2.LOAD CALCULATION:
a) Plinth Beam:
-----------------------------------------------------------
----------------------------------------
---------------------------------
5 of 121
d) Roof Slab:
Slab thickness -------------------------------------------------------------------------
= 150 mm
Dead load of Slab (DLS) -------------------------------------------------------------------------
= 25 x 0.15
DLS1 = 3.750KN/m²
Thickness of Water Proffing Marter ----------------------------------------------
= 100 mm
Dead load of Marter (DLM) ----------------------------------------------------------------------
= 25 x 0.1
---------------------------------------------------
----------------------------------------
DLM = 2.500KN/m²
Roof Finishing (RF) -------------------------------------------------------------------------
= 0.250 KN/m² Table 2-IS 875 (Part-1)-1987 _pg 30.
Total Roof Load (W1) -------------------------------------------------------------------------
= 3.75+2.5+0.25
W1 = 6.5KN/m²
Total Roof Load (W2) -------------------------------------------------------------------------
= 3.125+2.5+0.25
W2 = 5.9KN/m²
= II
Wind zone ------------------------------------------------------------------------- Table 1- IS 875 (Part 3)- 1987 _pg 11.
Basic Wind Speed (Vb) -------------------------------------------------------------------------
= 39 m/s Table 1- IS 875 (Part 3)- 1987 _pg 11.
Design Wind Speed (Vz) -------------------------------------------------------------------------
= Vbxk1xk2xk3 IS 875 (Part 3)- 1987 _pg 08.
Risk Co-efficient (k1) -------------------------------------------------------------------------
= 1.06 Table 1- IS 875 (Part 3)- 1987 _pg 11.
Topography factor (k3) -------------------------------------------------------------------------
= 1.00 IS 875 (Part 3)- 1987 _pg 12.
Terrain factor (k2) -------------------------------------------------------------------------
.=> Table 2- IS 875 (Part 3)- 1987 _pg 12.
Terrain Category -------------------------------------------------------------------------
= 2 (1.5 to 10m) Surrounding the Structure
Terrain Category Class -------------------------------------------------------------------------
= B(20 to 50 m) Horizontal or Vertical Dimentions
Terrain Category Height -------------------------------------------------------------------------
= 10
Terrain factor (k2) -------------------------------------------------------------------------
= 0.98
Design Wind Speed (Vz) -------------------------------------------------------------------------
= 39x1.06x0.98x1 IS 875 (Part 3)- 1987 _pg 08.
Vz = 40.51 m/s
= 0.6Vz²
Wind Pressure (Pz) ------------------------------------------------------------------------- IS 875 (Part 3)- 1987 _pg 12.
Pz = 1.0 KN/m²
2.4 Seismic load:
= II
Seismic zone ------------------------------------------------------------------------- Table 2- IS 1893: 2002 _pg 16
Seismic Intensity (Z) -------------------------------------------------------------------------
= 0.10 Table 2- IS 1893: 2002 _pg 16
Structure type -------------------------------------------------------------------------
= Power station Table 6- IS 1893: 2002 _pg 18
Design Seismic Base Shear (VB) -------------------------------------------------------------------------
= Ah*W IS 1893: 2002 _pg 24
Seismic weight of Structure (W) -------------------------------------------------------------------------
= TDL+TLL As per STAAD Pro
Design Horizontal Acceleration (Ah) -------------------------------------------------------------------------
= (Z*I / 2R)*(Sa/g) IS 1893: 2002 _pg 14
Impartance factor (I) -------------------------------------------------------------------------
= 1.50 Table 6- IS 1893: 2002 _pg 18
Response Reduction factor (.R) -------------------------------------------------------------------------
= 5 Table 7- IS 1893: 2002 _pg 23
Spectral Acceleration Coefficient (Sa/g) -------------------------------------------------------------------------
.=> IS 1893: 2002 _pg 16
= 0.09*h / √ d
Fundamental Natural Period (Ta) -------------------------------------------------------------------------
IS 1893: 2002 _pg 24
Lateral Dimension of Structure (d-x direction) -------------------------------------------------------------------------
= 35.53 m
Height of the of Structure (h) -------------------------------------------------------------------------
= 5.90 m
Fundamental Natural Period (Ta) -------------------------------------------------------------------------
= 0.09 sec .=X-direction
Lateral Dimension of Structure (d-z direction) -------------------------------------------------------------------------
= 9.30 m
Height of the of Structure (h) -------------------------------------------------------------------------
= 5.90 m
Fundamental Natural Period (Ta) -------------------------------------------------------------------------
= 0.17 sec .=Z-direction
Type of Soil -------------------------------------------------------------------------
= Rocky or Hard Soil IS 1893: 2002 _pg 16
Spectral Acceleration Coefficient (Sa/g) -------------------------------------------------------------------------
= 2.34
Design Horizontal Acceleration (Ah) -------------------------------------------------------------------------
= 0.035 .=(Z*I / 2R)*(Sa/g)
Design Seismic Base Shear (VB) -------------------------------------------------------------------------
= (TDL+TLL)x0.035 .=Ah*W= VB
6 of 121