Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Abstract— Previously published research findings [1] on are added or subtracted through switching via a tap
the impact of tap changer position on the steady state changer.
performance of distribution networks indicate that very little
impact results from varying the tap changer position. In this In [3, 4, 5, 6, 7, 8] transformer tap changers were used to
paper, a similar investigation is carried out, but on a network control and restore system voltages in order to eliminate
with very high voltage transmission lines operating in parallel voltage instability. Tap Changers were tested on practical
with a well-developed corridor of 400kV lines. The per-unit systems and they demonstrated the capability of controlling
impedance of a line is reduced drastically as the line voltage is and restoring voltage of the power systems with no effect on
increased. When the design voltage of the transmission lines is
the maximum power transfer. In one other study, the effect
high, the transformer impedance becomes dominant and plays
a key role in the system. This paper investigates the effect of of on-load tap changers was investigated on the basis of
varying the impedance of a 765/400kV transformer on the small, 11-bus power system for both 10kV and 110kV
steady-state (loadflow and active power losses) and voltage feeders which are supplied by 110/10kV and 220/110kV
stability of the Cape corridor. substation transformers. It was illustrated that power transfer
limit from the power source to the load centre can be
Keywords-transformer; tap changer; power flow; system
losses; voltage stability
extended through tap changer optimization [1].
The Eskom’s Cape system consists of a group of many,
parallel-operated of 400kV lines, in parallel to which some
I. INTRODUCTION 765kV lines were later built. This network supplies loads
A transformer is a static device which by that are remotely located from generation sources that are to
electromagnetic induction transforms alternating voltage be found in the North Eastern part of the country [9]. The
and current between the windings at different values of system has 765/400kV transformers feeding power through
voltage and current. Systems for transmission and long transmission lines operated at 400kV and proposed
distribution of electric power are designed on the basis 765kV voltages. Refer to Figure 2 for the geographic map.
parallel lines and substantially constant voltage. It is The amount of power transmitted through the lines is a
desired that the power transformer delivers a reasonable function of the line impedance. As the voltage becomes
constant voltage under variable loading conditions. Power high the impedance of the line becomes less significant in
transformers are made up of two circuits, low voltage and relation to that of a transformer, based on the per unit basis
high voltage windings, and their relationship is calculation of the impedances. As a result transformer
characterized by the turn’s ratio of the windings [2]. impedance becomes dominant and exerts greater influence
The number of turns in the winding determines the on the maximum power transfer limit of the system. This
voltage, and to change or compensate for line, extra turns paper reports on the influence of the Zeus 765/400kV
must be connected to or disconnected from the winding. A transformer impedance on the steady state (i.e., loadflows
tap changer is used as a switch to add or subtract the and active power losses) and voltage stability performance
winding turns to maintain voltage limits. If all the taps or of the system described above.
turns of the winding are connected to the circuit the voltage Section II of the paper discusses some theoretical
becomes high or else voltages become low. In addition, the aspects related to how transformer impedance can affect
impedance of a transformer changes as the number of turns voltage stability. A methodology of the study carried out on
electrical degrees The system loadflow analysis was carried out only for
system healthy conditions. The studies were carried for
X is the inductive line impedance in ohms each of the tap changer positions, changing the ratio from
Xt is the transformer impedance in ohms 0.95 to 1.05. For each tap changer position, loadflow results
were recorded.
PR is the transferable power (or receiving
C. Active Power System Losses
end active power) MW
The active power system losses were also recorded for
Xpu is the per-unit reactance/impedance each of the tap changer positions. The results would be
Sbase is the system base power used to evaluate the impact of tap changer position on these
losses.
Vbase is the base voltage
Xactual is the actual impedance of the line D. Voltage Stability Studies
Again, studies were carried out only for system healthy
conditions, by varying the tap changer position of the Zeus
In both equations (1) and (2), it can be seen that for
400/765kV transformer, and calculating the voltage
constant VS, VR, and δ (phase angle), the active power
transferred through the network depends on both the stability.
impedance of the line and that of the transformer, and the
Figure 2: Geographic Layout of the Corridor in 2013
B. Active Power System Losses At the tap changer position corresponding to the
transformer ratio of 0.95 pu, the transfer is seating at 85
The issue of active power losses is presented in Figure MW less that at the starting position of ratio of 1.0115 pu.
5, which shows impact of the tap changer position of the
resulting active power losses of the system. As the ratio is increased, there is a maintained
improvement in the voltage stability limit realized.
As the tap changer position is moved, there is a net Maximum voltage stability limit, which is 30 MW more
power losses increase at a ratio of 0.95pu. This increase in than the value used as a base, is achieved at the ratio of 1.05
active power losses is reduced as the ratio is increased. pu.
From a ratio of 1.02pu, losses start to decrease, and a
maximum reduction is achieved a ratio of 1.05pu. The figure shows that as the tap changer ratios are
changed from a minimum of 0.95 pu to a maximum value of
The graph shows that losses can be changed from a net 1.05, the transfer can be changed, i.e., increased, by around
increase of 8.4 MW, at a ratio of 0.95pu, to a net decrease of 115 MW.
4.3 MW, at a ratio of 1.05pu. This is a potential swing of
12.5 MW in active power losses. The swing, in financial V. CONCLUSIONS
terms, based on the assumptions that Eskom [13] uses to The study has shown that the tap changer of a
calculate a net present value (NPV) of a 1 MW of active transformer can have a significant impact on the power
power loss or saving, is to the value of R250 million (or flow, active power losses, and voltage stability limits
approximately $31, 25 assuming an exchange rate of US $1: obtained in a power system where high voltage transmission
South African R8) over a period of 25 years, and is therefore lines are used, with power transformed from lower voltage
worthy of attention. lines using transformers.
The study has shown that in such networks, depending
on the tap changer position chosen, power flowing in the
transmission lines can be made to swing within quite a
sizeable range as the position of the tap changer is varied. If
there are parallel networks at different voltages, the power
flows in these can be influenced by the position of the tap
changer.
Also, it has been shown by the study that active power
losses of the system can be varied quite substantially as the
position of a tap changer is varied through the allowable
range.
Lastly, the voltage stability limits calculated can be
seriously impacted by the position of the tap changer
chosen, with significantly higher transfers at certain tap
changer positions.
Figure 5: Reduction in Active Power Losses with Tap Changer Position
It is, therefore, important when planning and operating a
C. Voltage Stability Studies power system, that the setting of tap changers be considered
carefully. They can have a huge impact on the technical and
The effect of varying the tap changer position on the economic considerations for expansion and operation of the
transfer capability into the Cape network is shown network.
graphically in Figure 6.
REFERENCES
[7] L. Wang, Y. Liu, and Z. Luan,"Voltage Stability Affected By On-
Load Tap Changer Considering Excitation Reactance of Induction
[1] T. X. Zhu, S. K. Tso, and K. L. Lo, "An Investigation into the OLTC Motor," IEEE Transaction on Power Systems , May 2005.
Effects On Voltage Stability," IEEE Transactions On Power
Systems, Vol. 15, No. 2, May 2000. [8] P. L. Swe, W. Swe, and K. M. Lin, "Effects of Tap Changing
Transformer and Shunt Capacitor on Voltage Stability Enhancement
[2] J. D. Glover and M. Sarma, Power System Analysis and Design, of Transmission Network," World Academy of Science, Engineerign
Second Edition. and Technology, 75, 2011.
[3] M. Z. El-Sadek, G.A. Mahmoud, M.M. Dessouky, and W.I. Rashed, [9] Eskom Transmission Division, Eskom Transmission Develpment
"Tap-Changing Transformer Role in Voltage Stability Plan 2010-2019, 2010.
Enhancement," Electric Power Systems Research, 50 (1999), pp.
115-118. [10] T. Custem, and C. Vournas, Voltage Stability of Electric Power
Systems, pp. 21.
[4] Y.Y. Hong and H.Y. Wang, "Investigation of the Voltage Stability
Region Involving On-Load Tap Changers," Electric Power Systems [11] PSS™E 32.0, Siemens Power Transmission & Distribution, Inc.
Research, 32 (1995), pp. 45-54. PowerTechnologies International, User manual, December 2007.
[5] D. Thukaram, K. Parthasarathy, H.P. Khincha, N. Udupa, and A. [12] VSTAB v4.1, Powertech Lab Inc, Revised User’s Manual, December
1995.
Bansilal, "Voltage Stability Improvement: Case Studies of India
Power Networks," Electric Power Systems Research, 44 (1998), pp. [13] Corporate Finance, Economic Evaluation Parameters 2006-2010,
35-44. April 2006.
[6] C. D. Vournas and G. A. Manos, "Emergency Tap-Blocking to
Prevent Voltage Collapse," 2001 IEEE Porto Power Tech
Conference 10-13 September, Porto, Portugal, 2001.