Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1.1 Introduction
The per unit system is fundamental in the analysis of power systems, due to the large
amount of power transmitted, parameters such as voltage and power are usually in the
kilo or mega range. These values along with current and impedance are usually
represented as a percent of per unit of a base or reference value.
Usually base megavolt amperes (MVA) and base voltage in kilovolts are selected to
specify the base.
Vb
(1) Zb = /per phase where Zb is the base impedance
3I b
(KVb ) 2
= ()
MVA b
(3) Therefore,
Zpu x 100 = Z%
1
Zb (KV)2
MVA
1
Zpu MVA
(KV) 2
KVb old
Note: ( ) = 1 for this course hence,
KVb new
MVA b new
Zpu new = Zpu old . ( )
MVA b old
Example:
Given a transformer with the following specifications: 100MVA, 66KV/12KV, 0.1 pu
(10%)
MVA b new
Zpu new = Zpu old . ( )
MVA b old
200
= (0.1) ( )
100
= 0.2
(5) The PU system is used to extract the current that would flow when a fault
occurs.
1 pu
System 1
Zpu
Therefore,
Vpu 1
Isc = ( )= ( ) (pu) since Vpu = 1
Z pu Z pu
1
MVAsc pu = Vpu . Isc pu = ( )
Z pu
When a fault occurs, the symmetry of the system doesn’t change. The rotation, magnetic
and angular displacement must be constant. See figure 2.
120 120
120
C B
The most common fault is the Single Line to Ground Fault (SLG) which occurs over 90%
of the time.
Question:
From the diagram of figure 4, what should be the short-circuit rating on the breaker at E.
Note: The impedance between circuit breakers are negligible, therefore the rating is the
same for all breakers on the same bus.
Given:
G1 and G2 = 25MVA, 0.1ou
G3 = 20MVA, 0.1pu
Tf1 and tf2 = 50MVA, 10%
Lines AB, AC, BD, CD = j10Ω
Line B'C' = j0.75Ω
Steps:
(1) Let base value = 100MVA
→ Convert all values to a common base pu value.
Z given j10
Zpu = = = j0.92 pu
Zb 10.89
j0.75
Line B'C' = = 0.52pu
1.44
(2) Using 100MVA as the base, the 50MVA transformers must be converted to its
equivalent value.
MVA b new
Recall: Zpu new = Zpu old . ( )
MVA b old
100
= j0.1 ( ) = j0.2 pu
50
MVA b new
Again recall: Zpu new = Zpu old . ( )
MVA b old
100
Zpu (G1 & G2) = j0.1 ( ) = j0.4 pu
25
100
Zpu (G3) = j0.1 ( ) = j0.5 pu
20
The neutral of the generators is used as the common point for the diagram.
G1 G2 G3
j0.92 j0.92
B C
1 pu
j0.345
1 1
IF SC = MVAsc = ( )= ( ) = 2.89 pu
Z pu 0.345
Check: MVA = √3 VI
= √3 (33x103)(5071)
= 289
Additional work:
From diagram 2, find the fault level at A, B and C.
1.3.2 Example:
132kV 3500MVAsc
A
90 MVA
22.5%
33kV
B
23MVA
23%
11kV
C
1MVA
5%
415V
D
Question:
Find the short-circuiting rating on each bus A, B, C and D from the diagram in figure1.
Solution:
→ The source of supply from the plant is coming from the utility.
→ It is necessary to determine the short-circuit level at the plant, that is, the rating on the
132kV bus.
Steps:
1) Select the base value
MVA b 100
Zpu source = = = 0.0285 pu
MVA sc 3500
100
Zpu tf A&B = 0.225 ( )
90
≈ 0.25pu
100
Zpu tf B&C = 0.23 ( ) ≈ 1pu
23
100
Zpu tf C&D = 0.05 ( ) ≈ 5pu
1
1 pu
utility
0.0285 pu
132kV
A
0.25 pu 0.25 pu
33kV
B
1 pu 1 pu
11kV
C
5 pu
415V
D
A B C D
100MVA sc
1 1
MVASC A = ( )= ( ) = 35pu = 3500MVA
Z pu 0.0285
1
MVASC B= = 6.51pu = 651MVA
(0.0285 0.125)
1
MVASC C = = 1.53pu = 153MVA
(0.0285 0.125 0.5)
1
MVASC D = = 0.177pu = 17.7MVA
(0.0285 0.125 0.5 5)
IF A = 35 pu
651 x 106
IF B = = 11.4kA
3 x 33 x 103
153 x 106
IF C = = 8.03kA
3 x 11 x 103
17.7 x 106
IF D = = 24.6kA
3 x 415
132kV 3500MVAsc
A
j 1.09
33kV
B
j 0.12
11kV
C
415V
D
(KVb ) 2
Zb =
MVA b
(33) 2
Zb B = =10.89
100
(11) 2
Zb C = =1.21
100
Z given 1.09
Therefore, Zpu B = = = 0.1
Zb 10.89
0.12
And Zpu C = = 0.1
1.21
(1) Sectionalizers
In operation, it functions in the same way as a circuit breaker. However, it cannot
interrupt a fault or load current. It is designed to carry only load currents.
Old New
5 MVA
12%
10 MVA
9%
Loads
1.4.1 Example:
Question:
Determine the impedance of a 15MVA reactor which can be installed to limit the short-
circuit rating of the old system at 100 MVA.
Solution:
Let base value = 10MVA
x
10 pu
1
At F, = 10
Z pu
j0.12 j0.09
x
F
Z = 0.12 (0.09 + x)
1
10 =
0.12 //(0.09 x)
x = 0.51 pu
MVA new
Recall: xnew = xold . ( )
MVA old
15
= 0.51 ( )
10
= 0.765 pu
2.1 Introduction
R
120
120
120
The vectors remained balanced such that, |VR| = |VY| = |VB| and |IR| = |IY| = |IB|.
When a fault occurs, the vectors become unbalanced such that, |VR| |VY| |VB|.
In such a case, the unbalanced system can be replaced with an equivalent set of balanced
systems, which can be summed to give the unbalanced system. The normal mathematical
operations can then be performed on the equivalent balanced systems.
B R2
B1
R0
Y0
R 120 R1
= + 120 120
+ B0
120
120
120
Y Y1
Y2 B2
Faulted System +ve sequence -ve sequence zero sequence
And
IR = IR1 + IR2 + IR0
IB = IB1 + IB2 + IB0
IY = IY1 + IY2 + IY0
The ‘a’ Operator: a command to rotate a vector (or anything it acts on) 120 counter
clockwise.
a3 = 1360 = 1
Note:
-j = 1-90
but –a 1-120
since –a = (-1)(a)
= j2 (a)
= 1180(a)
= 1180(1120)
= 1300= 1-60
VB VR2
VB1
VR0
VR
VY0
120 VR1
= + 120 120
+ VB0
120
120
120
VY1
VY VY2 VB2
Faulted System +ve sequence -ve sequence zero sequence
Recall:
And
|VR1| = |VY1| = |VB1|
|VR2| = |VY2| = |VB2|
|VR3| = |VY3| = |VB3| …(4)
Substituting eqns (5), (6) and (7) into (1), (2) and (3)
VR = VR1 + VR2 + VR0 (using the red phase as the reference once the
VY = a2 VR1 + aVR2 + VR0 fault does not occur on the red phase)
VB = aVR1 + a2VR2 + VR0
In a matrix form,
VR 1 1 1 VR0
V =
1 a a VY0 …(8)
2
Y
VB 1 a a 2 V
B0
Symmetrical component transformation matrix
I R 1 1 1 I R0
I = 2
Y 1 a a I Y0
I B 1 a a 2 I
B0
1 1 1
1
T-1 = 1 a a 2
3 2
1 a a
VR0 1 1 1 VR
V = 1 1 a a 2 V
Y0 3 Y
VB0 2 VB
1 a a
I R0 1 1 1 I R
I = 1 1 a a 2 I
Y0 3 Y
I B0 2 I B
1 a a
1
VR0 = V0 = (VR + VY + VB) …(9)
3
In a balanced system, V0 = 0 no zero sequence voltages.
1
IR0 = (IR + IY + IB) …(9) …(10)
3
IR + IY + IB = IN
IO = 3 IN
IN = 3 IO
Note: IN is equal to zero if the system is not earthed through the neutral IO = 0.
2.2.1 Application
IB = 100 IR = 100 0 A
IY = 100 120 A
IB = 100 -90 A
IR = 100
Qu: Determine IR0, IR1 and IR2 .
Solution
I R0 1 1 1 I R
1 I
Recall: I Y0 = 1 a a 2 Y
3
I B0 2 I B
1 a a
1
IR0 = (IR + IY + IB)
3
1
= (100 0 + 100 120 + 200 -90)
3
= 41.3 -66.2 A
1
IR1 = (IR + aIY + a2IB)
3
1
= (100 0 + (1 120) 100 120 + (1 240) 200 -90)
3
= 96.98 20.1 A
1
IR2 = (IR + a2IY + aIB)
3
1
= (100 0 + (1 240) 100 120 + (1 120) 200 -90)
3
= 41.3 174 A
System 1
120
|IR1| = 96.98 IR2
IB2
66.2
20.1 + +
6
VB0 VY0 VR0
IY1 |IY2| = 41.3
+ve sequence -ve sequence zero sequence
For static equipment, the positive sequence value is equal to the negative sequence value.
2.5 Transformers
Zp Zs
Zm >> Zp or Zs
Vp Zm Vs
Z1
Z1 = Z2
Vp Vs Positive sequence = negative sequence
Zo
a P S a
b b
Close contacts at ‘a’ iff zero sequence currents can flow. The result is an earthed
star configuration.
Close contacts at ‘b’ iff zero sequence currents can circulate. The result is a delta
configuration.
Else leave both contacts open to result in an unearthed star configuration.
Zo
a P S a
b b
Zo
a P Io S a
b b
Io
Zo
a P S a
b b
Zo
a P Io S a
b b
Z Z
Z
Z Z
Z
Z Z
3Io 3Zn
Zn
Z
Z
Z
Z Z
Example:
A 3-phase star connected solidly earthed generator has it’s a-phase subjected to a solidly
grounded earth fault. Calculate the fault currents developed and the line-to-line voltages
attained due to a fault.
Diagram
IA Z X
A
IB Z
B
100V
Ea = 100V
100V
Ic Z
C
Analysis:
From figure 1, it can be seen that
IB = IC = 0
VAx = 0 (Z = 0)
Z1 Z2 Z0
I1 I2 I0
E V1 E V2 E V0
I A0 1 1 1 I A
1 I
Now I A1 = 1 a a 2 B
3
I A2 2 I C
1 a a
1
Io = IA = I1 = I2
3
From the relationship above, it can be seen that all SLG faults can be analysed by
connecting the three (3) networks in series.
I1
Z1
V1
E
I2
Figure 3: Connection of the three networks
Z2
V2
in series
E IA/3
I0
Z0
V0
IA E 100 0 o
= I1 = I2 = I0 = = = -j 62.5A
3 Z1 Z 2 Z 0 j1.6
IF A = IA = 3(-j62.5) = -j187.5 A
I A 1 1 1 I 0
Recall: I B = 2
1 a a I1
I C 1 a a 2 I
2
VA 1 1 1 V0
Recall: VB = 2
1 a a V1
VC 1 a a 2 V
2
V2 = EA – I2Z2
= 0 - (-j 62.5)(j0.5)
= - 31.25V
V0 = E – I0Z0
= 0 - (-j 62.5)(j0.1)
= - 6.25V
IA Z
A
EA
EC
EB
IB Z
B
IC Z
XC
Analysis:
From the diagram in figure 1, neglecting load currents:
IA = 0
IB + IC = 0
And VB = VC
I A0 1 1 1 I A 0
I = 1 a a 2
1 I
A1 3 B
I A2 2 I C I B
1 a a
1
IA0 = (0 + IB - IB) = 0
3
1
IA1 = (0 + aIB – a2IB)
3
1
IA2 = (0 + a2IB - aIB)
3
1
IA1 = - IA2 = IB (a – a2)
3
(a – a2) = j3
I1 = - I2 = j0.58IB
The above relationship indicates that the networks are connected in parallel as shown in
figure 2 below.
I1 X I2
X
N
N
EA 100
I1 = = = - j 66.7A
Z1 Z 2 j1.0 j 0.5
I2 = 66.7A
I1 = j0.58IB
- j66.7
IB = = -114.9A
j 6.55
IC = 114.9A
V1 = EA – I1Z1 VA
100 V B
= 100 + (j66.7)(j1.0) 33.33
AV
= 33.33V VC 66.66
100 V C
33.33
V2 = -I2Z2 VB
100
= 33.33V
Figure 3: Resultant System
IA X Y
A
IB VA
B
IC VB
C
VC
V0 1 1 1 VA
Recall: V1 = 1 a a 2 V
1
3 B
V2 2 VC
1 a a
VA
And V0 = V1 = V2 =
3
I1 X
I2 X
I0 X
Z1 Z2 Z0
V1 V2 V0
EA
Y
N
N
I1
Z1 V1
Figure 3: Simplified System
V2 Zp (Z0 // Z2)
100 V0
1000
I1 = = -j92.31
j (1.0) j (0.083)
V1 = V2 = V0 = 100 – I1Z2
=100 – (-j92.31)(j1.0)
=7.69V
V2
I2 = = -j15.38A
Z2
V0
I0 = = 76.9A
Z0
Question:
Each end of two parallel three phase 66kV feeders has a 3 star connected 100MW
synchronous generator connected. Each end is fed through a star-star solidly earthed
transformer. Z1, Z2 and Z0 per unit are j0.15, j0.1 and j0.03 respectively for each
generator and j0.4, j0.4 and j0.7 for each line.
The pu sequence reactances for the transformer at A is j0.15 and j0.1 for the transformer
at B. All star points are solidly earthed, except that of generator B which is unearthed. All
pu values are on the 100MVA base.
Calculate the fault current for a DLG fault at the feeder terminals of transformer A.
Solution:
Draw a diagram of the system described above. See Figure 1 below.
66kV
TF A TF B
A B
Considering the positive, negative and zero sequence equivalent diagrams. See figures 2,
3 and 4.
neutral(ref bus)
A B
Figure 2: Positive Sequence
Diagram
j0.15 j0.15
j0.4
j0.15 j0.1
TF TF
j0.4
neutral
Figure 3: Negative Sequence
A B Diagram
j0.1 j0.1
j0.4
j0.15 j0.1
TF TF
j0.4
j0.1 j0.1
j0.4
j0.15 j0.1
TF A TF B
j0.4
Each of the above networks can be further simplified to determine the respective currents
flowing through them.
For the positive sequence network, the network can be simplified as shown in figures 5
and 6 below.
I1
A B
j0.3 j0.45 V1
j0.18
The negative sequence diagram in figure 3 can be simplified as shown in figures 7 and 8.
I2
j0.25 j0.4
V2
j0.154
The zero sequence diagram in figure 4 can be simplified to that shown in figure 9.
I0
V0
j0.18
Now for a double-line to ground fault, the networks must be connected in parallel as
shown in figure 10.
Ip
I1
I2 I0
10
V0
j0.18 j0.154 j0.18 V1
V2 Figure 10: Connection of sequence
networks in parallel
I1
Ip
10
j0.18 j0.083
(Z2//Z0)
Figure 11
10
I1 = = -j3.8 pu
j (0.018 0.083)
I1 Z 0
I2 = = j2.05 pu
Z0 Z2
I1 Z 2
I0 = = j1.75 pu
Z0 Z2
Note: a check can be performed to verify the results obtained using the relationship
IA = I1+ I2 + I0 = 0
I R 1 1 1 I 0
Recall: I Y = 2
1 a a I1
I B 1 a a 2 I
2
IR = (I0 + I1 + I2) = 0
And IF = IY + IB = j5.26
100x 10 6
Iactual = Ipu x Ibase where Ibase = = 874.8A
3 x 66x 103
IF = j4601.5A
IY = 5003.9 23.37
IB = 5003.9 152.7
Further work:
For the same system described in the question above (section 2.9), calculate the fault
current assuming that the fault is a single line to ground fault.
Ans: IF = -j5.84 pu
Loads
B
IF
Figure1: Zoning
3.2 DETECTION V, I
CT Characteristic
Vsec
knee point
ankle point
Iexciting
Dr. Chandrabhan Sharma P a g e | 40
The University of the West Indies
EE36C – Industrial and Commercial Energy Systems
Knee point – point at which a 10% increase in secondary voltage produces a 50%
increase in current excitation.
I1 I 2' X2
I2
E2 Xe XL
Ie
N1
I2 = I1
N2
I2 = I2 + Ie
E2 = I2 (X2 + XL)
I2 I2 I2
CT error = %
I2 I2
3.3.1 Example:
Sec
voltage
120
100
80
60
40
E2 = 5(4 – Ie)
20
0 2 4 6 8 10 12 14 Figure 1
Ie
0.6A
Given:
C.T ratio = 500:5
X2 = 0.5
Find I2 and the CT error for XL = 4.5 (burden on secondary of CT), X1 = 400A and
IF = 4000mA.
Solution:
N1
E2 = (X2 + XL) ( I1 – Ie)
N2
1
E2 = (0.5 + 4.5)( (400) – Ie)
100
E2 = 5(4 - Ie)
0.6
CT error = = 15%
4
Note: If a fault occurs beyond the knee point, the CT ratio must be adjusted such that it
operates in the linear region.
(1) EM PT
V2 n2
=
V1 n1
V1 V2
For high voltages, the cost of insulation of windings is very high resulting in increased
cost and therefore the capacitor voltage transformer is used.
(2) Capacitance PT
(1) EM Attraction
F = K1I2 – K2
At threshold, F = 0
K1I2 = K2
K2
I=
K1
The rod moves in the direction of the side with the greatest current.
An IDMT relay is referred to as a split phase induction motor since the relay uses the
principle of induction to develop a torque in the rotor disk.
Figure 1
Operation:
When the relay detects a current, this current induces a magnetic flux in the core of the
relay. The shorting rings split this flux in two (2) and causes opposing fluxes to be
induced in the disk, causing rotation (hence the term “split phase”). See diagram in figure
2.
where - flux
2 1 i - current
F - force
F2 F1
i1 i 2
Figure 2
1 = Φ1sint
2 = Φ2sin (t + )
i2 d 2 Φ2cos(t + )
dt
F Φ1Φ2 sin
T = k1VI cos( - ) – k2
I = rms current
At balance point, T = 0
k1VI cos( - ) = k2
k2
VI cos( - ) = = constant
k1
1. Amplitude comparators
2. Phase comparators
An inherent Amplitude Comparator operates like a phase comparator if the inputs are
changed to the sum and differences of the original inputs.
A
R |A| |B|
B
A+B
R |A+B| |A-B|
A-B
3.7.1 Example
A k 1A + k 2B
B N1
input #1 B
R A
Ref
input #2
A
N2
B k 3A + k 4B
[k1|A| + k2|B| cos( - )]2 + [k2|B| sin( - )]2 = [k3|A| + k4|B| cos( - )]2 + [k4|B|
sin( - )]2 …(3)
B
2
k k k k B k 12 k 3 2
+ 2 1 22 3 2 4 cos( - ) + = 0 …(5)
k 2 k 2
A k2 k4 A 2 4
2
B B
Eqn (5) is of the form: + 2C cos( - ) + C2 = r2 …(6)
A A
(the equation of a complex plane)
k k k 3k 4
C = 1 22 = -C
2
2k k 4
k k 2
2
and C 2 – r2 = 1 2 3 2
k2 k4
k k k 2k 3
r = 1 42
2
2k k 4
j B
A
Region of operation
r of the relay
C
B
A
The relay only operates when the product of the inputs is positive.
tan tan
=
1 tan tan
1 tan tan = 0
1
tan = …(3)
tan
Imag k 2 | B | sin( )
For a complex number, tan = = …(4)
real k 1 | A | k 2 | B | cos( )
k 4 | B | sin( )
tan = …(5)
k 3 | A | k 4 | B | cos( )
k2k4 |B|2 sin( - ) = -k1 k3 |A|2 - k1 k4|A||B| cos( - ) – k2k3|A| |B| cos( - )
-k2k4|B| cos2( - )
2 k k k k B k k
B
+ 1 4 3 2
cos( - ) + 1 3 = 0 …(5)
A A
k2 k4 k2 k4
k k k k k k k k
Radius, r = 1 4 2 3
and centre, C = - 1 4 2 3
2k 2 k 4 2k 2 k 4
3.7.3 Summary
W2 + 2C cos + C2= r2
Such that,
3.7.4 Example:
Given a percentage differential relay which operates if the difference of the currents
entering or leaving the ____ exceeds 5% of the sum of these currents or 10% of the main
through current.
Determine the characteristic equation of this relay in the complex plane.
I1 – I2
10
100 I1 I 2
2
Solution:
I1 I 2
I1 – I2 > s ( )
2
3 I1 I 2
( ) = k3 ( | I1 | + k4 | I2 | (cos + jsin)
2 2
k 1k 4 k 2 k 3 k 1k 2 k 3 k 4
Using r = and C = -
k2 k4 k2 k4
2 2 2 2
2
s
1
r=
s
C= 2
2 2
s s
1- 1-
2 2
For s = 0.1,
2
I2 I
- 2C 2 cos + C2 = r2
I1 I1
Further work:
Assume you have a phase comparator operating at this characteristic. Determine the
equation for the phase comparator which would act as an amplitude comparator for
protection.
s
Ans: k1 = k4 = 1
2
s
k2 = k3 = 1
2
4.1 Introduction
Magnetic saturation
t1
I1 I
t1 saturation
Ip I
t = operating time
M = plug setting multiplier
Total = 0.4s
Discrimination time = 5s
If2
T
TMS = where T = actual operating time (secs)
Tm
Tm = operating time obtained from the 1.0 TMS characteristic
A B C D
IL = 100A
4.7.1 Question:
Coordinate each relay such that they back up each other. (Assume all CTs are connected
to a relay)
Assume that the available plug settings for the relay are: 2, 4, 6, 8, 10
Discrimination time = 0.5s
Steps:
(1) Start at the furthest relay D
Select the lowest TMS available = 0.1 (from characteristic curve)
100
Relay current = = 2.5A
40
For a fault at D,
Primary current 2000
PSMD = = = 12.5
Primary Operating current 4 x 40
Step 2:
For a fault at D,
C must back up in (0.27 + 0.5) = 0.77s
100
Relay current = = 1.67A
60
choosing a PSC = 2
2000
PSMC = = 16.67
2 x 60
0.77
TMSC = = 0.314
2.45
For a fault at C,
3000
PSMC = = 25
2 x 60
At location B,
100
Relay current = = 1A
100
choosing a PS = 2
For a fault at C,
3000
PSMB = = 15
2 x 100
1.19
TMSB = = 0.476
2.5
For a fault at B,
5000
PSMB = = 25
2 x 100
100
Current to relay B = = 0.8
120
PSA = 2
For a fault at B,
5000
PSMA = = 20.8
2 x 120
4.7.2 Modification
A B C D
IL = 300
600/5 500/5 300/5 200/5
IL = 100A
IL = 200
300
Now, PS = = 2.5
120
choose PS = 4
5000
PSMA =
4 x 120
200
At E, PS = =2
100
PSE = 4
The different earth fault relay configurations are shown in figures 1, 2 and 3 below.
R R R
OC Relays
Figure 1
EF Relay
R R
OC Relays
EF Relay Figure 2
ia IA
A
ib IB
B
ic IC
C
Figure 3
ir
EF Relay
From figure 3,
I A I Ae I B I Be I C I Ce
ia = ; ib = ; ic =
n n n
ir = ia + ib + ic
1 1
= (IA + IB + IC) - (IAe + IBe + ICe)
n n
1
Ir = (3Io) – Ifr
n
Transformer Protection
Differential Protection
IA IB If IA > IB operation
U
Ia Ib
Ic
Figure 4
Nr Nr
2 2
Ia Ib
No Ic
Figure 5
Nr N
Relay operates when (NoIc)2 ( I a r I b )2 …(2)
2 2
At the threshold,
Nr N
(NoIc)2 = Ia r Ib
2 2
2k
Ib = ( ) Ia
2k
Ib
Ib = Ia
operate
Restrains
2k
Ia = ( ) Ib
2k
operate
4.9.1 Question:
A 100kVA 2400/240 V step down transformer is to be differentially protected. Determine
Nr
the ratio if the relay is to tolerate a mismatch in current of up to 20% primary
No
current.
Given: CT ratios: 500/5 (primary) and 5000/5 (secondary).
Solution:
Rated Full Load Current
100
Primary = = 41.7 A
2.4
Related secondary = 417 A
Ia Ib I Ib
2 2
> a
k 2
x
If
(1 - x)
Rm V
Figure 6
Let If = primary fault setting for the differential relay (pick up current to the relay)
V
IR =
R
I I R
x = 1 s or (1 – x) = s x100
IR V
4.10.1 Question:
The neutral point of a 3 20MVA, 11kVA alternator is earthed through a 5 resistor. The
relay is set to operate for an out of balance of 1.5A. The CT has a ratio of 1000:5.
Determine:
1. the percentage of winding protected against earth fault (x)
2. what should be the minimum value of the earthing resistance to protect 90% of
the winding.
Solution:
1000
Current to relay, Is = 1.5 x = 300 A
5
Is R
% of winding unprotected = x 100
V
300 x 5 x 3 x100
= = 23.6 %
11 x 10 3
x = 76.4 %
Is R
10 = x 100
V
10 x 11 x 10 3
R= = 2.12
3 x 360 x100
5.1 Introduction
The following characteristics must be the same in all transformers:
1. Polarity
2. Phase Sequence
3. Ratio
4. P.U. Impedance
5. Vector Group
5.1.1 Polarity
Additive or Subtractive
Additive: For two transformers, the vector on outputs would be in the opposite direction.
Subtractive: The vector on outputs would be in the same direction.
a2 a1
supply
A2 A1
a2 A2, a1
A2,a1 a2
R C
A
B Y
B
Figure 2
From figure 2,
R must be connected to A
Y must be connected to B
B must be connected to C
5.1.3 PU Impedance
The pu impedance must be the same despite different MVA ratings.
1:1
V 0 V
30
Figure 3
Note:
The following conditions MUST be satisfied: Polarity
Phase Sequence
Vector Group
I1
Z1
I2 I1 + I2 = IL
i/p Z2 o/p V ZL
Z2 Z
I1 = . IL = 12 . IL
Z1 Z 2 Z1
Z1 2
and I2 = . IL
Z2
S1 Z
= 2
S2 Z1
E1 E 2
Ic (circulating current) =
Z1 Z 2
E1
I1
E2
IL IL
I2 Figure 5
Question:
A 500kVA single phase transformer with impedance 0.01 + j 0.05 pu is to share a load of
750kVA at 0.8 power factor lag with a 250kVA transformer of impedance 0.015 + j0.04
pu. Find the loading of each transformer when:
1. secondary voltages are both 400V
2. open circuit secondary voltages are 405V and 415V respectively.
Solution:
(1) Equal voltages = 400
Z1 = (0.01 + j0.05) pu
= 0.051 79
Z2 = (0.03 + j0.08) pu
= 0.085 69
Z1 + Z2 = 0.04 + j0.13
= 0.136 73
0.08569
S1 = (750 37)( )
0.13673
= 468.8 33 kVA
0.05179
S2 = (750 37)( )
0.13673
= 218 43 kVA
E1 E 2 10 / 400
Ic = = = 0.184 -73
Z1 Z 2 0.13673
415
Transformer #2 new loading = x (0.184 -73) + 218 43
400
= 1.04 x (0.184 -73) + 218 43
= 253.6 23.2 kVA
Note: Both transformers are slightly overloaded because they both have to provide power
to the circulating current.
110V dc
Fixed
Medium
1) Air
2) Oil
3) SF6
4) Vacuum
Slepian’s Theory
If the medium can be replaced faster than the rate of build-up of the voltage, then the
result is circuit interruption.
Vacuum
Fixed
movable
Advantages:
1. Highest Insulating strength known
2. Interruption at the first current zero
3. Low maintainence
Disadvantages:
1. If arc constriction occurs, circuit breaker is useless
2. Once contact melts, metal bridges form and circuit breaker is inoperative
Assume fault on circuit breaker occurs at its terminal as shown in the diagram of figure 3.
L CB
If = 0 L = lumped inductance
V
of circuit
Vm cos w t
C Vc
C = lumped capacitance
to ground
Figure 3
It is necessary to find the voltage across the circuit breaker to determine if interruption
will occur.
Note: the higher the value of o, the greater the probability that the circuit breaker fails.
Real situation
Vm cos w t wo w1
wo w1
Figure 4
fo = 1/(2LC)
7.1 Introduction
Ib
Rg
Ig earth rod
resistivity of the soil must be
very low to ensure that most
of the current flows to ground.
In rocky terrain,
Earth mat
Cu
0.116
Ib = where Ib = body (heart) current
T
T = duration of currents (relay operating time)
7.2 Design
I
I
A Ib
Rb
VAB Rg1 Rb
B
Rf/2 Rf/2
Rg2
A Rg1 B Rg2
I
Rg1
I
A
Rf Ib
Rg2 Rb
Rb
B
Rf Rf Rf
Rg3
A Rg1 B Rg2 Rg3
Take Rb 1000
0.116 1 ρ
ESTEP = [(1000 + 6s) ]V=
T 2Π r
116 + 0.17 s
Ensure ETOUCH !> …(1)
T
116 + 0.696 s
ESTEP !> …(2)
T
EMESH = touch voltage that arise in the center of the mesh. (See figure 3.)
Figure 3
Primary requirements:
1. Ground resistivity ()
2. Available fault current
3. Grid geometry
Eg.
3V
IF =
3R g +(R1 +R 2 +R 0 )+j(X1 +X 2 +X0 )
Decrement factor, D – utilised to compensate for the fact that the current is not steady.
1 1 X -2ωT
D= T+ 1-e
x/R
where T = relay operating time
T W R
= system frequency
X = system reactance
R = system resistance
dx
Assume fault current enters the
I
electrode and dissipates
r
uniformly into the grid.
I 1 1
= [ - ]
2 r x
ρI
Voltage at surface of electrode = Eo =
2Πr
ρI
Ex =
2Πx
Eo ρi
R= =
I 2Πx 2
1 ρ
=
2Π r
Question:
For a hemispherical electrode of radius 0.5m, = 10m and I = 100A, find the resistance
at the electrode surface and the potential gradient at distance 0.6m from the electrode
reference.
Answer:
ρ 10
R= = = 3.18
2Πr 2Π (0.5)
ρi 10 x 100
Ex = 2
= = 131.5 V/m
2Πx 2Π(0.5+0.6) 2
Radius = r
Burial depth = h
i. h is very large
ρI
ex =
4x 2
ρI
Eo =
4 r
ρI ρI
Ex = ,R=
4 x 4 r
image
rod electrode
h
x'
P2
x
h I
r
P1
electrode
ρI 1 1
Eo =
4Π r 2h
ρI r
= 1
4 2h
Eo ρ r
R= = 1
I 4 r 2h
ρI 2
EP2 =
4 x h2
2
dE P2 ρI 2x
The potential gradient at the surface = = eP2 =
4
x
3
dx 2
h2 2
Potential difference between surface of the sphere and the earth’s surface vertically above
(Touch voltage)
ρI 1 3
Eo – EV =
4 r 2h
Assumption: l >> d
i
Can break up rod into two hemispheres: shells and spheres
I 3l
R = 0.366 1
log ( )
d
l 2x(l 2 x )
2 2
I
ex = 1
d 2x(l x )
2 2 2
2x
Eo – Ex = 0.366 i log where I = current/length
d
X = horizontal distance
on earth’s surface
Tm Ta
log( 1)
234 Ta
I=A
33S
Where I = current in A
A = cross-sectional area of conductor in circular mils
(1974 circular mils = 1mm2)
S = duration of fault time in seconds
TA = ambient temperature C
Tm = maximum allowable temperature C
Step = 1m
Touch = 1m (not realistic but caters for worse case scenario)
I
Emesh = KmKi
L
Where Km = coefficient which takes into account the physical dimensions of the mesh
Ki = irregularity factor
L = length of burial conductor
116 0.17ρ. I
Emesh safety = = KmKi
t L
K m K i ρI t
L= …(1)
116 0.17 S
ρ ρ
R =
4r L
116 0.17 s
Iff Emesh < Etouch = Good design
t
1 D2 1 2 5 7 2n 1
km = ln + ln [ ( )( )( ) …( )]
2 16hd 4 6 8 2n 2
1 1 1 1 1
ks = [( ) + ( )+ + +…]
2n Dh 2D 3D
(8)(a) If the design is not good, decrease R by (1) increasing the grid area (r )
(2) increasing L (n )
Question:
An electric utility plans to install a new 132kV system to feed an industrial load. The
proposed area of the substation is a rectangle of dimensions 42m x 100m. The soil in the
area is non-homogenous with s = 300m and = 1316m.
The system has the following impedances: X = 40.5, X = 41.0, X0 = 100.
The protection is so designed that the cleaning time for a fault is 0.4s. Given that km =
0.568 and ks =0.814 and irregularity factor ki = 20.
Estimate taking account of a decrement factor of 1.3 and future growth of fault level to
125%.
(a) The minimum length of copper conductor required to keep touch and step
voltages within the same limits.
(b) The resistance of the earth mat using the estimated copper used in (a).
(c) Give a proposed layout of the grid calculating the actual length of copper
conductor used. Maximum grid spacing = 6m,length of copper earth rods
available = 3m.
(d) For the layout in (c) check whether the maximum step voltage developed
is within tolerable limits.
Solution:
K m K i ρI t
(a) Conductor length = L =
116 0.17 S
= 3092.5m
ρ ρ
(b) R =
4r L
1 1
= 1316 [ ]
4r 3092.5
r2 = area of substation = 42 x 100
r = 36.6m
R = 9.4
(c) Layout
Let spacing on 100m side = 4m
Let spacing on 42m side = 6m
116 0.7 s
Tolerable Vstep =
t
116 0.7(3000)
=
0.4
= 3503.8V
Types of Illumination:
1. Incandescence
2. Flourescent
3. Mercury Vapour
4. Metal Halide
5. Sodium Vapour
Note:
lumen watt
lm.s joule
1 foot candle 10.76 lux
1 foot lambert 1/ cd/ ft2
Illuminance (E)
The illuminance of a surface is the density of the luminous flux incident on a surface.
Luminance (L)
The density of the luminous intensity leaving a surface in a particular direction is the
luminance (L) of that surface.
Question:
Assume the unit sphere with 1cd source is translucent. It has the property of transmitting
80% of the luminous flux it receives and absorbs the remaining 20% (non – reflected).
Find the luminance, L and the quantity of light, Q.
Solution:
Luminous flux leaving the sphere = 4 (1)2 (0.8) = 3.2 lm
Solution:
(of which 200 goes up and 200 lumen goes down, sharing up the flux emitted by source
equally)
Φ 380π
Illuminance = =
A 2π(0.5) 2
= 760 lux (on lower hemisphere)
m = 285 = 570 lm / m
2r2
285π
Idist =
2π
= 142.5 CD
142.5 142.5
L= = = 181.44 cd/m
πr 2
π(0.5) 2
I
ISL E= (assume surface vertical)
D2
I
E
D2
I cosβ
E=
D2
Example:
2000cd
stop sign
200m
5m
50m
D
h
Ep = I () cos
D2
= I () cos
(h2 + d2 )
= I () cos
h2
Example:
A flat circular fixture of 15 cm diameter is mounted on a ceiling in a recreation room. Its
luminance (luminous flux) in the direction of a point P on a table is 40cd/cm2. Find its
intensity in the direction of P and the horizontal illuminance on the table at P.
D
2m
3m P
Luminance = ______I______
Area of viewing
I () = (L x A) cos
= (40 x 56.25) cos (56.3)
= 3918.5 cd.
E = I () cos
D2