In general, the study for unit 230 sizing shall be divided in three
main phases: the first one involves a PSVs study, the second one
is related to BDVs, headers and flare sizing and the third one
concerns with the above mentioned flare radiation study. Each
phase requires care in evaluating relief / blowdown valves’
position, flowrate, etc. and during headers, K.O. drum and flare
sizing. The study consists in producing a list for all plant PSVs
and BDVs; the list shall contain the valve flowrate (for each valve)
for each upset condition. Once determined the most severe
overpressure condition (in most cases fire represents the worst
overpressure condition) for each plant section, the study may
proceed in headers, K.O. drum and flare sizing. Finally, the flare
radiation study shall be used to determine the flare thermal
radiation intensity and to evaluate the flare stack height.
• Relief devices sizing:
Set pressures and maximum relief pressures, expressed in
relation to the design pressure of the protected equipment, all
expressed in gauge pressures, shall not exceed the values given
in the following table (strictly related to ASME VIII).
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 62 of 93
To establish the size of a pressure relief device, the designer must first
determine the conditions for which overpressure protection may be
required. Reasonable care should be exercised in establishing the
various contingencies that could result in overpressure. The size of the
relief valve and the inlet and outlet piping shall be determined using the
largest relief load.
Pressure relief valves may be initially sized using the equations
presented in the following paragraphs, as appropriate for vapours, gases,
liquids, or two phase fluids.
The designer can then use API 526, Flanged Steel Pressure Relief
Valves, to select a pressure relief valve. This standard lists specific valve
configurations specified by inlet/outlet size and flange configuration,
materials of construction, pressure/temperature limits, inlet and outlet
centre to face dimensions, and effective orifice designation.
Design Considerations
The overpressure used for the calculation of the relief valve can be
derived from the maximum allowable accumulated pressure. This
overpressure is the maximum allowable accumulated pressure minus the
set pressure and the pressure drop of the piping connecting the relief
valve and the vessel. The pressure drop shall not exceed 3% of the set
pressure. This shall be based on the relief valve capacity.
It shall also be ensured that the blowdown pressure is above the
maximum operating pressure. However, if the blowdown pressure is set
too close to the set pressure the relief valve may open and close rapidly
causing damage to the valve. For most services the blowdown pressure
will usually be 5-7% below the valve set pressure.
For equipment protected by a pressure relieving device, either on the
equipment itself or elsewhere within the pressure system containing the
equipment, there shall be an adequate margin between the set pressure
and the maximum operating pressure.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 67 of 93
k
⎛ 2 ⎞ k −1
PCF = P1 ⎜ ⎟ (9)
⎝ k + 1⎠
So, the sizing equations for pressure relief devices in vapour or gas
service fall into two general categories depending on whether the flow is
critical or sub-critical.
Critical Flow (P2 ≤ PCF) — Safety valves in gas or vapour service may be
sized using the following equations:
131.6W T1 Z
A= (10)
CK d P1 K b K c MW
5.875QV T1 ZMW
A= (11)
CK d P1 K b K c
k +1
⎛ 2 ⎞ k −1
C = 520 k ⎜ ⎟ (12)
⎝ k + 1⎠
Where:
A = required effective discharge area of the device, [cm²]
W = flow, [kg/hr]
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 68 of 93
Sub-critical Flow (P2 > PCF) — For downstream pressures greater than the
critical-flow pressure, the relief valve orifice area can be calculated from
the following equations:
0.179W T1 Z
A= (13)
F2 K d K c MWP1 ( P1 − P2 )
Where:
P2 = downstream pressure at valve outlet [kPaa].
F2 = coefficient for sub-critical flow.
For a proper sizing Figure 1 or the following equation shall be
used.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 69 of 93
⎛ k ⎞ (2 ⎡ (1 − r (k −1) k ) ⎤
F2 = ⎜ ⎟⋅r
k)
⋅⎢ ⎥
⎝ k − 1⎠ ⎣ (1 − r ) ⎦
Where:
r = P2 / P1
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 70 of 93
1.904W
A= (14)
P1 K d K b K c K n K SH
Where:
Kn = Napier’s equation correction factor.
Kn shall be evaluated using the following equation:
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 72 of 93
0.02764 ⋅ P1 − 1000
• If 10340 kPaa < P1 < 22057 kPaa: Kn =
0.03324 ⋅ P1 − 1061
KSH = superheat steam correction factor (see Figure 4). For saturated
steam, for any pressure, KSH = 1.
For relief valves sizing for liquid service, the following equations shall be
used:
7.07 ⋅ Vl G
Turbulent flow: A= (15)
K d K c K w K v ( P1 − Pb )
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 73 of 93
Where:
Vl = flowrate at flowing temperature and pressure, [lt/sec].
G = relative density of liquid at flowing temperature, referred to water at
standard condition.
Kv = capacity correction factor due to viscosity.
Kw = capacity correction factor due to back pressure. If the back pressure
is atmospheric, use a value for Kw of 1.0.
Pb = back pressure, [kPag]
Laminar flow (Re < 4000): For liquids with laminar flow, the valve shall be
first sized using the above equation assuming Kv = 1. The so obtained
discharge area, A, is compared with manufacturer standard orifice sizes
and from manufacturer this is chosen the next larger orifice A’. Then, A’ is
used for Reynolds number determination:
112654 ⋅ Vl ⋅ G
Re = (16)
µ A'
With the just calculated Reynolds, using Figure 5, a first tentative value
of Kv shall be obtained.
For a preliminary sizing of a two phase relief valve, the following method
shall be considered:
• Determining gas and liquid relieving rates.
• Calculating the orifice area required to gas relieving.
• Calculating the orifice area required to liquid relieving
• Summing total areas calculated for liquid and vapour to obtain the
total required orifice area.
However, for a more rigorous solution, DIERS (Design Institute for
Emergency Relief Systems) proposed an alternative method based on
the classical homogeneous equilibrium model assuming no slip between
the liquid phase and the vapour phase.
B ⋅Q
Vl = (17)
1000 ⋅ G ⋅ S
Where:
Q = Heat input, [W]
S = Specific heat, [kJ/kg°C]
B = Liquid expansion coefficient at relieving temperature, [1/°C], see
Figure 6.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 75 of 93
After calculating the flowrate, Vl, the relief device shall be sized applying
equation (13).
In order to evaluate the flowrate, in case the heat input is due to solar
radiation, the interested surface area and the radiation (780-1040 W/m²)
must be determined.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 76 of 93
Reference Documents
API 521 recommends the use of High Integrity Protection System (HIPS)
only when the use of pressure relieving devices is impractical (e.g. due to
extreme field investments).
ASME Code Case 2211 sets the conditions under which overpressure
protection may be provided by an instrumented system instead of a
pressure relief valve (PRV). This ruling is intended to enhance the overall
safety and environmental performance of a facility by utilizing the most
appropriate engineered option for pressure protection. While there are no
specific performance criteria in the Case Code, the substitution of the
HIPS for the PRV should provide a safer installation. Consequently, the
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 77 of 93
substitution is generally intended for limited services where the PRV may
not work properly due to process condition, e.g. plugging, multiple
phases, raising temperature above thermal decomposition point and
causing an internal detonation or fire, etc.
The overpressure protection can be provided by a Safety Instrumented
System (SIS) in lieu of a pressure relieving device under the following
conditions:
a) The vessel is not exclusively in air, water, or steam service.
b) The decision to utilize overpressure protection of a vessel by
system design is the responsibility of the user. The manufacturer
is responsible only for verifying that the user has specified
overpressure protection by system design, and for listing Code
Case 2211 on the Data Report.
c) The user must ensure the maximum allowable working pressure
of the vessel is higher than the highest pressure that can
reasonably be expected to be encountered by the system.
d) A quantitative or qualitative risk analysis of the proposed system
must be made addressing all credible overpressure scenarios.
e) The analysis in (c) and (d) must be documented.
IEC 61508 The objective of these standards is to define the design and
documentation requirements for SIS.
One of the most important criteria for SIS design is the requirement that
the user assigns and verifies the Safety Integrity Level (SIL) for the SIS.
The assignment of SIL is a corporate decision based on risk
management philosophy and risk tolerance.
Safety instrumented systems (SIS) should be designed to meet a safety
integrity level, which is appropriate for the degree of hazard associated
with the process upset. Safety integrity levels per IEC 61508 are
designated in the following table:
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 78 of 93
Safety
Availability Probability to Fail
Integrated 1/PFD
Required on Demand (PFD)
Level (SIL)
4 > 99.99% E-005 to E-004 100000 to 10000
3 99.90 ÷ 99.99% E-004 to E-003 10000 to 1000
2 99.00 ÷ 99.90% E-003 to E-002 1000 to 100
1 90.00 ÷ 99.00% E-002 to E-001 100 to 10
Table 2 – Safety integrity level.
HIPS Justification
A decision tree can be utilized to facilitate the justification for HIPS in the
process industry.
Figure 7 is a simplified decision tree showing the key steps in assessing
and designing a HIPPS.
HIPS Design
maintenance program for each HIPS once the device, architecture, and
voting have been selected.
Logic Solver: This hardware must meet the required SIL, which often
means that it must comply with SIL-3 performance requirements, as
provided in IEC 61508.
The logic solver can be relays, solid state or Programmable Electronic
Systems (PES). If a PES is used, it must provide a high level of self-
diagnostics and fault tolerance. Redundancy of signal paths and logic
processing is necessary, and the trip output function must be configured
as de-energize to trip.
IEC 61508 requires that the safety logic be separate and independent
from the basic process control system; therefore, in order to reduce the
probability that both functions would become contemporary unavailable,
HIPS is separated from the Basic Process Control System.
Final Control Elements: The final control elements in HIPS are usually
two shutdown valves in series working in a 1oo2 configuration. On-line
testing provisions should be provided to permit each valve to be function
tested independently.
Eni S.p.A. 10004.HTP.PRC.PRG
Rev. 0 – January 2008
Exploration & Production Division
Sh. 82 of 93
GLOSSARY
DESIGN PRESSURE Value selected for the design of equipment for the
ELEVATED FLARE Flare where the burner is raised high above ground
level to reduce radiation intensity and to aid in dispersion.
FLARE BURNER / FLARE TIP Part of the flare where fuel and air are
mixed at the velocities, turbulence and concentration required to establish
and maintain proper ignition and stable combustion.
FLARE HEADER Piping system that collects and delivers the relief
gases to the flare.
JET FIRE Jet fire is a fire created when a leak from a pressurized
system ignites and forms a burning jet. Jet fires can occur when almost
any combustible / flammable fluid under pressure is released to
atmosphere.
LIQUID SEAL / WATER SEAL Device that directs the flow of relief gases
through a liquid (normally water) on the path to the flare burner, used to
protect the flare header from air infiltration or flashback, to divert flow, or
to create back pressure for the flare header.
PURGE GAS Fuel gas or non-condensable inert gas added to the flare
header to mitigate air ingress and burn-back.
RADIATION INTENSITY Local radiant heat transfer rate from the flare
flame, usually considered at grade level.
VENT HEADER Piping system that collects and delivers the relief
gases to the vent stack.
REFERENCE
The following documents have been the main reference for the
development of Unit 230 Best Practice.