Sei sulla pagina 1di 98

The University of the West Indies

EE36C – Industrial and Commercial Energy Systems

Chapter 1 – THE PER UNIT SYSTEM

1.1 Introduction

The per unit system is fundamental in the analysis of power systems, due to the large
amount of power transmitted, parameters such as voltage and power are usually in the
kilo or mega range. These values along with current and impedance are usually
represented as a percent of per unit of a base or reference value.

The per unit system has several advantages which include:


1) Calculations are simplified.
2) Equipment rating.
3) Provides a reference to voltages in the power system.
4) It is an international standard.

Usually base megavolt amperes (MVA) and base voltage in kilovolts are selected to
specify the base.

Vb
(1) Zb = /per phase where Zb is the base impedance
3I b
(KVb ) 2
= ()
MVA b

(2) Per Unit Conversion

Actual value of ' A'


Apu = where A can be either V, I or MVA
Base value of ' A'

Note: Apu is dimensionless

(3) Therefore,

Z given Zgiven .MVAb Vb


Zpu = = (since Zb = )
 kVb 
2
Zb 3I b

Zpu x 100 = Z%

Dr. Chandrabhan Sharma P age |1


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

(4) To compare two power systems with different MVAs

1
Zb  (KV)2 
MVA
1
Zpu   MVA
(KV) 2

KVb old 2 MVA b new


Zpu new = Zpu old ( ) .( )
KVb new MVA b old

KVb old
Note: ( ) = 1 for this course hence,
KVb new

MVA b new
Zpu new = Zpu old . ( )
MVA b old

Example:
Given a transformer with the following specifications: 100MVA, 66KV/12KV, 0.1 pu
(10%)

If the base value chosen is 200, then

MVA b new
Zpu new = Zpu old . ( )
MVA b old
200
= (0.1) ( )
100
= 0.2

(5) The PU system is used to extract the current that would flow when a fault
occurs.

1 pu
System 1 

Zpu

Figure 1: Resultant system


F
Isc
(pu)

Dr. Chandrabhan Sharma P age |2


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

The result is a 1pu generator whose voltage is 1pu.

Therefore,

Vpu 1
Isc = ( )= ( ) (pu) since Vpu = 1
Z pu Z pu
1
MVAsc pu = Vpu . Isc pu = ( )
Z pu

(6) Convert the pu values to the actual values

Isc actual (Amps) = Isc pu x Ib

MVA sc pu = MVAsc pu x MVAb


1
=( ) x MVAb
Z pu
200 x 10 6
eg. Ibf =
3 x 12x 103

Dr. Chandrabhan Sharma P age |3


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1.2 Three Phase Fault Calculations

There are 2 types of faults:


(1) Symmetrical Fault (three phase balanced)
(2) Unsymmetrical/ asymmetrical fault (SLG, DLG, DL, 1xOC, 2xOC)

1.2.1 Symmetrical Faults

When a fault occurs, the symmetry of the system doesn’t change. The rotation, magnetic
and angular displacement must be constant. See figure 2.

120 120

120

C B

Figure 2: Symmetrical Fault

1xOC – 1 line open circuit (has no power)

The most common fault is the Single Line to Ground Fault (SLG) which occurs over 90%
of the time.

Note: If the system is unbalanced, the relationship V = IR does not hold.

Dr. Chandrabhan Sharma P age |4


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1.2.2 Circuit Breakers

Circuit breakers are needed:


(1) to isolate equipment for maintenance and
(2) to open for faults.

Figure 3: Transient Impedance Graph

x'' – for current flow within the first 3-4 cycles


x' - for current flow after 15 cycles
x - for current flow after 60 cycles

 x'' < x' < x

Dr. Chandrabhan Sharma P age |5


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1.3 Fault Calculations

Figure 4: Fault System

Question:
From the diagram of figure 4, what should be the short-circuit rating on the breaker at E.

Note: The impedance between circuit breakers are negligible, therefore the rating is the
same for all breakers on the same bus.

Given:
G1 and G2 = 25MVA, 0.1ou
G3 = 20MVA, 0.1pu
Tf1 and tf2 = 50MVA, 10%
Lines AB, AC, BD, CD = j10Ω
Line B'C' = j0.75Ω

Steps:
(1) Let base value = 100MVA
→ Convert all values to a common base pu value.

For the 33kV bus,


(KVb ) 2 332
Zb 33k = = = 10.89Ω
MVA b 100

MVA 100 x 106


Ib 33k = = = 1749.5A
3V 3 x 33 x 103
Vb
Zb = = 10.89 Ω
3I b

Dr. Chandrabhan Sharma P age |6


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Z given j10
 Zpu = = = j0.92 pu
Zb 10.89

For 12kV bus,


(KVb ) 2 12 2
Zb 12k = = = 1.44 Ω
MVA b 100

MVA 100 x 106


Ib 12k = =
3V 3 x12 x103

j0.75
Line B'C' = = 0.52pu
1.44

(2) Using 100MVA as the base, the 50MVA transformers must be converted to its
equivalent value.

MVA b new
Recall: Zpu new = Zpu old . ( )
MVA b old
100
= j0.1 ( ) = j0.2 pu
50

(3) Now the generators must be converted to its equivalent pu values.

MVA b new
Again recall: Zpu new = Zpu old . ( )
MVA b old

100
Zpu (G1 & G2) = j0.1 ( ) = j0.4 pu
25

100
Zpu (G3) = j0.1 ( ) = j0.5 pu
20

(4) Draw a single line diagram of the system (100MVA system)

The neutral of the generators is used as the common point for the diagram.

Dr. Chandrabhan Sharma P age |7


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

G1 G2 G3

j0.4 j0.4 j0.5


A

j0.92 j0.92

B C

j0.2 j0.52 j0.2


j0.92 j0.92
D

Figure 1: Single line diagram of the system in pu

(5)Collapse the system further and simplify.

1 pu

j0.345

Figure 2: Simplified single line diagram of the system

Dr. Chandrabhan Sharma P age |8


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1 1
IF SC = MVAsc = ( )= ( ) = 2.89 pu
Z pu 0.345

MVAsc = (2.89)(100) = 289MVA

ISC actual = Ipu x Ib


= 2.89 x 1749.5
= 5071A

Check: MVA = √3 VI
= √3 (33x103)(5071)
= 289 

 Additional work:
From diagram 2, find the fault level at A, B and C.

Answers: MVAA = 570, MVAB = MVAC = 198

Dr. Chandrabhan Sharma P age |9


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1.3.2 Example:
132kV 3500MVAsc
A

90 MVA
22.5%

33kV
B

23MVA
23%

11kV
C

1MVA
5%

415V
D

Figure1: Fault System

Question:
Find the short-circuiting rating on each bus A, B, C and D from the diagram in figure1.

Solution:
→ The source of supply from the plant is coming from the utility.
→ It is necessary to determine the short-circuit level at the plant, that is, the rating on the
132kV bus.

Steps:
1) Select the base value

Let base = 100MVA

MVA b 100
Zpu source = = = 0.0285 pu
MVA sc 3500

2) Convert the transformers impedance to pu

Considering the transformers between A and B,


MVAb = 100

Dr. Chandrabhan Sharma P a g e | 10


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

100
Zpu tf A&B = 0.225 ( )
90
≈ 0.25pu

Considering the transformers between B and C,


MVAb = 100

100
Zpu tf B&C = 0.23 ( ) ≈ 1pu
23

Considering the transformers between C and D,


MVAb = 100

100
Zpu tf C&D = 0.05 ( ) ≈ 5pu
1

3) Redraw the diagram with the equivalent pu values.

1 pu

utility

0.0285 pu

132kV
A

0.25 pu 0.25 pu

33kV
B

1 pu 1 pu

11kV
C

5 pu

415V
D

Figure2: Circuit for calculating the short-circuit levels

Dr. Chandrabhan Sharma P a g e | 11


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

4) Collapse the diagram into an equivalent circuit as shown in figure 3 below.

A B C D
100MVA sc

0.0285 0.125 0.5 5.0

Figure 3: Simplified diagram

1 1
MVASC A = ( )= ( ) = 35pu = 3500MVA
Z pu 0.0285

1
MVASC B= = 6.51pu = 651MVA
(0.0285  0.125)

1
MVASC C = = 1.53pu = 153MVA
(0.0285  0.125  0.5)

1
MVASC D = = 0.177pu = 17.7MVA
(0.0285  0.125  0.5  5)

5) Considering the short-circuit current, Isc.

IF A = 35 pu

MVA 3500 x 106


IB A = = = 15.3kA
3V 3 x 132 x 103

651 x 106
IF B = = 11.4kA
3 x 33 x 103

153 x 106
IF C = = 8.03kA
3 x 11 x 103

17.7 x 106
IF D = = 24.6kA
3 x 415

Dr. Chandrabhan Sharma P a g e | 12


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1.3.3 Example: Modified System (cables included)

132kV 3500MVAsc
A

j 1.09

33kV
B

j 0.12

11kV
C

415V
D

Figure 4: Modified System

It is necessary to convert the cable impedances into pu values.

Base value = 100MVA

(KVb ) 2
Zb =
MVA b
(33) 2
Zb B = =10.89
100

(11) 2
Zb C = =1.21
100

Z given 1.09
Therefore, Zpu B = = = 0.1
Zb 10.89

0.12
And Zpu C = = 0.1
1.21

Dr. Chandrabhan Sharma P a g e | 13


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1.4 Limiting Short Circuit Levels

(1) Sectionalizers
In operation, it functions in the same way as a circuit breaker. However, it cannot
interrupt a fault or load current. It is designed to carry only load currents.

(2) Installation of a reactor

Old New
5 MVA
12%

10 MVA
9%

Loads

1.4.1 Example:

j0.24 j0.24 j0.9


3.3 kV
x
10 pu

Question:
Determine the impedance of a 15MVA reactor which can be installed to limit the short-
circuit rating of the old system at 100 MVA.

Solution:
Let base value = 10MVA

j0.24 j0.24 j0.09

x
10 pu

Figure1: Single line diagram of the system

Dr. Chandrabhan Sharma P a g e | 14


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1
At F, = 10
Z pu

Therefore, we need to find the value of x for which Zpu F = 10.

Simplifying the equivalent circuit diagram of Figure 1:

j0.12 j0.09

x
F

Figure 2: Simplified Figure 1

Z = 0.12  (0.09 + x)
1
10 =
0.12 //(0.09  x)
x = 0.51 pu

MVA new
Recall: xnew = xold . ( )
MVA old
15
= 0.51 ( )
10
= 0.765 pu

1.4.2 Limitations of the reactor

(1) Voltage regulation


(2) Power factor depreciation – adding a large imaginary part (76.5% in the example)
(3) Losses – reactor has resistance

Dr. Chandrabhan Sharma P a g e | 15


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

CHAPTER 2 – SYMMETRICAL COMPONENTS THEORY

2.1 Introduction

The diagram of figure 1 below shows the case of a balanced fault.

 R
 120
120

120

Figure1: Balanced Fault

The vectors remained balanced such that, |VR| = |VY| = |VB| and |IR| = |IY| = |IB|.

When a fault occurs, the vectors become unbalanced such that, |VR|  |VY|  |VB|.

In such a case, the unbalanced system can be replaced with an equivalent set of balanced
systems, which can be summed to give the unbalanced system. The normal mathematical
operations can then be performed on the equivalent balanced systems.

The unbalanced system as shown in figure 2 can be replaced by:


1. A positive sequence system of three (3) balanced phasors of equal magnitude rotating
in the same direction as the original phasor system.

2. A negative sequence system of three balanced phasors rotated in the opposite


direction of the original system.

Dr. Chandrabhan Sharma P a g e | 16


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

3. A zero sequence system of three phasors of equal magnitude and direction.

B R2
B1   
R0
Y0
R 120 R1  
=  + 120 120
+ B0
120 
120 
120
Y Y1
Y2 B2
Faulted System +ve sequence -ve sequence zero sequence

Figure2: Equivalent unbalanced system

From the diagram in figure 2,

VR = VR1 + VR2 + VR0


VB = VB1 + VB2 + VB0
VY = VY1 + VY2 + VY0

And
IR = IR1 + IR2 + IR0
IB = IB1 + IB2 + IB0
IY = IY1 + IY2 + IY0

The ‘j’ operator is a command to rotate a vector 90


j  190

The ‘a’ Operator: a command to rotate a vector (or anything it acts on) 120 counter
clockwise.

a  1120 = ej2/6 = 0.5 + j(3/2)

a2 = 1240 = - 0.5 - j(3/2)

a3 = 1360 = 1

Dr. Chandrabhan Sharma P a g e | 17


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Note:
-j = 1-90
but –a  1-120
since –a = (-1)(a)
= j2 (a)
= 1180(a)
= 1180(1120)
= 1300= 1-60

Dr. Chandrabhan Sharma P a g e | 18


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

2.2 Consider the unbalanced system as shown in figure 3 below.

VB VR2
VB1   
VR0
VR
VY0
120 VR1  
=  + 120 120
+ VB0
120 
120 
120
VY1
VY VY2 VB2
Faulted System +ve sequence -ve sequence zero sequence

Figure 3: Equivalent representation of a typical faulted system

Recall:

VR = VR1 + VR2 + VR0 …(1)


VB = VB1 + VB2 + VB0 …(2)
VY = VY1 + VY2 + VY0 …(3)

And
|VR1| = |VY1| = |VB1|
|VR2| = |VY2| = |VB2|
|VR3| = |VY3| = |VB3| …(4)

From the positive sequence,


VY1 = a2 VR1
VR1 = a VR1 …(5)

From the negative sequence,


VY2 = a2 VR2
VB2 = a VB2 …(6)

From the zero sequence,


VR0 = VY0 = VB0 …(7)

Substituting eqns (5), (6) and (7) into (1), (2) and (3)

 VR = VR1 + VR2 + VR0 (using the red phase as the reference once the
VY = a2 VR1 + aVR2 + VR0 fault does not occur on the red phase)
VB = aVR1 + a2VR2 + VR0

Dr. Chandrabhan Sharma P a g e | 19


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

In a matrix form,

VR  1 1 1  VR0 
V  =    
1 a a  VY0  …(8)
2
 Y
VB  1 a a 2  V 
   B0 
 Symmetrical component transformation matrix

I R  1 1 1  I R0 
I  =  2
  
 Y 1 a a  I Y0 
I B  1 a a 2  I 
   B0 

From inversion, we obtain

1 1 1 
1  
T-1 = 1 a a 2 
3  2 
1 a a 

VR0  1 1 1  VR 
V  = 1 1 a a 2  V 
 Y0  3    Y
VB0   2  VB 
1 a a 

I R0  1 1 1  I R 
I  = 1 1 a a 2  I 
 Y0  3    Y
I B0   2  I B 
1 a a 

1
VR0 = V0 = (VR + VY + VB) …(9)
3
 In a balanced system, V0 = 0  no zero sequence voltages.

1
IR0 = (IR + IY + IB) …(9) …(10)
3

IR + IY + IB = IN
IO = 3 IN
IN = 3 IO

Note: IN is equal to zero if the system is not earthed through the neutral  IO = 0.

Dr. Chandrabhan Sharma P a g e | 20


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

2.2.1 Application

IB = 100 IR = 100  0 A
IY = 100  120 A
IB = 100  -90 A
IR = 100
Qu: Determine IR0, IR1 and IR2 .

IY = 200 Figure 4: System 1

Solution

I R0  1 1 1  I R 
  1   I 
Recall: I Y0  = 1 a a 2   Y
3  
I B0  2 I B 
1 a a 

1
IR0 = (IR + IY + IB)
3
1
= (100  0 + 100  120 + 200  -90)
3
= 41.3  -66.2 A

1
IR1 = (IR + aIY + a2IB)
3
1
= (100  0 + (1 120) 100  120 + (1 240) 200  -90)
3
= 96.98  20.1 A

1
IR2 = (IR + a2IY + aIB)
3
1
= (100  0 + (1 240) 100  120 + (1 120) 200  -90)
3
= 41.3  174 A

See resultant diagram in figure 5 below.

Dr. Chandrabhan Sharma P a g e | 21


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

System 1 

120 
|IR1| = 96.98 IR2
IB2
66.2
20.1 + +
6
VB0 VY0 VR0
IY1 |IY2| = 41.3
+ve sequence -ve sequence zero sequence

Figure 5: Equivalent representation of System 1

Dr. Chandrabhan Sharma P a g e | 22


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

2.3 Synchronous Generators

 The positive sequence is not equal to the negative sequence.


 Xd, Xd and Xd are positive sequence.
 The generated emfs are of positive sequence only.
 The reference bus for both the positive and negative sequence networks is the
neutral of the generator.
 The reference bus for the zero sequence network is earth.
 There are no generated EMFs in the negative and zero sequence networks.

2.4 Cables and Lines

For static equipment, the positive sequence value is equal to the negative sequence value.

The zero sequence depends on the connection to earth.


Z0  (2-5) Z1

2.5 Transformers

Zp Zs

Zm >> Zp or Zs
Vp Zm Vs

Figure1: Equivalent Circuit

Refer all impedances either to the primary or secondary side

Z1
Z1 = Z2
Vp Vs Positive sequence = negative sequence

Figure2: Simplified Circuit

Dr. Chandrabhan Sharma P a g e | 23


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

2.5.1 Zero Sequence Network (Transformer)

Zo
a P S a

b b

Figure3: Diagram to determine the different transformer configurations


for the zero sequence network

 Close contacts at ‘a’ iff zero sequence currents can flow. The result is an earthed
star configuration.
 Close contacts at ‘b’ iff zero sequence currents can circulate. The result is a delta
configuration.
 Else leave both contacts open to result in an unearthed star configuration.

2.5.2 Different transformer configurations

Zo
a P S a

b b

Zo
a P Io S a

b b

Io

Dr. Chandrabhan Sharma P a g e | 24


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Zo
a P S a

b b

Zo
a P Io S a

b b

2.5.2.1 Static Loads

Z Z


Z

Z Z


Z

Dr. Chandrabhan Sharma P a g e | 25


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Dr. Chandrabhan Sharma P a g e | 26


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Z Z

3Io 3Zn

Zn
Z

Z
Z

Z Z

Dr. Chandrabhan Sharma P a g e | 27


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

2.6 Single Line to Ground Fault

Example:
A 3-phase star connected solidly earthed generator has it’s a-phase subjected to a solidly
grounded earth fault. Calculate the fault currents developed and the line-to-line voltages
attained due to a fault.

Given: Prefaulted LN voltage of generator as 100V, Z1 = j1, Z2 = j0.5, Zo = j0.1.

Diagram

IA Z X
A

IB Z
B
100V

Ea = 100V

100V

Ic Z
C

Figure1: System with a SLG Fault

Analysis:
From figure 1, it can be seen that
IB = IC = 0
VAx = 0 (Z = 0)

Z1 Z2 Z0
I1 I2 I0

E V1 E V2 E V0

positive sequence negative sequence zero sequence

Figure 2: Circuit diagrams of the positive, negative and zero sequences

I A0  1 1 1  I A 
  1   I 
Now I A1  = 1 a a 2   B
3  
I A2  2 I C 
1 a a 

Dr. Chandrabhan Sharma P a g e | 28


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1
Io = IA = I1 = I2
3
From the relationship above, it can be seen that all SLG faults can be analysed by
connecting the three (3) networks in series.

I1
Z1
V1

E
I2
Figure 3: Connection of the three networks
Z2

V2
in series
E IA/3
I0

Z0

V0

IA E 100 0 o
= I1 = I2 = I0 = = = -j 62.5A
3 Z1  Z 2  Z 0 j1.6

 IF A = IA = 3(-j62.5) = -j187.5 A

IB and IC can now be determined.

I A  1 1 1  I 0 
   
Recall: I B  = 2
1 a a  I1 
I C  1 a a 2  I 
   2

Considering the voltages,

VA  1 1 1  V0 
   
Recall: VB  = 2
1 a a  V1 
VC  1 a a 2  V 
   2

Dr. Chandrabhan Sharma P a g e | 29


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Expanding the above matrix gives the following,


VA = V0 + V1 + V2 …(1)
VB = V0 + a2V1 + aV2 …(2)
VC = V0 + aV1 + a2V2 …(3)

From the network in figure 3,


V1 = EA – I1Z1
= 100 0 o - (-j 62.5)(j10)
= 37.5V

V2 = EA – I2Z2
= 0 - (-j 62.5)(j0.5)
= - 31.25V

V0 = E – I0Z0
= 0 - (-j 62.5)(j0.1)
= - 6.25V

Substitute V1, V2 and V0 into eqns (1), (2) and (3)


VA = V0 + V1 + V2 = 0
VC = 60.23

VB = (- 9.37 – j59.5)


= 60.23  -98.9 8.9
o

VC = -9.37 + j59.5


= 60.23  -98.9
o
8.9

VAB = 60.23  -81.1


VBC = 119  -90 VB = 60.23

VCA = 60.23  -98.9 Figure 4: Resultant System

Dr. Chandrabhan Sharma P a g e | 30


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

2.7 Double Line Fault (Line to line)

IA Z
A
EA
EC

EB
IB Z
B

IC Z
XC

Figure1: System with a Double Line Fault

Analysis:
From the diagram in figure 1, neglecting load currents:
IA = 0
IB + IC = 0
And VB = VC

I A0  1 1 1  I A  0 
I  = 1 a a 2 
1 I 
 A1  3    B 
I A2   2  I C  I B 
1 a a 

1
IA0 = (0 + IB - IB) = 0
3

1
IA1 = (0 + aIB – a2IB)
3
1
IA2 = (0 + a2IB - aIB)
3

IA0 = 0 (no zero sequence network)

1
IA1 = - IA2 = IB (a – a2)
3
(a – a2) = j3

 I1 = - I2 = j0.58IB

Dr. Chandrabhan Sharma P a g e | 31


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

The above relationship indicates that the networks are connected in parallel as shown in
figure 2 below.

I1 X I2
X

Figure 2: Connection of the two networks


Z1 Z2
in parallel
V1 V2
EA

N
N

From the diagram above in figure 2,

EA 100
I1 = = = - j 66.7A
Z1  Z 2 j1.0  j 0.5

I2 = 66.7A

I1 = j0.58IB

- j66.7
IB = = -114.9A
j 6.55

 IC = 114.9A

Considering the voltages,

V1 = EA – I1Z1 VA
100 V B
= 100 + (j66.7)(j1.0) 33.33
AV
= 33.33V VC 66.66
100 V C
33.33

V2 = -I2Z2 VB
100

= 33.33V
Figure 3: Resultant System

Dr. Chandrabhan Sharma P a g e | 32


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

2.8 One line Open Circuit

IA X Y
A

IB VA
B

IC VB
C

VC

Figure 1: System with a One Line Open Circuit Fault

From inspection, IA = 0 and


VB = VC = 0

V0  1 1 1  VA 
 
Recall: V1  = 1 a a 2  V 
1
3   B
V2  2  VC 
1 a a 

VA
And V0 = V1 = V2 =
3

I1 X
I2 X
I0 X

Z1 Z2 Z0
V1 V2 V0
EA

Y
N
N

Figure 2: Connection of the three sequence networks in parallel

Collapsing the system further to obtain Z0 and Z1. See Figure 3.

Dr. Chandrabhan Sharma P a g e | 33


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

I1
Z1 V1
Figure 3: Simplified System
V2 Zp (Z0 // Z2)

100 V0

1000
I1 = = -j92.31
j (1.0)  j (0.083)

V1 = V2 = V0 = 100 – I1Z2
=100 – (-j92.31)(j1.0)
=7.69V

 V2
I2 = = -j15.38A
Z2

 V0
I0 = = 76.9A
Z0

VA= 3V1 = 23.07V

Using these values, IA, IB and IC can be found.

Dr. Chandrabhan Sharma P a g e | 34


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

2.9 Double Line to Ground (DLG) Fault

Question:
Each end of two parallel three phase 66kV feeders has a 3 star connected 100MW
synchronous generator connected. Each end is fed through a star-star solidly earthed
transformer. Z1, Z2 and Z0 per unit are j0.15, j0.1 and j0.03 respectively for each
generator and j0.4, j0.4 and j0.7 for each line.

The pu sequence reactances for the transformer at A is j0.15 and j0.1 for the transformer
at B. All star points are solidly earthed, except that of generator B which is unearthed. All
pu values are on the 100MVA base.

Calculate the fault current for a DLG fault at the feeder terminals of transformer A.

Solution:
Draw a diagram of the system described above. See Figure 1 below.

66kV
TF A TF B
A B

Figure 1: Diagram of the Power System

Base value = 100MVA

Considering the positive, negative and zero sequence equivalent diagrams. See figures 2,
3 and 4.

Dr. Chandrabhan Sharma P a g e | 35


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

neutral(ref bus)

A B
Figure 2: Positive Sequence
Diagram
j0.15 j0.15
j0.4
j0.15 j0.1

TF TF
j0.4

neutral
Figure 3: Negative Sequence
A B Diagram
j0.1 j0.1
j0.4
j0.15 j0.1

TF TF
j0.4

reference Figure 4: Zero Sequence


A B Diagram

j0.1 j0.1
j0.4
j0.15 j0.1

TF A TF B
j0.4

Each of the above networks can be further simplified to determine the respective currents
flowing through them.

Dr. Chandrabhan Sharma P a g e | 36


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

For the positive sequence network, the network can be simplified as shown in figures 5
and 6 below.

I1
A B

j0.3 j0.45 V1
j0.18

Figure 5: Positive Sequence network Figure 6: Simplified Diagram

The negative sequence diagram in figure 3 can be simplified as shown in figures 7 and 8.

I2

j0.25 j0.4
V2
j0.154

Figure 7: Negative Sequence network Figure 8: Simplified Diagram

The zero sequence diagram in figure 4 can be simplified to that shown in figure 9.

I0

V0
j0.18

Dr. Chandrabhan Sharma P a g e | 37


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Figure 9: Simplified Zero Sequence Diagram

Now for a double-line to ground fault, the networks must be connected in parallel as
shown in figure 10.

Ip
I1
I2 I0
10
V0
j0.18 j0.154 j0.18 V1
V2 Figure 10: Connection of sequence
networks in parallel

Figure 10 can be further simplified to that in figure 11.

I1
Ip
10

j0.18 j0.083
(Z2//Z0)
Figure 11

I1 can now be calculated, from which I2 and I0 can be found.

10
I1 = = -j3.8 pu
j (0.018  0.083)

 I1 Z 0
I2 = = j2.05 pu
Z0  Z2

 I1 Z 2
I0 = = j1.75 pu
Z0  Z2

Note: a check can be performed to verify the results obtained using the relationship

IA = I1+ I2 + I0 = 0

IR, IY and IB can now be determined.

Dr. Chandrabhan Sharma P a g e | 38


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

I R  1 1 1  I 0 
   
Recall: I Y  = 2
1 a a  I1 
I B  1 a a 2  I 
   2

IR = (I0 + I1 + I2) = 0

IY = (I0 + aI1 + a2I2) = 5.7223.37 pu

IB = (I0 + a2I1 + aI2) = 5.27152.7 pu

And IF = IY + IB = j5.26

100x 10 6
Iactual = Ipu x Ibase where Ibase = = 874.8A
3 x 66x 103

IF = j4601.5A

IY = 5003.9 23.37

IB = 5003.9 152.7

 Further work:
For the same system described in the question above (section 2.9), calculate the fault
current assuming that the fault is a single line to ground fault.

Ans: IF = -j5.84 pu

Dr. Chandrabhan Sharma P a g e | 39


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Chapter 3 - Power System Protection

Loads
B

IF

Figure1: Zoning

3.1 Criteria for a Proper Protection System

1. Reliability  system must operate when called on.


2. Selectivity  operation in its prescribed zone.
3. Speed of Operation  the longer the fault is ‘on’, the greater the danger of fire.
4. Discrimination  must be able to distinguish between normal, overload and fault
load currents.

3.2 DETECTION  V, I

CT Characteristic

Vsec

knee point

ankle point

Iexciting
Dr. Chandrabhan Sharma P a g e | 40
The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Knee point – point at which a 10% increase in secondary voltage produces a 50%
increase in current excitation.

3.3 Equivalent Circuit of a Current Transformer (CT)

I1 I 2' X2
I2
E2 Xe XL
Ie

Figure 2: Equivalent circuit of transformer

N1
I2 = I1
N2
I2 = I2 + Ie

E2 = I2 (X2 + XL)

E2 = I2 - Ie (X2 + XL)


N
= (X2 + XL) ( 1 I1 - Ie)
N2

I2   I2  I2 
CT error  =   %
I2   I2  

3.3.1 Example:

Sec
voltage
120
100
80
60
40
E2 = 5(4 – Ie)
20

0 2 4 6 8 10 12 14 Figure 1
Ie
0.6A

Dr. Chandrabhan Sharma P a g e | 41


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Given:
C.T ratio = 500:5
X2 = 0.5 

Find I2 and the CT error for XL = 4.5 (burden on secondary of CT), X1 = 400A and
IF = 4000mA.

Solution:

N1
E2 = (X2 + XL) ( I1 – Ie)
N2

1
E2 = (0.5 + 4.5)( (400) – Ie)
100

E2 = 5(4 - Ie)

0.6
 CT error = = 15%
4

Note: If a fault occurs beyond the knee point, the CT ratio must be adjusted such that it
operates in the linear region.

Dr. Chandrabhan Sharma P a g e | 42


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

3.4 Potential Transformer (PT, VT)

(1) EM PT

V2 n2
=
V1 n1
V1 V2

For high voltages, the cost of insulation of windings is very high resulting in increased
cost and therefore the capacitor voltage transformer is used.

(2) Capacitance PT

For voltages  132kV


C1 C1
V2 = . V1
C1  C 2
V1
C2 Voutput
V2

3.5 Protection relays

(1) EM Attraction

F = K1I2 – K2
At threshold, F = 0
 K1I2 = K2
K2
I=
K1

Dr. Chandrabhan Sharma P a g e | 43


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

(2) Balance Beam

The rod moves in the direction of the side with the greatest current.

(3) Electromagnetic Induction Type (IDMT relay)

An IDMT relay is referred to as a split phase induction motor since the relay uses the
principle of induction to develop a torque in the rotor disk.

Figure 1

Operation:
When the relay detects a current, this current induces a magnetic flux in the core of the
relay. The shorting rings split this flux in two (2) and causes opposing fluxes to be
induced in the disk, causing rotation (hence the term “split phase”). See diagram in figure
2.

Dr. Chandrabhan Sharma P a g e | 44


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

where  - flux
2 1 i - current
F - force

F2 F1
i1 i 2
Figure 2

1 = Φ1sint
2 = Φ2sin (t + )

 = angle between 1 and 2

i1  d1  Φ1cost


dt

i2  d 2  Φ2cos(t +  )
dt

Net force = F = F2 – F1  (2 i1 - 1 i2)

F  Φ1Φ2 [sin (t + )cost + - sint cos(t +  )]

F  Φ1Φ2 sin

Fmax occurs at  = 90

Dr. Chandrabhan Sharma P a g e | 45


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

3.6 Current Voltage Relays

T = k1VI cos( -  ) – k2

Where V = rms voltage

I = rms current

 = angle between V and I

 = angle for maximum torque

At balance point, T = 0

k1VI cos( -  ) = k2

k2
VI cos( -  ) = = constant
k1

3.7 General Relay Equations

Relays are of two (2) types:

1. Amplitude comparators

2. Phase comparators

 An inherent Amplitude Comparator operates like a phase comparator if the inputs are
changed to the sum and differences of the original inputs.

 Similarly, an inherent Phase Comparator operates like an amplitude comparator if the


inputs are changed to the original inputs. See figures 1 and 2.

A
R |A|  |B|
B

Figure 1: An amplitude comparator

Dr. Chandrabhan Sharma P a g e | 46


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

A+B
R |A+B|  |A-B|
A-B

Figure 2: An amplitude comparator as a Phase comparator

3.7.1 Example

A k 1A + k 2B
B N1

input #1 B


R  A

Ref
input #2
A
N2
B k 3A + k 4B

Figure 3: A comparator network

General equations for the inputs with A as reference:

Input #1  k1|A| + k2|B| [cos( - ) + j sin( - )] …(1)

Input #2  k3|A| + k4|B| [cos( - ) + j sin( - )] …(2)

Where k1, k2, k3 and k4 are design constants.

Amplitude Comparator (R)

At threshold, input #1 = input #2

 [k1|A| + k2|B| cos( - )]2 + [k2|B| sin( - )]2 = [k3|A| + k4|B| cos( - )]2 + [k4|B|
sin( - )]2 …(3)

Rearranging eqn (3) gives,


(k12 – k32) |A|2 + 2(k1k2 – k3k4) |A| |B| cos( - ) + (k22 – k42) |B|2 = 0 …(4)

Dr. Chandrabhan Sharma P a g e | 47


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Dividing eqn (4) by (k22 – k42) |A|2 gives,

B
2
k k k k  B  k 12  k 3 2 
+ 2  1 22 3 2 4  cos( - ) +   = 0 …(5)
k 2 k 2 
A  k2  k4  A  2 4 

2
B B
Eqn (5) is of the form: + 2C cos( - ) + C2 = r2 …(6)
A A
(the equation of a complex plane)

Comparing coefficients for eqns (5) and (6),

 k k  k 3k 4 
 C =  1 22  = -C
2 
 2k  k 4 

 k k 2
2 
and C 2 – r2 =  1 2 3 2 
 k2  k4 

 k k  k 2k 3 
 r =  1 42 
2 
 2k  k 4 

j B
A

Region of operation
r of the relay
C

B
A

Figure 4: Region of relay operation

Dr. Chandrabhan Sharma P a g e | 48


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

3.7.2 R is a Phase Comparator

Input #1  k1|A| + k2|B| [cos( - ) + j sin( - )] …(1)

Input #2  k3|A| + k4|B| [cos( - ) + j sin( - )] …(2)

The relay only operates when the product of the inputs is positive.

Let  be the phase angle of input #1


Let  be the phase angle of input #2

Threshold for operation occurs when ( - ) =  90

 for threshold, tan( - ) = 

tan   tan 
 =
1  tan  tan 

 1 tan  tan  = 0

1
tan  = …(3)
tan 


Imag k 2 | B | sin(   )
For a complex number, tan  = = …(4)
 
real k 1 | A |  k 2 | B | cos(   )


k 4 | B | sin(   )
tan = …(5)
 
k 3 | A |  k 4 | B | cos(   )

Substitute eqns (4) and (5) in (3),

 k2k4 |B|2 sin( - ) = -k1 k3 |A|2 - k1 k4|A||B| cos( - ) – k2k3|A| |B| cos( - )
-k2k4|B| cos2( - )

Divide across by k2k4|A|2

2  k k   k k   B  k k  

B
+  1 4 3 2 
cos( - ) +  1 3  = 0 …(5)
A     A   
 k2 k4   k2 k4 

Dr. Chandrabhan Sharma P a g e | 49


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Equation (5) is in the form of a circle in the complex plane with

 k k   k k    k k   k k  
Radius, r =  1 4 2 3 
and centre, C = -  1 4 2 3 
       
 2k 2 k 4   2k 2 k 4 

3.7.3 Summary

The general equation of a relay is given by

W2 + 2C cos + C2= r2

Such that,

Amplitude comparator Phase comparator


k 1k 4  k 2 k 3    
k1 k 4  k 2 k 3
r
k2  k4
2 2
 
2k 2 k 4
k 1k 2  k 3 k 4    
k1 k 4  k 2 k 3
C -  
k2  k4
2 2
 
2k 2 k 4

Dr. Chandrabhan Sharma P a g e | 50


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

3.7.4 Example:
Given a percentage differential relay which operates if the difference of the currents
entering or leaving the ____ exceeds 5% of the sum of these currents or 10% of the main
through current.
Determine the characteristic equation of this relay in the complex plane.

I1 – I2

10

100 I1  I 2
2

Solution:

I1  I 2
I1 – I2 > s ( )
2

Set I1 – I2 = k1| I1 | + k2 | I2 | (cos - jsin)

3 I1  I 2
( ) = k3 ( | I1 | + k4 | I2 | (cos + jsin)
2 2

where  is the angle between I1 and I2.

Comparing coefficients gives,


s
k1 = - k2 = 1 and k3 = k4 =
2

k 1k 4  k 2 k 3 k 1k 2  k 3 k 4
Using r = and C = -
k2  k4 k2  k4
2 2 2 2

2
s
1  
r=
s
C=  2
2 2
s s
1-   1-  
 2  2

Dr. Chandrabhan Sharma P a g e | 51


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

For s = 0.1,

 r = 0.1004 and C = 1.004 

The equation now becomes,

2
I2 I
- 2C 2 cos + C2 = r2
I1 I1

 Further work:
Assume you have a phase comparator operating at this characteristic. Determine the
equation for the phase comparator which would act as an amplitude comparator for
protection.

s
Ans: k1 = k4 = 1
2

s
k2 = k3 = 1
2

Dr. Chandrabhan Sharma P a g e | 52


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Chapter 4 Over Current Relays

4.1 Introduction

Magnetic saturation
t1

I1 I

Figure 1: Relay Characteristic

There are four (4) types of relays:


1. Definite Time
2. Inverse Definite Minimum Time (IDMT) (most popular)
3. Very Inverse
Have been replaced by
4. Extremely Inverse static relays

4.2 The IDMT Relay Characteristic

t1 saturation

Ip I

Log(t) = C1 + C2 log M + C3 (log M)2

Where Cn = curve fitting coefficients

Dr. Chandrabhan Sharma P a g e | 53


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

t = operating time
M = plug setting multiplier

4.3 Over Current Protection

1. Non-directional time and current grading


2. Directional time and current grading

4.3.1 Non-directional time and current grading

Two(2) ways to protect a system:


1. Time grading
2. Current grading

Discrimination time between successive breakers is made up of:


1. Fault Clearance time of CB ( 0.153)
2. Finite contact gap ( 0.15)
3. Overshoot (saturation) ( 0.05)
4. Relay and CT tolerances ( 0.1)

Total = 0.4s
Discrimination time = 5s

4.3.2 Time grading

1.85 1.35 0.8 0.35

If2

4.3.3 Current grading

Ip4 Ip3 Ip2 Ip1

4000 3000 2000 1000

Dr. Chandrabhan Sharma P a g e | 54


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

4.4 Time Multiplier Setting (TMS)

This gives the actual operating time of the system where

T
TMS = where T = actual operating time (secs)
Tm
Tm = operating time obtained from the 1.0 TMS characteristic

4.5 Plug Setting (PS)

This indicates the minimum operating current.

This value can be determined in two (2) ways:


a) Actual values eg. 2, 4, 6, 8
4  Minimum operating current of the relay = 4A

b) As a percentage of CT secondary current eg. 100%, 200%, 500%


CT ratio 100/1  setting 150% = 150% of 1 = 1.5
CT ratio 5005  setting 150% = 150% of 5 = 7.5

4.6 Plug Setting Multiplier (PSM)

Primary current Actual current in relay


PSM = =
Primary Operating current Minimum Operating current

 Recall: Primary Operating Current = Actual current into relay x CT ratio

Dr. Chandrabhan Sharma P a g e | 55


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

4.7 Relay Co-ordination

A B C D

600/5 500/5 300/5 200/5

IL = 100A

6000 A 5000 A 3000 A 2000 A

Figure 1: System for relay co ordination

4.7.1 Question:
Coordinate each relay such that they back up each other. (Assume all CTs are connected
to a relay)

Station If (A) IL CT ratio PS TMS


A 6000 100 120 2 0.67
B 5000 100 100 2 0.476
C 3000 100 60 2 0.314
D 2000 100 40 4 0.1

Table 1: Relay Information and results obtained

Assume that the available plug settings for the relay are: 2, 4, 6, 8, 10
Discrimination time = 0.5s

Steps:
(1) Start at the furthest relay  D
Select the lowest TMS available = 0.1 (from characteristic curve)

For a load of 100A,

Dr. Chandrabhan Sharma P a g e | 56


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

100
Relay current = = 2.5A
40

Therefore, choosing the most appropriate PS from the set  PSD = 4

For a fault at D,
Primary current 2000
PSMD = = = 12.5
Primary Operating current 4 x 40

For a TMS = 1.0 and PSM = 12.5,


Operating time = 2.7s (from the characteristic curve)

Actual operating time of relay ‘D’ = 2.7 x 0.1 = 0.27s


Relay C must operate at (0.27s + discrimination time) to back up relay D.

Step 2:
For a fault at D,
C must back up in (0.27 + 0.5) = 0.77s
100
Relay current = = 1.67A
60
 choosing a PSC = 2

2000
PSMC = = 16.67
2 x 60

For a TMS = 1.0 and PSM = 16.67,


Operating time = 2.45s (from the characteristic curve)

0.77
TMSC = = 0.314
2.45

Dr. Chandrabhan Sharma P a g e | 57


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

For a fault at C,
3000
PSMC = = 25
2 x 60

For TMS = 1.0 and PSMC = 25,


Operating time for relay C = 2.2s
Actual operating time for fault at C = (2.2)(0.314) =0.69s

For relay B to back up relay C, relay B should operate in


= time for relay C to clear fault + discrimination time
= 0.69 + 0.5 = 1.19s

At location B,
100
Relay current = = 1A
100
 choosing a PS = 2

For a fault at C,
3000
PSMB = = 15
2 x 100

For a TMS = 1.0 and PSM = 15,


Operating time = 25s (from the characteristic curve)

1.19
TMSB = = 0.476
2.5

For a fault at B,

Dr. Chandrabhan Sharma P a g e | 58


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

5000
PSMB = = 25
2 x 100

For a TMS = 1.0 and PSM = 25,


Operating time = 2.2s (from the characteristic curve)
Actual operating time = 2.2 x 0.476 = 1.05s

Relay A to back up relay B, should operate in (1.05 + 0.5) = 1.55s

100
Current to relay B = = 0.8
120
 PSA = 2

For a fault at B,
5000
PSMA = = 20.8
2 x 120

Operating time (for TMS = 1.0) = 2.3


1.55
TSMA = = 0.67
2.3

4.7.2 Modification

A B C D
IL = 300
600/5 500/5 300/5 200/5

IL = 100A

IL = 200

Dr. Chandrabhan Sharma P a g e | 59


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

300
Now, PS = = 2.5
120
 choose PS = 4

5000
PSMA =
4 x 120

200
At E, PS = =2
100
 PSE = 4

Dr. Chandrabhan Sharma P a g e | 60


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

4.8 Earth Fault Relays

The different earth fault relay configurations are shown in figures 1, 2 and 3 below.

R R R
OC Relays

Figure 1
EF Relay

R R
OC Relays

EF Relay Figure 2

ia IA
A

ib IB
B

ic IC
C
Figure 3
ir

EF Relay

Dr. Chandrabhan Sharma P a g e | 61


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

From figure 3,

Let CT turns ratio = n

I A  I Ae I B  I Be I C  I Ce
ia = ; ib = ; ic =
n n n

ir = ia + ib + ic
1 1
= (IA + IB + IC) - (IAe + IBe + ICe)
n n

1
Ir = (3Io) – Ifr
n

4.9 UNIT PROTECTION

 Transformer Protection

 Differential Protection

 Mertz Price System

IA IB If IA > IB  operation
U

Ia Ib

Ic

Dr. Chandrabhan Sharma P a g e | 62


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Figure 4

Nr Nr
2 2
Ia Ib

No Ic

Figure 5

Relay operates when Ia  Ib

At the decision node, Ic = Ia – Ib …(1)

Nr N
Relay operates when (NoIc)2  ( I a  r I b )2 …(2)
2 2

Let Nr = kNo (0 < k < 1) …(3)

At the threshold,

Nr N
(NoIc)2 = Ia  r Ib
2 2

Substituting eqns (1) and (3) into (2) gives,

2k
Ib = ( ) Ia
2k
Ib
Ib = Ia
operate
Restrains

2k
Ia = ( ) Ib
2k
operate

Dr. Chandrabhan Sharma Ia P a g e | 63


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

4.9.1 Question:
A 100kVA 2400/240 V step down transformer is to be differentially protected. Determine
Nr
the ratio if the relay is to tolerate a mismatch in current of up to 20% primary
No
current.
Given: CT ratios: 500/5 (primary) and 5000/5 (secondary).

Solution:
Rated Full Load Current
100
Primary = = 41.7 A
2.4
Related secondary = 417 A

For a 20% mismatch, Ia = 0.8Ib


For threshold,
2k
Ib =   Ia …(1)
2k
2k
Ib =   (0.8 Ib) …(2)
2k

Solving equations (1) and (2)  k = 0.222


Ia  Ib I  Ib
> a
k 2

Ia  Ib I  Ib
2 2

> a
k 2

Dr. Chandrabhan Sharma P a g e | 64


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Problem with application of the system:


1. Unmatched CT characteristics
2. Tap changing
3. Inrush Magnetic Current
4. Zero Sequence Circuit

4.10 Stator Protection

x
If

(1 - x)

Rm V

Figure 6

Let If = primary fault setting for the differential relay (pick up current to the relay)

For the given conditions,


V
If = (1 - x)
R
V
Let If = Is = (1 – x)
R

Note: the relay operates for If > pick-up current (Is).

Dr. Chandrabhan Sharma P a g e | 65


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

V
IR =
R
 I  I R 
x = 1  s  or (1 – x) =  s x100 
 IR   V 

where (1 – x) = % winding unprotected

4.10.1 Question:
The neutral point of a 3 20MVA, 11kVA alternator is earthed through a 5 resistor. The
relay is set to operate for an out of balance of 1.5A. The CT has a ratio of 1000:5.
Determine:
1. the percentage of winding protected against earth fault (x)
2. what should be the minimum value of the earthing resistance to protect 90% of
the winding.

Solution:
1000
Current to relay, Is = 1.5 x = 300 A
5

Is R
% of winding unprotected = x 100
V
300 x 5 x 3 x100
= = 23.6 %
11 x 10 3
x = 76.4 %

However, we want to protect 90% of the winding  10 % unprotected

Is R
10 = x 100
V

10 x 11 x 10 3
R= = 2.12
3 x 360 x100

Dr. Chandrabhan Sharma P a g e | 66


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Chapter 5 Parallel Operation of Transformers

5.1 Introduction
The following characteristics must be the same in all transformers:
1. Polarity
2. Phase Sequence
3. Ratio
4. P.U. Impedance
5. Vector Group

5.1.1 Polarity
 Additive or Subtractive

Additive: For two transformers, the vector on outputs would be in the opposite direction.
Subtractive: The vector on outputs would be in the same direction.

a2 a1

supply

A2 A1

Figure 1: Configuration of two parallel transformers

a2 A2, a1

A2,a1 a2

Dr. Chandrabhan Sharma P a g e | 67


A1 A1A2 < supply A1 A1A2 > supply
Additive Subtractive
The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Dr. Chandrabhan Sharma P a g e | 68


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

5.1.2 Phase Sequence

R C

 A

B Y
B

Figure 2

From figure 2,
R must be connected to A
Y must be connected to B
B must be connected to C

5.1.3 PU Impedance
The pu impedance must be the same despite different MVA ratings.

5.1.4 Vector Group


There is a vector shift when transformers are paralleled ( 30). See figure 3.

1:1

V 0 V 
30

Figure 3

Dr. Chandrabhan Sharma P a g e | 69


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Note:
The following conditions MUST be satisfied: Polarity
Phase Sequence
Vector Group

5.2 Equal Ratios

Consider the diagram in figure 4 below.

I1

Z1

I2 I1 + I2 = IL

i/p Z2 o/p V ZL

Figure 4:Parallel connection of two single phase transformers

Z1 and Z2 are the leakage impedances of the transformer

V = I1Z1 = I2Z2 = ILZL


Z1Z 2
= ILZ12 where Z12 = Z1 // Z2 =
Z1  Z 2

Z2 Z
 I1 = . IL = 12 . IL
Z1  Z 2 Z1

Dr. Chandrabhan Sharma P a g e | 70


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Z1 2
and I2 = . IL
Z2

 the power output of each transformer is given by:


Z2 Z2
S1 = VI1 = VIL . = ST . where ST = total power (to the load)
Z1  Z 2 Z1  Z 2
Z1 Z1
S2 = VI2 = VIL . = ST .
Z1  Z 2 Z1  Z 2

S1 Z
= 2
S2 Z1

S1Z1 = S2Z2 = k where k is a constant

5.3 Unequal Ratios

Let the output of transformer 1 = E1


Let the output of transformer 2 = E2
Such that | E1| > | E2|

E1  E 2
Ic (circulating current) =
Z1  Z 2

 New Power output from tf #1 = E1 …(1)


New Power output from tf #2 = E2I2 – E2Ic …(2)
Eqn (1) + (2) = ST

Solve for Ic and define E1 and E2 in terms of pu. Refer to figure 5.

E1
I1

E2
IL IL
I2 Figure 5

Dr. Chandrabhan Sharma P a g e | 71


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Question:
A 500kVA single phase transformer with impedance 0.01 + j 0.05 pu is to share a load of
750kVA at 0.8 power factor lag with a 250kVA transformer of impedance 0.015 + j0.04
pu. Find the loading of each transformer when:
1. secondary voltages are both 400V
2. open circuit secondary voltages are 405V and 415V respectively.

Solution:
(1) Equal voltages = 400
Z1 = (0.01 + j0.05) pu
= 0.051  79

Z2 = (0.03 + j0.08) pu
= 0.085  69

Z1 + Z2 = 0.04 + j0.13
= 0.136  73

Load ST = 750 at 0.8 lag


= 750  37

0.08569
S1 = (750  37)( )
0.13673
= 468.8  33 kVA

0.05179
S2 = (750  37)( )
0.13673
= 218  43 kVA

Dr. Chandrabhan Sharma P a g e | 72


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

(2) Finding the circulating current

E1  E 2 10 / 400
Ic = = = 0.184  -73
Z1  Z 2 0.13673

415
Transformer #2 new loading = x (0.184  -73) + 218  43
400
= 1.04 x (0.184  -73) + 218  43
= 253.6  23.2 kVA

Power supplied by tf #1 from tf #2 = IcE1


= (0.184  -73) x 1.01x 500
= 93.15  -73

Power supplied by tf #1 = (468.8 33) – (93.15  -73)


= 502.6  43.3

Note: Both transformers are slightly overloaded because they both have to provide power
to the circulating current.

Dr. Chandrabhan Sharma P a g e | 73


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Chapter 6 CIRCUIT BREAKERS

110V dc

Fixed

Medium
1) Air
2) Oil
3) SF6
4) Vacuum

Figure1: Diagrams of Circuit Breakers

Slepian’s Theory

 If the medium can be replaced faster than the rate of build-up of the voltage, then the
result is circuit interruption.

Dr. Chandrabhan Sharma P a g e | 74


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Vacuum

Fixed
movable

Figure 2: Vacuum Circuit Breaker

Advantages:
1. Highest Insulating strength known
2. Interruption at the first current zero
3. Low maintainence

Disadvantages:
1. If arc constriction occurs, circuit breaker is useless
2. Once contact melts, metal bridges form and circuit breaker is inoperative

Dr. Chandrabhan Sharma P a g e | 75


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Single Frequency Oscillation

Assume fault on circuit breaker occurs at its terminal as shown in the diagram of figure 3.

L CB

If = 0 L = lumped inductance
V
of circuit
Vm cos w t
C Vc
C = lumped capacitance
to ground

Figure 3

It is necessary to find the voltage across the circuit breaker to determine if interruption
will occur.

Looking at the first current zero,


Applying Kirchoff’s Law,

Vm cost = L di/dt + Vc …(1)


Vc = 1/C  i dt or i = C dV/dt

Substitute eqn (2) in (1) gives,

LC (d2Vc / dt2) + Vc = Vm cost …(2)

Solving eqn (2) using the Laplace Transform gives,

Dr. Chandrabhan Sharma P a g e | 76


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Vc (s) = (o2Vm / o2 - 2) [(s / s2 + 2) - (s / s2 + o2)]

Taking the inverse LT gives,

Vc(t) = (o2Vm / o2 - 2) (cost - cosot)

Now, o2 >> 


 Vc(t) = Vm (cost - cosot)

Note: the higher the value of o, the greater the probability that the circuit breaker fails.

Real situation

Vm cos w t wo w1
wo w1

Figure 4

fo = 1/(2LC)

time =  /o = LC

Rate of rise of recovery voltage, RRRV = 2Vm /t kV/s

Dr. Chandrabhan Sharma P a g e | 77


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Chapter 7 SYSTEM EARTHING

7.1 Introduction

 Normal person can feel 1mA.


 For (10-25) mA  lose muscular control.
 At 100mA  Ventricular fibrillation (death)

Ib

Rg
Ig earth rod
resistivity of the soil must be
very low to ensure that most
of the current flows to ground.

Conduction  electrolytic process


 moisture content > 22% by weight

In rocky terrain,

Earth mat

Cu

0.116
Ib = where Ib = body (heart) current
T
T = duration of currents (relay operating time)

Dr. Chandrabhan Sharma P a g e | 78


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

7.2 Design

7.2.1 Touch Voltages

I
I
A Ib
Rb
VAB Rg1 Rb
B

Rf/2 Rf/2
Rg2
A Rg1 B Rg2

Figure 1: Condition for Touch Voltages

To decrease Ib, VAB must be reduced by reducing I or Rf/2 or Rg2.

7.2.2 Step Voltages

I
Rg1
I
A
Rf Ib

Rg2 Rb
Rb
B

Rf Rf Rf
Rg3
A Rg1 B Rg2 Rg3

Figure 2: Condition for Step Voltages

Take Rb  1000

Rf = 3s where s = soil resistivity at the surface.

Dr. Chandrabhan Sharma P a g e | 79


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Assuming the foot is equivalent to circular plate electrode,


For touch voltages,
Rf
Rh = Rb + = (1000 + 1.5s) 
2

For step voltages,


Rh = Rb + 2Rf = (1000 + 6s) 

0.116 116 + 0.17 s


ETOUCH = [(1000 + 1.5s) ]V=
T T

0.116 1 ρ
ESTEP = [(1000 + 6s) ]V=
T 2Π r

116 + 0.17 s
Ensure ETOUCH !> …(1)
T

116 + 0.696 s
ESTEP !> …(2)
T

EMESH = touch voltage that arise in the center of the mesh. (See figure 3.)

Figure 3

Dr. Chandrabhan Sharma P a g e | 80


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

7.3 EARTH MAT DESIGN

Primary requirements:
1. Ground resistivity ()
2. Available fault current
3. Grid geometry

(1) Ground resistivity ()

Eg.

Type of Soil Approximate  (m)


Wet organic 10
Moist 102
Dry 103
Bedrock 104

(2) IF for SLG

3V
IF =
3R g +(R1 +R 2 +R 0 )+j(X1 +X 2 +X0 )

Where V = prefault phase voltage


Rg = ground resistance to ground
R1, R2, R0 = positive, negative and zero sequence resistance

 Design for maximum fault current.

Decrement factor, D – utilised to compensate for the fact that the current is not steady.

Cycles (60Hz) Time (s) D


½ 0.08 1.65
6 0.10 1.25
15 0.25 1.1
>30 >0.5 1.0

Above the decrement factor (30 cycles) steady state is reached.

Dr. Chandrabhan Sharma P a g e | 81


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

1 1 X  -2ωT 
D= T+ 1-e
x/R
 where T = relay operating time
T  W R   
 = system frequency

X = system reactance

R = system resistance

(3) Grid Geometry

i. Grid burial depth


ii. Length and diameter of conductors
iii. Spacing between the conductors
iv. Duration of fault current
v. Proximity of fault electrode to the ground

7.4 Earthing Electrodes

(1) Hemispherical Electrode at the earth’s surface

dx
Assume fault current enters the
I
electrode and dissipates
r
uniformly into the grid.

Figure 4:Hemispherical Electrode at earth’s surface

Current density at a distance X from hemisphere = i


I
= (A/m2)
2 x 2

 Potential gradient at distance X across a hemispherical shell, dx:


Voltage drop = i dx
= I / 2x2 dx (V)

Dr. Chandrabhan Sharma P a g e | 82


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

 Potential gradient = I / 2x2 = ex (V/m)

 Vx = voltage drop from r to x


x I
=  dx
r 2 x 2

I 1 1
= [ - ]
2 r x

ρI
Voltage at surface of electrode = Eo =
2Πr

ρI
Ex =
2Πx

Eo ρi
R= = 
I 2Πx 2
1 ρ
=
2Π r

Question:
For a hemispherical electrode of radius 0.5m,  = 10m and I = 100A, find the resistance
at the electrode surface and the potential gradient at distance 0.6m from the electrode
reference.

Answer:

ρ 10
R= = = 3.18
2Πr 2Π (0.5)

ρi 10 x 100
Ex = 2
= = 131.5 V/m
2Πx 2Π(0.5+0.6) 2

Dr. Chandrabhan Sharma P a g e | 83


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

7.5 Spherical Electrode

Radius = r
Burial depth = h

i. h is very large
ρI
ex =
4x 2

ρI
Eo =
4 r

ρI ρI
Ex = ,R=
4 x 4 r

ii. h is finite such that h >> r

image
rod electrode

h
x'
P2
x

h I

r
P1
electrode

Potential at P1 due to both electrodes,


ρI  1 1 
EP1 =   
4  x1 x 

For a point on the surface of the electrode,


(x1 = r , x = 2h)

ρI  1 1 
Eo =   
4Π  r 2h 

Dr. Chandrabhan Sharma P a g e | 84


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

ρI  r 
= 1  
4  2h 

Eo ρ  r 
R= = 1  
I 4 r  2h 

Using P2 to find the step voltage,

ρI 2
EP2 =
4 x  h2
2

dE P2 ρI 2x
The potential gradient at the surface = = eP2 =
4
x 
3
dx 2
 h2 2

Potential at the earth’s surface vertically above (x = 0),


ρI 2
EV =
4 h

Potential difference between surface of the sphere and the earth’s surface vertically above
(Touch voltage)

ρI  1 3 
Eo – EV =   
4  r 2h 

Dr. Chandrabhan Sharma P a g e | 85


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

7.6 Rod Electrode

Assumption: l >> d
i
Can break up rod into two hemispheres: shells and spheres

I 3l
R = 0.366 1
log ( )
d
l 2x(l 2  x )
2 2

I
ex = 1
d 2x(l  x )
2 2 2

2x
Eo – Ex = 0.366 i log where I = current/length
d
X = horizontal distance
on earth’s surface

Dr. Chandrabhan Sharma P a g e | 86


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

7.7 EARTH MAT DESIGN

1. Determine the soil characteristics.


2. Determine the maximum possible fault current (SLG)
3. Preliminary design of earth mat
4. Calculate the resistance of the mat in (3)
5. Calculate the maximum grid potential rose
6. Calculate the step voltages at periphery
7. Calculate the internal step and touch voltages
8. Refine the design so as to satisfy 5, 6 and 7 for safety
9. Construct the mat as per design (make sure measured values compares favourably
with the calculated values)
10. Review 5, 6, 7, 8 based on actual measurement.

7.8 Methodology for Earth Mat Design

(1), (2) Steps 1 and 2 completed.

(3) Preliminary Grounding Design.

(3.1) Determination of conductor size

Tm  Ta
log(  1)
234  Ta
I=A
33S

Where I = current in A
A = cross-sectional area of conductor in circular mils
(1974 circular mils = 1mm2)
S = duration of fault time in seconds
TA = ambient temperature C
Tm = maximum allowable temperature C

(3.2) Length of conductor required

Step = 1m
Touch = 1m (not realistic but caters for worse case scenario)

Laurent developed three (3) relationships:


Estep = (0.1  0.5)I
Etouch = (0.6  0.8)I
Emesh = I

Dr. Chandrabhan Sharma P a g e | 87


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

I
Emesh = KmKi 
L

Where Km = coefficient which takes into account the physical dimensions of the mesh
Ki = irregularity factor
L = length of burial conductor

116  0.17ρ. I
Emesh safety = = KmKi 
t L

K m K i ρI t
L= …(1)
116  0.17 S

Where S = resistivity on surface


 = average resistivity
t = relay operating time/shock time

(4) Resistivity of Mat (Grounding System)

 ρ ρ
R =   
 4r L 

Resistance To compensate for


assuming area the fact that it is not
was circular circular (removes
where ‘r’ is radius the errors)

(5) Maximum grid potential rise, E


E = IR where I = maximum SLG s/c current

116  0.17 s
Iff Emesh < Etouch =  Good design
t

(6) Voltage at periphery (assume  = s)


I 116  0.17 s
Estep max = kskm <  Good
L t

Dr. Chandrabhan Sharma P a g e | 88


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

(7) Let d = diameter of conductor


D = spacing
n = # of parallel conductors
h = burial depth

1 D2 1 2 5 7 2n  1
km = ln + ln [ ( )( )( ) …( )]
2 16hd  4 6 8 2n  2

1 1 1 1 1
ks = [( ) + ( )+ + +…]
 2n Dh 2D 3D

(8)(a) If the design is not good, decrease R by (1) increasing the grid area (r )
(2) increasing L (n )

(b) Space the conductors closer to each other (D )

(c) Increase s by addition of a high resistance surface  washed gravel ( > ¾ “)

Dr. Chandrabhan Sharma P a g e | 89


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Question:

An electric utility plans to install a new 132kV system to feed an industrial load. The
proposed area of the substation is a rectangle of dimensions 42m x 100m. The soil in the
area is non-homogenous with s = 300m and  = 1316m.

The system has the following impedances: X = 40.5, X = 41.0, X0 = 100.
The protection is so designed that the cleaning time for a fault is 0.4s. Given that km =
0.568 and ks =0.814 and irregularity factor ki = 20.

Estimate taking account of a decrement factor  of 1.3 and future growth of fault level to
125%.

(a) The minimum length of copper conductor required to keep touch and step
voltages within the same limits.
(b) The resistance of the earth mat using the estimated copper used in (a).
(c) Give a proposed layout of the grid calculating the actual length of copper
conductor used. Maximum grid spacing = 6m,length of copper earth rods
available = 3m.
(d) For the layout in (c) check whether the maximum step voltage developed
is within tolerable limits.

Solution:

3Vin 3 x 132 x 103


Estimate the fault lines in Amps…(SLG) = = = 1260A
XT 3 x 181.5

Design Fault current = 1260 x D x growth


= 1260 x 1.3 1.25
Idesign = 2047.5A

Dr. Chandrabhan Sharma P a g e | 90


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

K m K i ρI t
(a) Conductor length = L =
116  0.17 S

0.568 x 2 x 1316 x 2047.5 x 0.4


=
116  0.17(3000)

= 3092.5m

 ρ ρ
(b) R =   
 4r L 
1 1
= 1316 [  ]
4r 3092.5
 r2 = area of substation = 42 x 100
 r = 36.6m
 R = 9.4

Maximum Grid Potential Rise, E = IfR


= (2047.5)(9.4)
= 19.28kV

(c) Layout
Let spacing on 100m side = 4m
Let spacing on 42m side = 6m

Then the length of Cu needed on Grid:


 100   42 
  142 +   1100 = 1892m
 4   6 
(short of 3092.5,  change spacing on sides and recalculate)
 3092.5  1892 
Length of Cu still needed =    400
 3 
Note: use 10% more (safety factor to ensure extra protection)

Dr. Chandrabhan Sharma P a g e | 91


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Therefore, the number of earth rods = 440


 length of Cu actually utilised = 1320 + 1892 = 3212m

(d) Checking Touch and Step Voltages


I
Maximum Estep = kiks   
L

 0.814 x 2.0 x 1316 x 2047.5


=  = 1365.7V
 3212 

116  0.7 s
Tolerable Vstep =
t
116  0.7(3000)
=
0.4
= 3503.8V

Figure 5: Earth Mat

Dr. Chandrabhan Sharma P a g e | 92


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Chapter 8 ILLUMINATION ENGINEERING

Types of Illumination:
1. Incandescence
2. Flourescent
3. Mercury Vapour
4. Metal Halide
5. Sodium Vapour

Entities in Illumination Engineering

Symbol Concept English Unit SI unit


I Luminous intensity Candela (cd) Candela
 Luminous flux lumen (lm) Lumen
E Illuminance lumen foot candle /ft2 (lfc) lm/m2 , lux (lx)
M Luminous exitance lm/ ft2 lm/m2
L Luminance cd/ ft2 (foot lambert) cd/m2
Q Quantity of light lm.s lm.s

Note:
lumen  watt
lm.s  joule
1 foot candle  10.76 lux
1 foot lambert  1/ cd/ ft2

Dr. Chandrabhan Sharma P a g e | 93


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Luminous Intensity (I)


The intensity of a spermecetic candle of a particular weight burning at a particular rate
emits a luminous intensity = 1 cd.

Luminous flux ()


A luminous flux of 1 lumen is the rate at which the luminous intensity on a surface of
area 1m2 which is placed 1m from a luminous source of 1cd.

 = AI/D2 (lm) where A = area of surface (m2)


D = distance from source (m)
I = candela

If A is kept constant, lum flux ()  1/D2

Illuminance (E)
The illuminance of a surface is the density of the luminous flux incident on a surface.

E = /A (lux) (lm/ m2)

Luminous exitance (M)


This is the flux density which leaves the surface.

M = reflected/ transmitted x reflective index

Luminance (L)
The density of the luminous intensity leaving a surface in a particular direction is the
luminance (L) of that surface.

L = luminous intensity (in a particular direction) / area of viewing (cd/m2)

Dr. Chandrabhan Sharma P a g e | 94


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Question:
Assume the unit sphere with 1cd source is translucent. It has the property of transmitting
80% of the luminous flux it receives and absorbs the remaining 20% (non – reflected).
Find the luminance, L and the quantity of light, Q.

Solution:
Luminous flux leaving the sphere = 4 (1)2 (0.8) = 3.2 lm

Luminous exitance (M) = 3.2 / 4 = 0.8 lm/m2

L = 0.8/r2 = (0.8/) cd/m2

Quantity of Light, Q = luminous energy ( in 1 min)


= flux x 60s
= 3.2 x 60
= 192 /min
Question:
The upper hemisphere of a glass globe is silvered on the inside so that 90% of the lumen
incident on it is reflected to the lower hemisphere. The latter is translucent glass and has a
transmittance of 75% and an absorbance of 25%. The sphere has a radius of 0.5m with a
100cd source at its center. The lamp emits lumens uniformly in all directions as does the
lower hemisphere. Find the illuminance on the inside of the lower hemisphere, the
luminance exitance and luminance on outside of the lower hemisphere.

Solution:

1. Luminous flux emitted by source

 = (4) (100) = 400 lm

(of which 200 goes up and 200 lumen goes down, sharing up the flux emitted by source
equally)

Total flux to lower hemisphere

= (200 ) + (0.9 x 200 )


= 380 lm

Dr. Chandrabhan Sharma P a g e | 95


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Φ 380π
Illuminance = =
A 2π(0.5) 2
= 760 lux (on lower hemisphere)

2. Luminance exitance (m)

luminous flux transmitted = (0.75) (380)


= 285 lm

m = 285 = 570 lm / m
2r2

3. L = luminous Intensity in particular direction


Area of viewing

285π
Idist =

= 142.5 CD

142.5 142.5
L= = = 181.44 cd/m
πr 2
π(0.5) 2

Inverse Square Law

I
ISL  E= (assume surface vertical)
D2

I
E 
D2

Now assume surface not vertical or perpendicular

I cosβ
E=
D2

Dr. Chandrabhan Sharma P a g e | 96


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Example:

2000cd

stop sign

200m

5m

50m

B= 16.7 (from geometry)

I cosβ 2000 cos16.7


E= = = 0.7 lux
D 2
152  502

Now from a horizontal plane,


D

h 

Ep = I () cos 
D2
= I () cos 
(h2 + d2 )
= I () cos 
h2

Dr. Chandrabhan Sharma P a g e | 97


The University of the West Indies
EE36C – Industrial and Commercial Energy Systems

Example:
A flat circular fixture of 15 cm diameter is mounted on a ceiling in a recreation room. Its
luminance (luminous flux) in the direction of a point P on a table is 40cd/cm2. Find its
intensity in the direction of P and the horizontal illuminance on the table at P.


D

2m 

3m P

Area of light surface = r2 = 56.25 cm2

Luminance = ______I______
Area of viewing

I () = (L x A) cos 
= (40 x 56.25) cos (56.3)
= 3918.5 cd.

E = I () cos 
D2

= (3918.5) cos 56.3


13
=167.24 lux

Dr. Chandrabhan Sharma P a g e | 98

Potrebbero piacerti anche