Sei sulla pagina 1di 6

IEEE Africon 2017 Proceedings

Resonant characteristics of the transmission line


compensated with the Static Synchronous Series
Compensator

M.J. Masenkane R. Pillay Carpanen


Electrical Engineering Programme Electrical Engineering Programme
University of KwaZulu-Natal University of KwaZulu-Natal
Durban, 4001, South Africa Durban, 4001, South Africa
jmasenkane@yahoo.com PillayR21@ukzn.ac.za

Abstract— This paper examines resonant characteristics of current (AC) transmission lines by solid state synchronous
the transmission line compensated with the Static Synchronous voltage sources was proposed by Gyugyi [6]. One such a
Series Compensator. Frequency-domain characteristics of the device is a Static Synchronous Series Compensator (SSSC)
line impedance are studied to evaluate whether the SSSC can which injects voltage in series with the line and in quadrature
cause electrical resonance in the line, hence the potential to excite with the line current. The SSSC can be designed to operate
subsynchronous resonance (SSR) in neighboring turbine- either as voltage controlled or reactance controlled. It was
generator plants. Detailed studies are performed in PSCAD using initially believed that these inverter-based series compensators
the modified IEEE first benchmark (IEEE FBM) model. The cannot cause SSR since they do not employ series capacitors.
results show that the SSSC has a potential to excite SSR since it
The above claim on the immunity of these devices to SSR was
provides capacitive reactance not only at the rated system
made based on the assumption that the voltage they inject into
frequency but also at subsynchronous frequencies.
the transmission line could be restricted to the synchronous
Keywords— Subsynchronous resonance; SSSC; Resonant frequency of the network. The work of [7] later revealed that
frequency; conventional capacitors detailed analysis of the SSR characteristics of these devices is a
prerequisite to drawing conclusions regarding their potential to
cause SSR. This includes among other issues the use of
I. INTRODUCTION benchmark study systems developed for such investigations
Construction of new electrical power generation and [8], and considering different system operating conditions.
transmission infrastructure to meet the ever growing energy There are different analytical tools used to assess the
demand is restricted by economic, environmental and potential existence and severity of SSR and the most dominant
regulatory policies inter alia. Also, through decentralization of ones in industry are frequency scanning, eigenvalue analysis
electric power generation, more renewable energy sources are and electromagnetic transient simulations [1], [9]. Frequency
being integrated into existing power grids, hence more power scanning technique offers a quick method to assess and identify
needs to be transmitted over power lines than before. This the potential risk of SSR. In this paper, frequency–response
increases the level of uncertainty in the operation of power simulation tests are carried out in PSCAD to study the SSR
networks [1] and potentially endanger their stability [2]. These characteristics of the SSSC. This frequency-response method is
call for enhancement of power transfer capability of existing initially validated by comparing it with the harmonic
transmission lines beyond their present operating region but impedance theoretical solution. To attain clearer perception of
below their thermal limits [3]. Series compensation by means the SSR characteristics of the SSSC, the resonant
of conventional series capacitor banks has been used for characteristics of the SSSC compensated transmission line are
decades to serve this purpose [4]. Connecting these capacitors compared with the resonant characteristics of the capacitor
in series with the transmission line reduces the effective compensated line that are known to cause the SSR problem.
inductive reactance of the line, allowing more power to be Finally, time domain simulations are performed together with
transferred along the line. The use of these devices is, however, frequency scanning to determine the exited torsional modes.
restricted by their potential to excite subsynchronous resonance This paper has considered a SSSC operating in the reactance-
(SSR) in neighboring turbine-generators. SSR is a form of control mode.
dynamic instability which may result in failure or damage of
turbine shafts in its worst exhibition [5]. It is for this reason
that alternative forms of series compensation were sought. II. SUBSYNCHRONOUS RESONANCE

In the late 1980s, dynamic compensation of alternating A. The SSR study system

614

978-1-5386-2775-4/17/$31.00 ©2017 IEEE


IEEE Africon 2017 Proceedings

frequency (f0 - fer) in the air gap. SSR due to torsional


interaction results if this slip frequency gets significantly close
to any of the turbine-generator natural torsional modes.

III. MODELLING OF THE SSSC

A. SSSC principle of operation


Fig. 2 shows the SSSC connected to the transmission line
by means of an injection transformer. The SSSC consists of a
Sinusoidal Pulse Width (SPWM) voltage source inverter (VSI)
Fig. 1. Single Machine Infinite Bus system of the IEEE first benchmark model using power IGBTs with switching frequency of 1260 Hz
(21×f0). The SSSC can provide capacitive or inductive
The study system c study system consists of the single reactance in series with the transmission line independent of
892.4 MVA generator feeding an infinite bus through a single the line current, although only capacitive mode of operation is
series compensated 500kV transmission line as shown in considered in this paper. The DC link voltage is maintained at
Fig. 1. Series compensation is either provided by the the predetermined value by ensuring that no active power is
conventional capacitor banks or by the SSSC at system exchanged between the SSSC and the line, except a small
frequency of 60 Hz. The turbine-generator shaft consists of a amount that is rectified to charge the capacitor and compensate
six-mass rotor system representing different shaft sections. for the inverter losses.
This system has numerous vibration torsional modes; below
and above the rated system frequency. For the purpose of SSR
studies, however, only the subsynchronous frequency range
(i.e. below system rated frequency) is of interest.

Table I provides the torsional vibration modes of the six-mass


rotor system.

TABLE I. TURBO-GENERATOR ROTOR TORSIONAL MODES [10]


Mode Frequency, fn

Mode 0 1.6 Hz
Mode 1 15.71 Hz
Mode 2 20.21 Hz
Mode 3 25.55 Hz Fig. 2. The SSSC installed on a transmission line

Mode 4 32.285 Hz The phase and magnitude control of the voltage injected by
Mode 5 47.46 Hz the SSSC are obtained from the SSSC internal controls shown
in Fig. 2. The line current is measured and its peak value, Ipk or
|I| is obtained. The output from the magnitude control is
B. Mechanism of SSR given by (2), with kconv being the converter gain.
An RL transmission line compensated with conventional
series capacitors represents a resonant RLC network. This 1
network exhibits a resonant minimum in its impedance at a Sm I pk X sssc (2)
resonant frequency at which the inductive reactance and Vdc K conv
capacitive reactance cancel out. The network resonant
frequency, fer, is given by (1), where XC is the capacitive The angle calculator consists of the inner power loop and
reactance at a system frequency, f0. The total network inductive
outer voltage loop. In the outer loop, the error between the DC
reactance consists of the line reactance, XL, the step up
transformer reactance, Xt, the infinite bus reactance, Xsys as well link voltage Vdc and the reference voltage Vdc* is calculated and
as the generator sub-transient reactance, X ̎ ad. converted into a commanded power, P*. The error, ƐP,
between the commanded power and the actual power, Pi, at
XC the inverter AC terminals is obtained in the inner loop and
f er f0 (1) converted to angle error, Ɛϴ using (3).
X L  X t  X Sys  X ad
"

1
A disturbance in the power system containing such a network HT HP (3)
3 2
results in currents at the frequency fer to flow in the nearby I pk X sssc
generator stator windings, developing a torque with the slip 2

615
IEEE Africon 2017 Proceedings

The angle error Ɛϴ is taken through the PI controller to get in a SSSC compensated network. However, it will be used to
the angle ϴ, whose dynamics are defined by (4), which is then check the validity of the frequency-response test methodology
added to the transmission angle, w0t obtained using the phase to be used in SSSC compensated transmission line.
locked loop (PLL), to get the required angle, φv [11].
B. Frequency-response test simulation
dT
dt 3 2
K ai
^K V
vp
*
dc
 Vdc  Pi ` (4) As mentioned in the previous section, when compensation
I pk X sssc is provided by a complex power-electronic device such as the
2 SSSC, frequency response cannot be predicted from circuit
theory analysis (e.g. using the harmonic impedance solution).
The frequency-response test method adopted from [7] is used
IV. SSR CHARACTERISTICS IN THE FIRST BENCHMARK MODEL instead, given in Fig. 4 and summarized below:
In order to study the SSR characteristics of the SSSC or the 1) The transmission network is fed with the normal
conventional series capacitors using the IEEE first benchmark transmission line voltage at its sending and receiving
model, the synchronous machine is first replaced by the ends which are separated by some transmission angle
grounded three-phase AC source of the same amplitude and δ. A small subsynchronous voltage VSS (10% of the
frequency behind a sub-transient reactance.
sending-end voltage amplitude) is inserted in each
phase at the sending end, as in Fig. 4. The frequency
A. Harmonic impedance solution of the subsynchronous voltage is set to a value lower
The simulation package PSCAD has a powerful than the power system frequency.
component or feature which allows impedance scanning of 2) Steady-state response of the transmission line voltages
electrical systems [12]. Fig. 3 shows the use of this component and currents to this combination of subsynchronous
to scan the impedance of the capacitor compensated network and synchronous forcing voltages is obtained.
as seen looking from the armature of the generator in the IEEE 3) The Fast Fourier Transform (FFT) analysis is carried
first benchmark model. For transmission line or cable models, out on time domain results to extract the magnitude
this component uses the RLC data directly. The system and phase relationship between the phase ‘a’ voltage
impedance matrix is generated in phase domain and then and current so as to obtain the net impedance of the
collapsed into an equivalent matrix as seen from the interface line at the given frequency.
point. The process is repeated for each frequency in the range 4) The frequency domain characteristics of the line are
specified by the user in the parameter inputs. Accurate obtained by repeating the above steps (1) to (3) for a
representation for unbalanced transmission lines or Y-∆ frequency range of interest.
transformers is obtained by solving equations in phase domain
without using sequence networks. The impedance of the
sending end source is kept high during simulation to ensure
the impedance scanned corresponds to the transmission
network impedance. Output data from the harmonic
impedance solution is in a form of a text file and can be
analysed in any external graphical analysis program, such as
Matlab which is used in this paper. Assumptions made in the
harmonic impedance solution are as follows:
x Transformer saturation and arresters are assumed to
be in their unsaturated region.
x All power electronic devices are assumed to be in
their OFF state. Fig. 4. Diagram of the simulated frequency-response test equivalent circuit
This is why the method is not suitable for resonance studies

V. SIMULATION RESULTS AND DISCUSSIONS

A. Resonant characteristics of the conventional capacitor


compensated IEEE FBM
In this subsection, variation of the resonant frequency of the
capacitor compensated network with the degree of
compensation is investigated. Harmonic impedance solution is
used to obtain the theoretical frequency-response of the
transmission line impedance and the results are shown in
Fig. 5. The results show that the impedance of a conventionally
Fig. 3. Diagram showing the interface to harmonic impedance solution to scan compensated line does exhibit a resonant minimum at some
the network impedance

616
IEEE Africon 2017 Proceedings

From Fig. 6, it is observed that the results from the


frequency-response test simulations agree closely with the
theoretical results which guarantees the accuracy of the
frequency-test methodology. The resonant frequency is found
to be 39.9 Hz. This will result in the generator air gap torque
at a slip frequency of 20.1 Hz, which is close to mode 2
(at 20.21 Hz) in table I. Thus, there is a risk of SSR due to
torsional interaction through destabilization of this particular
mode at the 74.1% compensation by conventional capacitors.

C. Resonant characteristics of the SSSC compensated IEEE


FBM
In this subsection, the net impedance of the SSSC
compensated transmission line is examined as a function of
frequency. The frequency-response test technique described in
section IV is used to establish the electrical resonance of the
Fig. 5. Resonant characteristics of the transmission line compensated with SSSC compensated transmission line at different degrees of
conventional series capacitors
series compensation. Fig. 7 and Fig. 8 show the resonance
subsynchronous frequency. At this frequency, the impedance is characteristics of the SSSC compensated line at 25%
minimum and purely resistive and this is the origin of the SSR (Xsssc = 0.125 pu) and 74.1% (Xsssc = 0.3707 pu) series
problem in conventionally compensated networks. Also, the compensation respectively.
resonant frequency increases with the degree of series
compensation. For all degrees of compensation considered, the The results of Fig. 7 and Fig. 8 show that a SSSC
minimum impedance at resonant frequency is the same compensated line also exhibits a resonant minimum at a
(0.01416 Ω), which is the line resistance seen from the resonant frequency, just like the capacitor compensated line.
armature of the generator. Resonant frequency in each case is Therefore, the SSSC has a potential to cause SSR at the given
the same as that calculated using (1). degrees of compensation. Further, the resonant frequency
increases with the degree of series compensation just like a
B. Validation of the frequency-response test methodology case of conventionally compensated line. However, the
In order to obtain confidence in the frequency-response resonant frequency with SSSC compensation is different from
test methodology for investigating the impedance resonant that with series capacitors, even at the same value of
characteristics, results from this method need to be validated. compensating reactance. This implies that the SSR
This subsection evaluates the accuracy of the frequency- characteristics of these compensators will differ. From Fig. 8,
response test methodology in a capacitor compensated IEEE the resonant frequency is 30 Hz, the slip frequency of the air
FBM. Fig. 6 shows comparison of the frequency-response test gap torque will be 30 Hz which is close to Mode 4 (at 32.285
results to the theoretical results for 74.1% compensation of the Hz). Hence SSR due to destabilization of Mode 4 can be
line reactance (Xc = 0.3707 pu). expected when this level of series compensation is provided

Fig. 6. Comparison of the frequency-response test results to the theoretical Fig. 7. Resonant characteristics of the transmission line with SSSC at 25%
results with capacitor compensation (Xc = 0.3707 pu) compensation (Xsssc = 0.125 pu)

617
well as the dominant mode(s) of oscillation. The FFT analyses
of the generator speed deviation with conventional capacitors
is compared to that with SSSC compensation in Fig. 10. The
FFT analyses show that Mode 2 is dominant in a capacitor
compensated line while Mode 4 is dominant in the SSSC
compensated transmission line. These results are in agreement
with the predictions made from the resonance characteristics
of the compensated IEEE first benchmark model in section IV.

Fig. 8. Resonant characteristics of the transmission line with SSSC at 74.1%


compensation (Xsssc = 0.3707 pu)

by the SSSC. Furthermore, the line impedance at resonant


frequency is larger with SSSC compensation than with
capacitor compensation. Previous work by others [7] has
shown that this is due to the fact that the SSSC injects not only
capacitive reactance but also some resistance at
subsynchronous frequencies. Increasing line resistance has
been identified as one way to provide some positive damping
of SSR [7], [13].

D. Time domain simulation results


In subsections B and C, the resonance characteristics of the
transmission line were investigated when series compensation
is provided by conventional series capacitors and by the SSSC
respectively. With both devices the transmission line
impedance exhibits a resonant minimum at the resonant
frequency which increases with the degree of compensation.
However, the resonant frequency is distinct for each device.
This subsection now looks at the detailed time domain
response of the study system for SSR analysis at one particular
degree of compensation in order to investigate the possible
interaction between the network natural frequencies and the
mechanical shaft modes. It must be noted that all mutual and
self-damping coefficients for the six rotor system masses are
zero.
Fig. 9 shows the system response when a three-phase to
ground fault lasting for 75ms is applied at t=1.5 s. This fault
duration represents the time for a circuit breaker to interrupt
the fault. The results show that both the conventional series
capacitors and the SSSC have a potential to excite SSR at one
of the degree of compensation considered (0.3707 pu) in the
previous section. For the capacitor compensated network,
there is rapid growth in shaft torque oscillations which will
lead to shaft damage. On the other hand, the SSSC provides
some positive damping of SSR. However, sustained shaft
torque oscillations will reduce the shaft fatigue. FFT analyses
of these signals show the frequency components present as
IEEE Africon 2017 Proceedings

VI. CONCLUSION System and fault Impedances


In this paper, SSR characteristics of the Static Synchronous XSys = 0.06 pu Xf = 0.04 pu
Series Compensator have boon studied utilizing the IEEE first
benchmark model. The detailed model of the reactance Infinite Bus
Rated frequency = 60 Hz Voltage = 500 kV L-L
controlled SSSC is developed in PSCAD. The results show that
the SSSC can cause electrical resonance in the line. Thus, this
device provides capacitive reactance not only at the rated TABLE IV. TRANSFORMER PARAMETERS
system frequency but also at subsynchronous frequencies,
hence it has a potential to excite SSR in nearby generating Parameter Value
units. Therefore, when installing the device in the transmission Rated Power 892.4 MVA
line, its SSR characteristics should be known as well as Nominal Frequency 60 Hz
mechanical resonances of all nearby turbine-generator shafts. Rated Voltage (LV/HV) 26/539 kV
Although the SSSC does provide some positive damping to the Vector Group and Phase Shift YNd1
torsional oscillations, additional damping of the critical Positive Sequence Impedance 0.14 p.u.
torsional modes is required to mitigate the risk of Zero Sequence Impedance 0.14 p.u.
subsynchronous resonance and avoid shaft failure due to
fatigue.

REFERENCES
APPENDIX
[1] A. Adrees, “Risk Based Assessment of Subsynchronous Resonance in
Additional parameters of the IEEE first benchmark model to AC/DC Systems,” Springer, 2016.
those given in Fig. 1 are provided below. [2] R. Preece, “Improving the Stability of Meshed Power Networks: A
Probabilistic Approach Using Embedded HVDC Lines,” Springer
Generator parameters Science & Business Media, 2013.
Rated MVA = 892.4 MVA, Rated voltage = 26 kV L-L, [3] R. Pillay Carpanen, “Analysis of the impact of a FACTS-based power
Rated frequency = 60 Hz, Power factor = 0.9 lagging flow controller on subsynchronous resonance,” PhD Thesis, University
of KwaZulu-Natal, Durban, South Africa, 2012.
Xp = 0.13 pu, Xd = 1.79 pu, Xd' = 0.169 pu, X1 = 0.135 pu,
Xq = 1.71 pu, Xq' = 0.228 pu, Td0' = 4.3 s, Td0" = 0.032 s, [4] S. Panda, A.K. Baliarsingh, S. Mahapatra, and C.C. Swain,
"Supplementary damping controller design for SSSC to mitigate sub-
Tq0' = 0.85 s, Tq0" = 0.05 s synchronous resonance," Mechanical Systems and Signal Processing,
vol. 68, pp. 523-535, February 2016.
[5] IEEE Subsynchronous Resonance working Group, “Terms, definitions
TABLE II. MULTI-MASS ROTOR SYSTEM PARAMETERS and symbols for subsynchronous oscillations,” IEEE Transactions on
Power Aparatus and Systems, vol. 104, pp. 1326-1334, June 1985.
Inertia Inertia Shaft Spring Torque
[6] N.G. Hingorani, L. Gyugyi, and M. El-Hawary, “Understanding
constant Section constant Fraction
FACTS: Concepts and Technology of Flexible AC Transmission
(seconds) (pu Systems,” New York: IEEE Press, 2000.
T/rad)
[7] B.S. Rigby and R.G. Harley, “Resonant Characteristics of Inverter-
HP turbine 0.092897 - - 0.30 Based Transmission line series compensators,” Conference Record of
IP 0.155589 HP-IP 7277 0.26 the IEEE Power Electronics Specialists conference, June 1999,
LPA turbine 0.85867 IP-LPA 13168 0.22 Charleston, USA, ISBN 0-7803-5421-4, pp 412-417.
[8] F.W. Huang, “Modelling and Analysis of inverter-based FACTS devices
LPB 0.884215 LPA-LPB 19618 0.22 for power system dynamic studies,” PhD Thesis, University of
G 0.868495 LPB-G 26713 - KwaZulu-natal, Durban, South Africa, 2006.
Ex 0.034217 Gen-Ex 1064 - [9] G.V. Gotmare and V.B. Virulkar, “Eigenvalue Analysis of
Subsynchronous Resonance Study in Series Compensated Wind Farm,”
International Journal of Modern Trends in Engineering and Research,
Vol. 02, pp. 267 – 275, February 2015.
TABLE III. TRANSMISSION LINE PARAMETERS [10] IEEE SSR working group, “First benchmark model for computer
simulation of subsynchronous resonance,” IEEE Transactions on Power
Parameter Value Apparatus and Systems, Vol. 96, pp. 1565-1572, September 1977.
Type Overhead line [11] Rigby B.S, R.G. Harley, “An improved Control Scheme for a Series-
Positive sequence resistance RL = 0.02 pu Capacitive Reactance Compensator Based on a Voltage-Source
Inverter,” IEEE Trans. on IAS, Vol. 34, pp. 355-363, March 1998,.
Positive sequence reactance XL = 0.50 pu
[12] PSCAD/EMTDC Version 4.2.1 Online Help, Manitoba HVDC Centre
Inc.
SSSC parameters [13] Mahmoud A.A., T.H. Ortmeyer, R.G. Harley, and C. Calabrese, “Effects
Vdc0 = 70 kV, Cdc = 375 μF, Kvp = 9711.91, Kai = 1470.27, of reactive compensation on induction motor dynamic performance,”
IEEE Transactions on Apparatus and Systems, Vol. PAS-99, pp. 841-
Hv = 0.1pu, Hp = 0.3, Vdc* = 7 kV, K conv 1 / 2 2
846, May 1980.

619

Potrebbero piacerti anche