Halliburton

Multi-Chem Batch plant Project

Purchase Order
A8JE-4-0501-01
Number:
Purchase Order
Description:

Suppliers Name: THERMAX

Supplier’s Document
PZZYC2DC50 Rev: 0
Number and Revision:

Document Title: ELECRICAL MOTORS SPECIFICATION SHEET

Document Type: SUP-SPC-004

Equipment / Tag
NA
Number:

SDDC Reference No. -

Fluor Assigned
Rev. 0
Document Number: A8JE-4-0501-01-00074
ELECTRICAL MOTOR / SYSTEM REQUIREMENT (EMS)

Electrical Motor / System Requirements (EMS)


A Supply:
Voltage - 0.38kW to 200 kW 460 V AC ± 10%, Three Phase (As per MR Doc- A8JE-500-55-RQ-0001)
Voltage - up to 0.37 kW 230 V AC ±10%, Single Phase (As per MR Doc- A8JE-500-55-RQ-0001)
Frequency 60 Hz ±5%
50 kA for 1 Sec. (Solidly Grounded) - for System
Fault level 50 kA for 0.25 Sec. – for Terminal Box.
Combined variation ±10%
Phases 3
Wires 3+N+E

B Site:
Max. Ambient Design Temperature (Dry Bulb) 48.4 Deg. C
Min. Ambient Design Temperature (Dry Bulb) 2.9 Deg. C
Electrical Design Temperature 50 Deg. C (Outside) & 45 Deg. C (Inside)
Site Elevation from MWL (Mean sea level) EL. -- 1.380
Relative Humidity Design Max. / Min. 100% / 5%
Area classification with certification. SAFE & NON HAZARDOUS
Seismic Zone Category A, Site class = D (Refer Flour doc. No. A8JE-000-25-BD-0001, page no. 7 of 19.)

C Motor:
Type Squirrel cage induction motor shall be IE3.
Enclosure TEFC for all other motors except motorized actuators which shall be TENV.
Protection IP55. Shall conform to FLUOR PIP ELSMT01 or PIP ELEMT01
Duty cycle S1 - Continuous duty (for Fans, Pumps, Dosing)
S2 - Short-time duty (for Motorized Operated Valves)
Method of starting: DOL for Dosing pump, agitator, Feed water pumps & Oil pumps motors.
STAR-DELTA / Soft starter for FD fan motor.
RDOL for Motorized operated valves
No of starts Two hot , Three cold successive / Hour, Three equally spreaded/Hour.
Min. voltage permissible 85 % rated voltage for starting & run-up.
Motors shall be capable of operating satisfactorily at full load for 5 minutes
without injurious heating with 75% of the rated voltage at its terminals.
For LV motors, the voltage drop at the motor terminals shall not exceed 3% at full load
Volatge Drop current and 20% during starting, excluding supply variations.
Class of insulation, Temperature rise F, limited to B
Name plate Shall be as per FLUOR doc. No. PIP ELIMTN00

D Accessories: Motors shall be sized to operate satisfactorily under the lowest speed Conditions.
Lifting Eye bolt Required.
Space Heater Required for 30 KW & Above Motors (Supply 120 V AC, Single Phase.)
Winding Temerature RTD (Pt-100)-3 Wire YES
6 Simplex
Bearing Temerature RTD (Pt-100) -3 Wire For DE & NDE
One each YES
Duplex
i. Separate TB to be provided for Space Heater and thermistors / Temp. detectors.
ii. Terminal box shall be capable of withstanding a fault level of 50 kA for 0.25 sec.
E Terminal Box:
iii. Standard, at LHS from NDE. Adjustable at four 90°positions, separate terminal for auxiliaries.
Suitable Earthing stud shall be mounted inside the terminal box.
Terminal Box Location As per OEM Std.
Cable Entry Bottom/Side
Direction Of Rotation Bi- Directional

F Performance / Construction: As Per IEC-60034 & Other Related IEC Standards.


<85 dBA (for Continuous Operating Equipments @ 1.5 mtr) & <92dBA
Sound Pressure (for Feed water pumps @ 1mtr)
Torque max torque shall not be less than 200% of full load torque
Vibrations As per IEC 60034, but limited to 2.5 mm per sec for 2 pole motors
Entire Inspection shall be as per Customer ITP/QAP. Same to be complied / confirmed by vendor @ offer
Inspection
stage itself. Inspection shall be done by Customer / Thermax
Make As Per Approved Vendor List

The Supplier shall perform all Work related to surface preparation, priming and finish painting, in
G Painting accordance with the Supplier’s standard paint system with finish colors as per Table 4 and a minimum
corrosion protection level of 1000 hours (salt fog resistance) when tested in accordance with ASTM B117,
or apply painting / coating as per requirements of FLUOR specification.

MADE BY CHKD.BY APPD.BY Page No. 1 of 2


Date: 10.07.2019
CSP/ASL PRK RBB THERMAX OC NO : HIZYC2 Doc. No. PZZYC2DC50, Rev. No: 00
ELECTRICAL MOTOR / SYSTEM REQUIREMENT (EMS)

1) Motor Datasheet.
2) General arrangement drawing.
3) Starting Torque Vs Speed Curve.
4) P.F / Efficiency Vs Load Curve.
5) Thermal Withstand Current (Hot/Cold) Vs Time Curve.
6) Current Vs Speed Curve.
H Documentation required from vendor for Motor(s): 7) Starting time calculations.
8) TB & wiring details for auxiliaries.
9) Above all documents to be submitted as Post PO by Vendor to Thermax.
10) Vendor to submit any other documents as required by Customer / Consultant without
any delay & any commercial implications.
11) Terminal Box GA and Gland hole details.
12) Any other documents as per FLUOR requirement in soft or hard format.
1) Electrical design basis : A8JE-000-65-BD-0001
2) Electrical Design Criteria : A8JE-000-65-BD-0002 / PIP ELCGL01
3) Electrical requirements for packaged equipments : PIP ELSPS01
Motor / Panel Vendor to comply 100% for mentioned
I 4) Grounding Specifications : A7YX-000-65-SP-0001
FLUOR documents.
5) Specification for Painting: A8JE-000-50-SP-0003
6) Specification for basic Engg. design data: A8JE-000-25-BD-0001
7) Motor Name plate details: PIP ELIMTN00
Notes:
1. Vendor to mention "Thermax Limited project number / name / document - specification number" on each of their documents.
2. Specification number for each motor data sheet shall be given in line with respective specification released by Thermax Engg.
3. Vendor to send 100% compliance to this document along with the deviations (if applicable -- in Excel sheet only) to Thermax Engg. /
Customer for Approval / discussion.
4. For conventional motors / Non VFD motors eff. Norms shall be as per IEC-60034.
5. Two nos. Earthing pads (one on each side) to be provided on all motors.
6. All motors after achieving full operating temperature shall be capable of withstanding 150% overloads for 15 secs.
7. Motor subject to reverse rotation shall be designed to withstand the stresses encountered when starting with non energized shaft
rotating at 125% of rated speed in reverse direction.
8. Motor shall be provided with antifriction bearings, unless sleeve bearings are required by the Motor application.
9. The Motor shall be provided with rating plate of stainless steel in addition to minimum information requirement by IEC:
Following information shall be shown on motor rating plate:
a. Temperature rise in °C, under rated condition & method of measurement.
b. Degree of Protection.
c. Bearing identification number & recommended lubricant.
d. Location of insulated bearing. (If applicable)
e. Type of Rotor.
10. Any conditions / specifications which are mentioned / required in / by FLUOR documents shall be prevailing & shall superseeds these
specifications.
Voltage requirement for Instrumentation
J Supply (UPS power for Instrument) Applicable: UPS IS IN CUSTOMER SCOPE
Voltage for separately powered SOV 24 V DC
Voltage for Auto blowdown valve 230 V AC
Voltage for separately powered instruments 230 V AC
Voltage for Burner components 230 V AC

MADE BY CHKD.BY APPD.BY Page No. 2 of 2


Date: 10.07.2019
CSP/ASL PRK RBB THERMAX OC NO : HIZYC2 Doc. No. PZZYC2DC50, Rev. No: 00