Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
4100
AREA
PORCH 3.00m x 5.32m
3.7200 KITCHEN 3.5600
DIRTY KITCHEN
5.0000 BEDROOM 3
LIVING ROOM 5.25m x 5.32m
HALLWAY
BEDROOM 3 5.00m x 3.35m
3.6400 3.6000 3.6900
DINING AREA C.R 1 2.00m x 3.24m
2.0000 C.R 2 HALLWAY 2.0000
HALLWAY
2.0000 C.R 1 2.0000 DINING AREA 3.69m x 4.76m
3.0000 PORCH
HEIGHT
FLOOR TO CEILING 2.70 m
15.2400
1
REYDEL L. FAJARDO FLOOR PLAN with DIMENSIONS and AREA
P.B
GENERAL SPECIFICATION
ALL ELECTRICAL WORKS SHALL BE DONE ACCORDANCE WITH THE LATEST PROVISIONS OF THE PHILIPPINE
ELECTRICAL CODE (PEC) PART 1 & 2, NATIONAL BUILDING CODE % LOCAL UTILITY COMPANY.
GC GROUND ROD ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSED ELECTRICAL
PRACTITIONER (PROFESSIONAL ELECTRICAL ENGINEER, REGISTERED ELECTRICAL ENGINEER, AND REGISTERED
S.E MASTER ELECTRICIAN).
CIRCUIT 1 CALCULATIONS: THE ELECTRICAL INSTALLATION IN GENERAL AS SHOWN IN OUR ELECTRICAL DRAWING AND/OR IN THE
SPECIFICATIONS.
W = 100W per LIGHTING OUTLET No. of Conduits = 59.2m/ 3.048m = 20 pcs. SHORT CIRCUIT ANALYSIS:
N = 8 UNITS 3. MAXIMUM LENGTH OF WIRE PER BRANCH: ALL ELECTRICAL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER. ALL EXPOSED CONDUITS
V = 230 V UTILITY MAXIMUM
X = 0.073; R = 3.1 SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALL AND STRUCTURAL MEMBERS. JUNCTION BOX SHALL
VA = 8 x 100 = 800 VA INFINITE
%VDmax = 3%
BE SECURELY FASTENED; SET TRUE AND PLUMP, AND FLUSH WITH FURNISHED SURFACE WHEN WIRING METHOD
A = 800VA/ 230 V = 3.48 A CAPACITY FAULT
IS CONCEALED.
1. WIRE LENGTH: VDmax = (%VDmax/100) x V = 6.9 V TRANSFORMER LOAD
ACTUAL LENGTH = 0.7(3) + 0.5(3) + 2(3) + Lmax = (VDmax x 305)/(A 195 m TYPE OF ELECTRICAL SERVICE SUPPLY SHALL BE 230V, SINGLE PHASE, 0HZ AND CONNECTED INTO THE
KVA= 50 KVA (Maximum transformer load)
0.5(3) + 3.5(3) + 1.5(3) + 1(3) + 1.5(3) + VENDmax = V - VDmax = 223.1 V
COMMONAL TRANSFORMER PROVIDED BY THE UTILITY.
VOLTAGE= 230 V
1.3(3) + 0.5(3) + 3(3) + 2(3) + 1.5(3) + 1.3(3) 4. ACTUAL VOLTAGE DROP: Z= 2.5%
ALL MATERIALS SHALL BE NEW AND SHALL BE LISTED AND BEAR THE APPROPRIATE LABEL OF UNDERWRITERS
X = 0.073; R = 3.1 Isec = VA/V = 217.39 A LABORATORIES, INC, OR ANOTHER RECOGNIZED TESTING LABORATORY FOR THE SPECIFIC PURPOSE. THE
+ 6(3) + 3(3) + 0.5(3) + 2(3) + 1.5(3) + 1.5(3)
Lactual = 182 m Isc = Isec/Z (fault current symmetrical) MATERIAL SHALL BE THE SIZE AND TYPE SPECIFIED AND DRAWING AND/OR IN THE SPECIFICATIONS. OR IT
+ 1.3(4) + 1(3) + 3.5(3) + 1(3) + 1(3) + 2(3) +
= 8695.65 A (fault current) SHOULD HAVE THE APPROVED PS MARK OR ICC LABELS.
VDactual = (A 6.44 V
1.5(3) + 1.3(4) + 3.5(3) + 1(3) + 4.5(3) + = 8.70 KIAC; Therefore, use 10 KIAC
1.3(4) + 1(3) = 181.5 m or 182 m
%VDactual = (VDactual/V) x 100 = 2.8% THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION, HEIGHTS, OUTLETS AND SWITCH
VENDactual = V - VDactual = 223.56 V ARRANGEMENTS, AND EQUIPMENT PRIOR TO ROUGH-IN. NO ADDITIONS TO THE CONTRACT SUM WILL BE
LEGEND:
2. CONDUITS:
USE:
PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH THE OTHER WORK, AND SO ON. THE OWNER
CONDUIT LENGTH = 0.7 + 0.5 + 2 + 0.5 + 3.5 WIRE GOING UPWARD RESERVES THE RIGHT TO RELOCATE ANY DEVICE UP TO 3M PRIOR TO ROUGH-IN, WITHOUT ANY CHARGE BY THE
WIRE GOING HORIZONTAL ELECTRICAL CONTRACTOR.
+ 1.5 + 1 + 1.5 + 1.3 + 0.5 + 3 + 2 + 1.5 + 1.3
25 mm diameter EMT Conduits
WIRE GOING DOWNWARD
+ 6 + 3 + 0.5 + 2 + 1.5 + 1.5 + 1.3 + 1 + 3.5 + ALL PANEL BOARD SHALL BE FURNISHED WITH TYPED CORD DIRECTORIES WITH PROPER DESIGNATION OF THE
15AT 2P Circuit Breaker
1 + 1 + 2 + 1.5 + 1.3 + 3.5 + 1 + 4.5 + 1.3 + 1 BRANCH-CIRCUIT LOADS, FEEDER LOADS, AND EQUIPMENT'S SERVED. THE DIRECTORIES SHALL BE LOCATED IN
THE PANEL IN A HOLDER FOR CLEAR VIEWING.
= 59.2 m
2
REYDEL L. FAJARDO BRANCH CIRCUIT 1 (LIGHTING OUTLET)
P.B
GENERAL SPECIFICATION
ALL ELECTRICAL WORKS SHALL BE DONE ACCORDANCE WITH THE LATEST PROVISIONS OF THE PHILIPPINE
ELECTRICAL CODE (PEC) PART 1 & 2, NATIONAL BUILDING CODE % LOCAL UTILITY COMPANY.
GC GROUND ROD ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSED ELECTRICAL
PRACTITIONER (PROFESSIONAL ELECTRICAL ENGINEER, REGISTERED ELECTRICAL ENGINEER, AND REGISTERED
S.E MASTER ELECTRICIAN).
CIRCUIT 2 CALCULATIONS: THE ELECTRICAL INSTALLATION IN GENERAL AS SHOWN IN OUR ELECTRICAL DRAWING AND/OR IN THE
SPECIFICATIONS.
W = 100W per LIGHTING OUTLET No. of Conduits = 63.5m/ 3.048m = 21 pcs. SHORT CIRCUIT ANALYSIS:
N = 8 UNITS
3. MAXIMUM LENGTH OF WIRE PER BRANCH: ALL ELECTRICAL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER. ALL EXPOSED CONDUITS
V = 230 V UTILITY MAXIMUM
X = 0.073; R = 3.1 SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALL AND STRUCTURAL MEMBERS. JUNCTION BOX SHALL
VA = 8 x 100 = 800 VA
INFINITE BE SECURELY FASTENED; SET TRUE AND PLUMP, AND FLUSH WITH FURNISHED SURFACE WHEN WIRING METHOD
A = 800VA/ 230 V = 3.48 A %VDmax = 3% CAPACITY FAULT
1. WIRE LENGTH:
IS CONCEALED.
VDmax = (%VDmax/100) x V = 6.9 V TRANSFORMER LOAD
ACTUAL LENGTH = 0.7(3) + 4.5(3) + 7.5(3) +
Lmax = (VDmax x 305)/(A 195 m TYPE OF ELECTRICAL SERVICE SUPPLY SHALL BE 230V, SINGLE PHASE, 0HZ AND CONNECTED INTO THE
0.5(3) + 0.5(3) + 1(3) + 1.3(3) + 1.5(3) + 1.5(3) + KVA= 50 KVA (Maximum transformer load)
VENDmax = V - VDmax =223.1 V
COMMONAL TRANSFORMER PROVIDED BY THE UTILITY.
VOLTAGE= 230 V
1.3(3) + 0.5(3) + 1.5(3) + 1.5(3) + 2(3) + 1(3) +
4. ACTUAL VOLTAGE DROP: Z= 2.5%
1(3) + 1.3(3) + 3.5(3) + 2.5(3) + 1.5(3) + 4(3) +
ALL MATERIALS SHALL BE NEW AND SHALL BE LISTED AND BEAR THE APPROPRIATE LABEL OF UNDERWRITERS
X = 0.073; R = 3.1 Isec = VA/V = 217.39 A LABORATORIES, INC, OR ANOTHER RECOGNIZED TESTING LABORATORY FOR THE SPECIFIC PURPOSE. THE
0.5(3) + 1(3) + 2(3) + 2(3) + 1.5(3) + 1.3(3) +
Lactual = 193 m Isc = Isec/Z (fault current symmetrical) MATERIAL SHALL BE THE SIZE AND TYPE SPECIFIED AND DRAWING AND/OR IN THE SPECIFICATIONS. OR IT
0.5(3) + 2.5(3) + 2(3) + 1.3(4) + 3(3) + 4(3) + = 8695.65 A (fault current) SHOULD HAVE THE APPROVED PS MARK OR ICC LABELS.
VDactual = (A 6.83 V
1.3(4) = 193 m = 8.70 KIAC; Therefore, use 10 KIAC
%VDactual = (VDactual/V) x 100 = 2.97% THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION, HEIGHTS, OUTLETS AND SWITCH
2. CONDUITS:
VENDactual = V - VDactual = 223.17 V ARRANGEMENTS, AND EQUIPMENT PRIOR TO ROUGH-IN. NO ADDITIONS TO THE CONTRACT SUM WILL BE
LEGEND:
CONDUIT LENGTH = 0.7 + 4.5 + 7.5 + 0.5 + 0.5
USE:
PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH THE OTHER WORK, AND SO ON. THE OWNER
+ 1 + 1.3 + 1.5 + 1.5 + 1.3 + 0.5 + 1.5 + 1.5 + 2 +
WIRE GOING UPWARD RESERVES THE RIGHT TO RELOCATE ANY DEVICE UP TO 3M PRIOR TO ROUGH-IN, WITHOUT ANY CHARGE BY THE
1 + 1 + 1.3 + 3.5 + 2.5 + 1.5 + 4 + 0.5 + 1 + 2 + 2 WIRE GOING HORIZONTAL ELECTRICAL CONTRACTOR.
25 mm diameter EMT Conduits
+ 1.5 + 1.3 + 0.5 + 2.5 + 2 + 1.3 + 3 + 4 + 1.3 = WIRE GOING DOWNWARD
15AT 2P Circuit Breaker
ALL PANEL BOARD SHALL BE FURNISHED WITH TYPED CORD DIRECTORIES WITH PROPER DESIGNATION OF THE
63.5 m BRANCH-CIRCUIT LOADS, FEEDER LOADS, AND EQUIPMENT'S SERVED. THE DIRECTORIES SHALL BE LOCATED IN
THE PANEL IN A HOLDER FOR CLEAR VIEWING.
3
REYDEL L. FAJARDO BRANCH CIRCUIT 2 (LIGHTING OUTLET)
SERVICE DROP WIRE 2 EMT Utility Box 6 pcs. Php. 100.00 Php. 600.00
LIVE WIRE
3 EMT Pull Box 1 pc. Php. 120.00 Php. 120.00
NEUTRAL WIRE
4 EMT Conduit Pipe (25 mm) 18 pcs. Php. 260.00 Php. 4,680.00
GROUND WIRE
5 EMT Coupling 9 pcs. Php. 25.00 Php. 225.00
JUNCTION BOX
JBX
UBX
UTILITY BOX 6 EMT Connector 14 pcs. Php. 50.00 Php. 700.00
P.B
GENERAL SPECIFICATION
ALL ELECTRICAL WORKS SHALL BE DONE ACCORDANCE WITH THE LATEST PROVISIONS OF THE PHILIPPINE
ELECTRICAL CODE (PEC) PART 1 & 2, NATIONAL BUILDING CODE % LOCAL UTILITY COMPANY.
GC GROUND ROD ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSED ELECTRICAL
PRACTITIONER (PROFESSIONAL ELECTRICAL ENGINEER, REGISTERED ELECTRICAL ENGINEER, AND REGISTERED
S.E MASTER ELECTRICIAN).
CIRCUIT 3 CALCULATIONS: THE ELECTRICAL INSTALLATION IN GENERAL AS SHOWN IN OUR ELECTRICAL DRAWING AND/OR IN THE
SPECIFICATIONS.
W = 360W per 2-GANG CONVENIENCE OUTLET 3. MAXIMUM LENGTH OF WIRE PER BRANCH: SHORT CIRCUIT ANALYSIS:
N = 6 UNITS X = 0.063; R = 1.2 ALL ELECTRICAL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER. ALL EXPOSED CONDUITS
V = 230 V UTILITY MAXIMUM
%VDmax = 3% SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALL AND STRUCTURAL MEMBERS. JUNCTION BOX SHALL
VA = 6 x 360 = 2,160 VA
VDmax = (%VDmax/100) x V = 6.9 V
INFINITE BE SECURELY FASTENED; SET TRUE AND PLUMP, AND FLUSH WITH FURNISHED SURFACE WHEN WIRING METHOD
A = 2,160 VA/ 230 V = 9.39 A CAPACITY FAULT IS CONCEALED.
1. WIRE LENGTH: TRANSFORMER LOAD
Lmax = (VDmax x 305)/(A = 186.5 m
ACTUAL LENGTH = 0.7(3) + 3.5(3) + 1(3) + 4.5(3) +
VENDmax = V - VDmax = 223.1 V TYPE OF ELECTRICAL SERVICE SUPPLY SHALL BE 230V, SINGLE PHASE, 0HZ AND CONNECTED INTO THE
2.5(3) + 2.4(3) + 7(3) + 4(3) + 2.4(3) + 2(3) + 3.5(3) + KVA= 50 KVA (Maximum transformer load)
4. ACTUAL VOLTAGE DROP:
COMMONAL TRANSFORMER PROVIDED BY THE UTILITY.
VOLTAGE= 230 V
2.4(3) + 1(3) + 2.4(3) + 6.5(3) + 2.4(3) + 4(3) + 2.4(3)
X = 0.063; R = 1.2 Z= 2.5%
= 163.8 m or 164 m
ALL MATERIALS SHALL BE NEW AND SHALL BE LISTED AND BEAR THE APPROPRIATE LABEL OF UNDERWRITERS
Lactual = 164 m Isec = VA/V = 217.39 A LABORATORIES, INC, OR ANOTHER RECOGNIZED TESTING LABORATORY FOR THE SPECIFIC PURPOSE. THE
2. CONDUITS: VDactual = (A = 6.07 V
Isc = Isec/Z (fault current symmetrical) MATERIAL SHALL BE THE SIZE AND TYPE SPECIFIED AND DRAWING AND/OR IN THE SPECIFICATIONS. OR IT
CONDUIT LENGTH = 0.7 + 3.5 + 1 + 4.5 + 2.5 + 2.4 + = 8695.65 A (fault current) SHOULD HAVE THE APPROVED PS MARK OR ICC LABELS.
%VDactual = (VDactual/V) x 100 = 2.64%
7 + 4 + 2.4 + 2 + 3.5 + 2.4 + 1 + 2.4 + 6.5 + 2.4 + 4 + = 8.70 KIAC; Therefore, use 10 KIAC
2.4 = 54.6 m
VENDactual = V - VDactual = 223.93 V THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION, HEIGHTS, OUTLETS AND SWITCH
USE: ARRANGEMENTS, AND EQUIPMENT PRIOR TO ROUGH-IN. NO ADDITIONS TO THE CONTRACT SUM WILL BE
LEGEND:
No. of Conduits = 54.6m/ 3.048m = 18 pcs. PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH THE OTHER WORK, AND SO ON. THE OWNER
WIRE GOING UPWARD RESERVES THE RIGHT TO RELOCATE ANY DEVICE UP TO 3M PRIOR TO ROUGH-IN, WITHOUT ANY CHARGE BY THE
25 mm diameter EMT Conduits ELECTRICAL CONTRACTOR.
WIRE GOING HORIZONTAL
20AT 2P Circuit Breaker
WIRE GOING DOWNWARD
ALL PANEL BOARD SHALL BE FURNISHED WITH TYPED CORD DIRECTORIES WITH PROPER DESIGNATION OF THE
BRANCH-CIRCUIT LOADS, FEEDER LOADS, AND EQUIPMENT'S SERVED. THE DIRECTORIES SHALL BE LOCATED IN
THE PANEL IN A HOLDER FOR CLEAR VIEWING.
4
REYDEL L. FAJARDO BRANCH CIRCUIT 3 (CONVENIENCE OUTLET)
SERVICE DROP WIRE 2 EMT Utility Box 7 pcs. Php. 100.00 Php. 700.00
LIVE WIRE
3 EMT Junction Box 4 pcs. Php. 95.00 Php. 380.00
NEUTRAL WIRE
4 EMT Conduit Pipe (25 mm) 18 pcs. Php. 260.00 Php. 4,680.00
GROUND WIRE
5 EMT Coupling 6 pcs. Php. 25.00 Php. 150.00
JUNCTION BOX
JBX
UBX
UTILITY BOX 6 EMT Connector 22 pcs. Php. 50.00 Php. 1,100.00
P.B
GENERAL SPECIFICATION
ALL ELECTRICAL WORKS SHALL BE DONE ACCORDANCE WITH THE LATEST PROVISIONS OF THE PHILIPPINE
ELECTRICAL CODE (PEC) PART 1 & 2, NATIONAL BUILDING CODE % LOCAL UTILITY COMPANY.
GC GROUND ROD ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSED ELECTRICAL
PRACTITIONER (PROFESSIONAL ELECTRICAL ENGINEER, REGISTERED ELECTRICAL ENGINEER, AND REGISTERED
S.E MASTER ELECTRICIAN).
CIRCUIT 4 CALCULATIONS: THE ELECTRICAL INSTALLATION IN GENERAL AS SHOWN IN OUR ELECTRICAL DRAWING AND/OR IN THE
SPECIFICATIONS.
W = 360W per 2-GANG CONVENIENCE OUTLET 3. MAXIMUM LENGTH OF WIRE PER BRANCH: SHORT CIRCUIT ANALYSIS:
N = 7 UNITS X = 0.063; R = 1.2 ALL ELECTRICAL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER. ALL EXPOSED CONDUITS
V = 230 V UTILITY MAXIMUM
%VDmax = 3% SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALL AND STRUCTURAL MEMBERS. JUNCTION BOX SHALL
VA = 7 x 360 = 2,520 VA
VDmax = (%VDmax/100) x V = 6.9 V
INFINITE BE SECURELY FASTENED; SET TRUE AND PLUMP, AND FLUSH WITH FURNISHED SURFACE WHEN WIRING METHOD
A = 2,160 VA/ 230 V = 10.96 A CAPACITY FAULT IS CONCEALED.
1. WIRE LENGTH: TRANSFORMER LOAD
Lmax = (VDmax x 305)/(A = 159.79 m
ACTUAL LENGTH = 0.7(3) + 6.5(3) + 4.5(3) + 2.4(3) +
VENDmax = V - VDmax = 223.1 V TYPE OF ELECTRICAL SERVICE SUPPLY SHALL BE 230V, SINGLE PHASE, 0HZ AND CONNECTED INTO THE
4.5(3) + 2.4(3) + 4(3) + 0.5(3) + 2.4(3) + 2.5(3) + 2(3) KVA= 50 KVA (Maximum transformer load)
4. ACTUAL VOLTAGE DROP:
COMMONAL TRANSFORMER PROVIDED BY THE UTILITY.
VOLTAGE= 230 V
+ 2.4(3) + 1(3) + 5.5(3) + 2.4(3) + 2(3) + 2.4(3) + 2(3)
X = 0.063; R = 1.2 Z= 2.5%
+ 2.4(3) = 157.5 m or 158 m
ALL MATERIALS SHALL BE NEW AND SHALL BE LISTED AND BEAR THE APPROPRIATE LABEL OF UNDERWRITERS
Lactual = 158 m Isec = VA/V = 217.39 A LABORATORIES, INC, OR ANOTHER RECOGNIZED TESTING LABORATORY FOR THE SPECIFIC PURPOSE. THE
2. CONDUITS: VDactual = (A = 6.823 V
Isc = Isec/Z (fault current symmetrical) MATERIAL SHALL BE THE SIZE AND TYPE SPECIFIED AND DRAWING AND/OR IN THE SPECIFICATIONS. OR IT
CONDUIT LENGTH = 0.7 + 6.5 + 4.5 + 2.4 + 4.5 + 2.4 = 8695.65 A (fault current) SHOULD HAVE THE APPROVED PS MARK OR ICC LABELS.
%VDactual = (VDactual/V) x 100 = 2.97%
+ 4 + 0.5 + 2.4 + 2.5 + 2 + 2.4 + 1 + 5.5 + 2.4 + 2 + = 8.70 KIAC; Therefore, use 10 KIAC
VENDactual = V - VDactual = 223.177 V THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION, HEIGHTS, OUTLETS AND SWITCH
2.4 + 2 + 2.4 = 52.5 m
USE: ARRANGEMENTS, AND EQUIPMENT PRIOR TO ROUGH-IN. NO ADDITIONS TO THE CONTRACT SUM WILL BE
LEGEND:
No. of Conduits = 52.5m/ 3.048m = 18 pcs. PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH THE OTHER WORK, AND SO ON. THE OWNER
WIRE GOING UPWARD RESERVES THE RIGHT TO RELOCATE ANY DEVICE UP TO 3M PRIOR TO ROUGH-IN, WITHOUT ANY CHARGE BY THE
25 mm diameter EMT Conduits
WIRE GOING HORIZONTAL ELECTRICAL CONTRACTOR.
20AT 2P Circuit Breaker
WIRE GOING DOWNWARD
ALL PANEL BOARD SHALL BE FURNISHED WITH TYPED CORD DIRECTORIES WITH PROPER DESIGNATION OF THE
BRANCH-CIRCUIT LOADS, FEEDER LOADS, AND EQUIPMENT'S SERVED. THE DIRECTORIES SHALL BE LOCATED IN
THE PANEL IN A HOLDER FOR CLEAR VIEWING.
5
REYDEL L. FAJARDO BRANCH CIRCUIT 4 (CONVENIENCE OUTLET)
A.C.U. - OUTDOOR UNIT 1 EMT Pull Box 1 pc. Php. 120.00 Php. 120.00
2 EMT Conduit Pipe (25 mm) 9 pcs. Php. 260.00 Php. 2,340.00
MAGNETIC STARTER
MS 3 EMT Coupling 2 pcs. Php. 25.00 Php. 50.00
SINGLE POLE CIRCUIT BREAKER
30 A 4 EMT Connector 5 pcs. Php. 50.00 Php. 250.00
PANEL BOARD
5 2 Hole Strap 15 pcs. Php. 15.00 Php. 225.00
SERVICE ENTRANCE
SERVICE DROP WIRE 6 Magnetic Starter 1 pc. Php. 1,200.00 Php. 1,200.00
LIVE WIRE 7 30AT 2P Circuit Breaker (Royu) 1 pc. Php. 230.00 Php. 230.00
NEUTRAL WIRE
TOTAL COST Php. 4,415.00
GROUND WIRE
INDOOR
OUTDOOR
PULL BOX
PBX
P.B
MS
GENERAL SPECIFICATION
SPARE
30 A
ALL ELECTRICAL WORKS SHALL BE DONE ACCORDANCE WITH THE LATEST PROVISIONS OF THE PHILIPPINE
ELECTRICAL CODE (PEC) PART 1 & 2, NATIONAL BUILDING CODE % LOCAL UTILITY COMPANY.
GC GROUND ROD ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSED ELECTRICAL
PRACTITIONER (PROFESSIONAL ELECTRICAL ENGINEER, REGISTERED ELECTRICAL ENGINEER, AND REGISTERED
S.E
MASTER ELECTRICIAN).
CIRCUIT 5 CALCULATIONS: THE ELECTRICAL INSTALLATION IN GENERAL AS SHOWN IN OUR ELECTRICAL DRAWING AND/OR IN THE
W = 1,835W per A.C.U OUTLET 3. MAXIMUM LENGTH OF WIRE PER BRANCH: SHORT CIRCUIT ANALYSIS: SPECIFICATIONS.
N = 1 UNITS X = 0.063; R = 1.2
V = 230 V UTILITY MAXIMUM ALL ELECTRICAL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER. ALL EXPOSED CONDUITS
%VDmax = 3%
VA = 1 x 1,835 = 1,835 VA
INFINITE
SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALL AND STRUCTURAL MEMBERS. JUNCTION BOX SHALL
A = 1,835 VA/ 230 V = 7.98 A VDmax = (%VDmax/100) x V = 6.9 V CAPACITY BE SECURELY FASTENED; SET TRUE AND PLUMP, AND FLUSH WITH FURNISHED SURFACE WHEN WIRING METHOD
FAULT
1. WIRE LENGTH: TRANSFORMER LOAD IS CONCEALED.
Lmax = (VDmax x 305)/(A = 219.47 m
ACTUAL LENGTH = 0.7(3) + 2(3) + 2(3) + 3(3) + 3(3)
VENDmax = V - VDmax = 223.1 V
+ 4(3) + 2.5(3) + 1(3) + 1(3) + 2(3) + 1(3) + 1(3) +2(3) KVA= 50 KVA (Maximum transformer load) TYPE OF ELECTRICAL SERVICE SUPPLY SHALL BE 230V, SINGLE PHASE, 0HZ AND CONNECTED INTO THE
4. ACTUAL VOLTAGE DROP: VOLTAGE= 230 V COMMONAL TRANSFORMER PROVIDED BY THE UTILITY.
= 75.6 m or 76 m
X = 0.063; R = 1.2 Z= 2.5%
2. CONDUITS: Lactual = 76 m Isec = VA/V = 217.39 A ALL MATERIALS SHALL BE NEW AND SHALL BE LISTED AND BEAR THE APPROPRIATE LABEL OF UNDERWRITERS
CONDUIT LENGTH = 0.7 + 2 + 2 + 3 + 3 + 4 + 2.5 + 1 Isc = Isec/Z (fault current symmetrical)
LABORATORIES, INC, OR ANOTHER RECOGNIZED TESTING LABORATORY FOR THE SPECIFIC PURPOSE. THE
VDactual = (A = 2.39 V
+ 1 + 2 + 1 + 1 + 2 = 25.2 m MATERIAL SHALL BE THE SIZE AND TYPE SPECIFIED AND DRAWING AND/OR IN THE SPECIFICATIONS. OR IT
= 8695.65 A (fault current)
%VDactual = (VDactual/V) x 100 = 1.04% SHOULD HAVE THE APPROVED PS MARK OR ICC LABELS.
No. of Conduits = 25.2m/ 3.048m = 9 pcs. = 8.70 KIAC; Therefore, use 10 KIAC
VENDactual = V - VDactual = 227.61 V
THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION, HEIGHTS, OUTLETS AND SWITCH
USE:
LEGEND: ARRANGEMENTS, AND EQUIPMENT PRIOR TO ROUGH-IN. NO ADDITIONS TO THE CONTRACT SUM WILL BE
WIRE GOING UPWARD PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH THE OTHER WORK, AND SO ON. THE OWNER
25 mm diameter EMT Conduits RESERVES THE RIGHT TO RELOCATE ANY DEVICE UP TO 3M PRIOR TO ROUGH-IN, WITHOUT ANY CHARGE BY THE
WIRE GOING HORIZONTAL
ELECTRICAL CONTRACTOR.
30AT 2P Circuit Breaker
WIRE GOING DOWNWARD
ALL PANEL BOARD SHALL BE FURNISHED WITH TYPED CORD DIRECTORIES WITH PROPER DESIGNATION OF THE
BRANCH-CIRCUIT LOADS, FEEDER LOADS, AND EQUIPMENT'S SERVED. THE DIRECTORIES SHALL BE LOCATED IN
THE PANEL IN A HOLDER FOR CLEAR VIEWING.
6
REYDEL L. FAJARDO BRANCH CIRCUIT 5 (A.C.U. OUTLET)
SERVICE DROP WIRE 2 EMT Utility Box 1 pc. Php. 100.00 Php. 100.00
LIVE WIRE 3 EMT Junction Box 1 pc. Php. 95.00 Php. 95.00
NEUTRAL WIRE
4 EMT Conduit Pipe (25 mm) 6 pcs. Php. 260.00 Php. 1,560.00
GROUND WIRE
5 EMT Coupling 3 pcs. Php. 25.00 Php. 75.00
JUNCTION BOX
JBX
R UTILITY BOX 6 EMT Connector 4 pcs. Php. 50.00 Php. 200.00
UBX
P.B
GENERAL SPECIFICATION
ALL ELECTRICAL WORKS SHALL BE DONE ACCORDANCE WITH THE LATEST PROVISIONS OF THE PHILIPPINE
ELECTRICAL CODE (PEC) PART 1 & 2, NATIONAL BUILDING CODE % LOCAL UTILITY COMPANY.
GC GROUND ROD ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSED ELECTRICAL
PRACTITIONER (PROFESSIONAL ELECTRICAL ENGINEER, REGISTERED ELECTRICAL ENGINEER, AND REGISTERED
S.E MASTER ELECTRICIAN).
CIRCUIT 6 CALCULATIONS: THE ELECTRICAL INSTALLATION IN GENERAL AS SHOWN IN OUR ELECTRICAL DRAWING AND/OR IN THE
SPECIFICATIONS.
W = 3,000W per A.C.U OUTLET 3. MAXIMUM LENGTH OF WIRE PER BRANCH: SHORT CIRCUIT ANALYSIS:
N = 1 UNITS X = 0.063; R = 1.2 ALL ELECTRICAL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER. ALL EXPOSED CONDUITS
V = 230 V UTILITY MAXIMUM
%VDmax = 3% SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALL AND STRUCTURAL MEMBERS. JUNCTION BOX SHALL
VA = 1 x 3,000 = 3,000VA
VDmax = (%VDmax/100) x V = 6.9 V
INFINITE BE SECURELY FASTENED; SET TRUE AND PLUMP, AND FLUSH WITH FURNISHED SURFACE WHEN WIRING METHOD
A = 3,000VA/ 230 V = 13.04 A CAPACITY FAULT
1. WIRE LENGTH:
IS CONCEALED.
Lmax = (VDmax x 305)/(A = 134.31 m TRANSFORMER LOAD
ACTUAL LENGTH = 0.7(3) + 5(3) + 5.5(3) + 4.5(3) +
VENDmax = V - VDmax = 223.1 V TYPE OF ELECTRICAL SERVICE SUPPLY SHALL BE 230V, SINGLE PHASE, 0HZ AND CONNECTED INTO THE
2.4(3) = 54.3 m or 55 m KVA= 50 KVA (Maximum transformer load)
4. ACTUAL VOLTAGE DROP:
COMMONAL TRANSFORMER PROVIDED BY THE UTILITY.
VOLTAGE= 230 V
2. CONDUITS: X = 0.063; R = 1.2 Z= 2.5%
CONDUIT LENGTH = 0.7 + 5 + 5.5 + 4.5 + 2.4 = 18.1 m
ALL MATERIALS SHALL BE NEW AND SHALL BE LISTED AND BEAR THE APPROPRIATE LABEL OF UNDERWRITERS
Lactual = 55 m Isec = VA/V = 217.39 A LABORATORIES, INC, OR ANOTHER RECOGNIZED TESTING LABORATORY FOR THE SPECIFIC PURPOSE. THE
No. of Conduits = 18.1m/ 3.048m = 6 pcs. VDactual = (A = 2.83 V
Isc = Isec/Z (fault current symmetrical) MATERIAL SHALL BE THE SIZE AND TYPE SPECIFIED AND DRAWING AND/OR IN THE SPECIFICATIONS. OR IT
= 8695.65 A (fault current) SHOULD HAVE THE APPROVED PS MARK OR ICC LABELS.
%VDactual = (VDactual/V) x 100 = 1.23%
= 8.70 KIAC; Therefore, use 10 KIAC
VENDactual = V - VDactual = 227.17 V THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION, HEIGHTS, OUTLETS AND SWITCH
USE: ARRANGEMENTS, AND EQUIPMENT PRIOR TO ROUGH-IN. NO ADDITIONS TO THE CONTRACT SUM WILL BE
LEGEND:
PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH THE OTHER WORK, AND SO ON. THE OWNER
WIRE GOING UPWARD RESERVES THE RIGHT TO RELOCATE ANY DEVICE UP TO 3M PRIOR TO ROUGH-IN, WITHOUT ANY CHARGE BY THE
25 mm diameter EMT Conduits
WIRE GOING HORIZONTAL ELECTRICAL CONTRACTOR.
30AT 2P Circuit Breaker
WIRE GOING DOWNWARD
ALL PANEL BOARD SHALL BE FURNISHED WITH TYPED CORD DIRECTORIES WITH PROPER DESIGNATION OF THE
BRANCH-CIRCUIT LOADS, FEEDER LOADS, AND EQUIPMENT'S SERVED. THE DIRECTORIES SHALL BE LOCATED IN
THE PANEL IN A HOLDER FOR CLEAR VIEWING.
7
REYDEL L. FAJARDO BRANCH CIRCUIT 6 (RANGE OUTLET)
MS
SERVICE ENTRANCE
4 EMT Conduit Pipe (25 mm) 5 pcs. Php. 260.00 Php. 1,300.00
SERVICE DROP WIRE
5 EMT Coupling 3 pcs. Php. 25.00 Php. 75.00
LIVE WIRE
P.B
GENERAL SPECIFICATION
ALL ELECTRICAL WORKS SHALL BE DONE ACCORDANCE WITH THE LATEST PROVISIONS OF THE PHILIPPINE
ELECTRICAL CODE (PEC) PART 1 & 2, NATIONAL BUILDING CODE % LOCAL UTILITY COMPANY.
GC GROUND ROD ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSED ELECTRICAL
PRACTITIONER (PROFESSIONAL ELECTRICAL ENGINEER, REGISTERED ELECTRICAL ENGINEER, AND REGISTERED
S.E MASTER ELECTRICIAN).
CIRCUIT 7 CALCULATIONS: THE ELECTRICAL INSTALLATION IN GENERAL AS SHOWN IN OUR ELECTRICAL DRAWING AND/OR IN THE
SPECIFICATIONS.
W = 700W per REFRIGERATOR OUTLET 3. MAXIMUM LENGTH OF WIRE PER BRANCH: SHORT CIRCUIT ANALYSIS:
N = 1 UNITS X = 0.068; R = 2.0 ALL ELECTRICAL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER. ALL EXPOSED CONDUITS
V = 230 V UTILITY MAXIMUM
%VDmax = 3% SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALL AND STRUCTURAL MEMBERS. JUNCTION BOX SHALL
VA = 1 x 700 = 700VA
VDmax = (%VDmax/100) x V = 6.9 V
INFINITE BE SECURELY FASTENED; SET TRUE AND PLUMP, AND FLUSH WITH FURNISHED SURFACE WHEN WIRING METHOD
A = 700VA/ 230 V = 3.04 A CAPACITY FAULT IS CONCEALED.
1. WIRE LENGTH: TRANSFORMER LOAD
Lmax = (VDmax x 305)/(A = 345.93 m
ACTUAL LENGTH = 0.7(3) + 1.5(3) + 8(3) + 2.4(3) =
VENDmax = V - VDmax = 223.1 V TYPE OF ELECTRICAL SERVICE SUPPLY SHALL BE 230V, SINGLE PHASE, 0HZ AND CONNECTED INTO THE
37.8 m or 38 m KVA= 50 KVA (Maximum transformer load)
4. ACTUAL VOLTAGE DROP:
COMMONAL TRANSFORMER PROVIDED BY THE UTILITY.
VOLTAGE= 230 V
2. CONDUITS: X = 0.063; R = 2.0 Z= 2.5%
CONDUIT LENGTH = 0.7 + 1.5 + 8 + 2.4 = 12.6 m
ALL MATERIALS SHALL BE NEW AND SHALL BE LISTED AND BEAR THE APPROPRIATE LABEL OF UNDERWRITERS
Lactual = 38 m Isec = VA/V = 217.39 A LABORATORIES, INC, OR ANOTHER RECOGNIZED TESTING LABORATORY FOR THE SPECIFIC PURPOSE. THE
No. of Conduits = 12.6m/ 3.048m = 5 pcs. VDactual = (A = 1.036 V
Isc = Isec/Z (fault current symmetrical) MATERIAL SHALL BE THE SIZE AND TYPE SPECIFIED AND DRAWING AND/OR IN THE SPECIFICATIONS. OR IT
= 8695.65 A (fault current) SHOULD HAVE THE APPROVED PS MARK OR ICC LABELS.
%VDactual = (VDactual/V) x 100 = 0.45%
= 8.70 KIAC; Therefore, use 10 KIAC
VENDactual = V - VDactual = 228.964 V THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION, HEIGHTS, OUTLETS AND SWITCH
USE: ARRANGEMENTS, AND EQUIPMENT PRIOR TO ROUGH-IN. NO ADDITIONS TO THE CONTRACT SUM WILL BE
LEGEND:
PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH THE OTHER WORK, AND SO ON. THE OWNER
WIRE GOING UPWARD RESERVES THE RIGHT TO RELOCATE ANY DEVICE UP TO 3M PRIOR TO ROUGH-IN, WITHOUT ANY CHARGE BY THE
25 mm diameter EMT Conduits ELECTRICAL CONTRACTOR.
WIRE GOING HORIZONTAL
20AT 2P Circuit Breaker
WIRE GOING DOWNWARD
ALL PANEL BOARD SHALL BE FURNISHED WITH TYPED CORD DIRECTORIES WITH PROPER DESIGNATION OF THE
BRANCH-CIRCUIT LOADS, FEEDER LOADS, AND EQUIPMENT'S SERVED. THE DIRECTORIES SHALL BE LOCATED IN
THE PANEL IN A HOLDER FOR CLEAR VIEWING.
8
REYDEL L. FAJARDO BRANCH CIRCUIT 7 (REFRIGERATOR OUTLET)
SERVICE DROP WIRE 2 EMT Utility Box 1 pc. Php. 100.00 Php. 100.00
LIVE WIRE 3 EMT Junction Box 1 pc. Php. 95.00 Php. 95.00
NEUTRAL WIRE
4 EMT Conduit Pipe (25 mm) 6 pcs. Php. 260.00 Php. 1,560.00
GROUND WIRE
5 EMT Coupling 4 pcs. Php. 25.00 Php. 100.00
JUNCTION BOX
JBX
UTILITY BOX 6 EMT Connector 4 pcs. Php. 50.00 Php. 200.00
UBX
GENERAL SPECIFICATION
P.B
ALL ELECTRICAL WORKS SHALL BE DONE ACCORDANCE WITH THE LATEST PROVISIONS OF THE PHILIPPINE
ELECTRICAL CODE (PEC) PART 1 & 2, NATIONAL BUILDING CODE % LOCAL UTILITY COMPANY.
ALL ELECTRICAL INSTALLATION SHALL BE DONE UNDER THE DIRECT SUPERVISION OF LICENSED ELECTRICAL
GC GROUND ROD PRACTITIONER (PROFESSIONAL ELECTRICAL ENGINEER, REGISTERED ELECTRICAL ENGINEER, AND REGISTERED
MASTER ELECTRICIAN).
S.E
THE ELECTRICAL INSTALLATION IN GENERAL AS SHOWN IN OUR ELECTRICAL DRAWING AND/OR IN THE
CIRCUIT 8 CALCULATIONS: SPECIFICATIONS.
W = 1,100W per MOTOR OUTLET 3. MAXIMUM LENGTH OF WIRE PER BRANCH: SHORT CIRCUIT ANALYSIS:
ALL ELECTRICAL WORK SHALL BE EXECUTED IN A NEAT AND WORKMANLIKE MANNER. ALL EXPOSED CONDUITS
N = 1 UNITS X = 0.063; R = 1.2
SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO WALL AND STRUCTURAL MEMBERS. JUNCTION BOX SHALL
V = 230 V UTILITY MAXIMUM
VA = 1 x 1,100 = 1,100VA
%VDmax = 3% BE SECURELY FASTENED; SET TRUE AND PLUMP, AND FLUSH WITH FURNISHED SURFACE WHEN WIRING METHOD
INFINITE IS CONCEALED.
A = 1,100VA/ 230 V = 4.78 A VDmax = (%VDmax/100) x V = 6.9 V CAPACITY FAULT
1. WIRE LENGTH: TRANSFORMER LOAD
Lmax = (VDmax x 305)/(A = 366.39 m
ACTUAL LENGTH = 0.7(3) + 0.5(3) + 12.5(3) + 1(3) +
TYPE OF ELECTRICAL SERVICE SUPPLY SHALL BE 230V, SINGLE PHASE, 0HZ AND CONNECTED INTO THE
VENDmax = V - VDmax = 223.1 V COMMONAL TRANSFORMER PROVIDED BY THE UTILITY.
1(3) + 2.4(3) = 54.3 m or 55 m KVA= 50 KVA (Maximum transformer load)
4. ACTUAL VOLTAGE DROP: VOLTAGE= 230 V
2. CONDUITS:
ALL MATERIALS SHALL BE NEW AND SHALL BE LISTED AND BEAR THE APPROPRIATE LABEL OF UNDERWRITERS
X = 0.063; R = 1.2 Z= 2.5%
CONDUIT LENGTH = 0.7 + 0.5 + 12.5 + 1 + 1 + 2.4 =
LABORATORIES, INC, OR ANOTHER RECOGNIZED TESTING LABORATORY FOR THE SPECIFIC PURPOSE. THE
Lactual = 55 m Isec = VA/V = 217.39 A
MATERIAL SHALL BE THE SIZE AND TYPE SPECIFIED AND DRAWING AND/OR IN THE SPECIFICATIONS. OR IT
18.1 m Isc = Isec/Z (fault current symmetrical)
VDactual = (A = 1.17 V SHOULD HAVE THE APPROVED PS MARK OR ICC LABELS.
No. of Conduits = 18.1m/ 3.048m = 6 pcs. = 8695.65 A (fault current)
%VDactual = (VDactual/V) x 100 = 0.509%
= 8.70 KIAC; Therefore, use 10 KIAC THE ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION, HEIGHTS, OUTLETS AND SWITCH
VENDactual = V - VDactual = 228.83 V ARRANGEMENTS, AND EQUIPMENT PRIOR TO ROUGH-IN. NO ADDITIONS TO THE CONTRACT SUM WILL BE
USE: PERMITTED FOR OUTLETS IN WRONG LOCATIONS, IN CONFLICT WITH THE OTHER WORK, AND SO ON. THE OWNER
LEGEND:
RESERVES THE RIGHT TO RELOCATE ANY DEVICE UP TO 3M PRIOR TO ROUGH-IN, WITHOUT ANY CHARGE BY THE
WIRE GOING UPWARD ELECTRICAL CONTRACTOR.
25 mm diameter EMT Conduits
WIRE GOING HORIZONTAL
30AT 2P Circuit Breaker
WIRE GOING DOWNWARD
ALL PANEL BOARD SHALL BE FURNISHED WITH TYPED CORD DIRECTORIES WITH PROPER DESIGNATION OF THE
BRANCH-CIRCUIT LOADS, FEEDER LOADS, AND EQUIPMENT'S SERVED. THE DIRECTORIES SHALL BE LOCATED IN
THE PANEL IN A HOLDER FOR CLEAR VIEWING.
9
REYDEL L. FAJARDO BRANCH CIRCUIT 8 (MOTOR OUTLET)
SCHEDULE OF LOADS
MAIN FEEDER CALCULATION:
4. MAXIMUM LENGTH OF WIRE PER BRANCH: SHORT CIRCUIT ANALYSIS: VOLTAGE DROP VOLTAGE DROP
Watts SWITCH OUTLET BOX ACCESSORIES WIRE CONDUIT CALCULATION PROTECTION
W = 12,915 VA X = 0.051; R = 0.49
(MAX) (ACTUAL)
MAGNETIC
V = 230 V UTILITY MAXIMUM No. CIRCUIT DESCRIPTION Qty.
%VDmax = 3% STARTER
INFINITE EMT 2 HOLE LENGTH (MAX/ACTUAL)
HIGHEST LOAD = 3,000 W Unit S1 S2 S3 2G UBX PBX JBX CONNECTOR SIZE CLASS DIA. TYPE LENGTH Qty. WATTS VOLTAGE AMPERE AT AF P KlAC VD %VD VEND VD %VD VEND
CAPACITY FAULT COUPLING STRAP
VDmax = (%VDmax/100) x V = 6.9 V
TRANSFORMER LOAD
1. AMPERE PROTECTION: Lmax = (VDmax x 305)/(A = 58.954 m 5 pcs. 42 pcs. 35 pcs.
1 LIGHTING OUTLET 8 100 2 3 0 0 0 5 0 8 195 MTRS 182 MTRS 2.00 THHN/THWN-2 25 mm EMT 59.2 m 20 pcs. 800 230 3.48 15 30 2 10 6.9 3% 223.1 6.44 2.8% 223.56
KVA= 50 KVA (Maximum transformer load)
A = [Total Load + (1.25 x Highest Load)]/V
VENDmax = V - VDmax = 223.1 V VOLTAGE= 230 V
= [12,915 VA + (1.25 x 3,000 VA)]/230 2 LIGHTING OUTLET 8 100 4 2 0 0 0 6 0 8 6 pcs. 44 pcs. 35 pcs. 195 MTRS 193 MTRS 2.00 THHN/THWN-2 25 mm EMT 63.5 m 21 pcs. 800 230 3.48 15 30 2 10 6.9 3% 223.1 6.83 2.97% 223.17
5. ACTUAL VOLTAGE DROP: Z= 2.5%
A = 72.46 A X = 0.051; R = 0.49 Isec = VA/V = 217.39 A
3 CONVENIENCE OUTLET 6 360 0 0 0 6 0 6 1 0 9 pcs. 14 pcs. 20 pcs. 186.5 MTRS 164 MTRS 5.50 THHN/THWN-2 25 mm EMT 54.6 m 18 pcs. 2,160 230 9.39 20 30 2 10 6.9 3% 223.1 6.07 2.64% 223.93
Lactual = 13 m Isc = Isec/Z (fault current symmetrical)
2. WIRE LENGTH: = 8695.65 A (fault current) 4 CONVENIENCE OUTLET 7 360 0 0 0 7 0 7 0 4 6 pcs. 22 pcs. 25 pcs. 159.79 MTRS 158 MTRS 5.50 THHN/THWN-2 25 mm EMT 52.5 m 18 pcs. 2,520 230 10.96 20 30 2 10 6.9 3% 223.1 6.823 2.97% 223.177
VDactual = (A = 1.522 V
ACTUAL LENGTH = 0.7(3) + 3(3) + 0.5(3) = 12.6 m = 8.70 KIAC; Therefore, use 10 KIAC
or 13 m %VDactual = (VDactual/V) x 100 = 0.65% 2 pcs. 5 pcs. 15 pcs. 219.47 MTRS 76 MTRS 5.50 9 pcs. 1,835
5 A.C.U. OUTLET 1 1835 0 0 0 1 1 0 1 0 THHN/THWN-2 25 mm EMT 23.2 230 7.98 30 60 2 10 6.9 3% 223.1 2.39 1.04% 227.61
VENDactual = V - VDactual = 228.478 V LEGEND:
6 RANGE OUTLET 1 3000 0 0 0 1 0 1 0 1 3 pcs. 4 pcs. 10 pcs. 134.31 MTRS 55 MTRS 5.50 THHN/THWN-2 25 mm EMT 18.1 m 6 pcs. 3,000 230 13.04 30 60 2 10 6.9 3% 223.1 2.83 1.23% 227.17
3. CONDUITS: USE: WIRE GOING UPWARD
CONDUIT LENGTH = 0.7 + 3 + 0.5 = 4.2 m WIRE GOING HORIZONTAL 7 REFRIGERATOR OUTLET 1 700 0 0 0 1 1 1 0 1 3 pcs. 4 pcs. 8 pcs. 345.93 MTRS 38 MTRS 3.50 THHN/THWN-2 25 mm EMT 12.6 m 5 pcs. 700 230 3.04 20 30 2 10 6.9 3% 223.1 1.036 0.45% 228.964
No. of Conduits = 4.2m/ 3.048m = 2 pcs. 25 mm EMT Conduits WIRE GOING DOWNWARD
8 MOTOR OUTLET 1 1100 0 0 0 1 0 1 0 1 4 pcs. 4 pcs. 12 pcs. 366.39 MTRS 55 MTRS 5.50 THHN/THWN-2 25 mm EMT 18.1 m 6 pcs. 1,100 230 4.78 30 60 2 10 6.9 3% 223.1 1.17 0.509% 228.83
100AT 2P Circuit Breaker
MAIN 0 0 0 0 0 0 0 0 0 1 pcs. 1 pcs. 5 pcs. 58.954 MTRS 13 MTRS 14.0 THHN/THWN-2 25 mm EMT 4.2 m 2 pcs. 12,915 230 72.46 100 125 2 10 6.9 3% 223.1 1.522 0.65% 228.478
10
REYDEL L. FAJARDO MAIN