Sei sulla pagina 1di 9

XLPE ARMOURED LV POWER CABLE RATING FACTOR FOR CABLES IN AIR

RATING FACTOR OF CABLES IN AIR ARE TAKEN FROM ELECTRICAL DESIGN HANDBOOK (LDM-P101), CHAPTER-III, PAGE 11 OF 51

1) Rating for variations in Ambient air temperatuer

Ambient Air temperature °C 20 25 30 35 40 45 50


Rating Factor 1.18 1.14 1.1 1.04 1 0.95 0.9

2) Rating Factor cables on Trays, Ladders

No. of Cables
Type of laying No. of Tray or Ladders
1 2 ≥3
1 0.97 0.85 0.74
Touching
≥2 0.97 0.83 0.71
On Metal Tray
1 0.97 0.96 0.93
With Spacing
≥2 0.97 0.94 0.90
1 1.00 0.87 0.74
Touching
≥2 1.00 0.86 0.71
On Metal Ladder
1 1.00 1.00 1.00
With Spacing
≥2 1.00 1.00 1.00

DESIGN CONDITION
1. Design Temperature : 42°C
2. Cable Tray : On Metal Ladder
3. Cable route : In Air

DERATING FACTOR FOR CABLES IN AIR

Rating factor for Air ambient temeperature (42°C) 0.95


Rating factor for Cable on Ladder with Touching 0.71
Overall Deraing Factor (Df) 0.67

Correction/Derating Factor considered as .6 for calculation.

FILE:441500161.xls/Rating Factor
1. K-VALUE FOR MV CABLE
Assumed Initial Limiting Final
Conductor Material Insulation Material K
Temperature °C Temperature °C
70°C PVC (General Purpose) 70 160/140 115/103
85°C PVC 85 160/140 104/90
60°C Rubber 60 200 141
85°C Rubber 85 220 134
90°C Thermosetting 90 250 143
COPPER
Impregnated Paper 80 160 108
Mineral
Plastic Covered or exposed to touch 70 160 115
Bare and neither exposed to touch nor in contact
105 250 135
with combustible material

2. MINIMUM CROSS SECTION OF THE MV CABLES(FOR MOTORS)

Short Circuit Current (I) in Amps = 50000


Fault Clearance time (t) in Seconds = 0.01
K value of the Cu Cable = 143

Now the minimum cross section of the cable is

S=I*SQRT (t/C*log ((T2+T0) / (T0+T1)) = 69.49 CM

= More than 35 sq mm equivalent

Considered minimum cable size is = 70.00 Sq. mm.

3. MINIMUM CROSS SECTION OF THE MAIN FEEDER CABLES(6.9kV)

Short Circuit Current (I) in Amps = 50000


Fault Clearance time (t) in Seconds = 0.25
K value of the Cu Cable = 143

Now the minimum cross section of the cable is


I√t
S= = 174.83 Sq. mm.
K

Considered minimum cable size is = 185.00 Sq. mm.

4. MINIMUM CROSS SECTION OF THE MAIN FEEDER CABLES FOR (115)kV

Short Circuit Current (I) in Amps = 25000


Fault Clearance time (t) in Seconds = 0.6
K value of the Cu Cable = 143

Now the minimum cross section of the cable is


I√t
S= = 135.42 Sq. mm.
K

Considered minimum cable size is = 150.00 Sq. mm.

FILE:441500161.xls/Minimum Cross Section-MV Cable


1. LV POWER CABLES
COPPER XLPE ARMOURED
CABLE DATA TAKEN FROM AS PER KEI & DRAKA(BASED ON IEC STANDARD PRACT

VOLTAGE GRADE : 0.6 / 1 kV


TYPE : 2XWY

MAX. AC MAX.
CURRENT
NO. OF CROSS SECTION RESISTANCE REACTANCE
RATING IN AIR
CORE AREA (mm2) AT 900C AT 50Hz
(AMP)
(ohm/Km) (ohm/Km)
3 2.5 9.640 0.1070 30
3 4 5.990 0.1000 36
3 6 3.970 0.0940 47
3 10 2.350 0.0880 62
3 16 1.480 0.0820 79
3 25 0.930 0.0800 108
3 35 0.671 0.0800 132
3 50 0.495 0.0780 162
3 70 0.343 0.0770 198
3 95 0.247 0.0740 240
3 120 0.197 0.0720 276
3 150 0.160 0.0720 318
3 185 0.129 0.0720 366
3 240 0.0970 0.0720 426
1 630 0.0774 0.0843 814

2. MV POWER CABLE
COPPER XLPE ARMOURED
CABLE DATA TAKEN FROM ELECTRICAL DESIGN HANDBOOK (LDM-P101), CHAPTER-I

VOLTAGE GRADE : 3.8/6.6kV (E)


TYPE : 2XWY

MAX. AC MAX.
CURRENT
NO. OF CROSS SECTION RESISTANCE REACTANCE
RATING IN AIR
CORE AREA (mm2) AT 900C AT 50Hz
(AMP)
(ohm/Km) (ohm/Km)
3 25 0.927 0.1200 110
3 35 0.668 0.1140 150
3 50 0.494 0.1070 190
3 70 0.342 0.1020 215
3 95 0.247 0.0972 265
3 120 0.197 0.0939 320
3 150 0.160 0.0911 350
3 185 0.129 0.0788 400
3 240 0.099 0.0885 470
1 630 0.044 0.0864 1030

FILE:441500161.xls/Cable Data
CABLE SELECTION TABLE FOR 380V MOTOR FEEDERS OF UNIT
1. Wiring Type 3Ph-3W 7.Voltage drop at full load (%) 5 13. Type of Starting : DOL
2.System Voltage(V) 400 8.Voltage Drop at motor Starting (% 15 :
3.Motor Voltage(V) 380 9.Design Air Temperature 420C
CABLE TYPE- COPPER XLPE ARMOURED POWER CABLES (2XWY)
4.Frequency 50Hz 10.Conductor Temperature 900C
5.Cable Type 2XWY 11.Soil Thermal Resistivity
6.Cable Installation Air 12.Derating Factor (DF) 0.600
NO OF CORE 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1
CABLE CROSS SECTION (mm2) 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 35 50 70 95 120 150 185 240 630
RESISTANCE(ohm/Km) 9.6400 5.9900 3.9700 2.3500 1.4800 0.9300 0.6710 0.4950 0.3430 0.2470 0.1970 0.1600 0.1290 0.0970 0.6710 0.4950 0.3430 0.2470 0.1970 0.1600 0.1290 0.0970 0.0774
REACTANCE(ohm/Km) 0.1070 0.1000 0.0940 0.0880 0.0820 0.0800 0.0800 0.0780 0.0770 0.0740 0.0720 0.0720 0.0720 0.0720 0.0800 0.0780 0.0770 0.0740 0.0720 0.0720 0.0720 0.0720 0.0843
NUMBER OF RUN 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2
AMPACITY IN AIR 30.00 36.00 47.00 62.00 79.00 108.00 132.00 162.00 198.00 240.00 276.00 318.00 366.00 426.00 264.00 324.00 396.00 480.00 552.00 636.00 732.00 852.00 1628.00
Iampacity WITH DERATING 18.00 21.60 28.20 37.20 47.40 64.80 79.20 97.20 118.80 144.00 165.60 190.80 219.60 255.60 158.40 194.40 237.60 288.00 331.20 381.60 439.20 511.20 976.80
MOTOR FEEDER
MOTOR
RATING P.F. IFLC P.F STARTER ISTART
LENGTH OF MAXIMUM CABLE RUN IN METER
KW RUNNING Ampere STARTING TYPE Ampere
0.50 0.80 1.19 0.20 DOL 7.12 1189 1905 2860 4782 7494 11669 15804 20871 28826 37905 42029 45062 47961 51376 31607 41742 57652 75810 84057 90123 95922 102752 94229
0.90 0.80 2.14 0.20 DOL 12.82 661 1059 1589 2657 4164 6483 8780 11595 16015 21059 23349 25034 26645 28543 17559 23190 32029 42117 46698 50068 53290 57085 52350
1.30 0.80 3.09 0.20 DOL 18.52 458 733 1100 1840 2883 4488 6079 8028 11087 14579 16165 17332 18447 19760 12157 16055 22174 29158 32330 34663 36893 39520 36242
1.70 0.80 4.04 0.20 DOL 24.22 350 561 841 1407 2205 3432 4648 6139 8479 11149 12362 13254 14107 15111 9296 12277 16957 22298 24723 26507 28213 30222 27715
2.30 0.80 5.46 0.20 DOL 32.76 259 415 622 1040 1630 2537 3436 4538 6267 8241 9137 9796 10427 11169 6871 9075 12534 16481 18274 19592 20853 22338 20485
2.50 0.80 5.94 0.20 DOL 35.61 238 381 572 957 1499 2334 3161 4175 5766 7581 8406 9013 9593 10276 6322 8349 11531 15162 16812 18025 19185 20551 18846
3.00 0.80 7.12 0.20 DOL 42.73 199 318 477 797 1249 1945 2634 3479 4805 6318 7005 7511 7994 8563 5268 6957 9609 12635 14010 15021 15987 17126 15705
3.50 0.80 8.31 0.20 DOL 49.85 170 273 409 684 1071 1667 2258 2982 4118 5415 6005 6438 6852 7340 4516 5964 8236 10830 12009 12875 13704 14679 13462
3.80 0.80 9.02 0.20 DOL 54.13 157 251 377 630 987 1536 2080 2747 3793 4988 5531 5930 6311 6760 4159 5493 7586 9975 11061 11859 12622 13520 12399
4.00 0.80 9.50 0.20 DOL 56.98 149 239 358 598 937 1459 1976 2609 3604 4739 5254 5633 5996 6422 3951 5218 7207 9477 10508 11266 11991 12844 11779
4.50 0.80 10.68 0.20 DOL 64.10 133 212 318 532 833 1297 1756 2319 3203 4212 4670 5007 5329 5709 3512 4638 6406 8424 9340 10014 10658 11417 10470
5.00 0.80 11.87 0.20 DOL 71.22 119 191 286 479 750 1167 1581 2088 2883 3791 4203 4507 4797 5138 3161 4175 5766 7581 8406 9013 9593 10276 9423
5.50 0.80 13.06 0.20 DOL 78.34 109 174 260 435 682 1061 1437 1898 2621 3446 3821 4097 4361 4671 2874 3795 5242 6892 7642 8193 8721 9342 8567
6.00 0.80 14.24 0.20 DOL 85.47 100 159 239 399 625 973 1317 1740 2403 3159 3503 3756 3997 4282 2634 3479 4805 6318 7005 7511 7994 8563 7853
6.50 0.80 15.43 0.20 DOL 92.59 92 147 220 368 577 898 1216 1606 2218 2916 3233 3467 3690 3952 2432 3211 4435 5832 6466 6933 7379 7904 7249
7.00 0.80 16.62 0.20 DOL 99.71 85 137 205 342 536 834 1129 1491 2059 2708 3003 3219 3426 3670 2258 2982 4118 5415 6005 6438 6852 7340 6731
7.50 0.80 17.81 0.20 DOL 106.83 80 127 191 319 500 778 1054 1392 1922 2527 2802 3005 3198 3426 2108 2783 3844 5054 5604 6009 6395 6851 6282
8.00 0.80 18.99 0.20 DOL 113.95 120 179 299 469 730 988 1305 1802 2370 2627 2817 2998 3211 1976 2609 3604 4739 5254 5633 5996 6422 5890
8.50 0.80 20.18 0.20 DOL 121.08 113 169 282 441 687 930 1228 1696 2230 2473 2651 2822 3023 1860 2456 3392 4460 4945 5302 5643 6045 5543
10.00 0.80 23.74 0.20 DOL 142.44 143 240 375 584 791 1044 1442 1896 2102 2254 2399 2569 1581 2088 2883 3791 4203 4507 4797 5138 4712
11.00 0.80 26.11 0.20 DOL 156.69 130 218 341 531 719 949 1311 1723 1911 2049 2181 2336 1437 1898 2621 3446 3821 4097 4361 4671 4284
14.00 0.80 33.24 0.20 DOL 199.42 171 268 417 565 746 1030 1354 1502 1610 1713 1835 1129 1491 2059 2708 3003 3219 3426 3670 3366
15.00 0.80 35.61 0.20 DOL 213.66 160 250 389 527 696 961 1264 1401 1503 1599 1713 1054 1392 1922 2527 2802 3005 3198 3426 3141
16.00 0.80 37.98 0.20 DOL 227.91 235 365 494 653 901 1185 1314 1409 1499 1606 988 1305 1802 2370 2627 2817 2998 3211 2945
18.50 0.80 43.92 0.20 DOL 263.52 203 316 428 565 780 1025 1136 1218 1297 1389 855 1129 1559 2049 2272 2436 2593 2778 2547
20.00 0.80 47.48 0.20 DOL 284.89 292 396 522 721 948 1051 1127 1200 1285 791 1044 1442 1896 2102 2254 2399 2569 2356
22.00 0.80 52.23 0.20 DOL 313.37 266 360 475 656 862 956 1025 1091 1168 719 949 1311 1723 1911 2049 2181 2336 2142
24.00 0.80 56.98 0.20 DOL 341.86 244 330 435 601 790 876 939 1000 1071 659 870 1202 1580 1752 1878 1999 2141 1964
25.00 0.80 59.35 0.20 DOL 356.11 234 317 418 577 759 841 902 960 1028 633 835 1154 1517 1682 1803 1919 2056 1885
27.00 0.80 64.10 0.20 DOL 384.59 217 293 387 534 702 779 835 889 952 586 773 1068 1404 1557 1669 1777 1903 1745
30.00 0.80 71.22 0.20 DOL 427.33 264 348 481 632 701 752 800 857 527 696 961 1264 1401 1503 1599 1713 1571
32.00 0.80 75.97 0.20 DOL 455.82 247 327 451 593 657 705 750 803 494 653 901 1185 1314 1409 1499 1606 1473
35.00 0.80 83.09 0.20 DOL 498.55 299 412 542 601 644 686 734 452 597 824 1083 1201 1288 1371 1468 1347
37.00 0.80 87.84 0.20 DOL 527.04 283 390 513 568 609 649 695 428 565 780 1025 1136 1218 1297 1389 1274
45.00 0.80 100.55 0.20 DOL 603.29 341 448 497 532 567 607 374 493 681 895 993 1064 1133 1214 1113
50.00 0.80 111.72 0.20 DOL 670.32 307 403 447 479 510 546 336 444 613 806 894 958 1020 1092 1002
56.00 0.80 125.13 0.20 DOL 750.76 360 399 428 455 488 300 396 547 720 798 855 910 975 894
60.00 0.80 134.06 0.20 DOL 804.38 336 373 399 425 455 280 370 511 672 745 798 850 910 835
65.00 0.80 145.24 0.20 DOL 871.41 344 369 392 420 259 342 472 620 687 737 784 840 771
75.00 0.80 167.58 0.20 DOL 1005.48 320 340 364 296 409 537 596 639 680 728 668
80.00 0.80 178.75 0.20 DOL 1072.51 300 319 342 278 383 504 559 599 637 683 626
85.00 0.80 189.92 0.20 DOL 1139.54 282 300 322 261 361 474 526 564 600 643 589
90.00 0.80 201.10 0.20 DOL 1206.57 284 304 341 448 497 532 567 607 557

FILE:441500161.xls/LV Motor Feeder


CABLE SELECTION TABLE FOR 380V MOTOR FEEDERS OF UNIT
1. Wiring Type 3Ph-3W 7.Voltage drop at full load (%) 5 13. Type of Starting : DOL
2.System Voltage(V) 400 8.Voltage Drop at motor Starting (% 15 :
3.Motor Voltage(V) 380 9.Design Air Temperature 420C
CABLE TYPE- COPPER XLPE ARMOURED POWER CABLES (2XWY)
4.Frequency 50Hz 10.Conductor Temperature 900C
5.Cable Type 2XWY 11.Soil Thermal Resistivity
6.Cable Installation Air 12.Derating Factor (DF) 0.600
100.00 0.80 223.44 0.20 DOL 1340.64 273 307 403 447 479 510 546 501
110.00 0.80 245.78 0.20 DOL 1474.70 249 367 406 436 464 497 456
115.00 0.80 256.96 0.20 DOL 1541.73 351 389 417 444 475 436
120.00 0.80 268.13 0.20 DOL 1608.76 336 373 399 425 455 418
130.00 0.80 290.47 0.20 DOL 1742.83 344 369 392 420 386
135.00 0.80 301.64 0.20 DOL 1809.86 331 355 378 405 371
140.00 0.80 312.82 0.20 DOL 1876.89 319 342 364 390 358
150.00 0.80 335.16 0.20 DOL 2010.95 320 340 364 334

Note: 1) Starting PF consider as 0.2 .


2) Considering effieiency of the motor is 80%(up to 37kW & above is ..85)
3) Starting Current : DOL Starting : 600% of FLC for all LV Motor
VSD Starting : 200% of FLC of LV Motor.
4) Minimum cable size to be slected based on derated cable ampacity (Iampacity) such that I ampacity > Iflc

FILE:441500161.xls/LV Motor Feeder


CABLE SELECTION TABLE FOR MV MOTOR FEEDERS OF UNIT
1. Wiring Type 3Ph-3W 7.Voltage drop at full load (%) 5 13. Minimum Cross-section of Cable for VCS 70.00 Sq. mm.
2.System Voltage(V) 6900 8.Voltage Drop at motor Starting (%) 15 15. Type of Starting : SOFT
CABLE TYPE- COPPER XLPE ARMOURED POWER CABLES 3.Motor Voltage(V) 6600 9.Design Air Temperature 420C : Reactor
(2XWY) 4.Frequency 50Hz 10.Conductor Temperature 900C : DOL
5.Cable Type 2XWY 11.Soil Thermal Resistivity
6.Cable Installation Air 12.Derating Factor (DF) 0.600
NO OF CORE 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
CABLE CROSS SECTION (mm2) 70 95 120 150 185 240 25 35 50 70 95 120 150 185 240 70 95 120 150 185 240
RESISTANCE(ohm/Km) 0.3420 0.2470 0.1970 0.1600 0.1290 0.0993 0.9270 0.6680 0.4940 0.3420 0.2470 0.1970 0.1600 0.1290 0.0993 0.3420 0.2470 0.1970 0.1600 0.1290 0.0993
REACTANCE(ohm/Km) 0.1020 0.0972 0.0939 0.0911 0.0788 0.0885 0.1200 0.1140 0.1070 0.1020 0.0972 0.0939 0.0911 0.0788 0.0885 0.1020 0.0972 0.0939 0.0911 0.0788 0.0885
NUMBER OF RUN 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3
AMPACITY IN AIR 215.00 265.00 320.00 350.00 400.00 470.00 110.00 150.00 190.00 430.00 530.00 640.00 700.00 800.00 940.00 645.00 795.00 960.00 1050.00 1200.00 1410.00
Iampacity WITH DERATING 129.00 159.00 192.00 210.00 240.00 282.00 132.00 180.00 228.00 258.00 318.00 384.00 420.00 480.00 564.00 387.00 477.00 576.00 630.00 720.00 846.00
MOTOR FEEDER
MOTOR
RATING P.F IFLC P.F STARTER ISTART
KW RUNNING Ampere STARTING TYPE Ampere
160.00 0.90 17.28 0.20 DOL 103.68 31302 38117 41956 45466 53521 51731 24873 33881 44891 62603 76234 83911 90931 107042 103462 93904 114351 125867 136396 160563 155193
200.00 0.90 21.60 0.20 DOL 129.60 25041 30494 33565 36373 42817 41385 19899 27105 35913 50082 60987 67129 72745 85634 82770 75123 91481 100694 109117 128450 124155
210.00 0.90 22.68 0.20 DOL 136.08 23849 29042 31967 34641 40778 39415 18951 25814 34203 47697 58083 63933 69281 81556 78829 71546 87125 95899 103921 122334 118243
270.00 0.90 29.16 0.20 DOL 174.96 18549 22588 24863 26943 31717 30656 14740 20078 26603 37098 45176 49725 53885 63433 61311 55647 67764 74588 80827 95149 91967
300.00 0.90 32.40 0.20 DOL 194.40 16694 20329 22377 24249 28545 27590 13266 18070 23942 33388 40658 44753 48497 57089 55180 50082 60987 67129 72745 85634 82770
315.00 0.90 34.02 0.20 DOL 204.12 15899 19361 21311 23094 27186 26277 12634 17209 22802 31798 38722 42622 46187 54371 52553 47697 58083 63933 69281 81556 78829
350.00 0.90 37.80 0.20 DOL 226.80 14310 17425 19180 20785 24467 23649 11371 15489 20522 28619 34850 38360 41569 48934 47297 42928 52275 57539 62353 73400 70946
360.00 0.90 38.88 0.20 DOL 233.28 13912 16941 18647 20207 23788 22992 11055 15058 19952 27824 33882 37294 40414 47575 45984 41735 50823 55941 60621 71362 68975
500.00 0.90 54.00 0.20 DOL 324.00 10017 12198 13426 14549 17127 16554 7960 10842 14366 20033 24395 26852 29098 34254 33108 30049 36593 40278 43647 51380 49662
520.00 0.90 56.16 0.20 DOL 336.96 9632 11729 12910 13990 16468 15918 7654 10425 13813 19263 23457 25819 27979 32936 31835 28894 35185 38729 41968 49404 47752
550.00 0.90 59.40 0.20 DOL 356.40 9106 11089 12206 13227 15570 15049 7236 9857 13060 18212 22178 24411 26453 31140 30098 27318 33266 36616 39679 46710 45147
580.00 0.90 62.64 0.20 DOL 375.84 8635 10515 11574 12543 14765 14271 6862 9347 12384 17270 21030 23148 25085 29529 28542 25905 31545 34722 37627 44294 42812
620.00 0.90 66.96 0.20 DOL 401.76 8078 9837 10828 11733 13812 13350 6419 8744 11585 16156 19674 21655 23466 27624 26700 24234 29510 32482 35199 41436 40050
600.00 0.90 64.80 0.20 SOFT 226.80 8347 11110 13474 16006 19544 22981 6633 9035 11971 16694 22219 26947 32011 39088 45962 25041 33329 40421 48016 58631 68943
1000.00 0.90 108.00 0.20 Reactor 378.00 5009 6666 8085 9604 11727 13789 3980 5421 7183 10017 13332 16169 19207 23453 27577 15025 19997 24253 28810 35179 41366
1100.00 0.90 118.80 0.20 Reactor 415.80 4553 6060 7350 8731 10661 12535 3618 4929 6530 9106 12120 14699 17461 21321 25070 13659 18179 22048 26191 31981 37605
1250.00 0.90 135.00 0.20 Reactor 472.50 5333 6468 7683 9381 11031 4337 5747 8014 10665 12935 15365 18762 22062 12020 15998 19402 23048 28143 33093
1500.00 0.90 162.00 0.20 Reactor 567.00 5390 6403 7818 9193 3614 4789 6678 8888 10779 12805 15635 18385 10017 13332 16169 19207 23453 27577
2000.00 0.90 216.00 0.20 Reactor 756.00 5864 6895 3592 5009 6666 8085 9604 11727 13789 7513 9999 12127 14405 17590 20683

Note: 1) Starting PF consider as 0.2 .


2) Considering effieiency of the motor is 90%
3) Starting Current : 350% of FLC for MV Motor( In Case of Reactor & Soft Starting)
4) Starting Current : 600% of FLC for MV Motor( In Case DOL Starting)
5) Minimum cable size to be slected based on derated cable ampacity (Iampacity) such that I ampacity > Iflc

FILE:441500161.xls/MV Motor Feeder


FILE:441500161.xls/MV Motor Feeder
CABLE SELECTION TABLE FOR MV FEEDERS OF UNIT
1. Wiring Type 3Ph-3W 7.Voltage drop at full load (%) 1 13. Minimum Cross-section of Cable for VCS 70.00 Sq. mm.
2.System Voltage(V) 6900 8.Voltage Drop at motor Starting (%) 14. Minimum Cross-section of Cable for Breaker =185 Sq. mm
CABLE TYPE- COPPER XLPE ARMOURED POWER CABLES 3.Motor Voltage(V) - 9.Design Air Temperature 420C 14.Power Factor = .9
(2XWY) 4.Frequency 50Hz 10.Conductor Temperature 900C
5.Cable Type 2XWY 11.Soil Thermal Resistivity
6.Cable Installation Air 12.Derating Factor (DF) 0.600
NO OF CORE 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1
CABLE CROSS SECTION (mm2) 70 95 120 150 185 240 25 35 50 70 95 120 150 185 240 70 95 120 150 185 240 630 630
RESISTANCE(ohm/Km) 0.3420 0.2470 0.1970 0.1600 0.1290 0.0993 0.9270 0.6680 0.4940 0.3420 0.2470 0.1970 0.1600 0.1290 0.0993 0.3420 0.2470 0.1970 0.1600 0.1290 0.0993 0.0435 0.0435
REACTANCE(ohm/Km) 0.1020 0.0972 0.0939 0.0911 0.0788 0.0885 0.1200 0.1140 0.1070 0.1020 0.0972 0.0939 0.0911 0.0788 0.0885 0.1020 0.0972 0.0939 0.0911 0.0788 0.0885 0.0864 0.0864
NUMBER OF RUN 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 1 2
AMPACITY IN AIR 215.00 265.00 320.00 350.00 400.00 470.00 110.00 150.00 190.00 430.00 530.00 640.00 700.00 800.00 940.00 645.00 795.00 960.00 1050.00 1200.00 1410.00 1030.00 2060.00
Iampacity WITH DERATING 129.00 159.00 192.00 210.00 240.00 282.00 132.00 180.00 228.00 258.00 318.00 384.00 420.00 480.00 564.00 387.00 477.00 576.00 630.00 720.00 846.00 618.00 1236.00
MOTOR FEEDER
RATING P.F IFLC P.F STARTER ISTART
KVA RUNNING Ampere STARTING TYPE Ampere
10350.00 866.05 - - - 1198
4000.00 334.71 - - - 1091 1296 1583 1861 1014 1350 1637 1944 2374 2791 1550 3100
3000.00 251.03 - - - 1241 902 1200 1455 1728 2110 2481 1352 1799 2182 2592 3165 3722 2067 4133
2000.00 167.35 - - - 1091 1296 1583 1861 732 970 1352 1799 2182 2592 3165 3722 2028 2699 3273 3888 4747 5582 3100 6199
1500.00 125.51 - - - 902 1200 1455 1728 2110 2481 716 976 1293 1803 2399 2909 3456 4220 4962 2704 3598 4364 5184 6330 7443 4133 8265
1000.00 83.68 - - - 1352 1799 2182 2592 3165 3722 1074 1463 1939 2704 3598 4364 5184 6330 7443 4055 5397 6545 7775 9494 11164 6199 12397
500.00 41.84 - - - 2704 3598 4364 5184 6330 7443 2148 2926 3877 5407 7196 8727 10367 12659 14885 8110 10794 13090 15550 18988 22327 12397 24794
800.00 66.94 - - - 1690 2249 2728 3240 3956 4652 1343 1829 2423 3379 4498 5455 6479 7912 9303 5069 6746 8182 9719 11868 13955 7748 15496
250.00 20.92 - - - 5407 7196 8727 10367 12659 14885 4296 5852 7754 10813 14391 17454 20733 25317 29769 16219 21587 26180 31100 37975 44654 24794 49587
150.00 12.55 - - - 9011 11993 14545 17278 21097 24808 7160 9753 12923 18021 23985 29089 34555 42194 49615 27032 35978 43633 51832 63291 74422 41323 82645

Note:
1) Minimum cable size to be slected based on derated cable ampacity (Iampacity) such that I ampacity > Iflc

FILE:441500161.xls/MAIN Feeder 6.9KV


CABLE SELECTION TABLE FOR 400V MAIN FEEDERS OF UNIT
1. Wiring Type 3Ph-3W 7.Voltage drop at full load (%) 1 13. Power Factor : 0.9
2.System Voltage(V) 400 8.Voltage Drop at motor Starting '-
CABLE TYPE- COPPER XLPE ARMOURED POWER 3.Motor Voltage(V) - 9.Design Air Temperature 420C
CABLES (2XWY) 4.Frequency 50Hz 10.Conductor Temperature 900C
5.Cable Type 2XWY 11.Soil Thermal Resistivity
6.Cable Installation Air 12.Derating Factor (DF) 0.600
NO OF CORE 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 1 1 1 1 1 1 1
CABLE CROSS SECTION (mm2) 16 25 35 50 70 95 120 150 185 240 35 50 70 95 120 150 185 240 120 150 185 240 630 630 630 630 630 630 630
RESISTANCE(ohm/Km) 1.4700 0.9300 0.6710 0.4950 0.3430 0.2470 0.1960 0.1590 0.1270 0.0965 0.6710 0.4950 0.3430 0.2470 0.1960 0.1590 0.1270 0.0965 0.1960 0.1590 0.1270 0.0965 0.0774 0.0774 0.0774 0.0774 0.0774 0.0774 0.0774
REACTANCE(ohm/Km) 0.0800 0.0800 0.0800 0.0780 0.0770 0.0740 0.0720 0.0720 0.0720 0.0720 0.0800 0.0780 0.0770 0.0740 0.0720 0.0720 0.0720 0.0720 0.0720 0.0720 0.0720 0.0720 0.0843 0.0843 0.0843 0.0843 0.0843 0.0843 0.0843
NUMBER OF RUN 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 3 3 3 3 1 2 3 4 5 6 7
AMPACITY IN AIR 79.00 108.00 132.00 162.00 198.00 240.00 276.00 318.00 366.00 426.00 264.00 324.00 396.00 480.00 552.00 636.00 732.00 852.00 828.00 954.00 1098.00 1278.00 814.00 1628.00 2442.00 3256.00 4070.00 4884.00 5698.00
Iampacity WITH DERATING 47.40 64.80 79.20 97.20 118.80 144.00 165.60 190.80 219.60 255.60 158.40 194.40 237.60 288.00 331.20 381.60 439.20 511.20 496.80 572.40 658.80 766.80 488.40 976.80 1465.20 1953.60 2442.00 2930.40 3418.80
MOTOR FEEDER
RATING IFLC P.F STARTER ISTART
PF
Ampere STARTING TYPE Ampere
1167.00 0.90 1684.47 - - - 52 65 78 91
1169.00 0.90 1874.84 47 58 70 82
824.00 0.90 1321.53 - - - 50 66 83 99 115
806.00 0.90 1292.66 - - - 51 68 84 101 118
488.00 0.90 782.65 - - - 56 84 111 139 167 195
461.00 0.90 739.35 - - - 80 59 89 118 147 177 206
394.00 0.90 631.90 - - - 76 93 69 104 138 172 207 241
348.00 0.90 558.12 - - - 72 86 105 78 117 156 195 234 273
343.00 0.90 550.10 - - - 73 87 107 79 119 158 198 237 277
323.00 0.90 518.03 - - - 77 92 114 84 126 168 210 252 294
232.00 0.90 372.08 - - - 72 86 105 90 107 128 158 59 117 175 234 292 350 409
239.00 0.90 383.31 - - - 83 102 87 104 125 153 57 114 170 227 284 340 397
196.00 0.90 314.34 - - - 71 85 101 125 107 127 152 187 70 139 208 277 346 415 484
150.00 0.90 240.57 - - - 82 76 93 111 132 163 139 166 198 244 91 181 271 361 452 542 632
141.00 0.90 226.14 - - - 87 60 81 99 118 141 173 148 176 211 260 96 192 288 384 480 576 672
112.00 0.90 179.63 - - - 74 89 109 54 76 102 124 148 177 218 186 222 265 327 121 242 363 484 605 725 846
99.00 0.90 158.78 - - - 71 84 100 124 61 85 115 141 167 200 247 211 251 300 370 137 274 411 547 684 821 957
91.00 0.90 145.95 - - - 77 91 109 134 50 67 93 125 153 182 218 268 229 273 326 402 149 298 447 595 744 893 1042

Note: 1) Minimum cable size to be slected based on derated cable ampacity (Iampacity) such that I ampacity > Iflc

FILE:441500161.xls/MAIN Feeder .4KV

Potrebbero piacerti anche