Sei sulla pagina 1di 3

FCYREFRI

Equations

COMPORTAMIENTO DEL SISTEMA DISEÑADO CUANDO LA TEMPERATURA AMBIENTE ES 8◦ c, BAJO ESTAS


CONDICIONES HABRA ENFRIAMIENTO GRATIS Y ENFRIAMIENTO CON sr
CALCULO DE LA POTENCIA Y LA TEMPERATTURA DE PREENFRIAMIENTO CON EL FREE COOLING, PARA
CUANDO LA Ta1=8◦ ,
COMO LA TEMPERATURA DEL AIRE EXTERIOR ES MAYOR QUE 4◦ c ENTONCES NO SE REGULA EL FLUJO
DE AIRE MAXIMO

U 1 = 0, 25 En Kw/m2◦ C (1)

T w1 = 15 (2)

AHORA EL FREE COOLING NO PODRA LLEVAR LA TEMPERATURA DEL AGUA A 10◦ C


T a1 = 8 (3)

mw = 5, 742 (4)

Q = mw·4, 18·(T w1 − T w2) El serpentin solo sacara una parte del calor total, Tw1=15 a la entrada y Tw2 debera determinarse(5)

Q = ma · Cpa · (T a2 − T a1) (6)

Cpa = cp (Airha ; T = T a1; P = 101) (7)

x = T w1 − T a2 (8)

y = T w2 − T a1 (9)
x−y
LM T D = (10)
ln (x/y)

F = LM T DCF (‘crossflow both unmixed’ ; P ; R) (11)

Q = U 1 · A1 · F · LM T D A1=102,1 m2, requerida cuando tiene enfriamiento gratuito a Tamb<4◦ C (12)

A1 = 102, 1 (13)
T a2 − T a1
R= (14)
T w1 − T w2
T w1 − T w2
P = (15)
T w1 − T a1
den8 = ρ (Airha ; T = T a1; P = 101) (16)

den4 = ρ (Airha ; T = 4; P = 101) (17)

ma = Ga · den8 /3600 flujo de aire en el free cooler en Kg/s (18)

Ga = 54000 Se mantiene igual al de la condicion maxima de diseño, En m3/h, corresponde a 7.5 Kw (19)

P ots = 7, 5·den8 /den4 Potencia en Kw consumida por el ventilador, a 60 Hz y para esta condicion de flujo y de temperatura del aire(20

1
CALCULO DE LA POTENCIA DEL COMPRESOR DEL SR PARA COMPLETAR EL ENFRIAMIENTO DEL AGUA
CUANDO LA Ta1=8◦
DATOS DEL EVAPORADOR
U e = 0, 8 Kw/m2◦ C (21)

(T w2 − T e) − (10 − T e)
LM T De =   (22)
ln T10−T
w2−T e
e

Q1 = U e · Ae · LM T De Como el area es ahora fijada, la Te debe acomodarse a la carga termica (23)

Q1 = mw · 4, 18 · (T w2 − 10) Parte del calor que debe retirar el chiller (24)

Ae = 20, 79 (25)

Q1 = mr · ER (26)

ER = h2 − h1 (27)

TERMODINAMICA DEL CICLO


R$ = ‘R134a’ (28)

h4 = h (R$; T = T c; x = 0) (29)

h1 = h4 (30)

pc = P (R$; T = T c; x = 0) (31)

pe = P (R$; T = T e; x = 0) (32)

h2 = h (R$; T = T e; x = 1) (33)

s2 = s (R$; T = T e; x = 1) (34)

den = ρ (R$; T = T e; x = 1) (35)

denl = ρ (R$; T = T c; x = 0) (36)

h3 = h (R$; p = P c; s = s2) (37)

T 3 = T (R$; p = pc; s = s2) (38)

Cp = cp (R$; p = pc; s = s2) (39)

Cv = cv (R$; p = pc; s = s2) (40)

CONDENSADOR
Qc = mr · (h3 − h4) (41)

Qc = mac · Cpac · (T ac2 − 8) (42)

Cpac = cp (Airha ; T = 8; P = 101) (43)

Qc = U c · Ac · LM T Dc (44)

Ac = 26, 67 (45)

2
(T c − T ac2) − (T c − 8)
LM T Dc =   (46)
ln T c−T ac2
T c−8

U c = 0, 5 (47)

T c = 5 + 1, 4 · T a1 condicion impuesta para cualquier condicion (48)

mac = Gac · den8 /3600 El ventilador debe regular el flujo Gac del condensador para garantizar la Tc impuesta (49)
3
P otc = 10 · (Gac/62000) · (den8 /den24 ) (50)

den24 = ρ (Airha ; T = 24; P = 101) (51)

COMPRESOR
n = Cp/Cv (52)
1/n
rel = (pc/pe) (53)

Et = 1 − 0, 08 · (rel − 1) (54)

mr = den·V f is·Et El compresor tambien debe regular su flujo volumetrico para acomodarse a la baja carga del sistema Q1<120 Kw(5

W c = mr · (h3 − h2) (56)

A1=102,1 Ac=26,67 Ae=20,79

Ga=54000 ma=18,78 Gac=17922 mac=6,232 Vfis=0,01299 mr=0,2427 mw=5,742

Potc =0,2553 Pots =7,393 Wc=1,318 Q=76,04 Q1=43,97 Qc=45,28

Ta1=8 Ta2=12,03 Tac2=15,22 Tc=16,2 Te=8,168 Tw1=15 Tw2=11,83