Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Page1
March1992
Changed since August 1990
Dala subjectlo changew~oul nolice
(90603) (90641)
Features eGreat flexibility in mounting and wiring -Each protection relay is independent with
eProtection relays can be delivered in pre- its own dc supply and secondary tesl:ing
wired and factory tested cubicles or as indi- facilities
vidual relays -SuitabJe for generators and other rotating
ac machines
Application COMBIFLEX generator protection relays can gapped CT cores are not required, but can be
be applied to any generator or other rotating ac used. Low knee-point voltage, typically in the
machines. They are particularly suitable for range of 60 V (with 5 A rating) is acceptable.
generators in the range of 5 to 100 MVA where .Interposing CT's are normally used to reduce
great flexibility in application is desired. Individ- the relaycurrent to 1 or2 A, and to lower the
ual relays can be used complementary to other saturation voltage imposed on the relay.
protection relay families or packages. For 'arge
machines, subdivision into dual schemes e.g. The main CT secondary circuit resistance,
mai n I and mai n II can easily be made. should be limited to 125 ohms, including CT's.
This guarantees correct operation irrespective
Besides the generator relays described here, a of fault-<:urrent magnitude or saturation.
great number of protection relays of multipur- An overcurrent supervision relay is included for
pose type are available (see References). added security. To trip multiple breakers and to
Short-circuit protection provide additional output functions, a separate-
Stator differential relays are commonly used. ly mounted latching relay is optional.
Depending on the earthing system, earth faults The RADHA relay is a three-phase high im-
mayaiso be detected. pedance differential relay, generally suitable for
small to medium generators. This relay is de-
The RADSG is used to provide high-speed scribed in other documents and used when
protection of any generator stator winding for (10-20 ms) tripping times are acceptable and
phase faults. Long dc time constant of large where dedicated CT's are available.
synchronous generators may result in fully off-
set asymmetrical fault current for an apprecia- Stator earth fault
ble time. Studies have shown that 250 ms may The common practice to earth the generator
el ap se before a zero-crossing of the fault cur- neutral through a resistor limits the earth cur-
rent occurs. Generator CT's will most likely sat- rent to 5-10 A. The COMBIFLEX stator earth
urate during this period and remain so until the fault relays are based on detection of the fun-
current goes through zero crossing. This would damental and third harmonic voltages in the
result in delayed operation of slower speed neutral (or broken delta).
conventionai differential relays. The RADSG The (RXIG 28) 95% stator earth fault rel:ay is
relay uses instantaneous measuring quantities set at 5% of maximum neutral voltage at solid
and detects an internai fault within 1-3 ms earth faults. At this setting 95% of the stator
(5-10 ms to trip) resulting in a correct operation winding and also the generator bus and ancil-
prior to CT saturation. RADSG can therefore be laries up to the next step-up transformer are
applied with CT's of standard design. Air- protected.
ABB Network Controi COMBIFLEX
& Protection Generator protection relays
Application (cont'd) The RAGEA relay covers 100% of the stator al time delayed overcurrent relays cannot ade-
winding and consists of a 95% measuring ele- quately protect the generator; therefore, special
ment (as RXIG 28 above) and an additional loss-of-excitation relays are required to ensure
element covering as a minimum 95-100% of tripping.
U'v vvi"di,,~. II~' af'f'li"alivll i~ ba~vd vllavaila- -rL..- n Ar"'n,.. __1__- 1_- L..- 1 ...L -_:
blity of a minimum 1% third harmonic voltage at The RAGF:'C relay.ca~ also be u~ed where par-
the neutral allel machlnes malntaln the terminal voltage
.above 0.85 p.u. on the machine having lost ex..
When more than the minimum 1 % third-har- citation. The relay therefore includes a current
monic voltage exists, the operating zone of the detector set at 1.1 p.u. current. The current re-
third harmonic 95-100% protection can be fur- ceived by the machine is generally in the order
the r extended and the set operating value of of 2-5 times rated, at lost excitation.
the 95% protection can be increased. A reduc- ..
tion in the operating time for the 95% protection The RAGPC relay 1.5sultable for all.types of
is then feasible without any loss in security. sy~c~rc:>nous machlnes. The operating ~harac-
terlstlc IS normally set as close as posslble to
The third-harmonic detector is supervised by t~e therma~ capability curve for the underex-
either a generator phase-tO-'phase voltage, or clted machlne.
generator current. The third-harmonic relay. .
setting is determined from the amount of gener- Negative sequence.current protectlon
ator neutral third-harmonic voltages. Calcula- When the generator IS connected t.o balan?ed
tions can be based on machine specifications load t~e phase curre:nts are equaJ In magmtud~3
and equipment capacitances or on field mea- and displaced electrlcally by 120 .
surements. Whe~ vo~tage s~pervision is l;Ised, The RARIB relay provides protection against
the 100% protectlon IS pr~vlded even during. excessive rotor heating that may occur due to
startup, when the voltage IS above the supervl- unbalanced phase currents. Single-phase and!
sion relay operate level. two-phase faults, phase rupture or asymmetri(~
.loading on the system can give rise to unbal-
Roto~field
The ea~h f~u.ltIS normally
clrcult protectlon kept .anced
Isolated from rents currents ' hence negative sequence cur-
earth. A single earth fault is therefore not of im- .
mediate danger. A s~cond fault can cause seri- If the negative sequence current is of high ma!~-
ous damage. Signalllng and alarm or delayed nitude, or if it persists for long periods of time,
tripping of the first earth fault is therefore sutfi- rotor parts can be damaged due to overheatin!~.
cient. It is normally assumed that a generator can
.sustain negative sequence currents which ex-
The (RXNB4) ro~or earth faL!lt ~el?y IS used ceed a given minimum value for a period of
w~en the excitation voltage IS ~1~lte~ to 600 V. time, t, which is determined from the following
It IS b?sed on 48 V dc voltage Injectlon to t~e equation:
negative pole. When a fault occurs, a certaln
contribution to the injection voltage is obtained
depending on the actual field voltage and loca-
tion of the fault. The sensitivity is therefore a t = KI(( IM ) 2
linear function of added excitation voltage. nBC
The RARIB provides a trip and alarm setting ple enables more sensitive protection than
capability corresponding to the machine capa- shaft-voltage measurements or vibration-moni-
bility. toring. Vibration monitors on ly operate after the
bearing is damaged. By applying RARIC, the
In addition, the inverse-time circuitry incorpo- machine can be tripped and the cause of the
rates a memory function that takes inta consid-
bearing insulation breakdown can often be
eration negative sequence currents that have eliminated before the bearing is damaged.
not caused tripping due to their short duration.
Repetitive, short duration, negative sequence The RARIC relay is available in two versions.
currents can be accumulated and when the set Version 1, most common, measures the funda-
value is reached, tripping is obtained. mental ac component in the shaft current. If the
lowest setting can be used (small distur-
The memory function provides the relay with a bances), the relay can detect primary shaft cur-
selectable resetting function that can be rents of 0.25-0.8 A. Version 2 is used when the I
adapted to the cooling down time of the ma-
shaft-current transformer is exposed to large
chine.
fundamentalleakage flux from the machine.
The relay cooling down time, ta, in seconds is Version 2 measures the third harmonic ac com-
given by equation ponent in the shaft current and can, at its: low-
est setting, (0.5 mA) detect primary shaft cur- -
rents of 0.25-0.8 A, 150 Hz. The shaft voltage ;
must contain a third harmonic component if ver-
sion 2 is to be used.
A shaft-current transformer is required for the
where b is a factory set constant in steps be- relay measurement of the shaft current.
tween O and 6.
Inadvertent energization protection
Reverse power protection Accidental energization of generators at stand-
The purpose of the reverse power relay is basi- still or on turning-gear can lead to catastrophic
cally to prevent damage on the prime mover failures of the generator and other related pow- L
(turbine). er station equipment. Generally, the time to
damage the generator stator from the high in- ;-
When the input to the prime mover is lost, the rush currents received during energization at j
generator functions as a synchronous compen- stand still is in the order of a few seconds. The
gator. This may lead to damage of the turbine bearing, however, may be damaged more r
blades, bearings or in cage of motors, insuffi- quickly due to the lack of oil pressure. Since
cient lubrication. Especially for turbogenerators, conventionai protection relays do not provide
the active power supplied to a machine running adequate protection when the generator is out-
as synchronous compensator may be as low as of-service, a dedicated high-speed protection
1 % of the generator rated power. is recommended by most major equipment '
The small active power to the machine, manufacturers.
depending on the excitation level, may be com- The RAGUA relay prevents damage due to ac-
bined with a substantiai reactive current. In cidental energization to the network. Tripping
order to secure operation in this cage, the an- time is about 8 ms.
gular error of the total measuring circuit (voIt-
age and current transformers plus relay) must Synchronizing
be extremely small. Correction of the angular The RASA 4 synchronizing relay is intencled for
error may be required when the reverse power automatic synchronizing of smaller generators.
is less than 2% of rating. The synchronizing pulse to the circuit-breaker
is given just prior to actual synchronism, to
The (RXPE 40) reverse power relay is based compensate for circuit-breaker closing time.
on single-phase measurement of generator Version A has a settable maximum frequency
current. A setting, down to 0.5% of rated gener- difference of 0.2-0.4 Hz and is used in small
ator current is possible. It has an extremely low power systems e.g. aboard ships.
power consumption at operation and a small
angular error, with correction possibilities. Version B has a fixed maximum frequency dif-
ference of 2 Hz and is used to synchroniz;e
Shaft current protection small generators e.g. standby- or hydrogenera-
If the bearing insulation on rotating machines tors to stronge r power systems. It has a IE~ad
breaks down, the induced voltage between time which automatically adapts itself to the
shaft ends from machine dissymmetries actual beat frequency. Approximately 40 ms is
creates a shaft current that can damage the allowed in the compensation-circuit fo! the cir-
bearings or other vital parts. The damage de- cuit-breaker closing time.
pends on the shaft-current magnitude and du-
ration. It is therefore desirable to provide sensi- Very small frequency differences can enable
tive protection that can detect shaft currents of operation, however, synchronizing pulse is not
1 A or less. The shaft-current measuring princi- obtained when no frequency difference exists.
RAGEA (RXNB 4)
100% Stator earth fault relay Rotor earth fault relay
Design (cont'd) dervoltage supervision unit, that operates in two timers, type RXKF 1, and one output rela~v,
addition to RXPE, for the loss-of-excitation type RXME 18, with flag and heavy duty con-
condition and a current unit RXIG 21 used for tacts or type RXSF 1, with flag and medium
trip supervision. An RTXP 18 test switch is pro- duty contacts.
vided for secondary injection testing.
Versions with or without the phase-angle cor-
RARIB rection unit, type RXTMB 1, are available.
Negative sequence current relay
The RXTMB 1 phase-angle compensating unit
is connected into the polarizing voltage circuits
of RXPE 40. The unit contains an RC circuit
with a potentiometer. By varying the resistance
value, the unit can be set to give a positive
phase displacement of 0-4 degrees in the po-
larizing voltage circuit of RXPE 40.
RARIC
Shaft-current relay
The RARIC relay includes a test switch, type
RTXP 18, ac-dc converter, overcurrent relay,
type RXIK 1, time relay, type RXKF 1, medium-
duty relay, type RXMA 1 and heavy-duty trip
relay, type RXME 18. Version 2 also includes ,a
(SE 90603) filter which attenuates the fundamental current
into the relay.
The RARIB relay is built up of six units
mounted on two apparatus bars. A hand reset flag indicates operation. The nec:-
essary time-delay for tripping is provided by
The RXTBIC 4, negative phase sequence cur- the RXKF 1.
rent filter, contains two transformers, one ampli-
The overcurrent relay includes surge suppres-.
fier and a low-pass filter which reduces har-
sion filteringon the input and has an output th,at
monics in the three-phase current. The filter is
is maintained even in cases of intermittent shaft
connected to eliminate any influence of zero-
currents.
sequence current. An option al instrument am-
plifier can be included in the filter for connecting The shaft-current transformer, type ILDD, is
to an optional instrument that indicates the neg- available for shafts with a diameter from 150 to
ative phase sequence current, Insc. 3000 mm. The core is made in two or four sec-
tions. for mounting between the rotor and the
The RXIEK 2H, measuring unit, contains twO nearest bearing on the side of the rotor with o ut
level detectors, for alarm and start, and four slip rings. The transformer uses special mag-
output relays for alarm, start, tripping, and netic iron and has a uniformly distributed wind-
blocking. On the front of the unit are thr~e po- ing and a test winding for testing the relay. To
tentiometers for making the following settings: mount the shaft-current transformer around thle
shaft, an axial distance of 250 mm or more is
-Adaption of the relay current to the rated cur-
recommended. The inner diameter of the shaft-
rent of the machine, IM. The scale is gra- current transformer should be at least 20 mm
duated (0.7-1.1) x In.
larger than the shaft diameter.
-Operate value for Alarm with scale gra-
duated 3-9% or 7-21% of IM. The test switch enables a complete test of
-Operate value for Start with scale graduated RARIC and the shaft-current transformer.
4-16% or 10.--40% of IM. RAGUA
On the front there are also LED's that indicate Dead machine relay
Alarm, Start, Trip and Block, and a Reset but- The RAGUA is a three-phase static overcur-
ton for the Alarm, Start and Trip indications. rent relay with voltage supervision.
The Block LED follows the pulses to the bIock- It includes instantaneous overcurrent relays,
ing relay. type RXIB 24, which are permitted to tri p only
The RXKEB 2H, timing unit, incorporates two after the generator voltage has dropped below
time delay circuits; one for definite-time-delay a set value, e.g. 85% of nominal voltage for a
of the alarm signal and one for inverse time- certain set period.
delay for the tripping and blocking functions. On The voltage is supervised by voltage relay,
the front, six toggle switches are used for set- RXEG, in two phases (separately fused) which
ting of the time constant, K. The setting can be are both required to operate to permit tripping.
made in steps of 1 s up to a maximum of 63 s.
This prevents a false operation in case of re-
The bottom switch is used for selecting the ti- moved or blown fuses in the voltage circuit.
me-delay of the alarm signal: OFF is equal to a A flag relay, RXSF 1, is incorporated to alarm
0.1 s time-delay and ON is equal to a 6 s time- for voltage disagreement and trip.
delay. The switch immediately above this one is
not used. The undervoltage relays controi two RXKE tim-
ers. One timer is used to ensure that tripping
The cooling down time-constant is internally will not be delayed by momentary generator
prograry'lmable in 7 steps (b = 0-6) and set be- transients greater than the setting of the volt-
fore delivery. age relays. During normal startup, this timer
(RXPE 40) Reverse power relay keeps RAGUA in service beyond 85% voltage
The reverse power relay is available in several relay setting.
versions. The relay contains one current direc- The other timer delays tripping when both un-
tional relay, RXPE 40, completed with one or dervoltage relays operate. This time is essentiai
A88 Network Controi COMBIFLEX 1 MDBO2(JIO6-EN
& Protection Generator protection relays Page 7
as close-in faults may drop the generator volt- RASA 4 is a four seat plug-in unit that clontains
age below the undervoltage setting. It also pro- two voltage input-transformers, static measu-
vides supplementary backup protection for ring-circuits, blocking and output relays for the
close-in faults. A two second delay is recom- synchronization of breakers. The input trans-
mended. former, which is connected to the network volt-
age, provides the relay with auxiliary vol1:age
RASA 4 after rectification and smoothing. The other in-
Synchronizing relay put transformer is supplied with the difference
between the network voltage and generated
voltage when an external synchronizing--switch
is active.
A blocking relay prevents an output signal in
case the output relay is closed when the exter-
nal synchronizing switch is activated. The LED
on the front indicates blocking.
A front-connected screw terminal panel base,
RXZ 41 , can be used for surface mountirlg of
RASA 4. The four-seat plug in unit can also be
mounted in a 19" equipment frame or RHGX
panel mounting case together with other relays.
(92664)
Technicaldata
Common data, uniess Disturbance test:
otherwise specified 1 MHz burst test 2.5 kV, 2 s
Pr is the heat dissipation in resistors Rd3 and Rs at rated through load IT3r = 2 A.
Recommended standard setting: S = 0.2, Rd3 = 5.0 ohms.
When 5/1 A auxiliary CT's are used the totalloop-resistance permitted in the 5 A circuits is:
Rx2 = 167/52 = 6.7 ohm
The data below is valid for RAGEA and parts referring to fundamental
frequencies are also valid for the 95% relay
Operating values
Power consumption
(at voltage = lowest setting)
Dimension
RAGEA 4U BOG
95% relay 4U 24G
Time--{jelay on pick-up
Rdc alarm 5s
Rdc trip Adjustable 0.5-3 s
Rac trip 5s
Maximum excitation
voltage
Continuously 1800 V dc
For10s 2700 V dc
For 1 s 5900 V dc
Maximum permitted
main voltage on the ac
side
If the machine is to be
tripped for an ac earth
fault 1100 V ac
Curve A Curve B
Insulation Insulation
kAI resistance OA
250
200
150
100
7,
5-
..3OOV U, »O , MIIV
Fig. 2 Operate range RXNB 4. Curve A valid for the relay version 300 Vand curve B valid for
relay version up to 600 V excitation voltage
Power consumption See RXPE 40 Operate time for alarm 0.1 s or 6 s (settable)
Scale ranges for Is = 1 A 5 A
Consistency <2%
Directional relay 0.1-0.4 A 1-4 A
Overcurrent relay 0.5-1.5 A 2.5-7.5 A Operate time for
Undervoltage relay 40-120 V 40-120 V acc.to Fig. 3
tripping
Time range (RXKF) 0.08-1.2 s
Consistency <3%
Disturbance test:
1 MHz burst test K.170
common mode 2.5 kV, 2 s Cooling down time, ta 2b
transverse mode 1.0 kV, 2 s
Consistency < 5%
Output relay conIact
dala See RXSF 1 Power consumption in
auxiliary voltage circuits
Weight approx. 6 kg Before operation 10W
After operation 13W
Dimensions 4U 42C
Power consumption in
input circuits at
In = 1 or 2 A < 0.1 VA/phase
RARIB negative sequence current relay In=5A < 0.2 VA/phase
Rated current, In 1, 2 or 5 A Disturbance tests:
Power frequency test 50 Hz. 0.5 kV. 2 min
Setting, IM (0.7-1.1)xln Fast transient test 4-8 kV. 2 min
Rated frequency 50 or 60 Hz
1 MHz burst test
Auxiliary dc voltage, EL 24-36, 48-60 or common mode 2.5 kV, 2 s
110-250 V transverse mode 1.0 kV, 2 s
ABB Network Controi COMBIFLEX 1 MDBO2006-EN
& Protection Generator protection relays Page 11
Auxiliary voltage
dependency
Operate time < 0.13%/% voltage
change
Operate value < 0.01 %1% voltage
change
Temperature
dependency
Operate time < O.13%rC
Operate value < O.O5°lol°C
Frequency dependency
Within +2 Hz < 1% equivalent In c
With in :t:S Hz < 1.5% equivalent fnsc
Dimension 4U 42C
(2006-3)
Rated ac voltage 110 V, 50-60 Hz Contact data See RXME 18, RXKF 1
and RXSF 1
Time range 0.2-3 or 2-30 s
(RXKF) For more detailed technical data see descriptions
for RXPE, RXKF and aux. relays. Please nate that
the current rating can not be increased by using a
current-limiting modul e with di odes when RXPE
40 is used as reverse power relay for generators.
Diagrams
(2006--4)
(2006-6)
(RXNB 4) rotor earth fault relay
Terminal diagram 7432 0O19-ABB
I I
"'El
1101
ABB Network Controi COMBIFLEX 1 MDBO2006-E;N
& Protection Generator protection relays Page 14
Diagrams (cont'd)
~ uc
101 RTXP 18
107 RXPE40
119 RxIG 2
131 RXTMA 1
319 RXEG 2
331 RXKF 1
337 RXSF 1
1) Tripping etc.
2) Alarm etc.
I I
'Ul-
(2006--8)
I I !
4U
101 RTXP 18
107 RXTUG 21H
113 RXTBIC 4
125 RXIEK2H
131 RXKF 1
337 RXMM 1
30C
4U
101 RTXP18
107 RXPE40
119 RXTMB 1
125.325 RXKF 1
319 RXSF 1
1) Tripping etc.
2) Alarm etc.
3) Event recorder
4) Aux. contact on turbine stop cojl
I.I(R>
---n+---'
L~-s;---r
L3<n--r+
I h ~--il [ --tt I
A f < -= T1rij- i"\ ---:il!
I'
.I
I ~~~~
.I U
[ --~,
--l II
SYNCImN I Z I NG PULSE
---fuc:~:;:;~ I III
I I III
L__~ --+ ;..J
Fig.11 RASA synchronizing relay il ~
Terminal diagram 5891 027-1 (2006-11
Differentiai-r:e-iay
RADSG Version A 7417 024- MA/-M RK 637 022-AA Specify Rd3 setting
RADSG Version B 7417024- BAA-/-BA RK 637 022-BA (standard = 5 ohms)
(BU rack)
---
Interposing CT's
SLCE 12 5/1 A - 4785 04o-BFB
SLCE 12 2/1 A 4785 04o-BFL
SLCE 12 1/1 A 4785 04o-BFC
SLXE 4 5/2 A 4785 04o-BEB
Stator earth faUlt-relays I Specify scale range
95% relayI for fundamental relay
without flag 7452469-AAN-AA RK 641 0O8-AA
RXIG 28.
with flag 7452469-CAN-CA RK 641 0O8-CA
II!
ABB Network Controi COMBIFLEX 1 MDBO2006-I:N
& Protection Generator protection relays Page 16