Sei sulla pagina 1di 14

Available online at www.sciencedirect.

com

ScienceDirect
Solar Energy 101 (2014) 117–130
www.elsevier.com/locate/solener

System analysis of a low-temperature solar process heat system


C. Lauterbach ⇑, B. Schmitt, K. Vajen
Institute of Thermal Engineering, University of Kassel, Kurt-Wolters-Strasse 3, 34125 Kassel, Germany

Received 26 May 2013; received in revised form 4 October 2013; accepted 14 December 2013
Available online 14 January 2014

Communicated by: Associate Editor Ursula Eicker

Abstract

Process heat generation is an unexploited application for solar thermal systems despite its large potential. Solar thermal systems can
achieve higher system yields in industrial applications compared to domestic ones. At the same time, systems can be more complex in
industrial applications because of the variety of heat consumers, hydraulic setups and temperature levels. In order to design and operate
solar process heat systems efficiently and to exploit the large potential, possible faults of such systems and their impact have to be eval-
uated. In this paper, an implemented solar process heat system is methodically analyzed based on monitoring data and simulations with a
validated model. Several faults are identified and their influence, as well as, the influence of a reduced load on the system yield is eval-
uated. The analysis shows that the reduced load is most influential and that the expected system yield can be reached if all faults are
eliminated. Further, the most important impact factors on the system performance are identified: the collector parameters (g0, a1)
and load characteristics (mass flow, temperature).
Ó 2013 Elsevier Ltd. All rights reserved.

Keywords: Solar heat for industrial processes; Monitoring; Model validation; Simulation; System performance

1. Introduction and heat consumers as well as components (especially col-


lectors) can be larger. Therefore, it is crucial to be aware of
Process heat generation is a rather unexploited applica- possible faults of such systems and their impact on the sys-
tion for solar thermal systems (STS) compared to domestic tem yield as the most important performance indicator.
applications like generation of hot water, space heating, or Some publications are available regarding the behavior
heating of swimming pools. Nevertheless, several studies and performance of solar process heat systems. Kutscher
for the use of solar heat for industrial processes determined and Davenport (1980) collected operating data of six SHIP
a large potential for this application (Schweiger et al., 2001; systems during 1979. The actual annual energy system effi-
Müller et al., 2004; Vannoni et al., 2008; Taibi et al., 2012; ciencies ranged from 8.1% to 19.7% which was between
Lauterbach et al., 2012). On the one hand, STS can achieve 25% and 50% of the predicted performance. This was
higher system yields in industry compared to the because the STS could not be fully utilized and caused by
mentioned domestic applications under certain boundary excessive thermal losses, but not due to failures of certain
conditions, like a low process temperature and constant components. Eskin (2000) states that the behavior of solar
load. On the other hand, systems for process heat genera- process heat systems strongly depends on the load profile,
tion are more complex, as the variety of hydraulic set ups nevertheless, the load profile was not varied in the pre-
sented simulation study to support the statement. Karagiorgas
et al. (2001) studied ten solar process heat installations in
⇑ Corresponding author. Tel.: +49 5618043890. Greece in the 1990s. The system utilization ratio (used/
E-mail address: solar@uni-kassel.de (C. Lauterbach). incident solar energy) as in Eq. (2)) of five systems for
URL: http://www.solar.uni-kassel.de.

0038-092X/$ - see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.solener.2013.12.014
118 C. Lauterbach et al. / Solar Energy 101 (2014) 117–130

Nomenclature

Aap collector field aperture area, m2ap T_DCF discharging loop flow temperature, °C
gchargecharging loop utilization ratio, % T_DCR discharging loop return temperature, °C
gsys system utilization ratio, % Tm average temperature of solar loop, °C
Gt global tilted irradiance, W/m2 T_SF solar flow temperature, °C
Ht Total irradiation on collector field (aperture), T_SR solar return temperature, °C
kWh ua specific heat transfer capacity rate (per m2 of
NC_Charge night cooling charging loop, kWh aperture area), W=ðm2ap KÞ
NC_Discharge night cooling discharging loop, kWh UA-value heat transfer capacity rate, W/K
Q_Charge heat quantity charging the store, kWh U-value heat loss coefficient, W/(m2K)
Q_Discharge heat quantity discharging the store, kWh V_ BW brewing water volume flow, m3/h
T_0.9 store temperature at 90% of store height, °C V_ C charging loop volume flow, m3/h
Ta ambient temperature, °C V_ DC discharging loop volume flow, m3/h
T_BWF brewing water loop flow temperature, °C V_ S solar loop volume flow, m3/h
T_BWR brewing water return flow temperature, °C Vstore heat store volume, m3
T_CF charging loop flow temperature, °C V_VVT volume variable volume tank, m3
T_col collector temperature, °C
T_CR charging loop return temperature, °C

which monitoring data was available ranged between 7.3% Up to now, no detailed analysis of a realized STS in
and 26.5% (average 18%) on a typical day of operation. In industry is available based on measurements and simula-
one case, the utilization ratio was low because of poor insu- tions with a validated model. Furthermore, the most
lation of heat store and an undersized solar heat exchanger. important factors that influence the performance of such
In case of another system, high heat losses occurred a system have neither been identified nor been quantified.
because the solar loop was not insulated. Finally, one sys- The objective of this paper is to identify possible faults that
tem was oversized which led to a low system utilization. may occur in an STS in industry and to evaluate their
System utilization ratios of 20.7% and 19.4% were found impact on its performance. In addition, the most important
for two annual monitoring periods of a STS at a brewery factors that influence the overall system performance are
in Germany (Wutzler et al., 2011). identified and their influence is evaluated. In addition, the
The system behavior and performance of large STS for paper describes the complex interaction between energy
domestic applications has been extensively studied in the efficiency measures (especially heat recovery) with the inte-
past. (Heimrath, 2004) performed a simulation-based gration of an STS in an industrial process.
analysis of solar system, heat distribution network, and An STS for process heat generation built at a brewery in
building for solar assisted space heating of multifamily Germany was analyzed as an example for this study. The
houses. Heimrath states that the design of the heat distri- performance of the system and its components was evalu-
bution network has the strongest thermal impact on the ated in detail enabling different faults which occurred dur-
efficiency of the STS. The author found that system-spe- ing operation to be identified and described. Due to these
cific parameters like e.g. UA-value of the charging and faults, the measured system yield was lower than the yield
discharging heat exchangers and inlet height of its return predicted in the design phase. A simulation model of the
can have an immense impact on the solar fraction which is system was developed. This was validated with measured
used as the target function. Croy et al. (2011) analyzed the data to evaluate the influence of each identified fault. A
state of the art of large STS for DHW and district heating global and a local sensitivity analysis were performed to
built in Germany between 1988 and 2005. A failure that identify and evaluate the most important factors that
occurred in about 10% of the systems was a reduced per- impact on the overall system performance.
formance of the heat exchangers. The authors also ana-
lyzed the long term performance of eight STS after 7 – 2. Pilot plant at a brewery
12 years of operation and compared it to the design value.
The system yield of these systems was between 38% and The studied brewery in Germany produces approxi-
90% (63% in average) of its design values. The authors’ mately 6200 m3 of beer per year and has an annual final
state that a deviation of the real load from the load energy consumption of 5 GWh. About 80% of the energy
expected during design was a major reason for the low is supplied by natural gas and used to provide process heat,
performance. They conclude that accurate determination hot water and space heating. All heat consumers are con-
of the load is a crucial issue for predicting the perfor- nected to a steam network that is fed by a boiler with a
mance of a STS. nominal capacity of 2.6 MWth. The production process is
C. Lauterbach et al. / Solar Energy 101 (2014) 117–130 119

operated in one shift on five days per week. During sum- Therefore, water from the lower part of the tank is
mer, the amount of produced beer increases by a factor heated up from 80 to 98 °C and stored in the upper part
of 1.3 compared to the winter period. Based on their pro- of the tank. The hot water from the upper part of the fixed
duction capacity, technical installations and energy con- volume tank is then taken to preheat the wort and fed into
sumption, the brewery is a representative example of a the variable volume tank afterwards. This modification
small to medium enterprise in the central European brew- resulted in a more efficient heat recovery since the waste
ing sector. heat is utilized at a higher temperature level. This has
two consequences: (i) steam for heating up the wort before
2.1. System description boiling is saved, and (ii) the available amount of hot water
from heat recovery is reduced, so that it can be provided by
The developed concept for the brewery combines an solar energy at a lower temperature level. Thus, an STS
energy efficiency measure with an improved heat recovery was integrated to heat up cold water of 15 °C that is fed
and the utilization of solar thermal energy. The initial state into the variable volume tank, depending on its filling level.
of the hot water supply of the brewhouse is shown in Fig. 1. This design leads to a simple system control and high
Two tanks are installed for the hot water supply of the expected solar gains.
whole brewery. One has a constant fluid volume of The hot water supply of the brewhouse was modeled in
50 m3, in the other it is possible to store a variable amount the transient system simulation software TRNSYS 17
of water up to 50 m3. This is necessary because of the fluc- (Klein et al., 2009) by creating profiles for all hot water
tuating streams of incoming hot water from heat recovery streams of the production process and simulation of both
and outgoing water to supply several process steps. The tanks. The design approach in the simulation study was
temperature level in the fixed volume tank is at 80 – 90 °C to determine the maximum amount of energy that can be
and slightly higher compared to the variable volume tank delivered by the STS while avoiding stagnation in summer.
at 70 – 80 °C. The hot water needed for mashing and lau- The simulation with the developed load profiles showed
tering is provided by the fixed volume tank. To supply the that a large amount of hot water is required at night time
required temperature, the water is cooled down by mixing and during morning hours. Therefore, the variable volume
with cold water of 10 °C. Additionally, this tank supplies tank has to be fed with solar heated water particularly dur-
the bottle filling hall with hot water of 80 °C, used for ing the early morning hours. Hence it was decided to install
cleaning of installations and filters. an additional solar heat store for the STS, as shown in
The tanks are fed by two heat recovery installations. Fig. 3. This design ensures a high specific system yield.
During the boiling and cooling process steps, brewing The collector field aperture area is Aap = 155.5 m2 and a
water at 10–15 °C is heated up to 80 °C by heat recovery volume of the solar heat store is Vstore = 10 m3.
and fed into the variable volume tank. In order to increase The collector array consists of 22 Thüsol S 7.69
energy efficiency, wort boiling at atmospheric pressure was (ITW, 2009) collectors with a gross area of 169 m2 (aper-
replaced by an efficient vacuum boiling technology that led ture area = 155.5 m2). The roof has an orientation of 40°
to energy savings of approximately 30% at this process south-west at a slope of 28°. Monitoring and control sensor
step. An additional heat exchanger was installed to preheat locations are shown in Fig. 3, where the grey colored sen-
the wort close to boiling temperature after lautering, saving sors are used for both control and monitoring. The solar
a part of the steam required for heating the wort before loop is controlled by the temperature difference (7 and
boiling. Further, the heat recovery during wort boiling is 3 K) between the collector and the lowest temperature in
used to additionally heat up the fixed volume tank instead the store. The secondary charging loop is controlled identi-
of heating cold water up to 80 °C (as shown in Fig. 2). cally, using the solar flow temperature (T_SF) instead of

Other processes

Cold water

Cold water Cold water


Fixed Variable
volume tank volume tank

Mashing Lautering Boiling Cooling 50 m³ 50 m³

58..76 °C 76 °C 76..100 °C 90...9 °C 80..90 °C 70..80 °C

Fermenting cellar
Heat Recovery

Fig. 1. Initial state of the hot water supply of the brewhouse. The process steps in the brewhouse are shown in grey.
120 C. Lauterbach et al. / Solar Energy 101 (2014) 117–130

Other processes Aap = 155.5 m²

Cold water

Cold water
Fixed Variable
volume tank volume tank
Solar
Mashing Lautering Boiling Cooling 50 m³ 50 m³ buffer
tank
58..76 °C 76 °C Preheating 94..100 °C 90...9 °C 80..98 °C 70..80 °C
of wort 10 m³
76..94 °C

Fermenting cellar
Heat Recovery Cold water

Fig. 2. Improved hot water supply of the brewhouse with integrated STS. The heat recovery from boiling is used to heat the fixed volume tank. Heat from
the upper part of the fixed volume tank is used to preheat the wort before boiling which leads to less available hot water and the possibility to integrate an
STS.

Ta T_col
T_R
Collector field
155.5 m² Charging loop
Gt T_0.9 Cold brewing
water Variable volume
Solar loop Solar heat store 10 m³ Discharge loop
tank
T_0.7 50 m³
Brewing water
V_VVT
T_SF T_CF T_0.5 T_DCF T_BWF

T_0.3

T_SR V_C T_BWR V_BW


V_S T_DCR V_E
T_CR
T_0.1

Q_Charge Q_Discharge

Fig. 3. Hydraulic scheme of the STS with monitoring sensors; the grey colored sensors are used not only for monitoring but also for control; dashed lines
show positions of heat balances.

the collector temperature. The solar heat store is dis- resistance temperature sensors (Pt-1000, class A) connected
charged if the filling level of the variable volume tank falls with two leads. The uncertainty of these sensors is
below 70% (and as long as it remains below 75%) and the ±(0.15 + 0.002*|T|)°C (DIN EN 60751, 2009), leading at
temperature in the upper part of the solar heat store 50 °C to a deviation of ±0.25 K. The multi-jet flow meters
exceeds 40 °C. When both conditions are fulfilled, the used within the STS have an uncertainty margin of ±3%
pumps in discharging and brewing water loop are switched (Aquametro, 2012). According to error propagation
on. Night cooling of the solar heat store is activated on (Taylor, 1997), the resulting maximum error for heat flows
weekends if T_0.1 is higher than 70 °C and the filling level is 4% when combining the uncertainty margins for volume
of the variable volume tank is more than 70%. flow and temperatures (Tflow = 70 °C; Treturn = 20 °C). The
Heat balances are calculated at the two positions hemispheric irradiance on the collector plane is measured
marked in Fig. 3. Measurements of the mass flow in the and used as an input for the simulation model. The irradi-
solar loop are difficult due to the properties and uncertain- ance sensor is a Kipp & Zonen CMP 6 pyranometer that
ties of the concentration of the water-glycol mixture, so the has an uncertainty given by the manufacturer of less than
heat quantity in the solar loop was not considered. The 5% for each day (Kipp and Zonen, 2011) with an uncer-
temperature sensors of the brewing water return flow tainty of 10 W ±4% estimated by de Keizer (2012) for a
(T_BWR) is located too far from the heat exchanger with single radiation measurement.
part of the piping outside the buildings, so that the heat
quantities for charging (Q_Charge) and discharging 2.3. Performance
(Q_Discharge) of the store are used in the following.
The described system has been monitored since June 1st,
2.2. Uncertainties of measurement 2010 with a measurement interval of 1 min. The utilization
ratio of the charging loop is the first performance indicator
It is necessary to calculate heat flows to evaluate the per- used for the evaluation. It is defined as the ratio between
formance of the STS and validate the simulation model. heat quantity charging the store and the total irradiation
The temperatures within the system are measured with on the collector field during the same period.
C. Lauterbach et al. / Solar Energy 101 (2014) 117–130 121

Heat quantity charging the store ðQ ChargeÞ Irradiation on collector plane Yield of solar loop (q_charge)
gcharge ¼
 System yield (q_discharge) Solar loop utilization ratio
Total irradiation on collector field ðHtÞ

Irradiation / specific energy yield (kWh/m2a)


System utilization ratio
200 45%
ð1Þ 180 40%
160
The heat quantity charging the store (Q_Charge) is used 35%
140

Utilization ratio
to calculate the energy delivered to the solar buffer because 30%
120
it can be measured with higher accuracy compared to the 25%
100
solar loop as water instead of water–glycol is used. As ther- 80
20%

mal losses in the heat exchanger are very small, this does 60
15%

not lead to a major deviation (Mies et al., 2006). The sec- 40 10%
ond performance indicator is the system utilization ratio, 20 5%
defined as the ratio of heat quantity discharging the store 0 0%
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
to total irradiation on the collector field during the same
period. Fig. 4. Irradiation on collector plane, specific collector and system yield;
solar loop and system utilization ratio for 2011.
Heat quantity discharging the store ðQ DischargeÞ
gsys ¼

Total irradiation on collector field ðHtÞ
ð2Þ
Although the filling level of the variable volume tank was
In 2011 the total
 specific
 irradiation on  the collector
 field below 70% and solar heated water could be fed in, the
was 1.167 kWh= m2ap a and 373 kWh= m2ap a were deliv- brewing water pump was turned off manually by opera-
ered to the solar heat store resulting in a collector loop uti- tional staff in the brewhouse. This resulted in an infrequent
lization ratio of 32%, as shown
 in Table 1. discharge of the solar heat store, extensive periods of stag-
In 2011, 311 kWh= m2ap a was delivered to the brewing nation and a relatively low utilization of the STS. Fig. 5
water resulting in a system utilization ratio of 27%. Fig. 4 shows a typical production week with undesired manual
shows the monthly total irradiation on the collector field, interference in the discharge control.
the energy delivered to the solar heat store and the brewing As Fig. 5 shows, the brewing water pump is manually
water, as well as, the monthly collector loop and system switched off before the filling level reaches the limit of
utilization ratio. 75%, which is the control criterion to switch off the pump.
During the design
 of the system, a collector yield
 of
 The operational staff claimed “long term experience with
475 kWh= m2ap a and system yield of 446 kWh= m2ap a correct filling levels” of the variable volume tank as a rea-
were calculated on the basis of detailed simulations. With son for the manual interference. As the manual switch off
an annual irradiation
 on the collector plane of of the pump is not transferred to the control, the pump
1076 kWh= m2ap a the resulting utilization ratios were in the discharge loop operates until the filling level reaches
43% for the solar loop and almost 42% for the whole 75% and the solar heat store is more or less fully mixed. As
system. As the values for utilization ratios and specific the lower part of the solar heat store is heated up, the effi-
collector and system yield show, the system performance ciency of the STS system decreases and accordingly stagna-
is below the expectations as the predicted utilization ratios tion can occur in summer. The system analysis with
are not reached in any month of 2011. Further, the differ- simulations described in Section 4 shows that the manual
ence between both ratios and thus the losses of piping and interference has a high impact on the system yield. The sys-
heat store are higher than predicted in the design. Follow- tem yield rose by 21% after implementing automated con-
ing, the reasons for this low performance are investigated. trol in the simulation model, as shown in Fig. 9.
Another reason for low performance of the STS is the
2.4. Operational experience operation of the improved heat recovery. Instead of heat-
ing up the fixed volume tank by recovering heat from boil-
After the start-up, the monitoring of the STS showed a ing, the latter was still very often used manually to produce
lot of manual interference in the discharge control. hot water for the variable volume tank. This leads to a

Table 1
Heat quantities for charging, discharging and night cooling of the STS and utilization ratio for 2011.
Energy quantity/utilization ratio Abbreviation Total [MWh] Specific [kWh=m2ap ]
Irradiation on collector plane Ht 181 1167
Heat charging the store Q_Charge 58 373
Heat discharging the store Q_Discharge 48 311
Night cooling: charging loop NC_Charge 1.2 8
Night cooling: discharging loop NC_Discharge 0.5 3
Charging loop utilization ratio gcharge 32.0% 32.0%
System utilization ratio gsys 26.6% 26.6%
122 C. Lauterbach et al. / Solar Energy 101 (2014) 117–130

The efficiency of the collector field was calculated from


Filling level of variable volume tank [%]

Filling level Volume flow discharge loop Volume flow brewing water
110 5.5
100 5
monitoring data and compared to the efficiency curve by
90 4.5 using the collector parameters from a laboratory collector
80 test according to (DIN EN12975-2, 2006). The tempera-

Volume flow [m3/h]


4
70 3.5 tures (T_CF, T_CR) and volume flow (V_ C ) of the charging
60 3 loop are used to calculate the collector field efficiency as
50 2.5 these sensors were calibrated before installation and the
40 2 volume flow can be measured with a higher accuracy com-
30 1.5
pared to the solar loop, where a water–glycol mixture is
20 1
used. Thus, the calculated efficiency also incorporates the
10 0.5
0 0
piping losses of the collector field, solar loop and the charg-
12:00 12:00 12:00 12:00 12:00 12:00 ing plate heat exchanger. Due to this fact, the collector effi-
Sunday Monday Tuesday Wednesday Thursday Friday
ciency is expected to be lower compared to the EN-tests.
Fig. 5. Filling level of the variable volume tank and volume flows of To calculate the collector field efficiency, operating
discharge and brewing water loop for a week in April 2011. points were selected in which the STS was in an almost sta-
tionary state. Thus, operating points between noon and
reduced amount of cold water which could be heated by the 4 pm (the collector field is orientated south-west) on cloud-
STS and therefore, less operation time for the solar thermal less days were selected, where the irradiance on the collec-
system. Finally, the brewery staff demanded a threshold for tor plane was higher than 850 W/m2. In addition, operating
discharging the solar heat store of minimum 40 °C for points were only selected if the incidence angle was lower
T_0.9. A further increase of system yield of six percentage than 20°, so that effects of the incidence angle modifier
points can be achieved by correcting both the operation of (0.99 at 20°) can be neglected. Furthermore, data sets were
heat recovery and minimum temperature for discharging, excluded if the change of one of the temperature sensors
compared to solely implementing an automated discharge (T_SF, T_SR) was larger than ±0.7 K compared to the
control (see Fig. 9 in Section 4). previous data set. The same was done for data sets in which
the irradiance (Gt) changed more than 30 W/m2. For the
2.5. Component analysis remaining operating points the efficiency was calculated
by dividing the power in the charging loop by the total irra-
Besides the operational reasons described in the previ- diation on the collector field as shown in Eq. (4).
ous section, faults of the components of the system could
possibly have a negative impact on the system perfor- m_ charge  cp  ðT CF  T CR Þ
gcol ¼ ð4Þ
mance. Therefore, the collector field and its piping, the heat GT  Acol
exchangers, and the solar heat store are analyzed in this
section, in order to judge about their influence on the low The average temperature in the solar loop (Tm) is calcu-
performance of the STS compared to the design values. lated as the arithmetic mean of flow (T_SF) and return
First, the collector field and piping of the solar loop are (T_SR) temperature. Fig. 6 shows the efficiency of the col-
investigated. In order to assess the quality of the pipe insu- lector field compared to the efficiency curve of the collector
lation, the heat loss coefficient (U-value) calculated from
measured data was compared to that calculated from mate-
rial properties. The latter U-value is 0.9 W/(m2K) for a 1.0

thermal conductivity of 0.04 W/(mK) and 100% insulation 0.9

(di = 0.04 m; dout = 0.124 m). To calculate a U-value from 0.8 Efficiency curve

measured data, the heat transfer capacity rate (UA-value) 0.7


was determined first. Therefore, operating points were
Efficiency

0.6
selected where the pump of solar loop and charging loop 0.5 Trend line of
calculated efficiencies
were both in operation. The heat transfer capacity rate 0.4
was then calculated according to Eq. (3). 0.3 Efficiency at selected
points of operation

m_ solar  cp  ðT col  T SF Þ 0.2


UA ¼ ðT col T SF Þ
ð3Þ Collector parameters:
 T room 0.1
2 η0= 0.76; a1= 3.779 W/m²K; a2= 0.009 W/m²K²
0.0
The U-value can then be calculated by dividing the 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
average heat transfer capacity rate by the pipe surface. A (Tm-Ta)/Gt [Km2/W]
U-value of 2.8 W/(m2K) was calculated from the average
Fig. 6. Efficiency of the collector field for selected stationary operating
measured heat transfer capacity rate of 26.8 W/K. As pipe
points compared to the efficiency curve of the collector from a collector
insulation is seldom ideally installed and additional heat test; the solid line shows the trend of the collector field efficiency at selected
losses are caused by fittings, the calculated U-value is quite operating points; an uncertainty margin is added for a single point to
high, without being unrealistic. demonstrate the uncertainty of measured data.
C. Lauterbach et al. / Solar Energy 101 (2014) 117–130 123

for selected operating points. The calculated efficiency val- perature (3) of the store fall faster than the middle temper-
ues are, with a few exceptions, below the efficiency curve of ature which remains almost constant over the next 12 h.
the collector. This is because the bottom of the store is not insulated
The trend line of the calculated efficiencies shows that and is placed on a metal ring on the ground. Therefore,
the average of the calculated efficiencies is below the effi- an air gap of about 20 cm exists under the store which is
ciency curve due to piping losses. An uncertainty margin only insulated on its sides. The insulation at the top of
is added for a single point to demonstrate the uncertainty the store is not ideal either, as quarter circles are simply
of measured data. It can be concluded that the collector put on top. Additional heat losses occur through the dis-
field at the studied brewery has a sufficiently similar perfor- charge return pipe. As shown in Fig. 7 the discharge return
mance compared to the tested collector. temperature (T_DCR) remains slightly under the lowest
The heat losses of the solar heat store were evaluated. store temperature (T_0.1) after the discharge pump stops.
Table 1 shows a reasonable difference between the heat In the following, T_DCR is always slightly lower than
quantities in the charging and discharging loop. To judge T_0.1 although it should be close to room temperature.
the losses of the solar heat store, at first the theoretical This is because no convection barrier was installed in the
UA-value of the store was calculated using its geometrical discharge return close to the solar heat store. This causes
properties (di = 2.06 m; dout = 2.46 m; h = 3 m) and ther- a thermal convection out of the lower part of the store into
mal conductivity (0.04 W/(mK)) of the insulation to be the discharge loop and therefore additional heat losses
6 W/K. In addition, periods were analyzed in which the through non insulated pump and fittings. The high heat
store was neither charged nor discharged. In total 13 peri- losses shown in Table 1 can be explained by the missing
ods with durations between 24 and 336 h were analyzed insulation at the bottom of the store and the missing con-
and an average UA-value of 15.1 W/K with an uncertainty vection barrier. The system yield increases by 3% if the heat
of ±3.6 W/K was determined. To further investigate the losses are reduced to a value calculated from insulation
rather high heat losses of the solar heat store in detail, thickness and properties (see Fig. 9 in Section 4).
Fig. 7 shows the temperatures within the store, the dis- Both heat exchangers of the system are analyzed. The
charge return and the room temperature for two days in heat exchanger for charging the solar heat store was
August 2011. Additionally, the volume flows in charging, designed with a UA-value of 20.2 kW/K, which corre-
discharging and brewing water loop are shown. sponds to a logarithmic temperature difference of 5.7 K
First of all, the manual interference in the operation of at a nominal heat transfer capacity of 115 kW. This leads
the brewing water pump is shown on the first day (1), as to a specific value related to the collector field aperture area
explained above in Section 2.4. The discharge of the store of ua = 130 W=ðm2ap KÞ that is larger than the recom-
starts at 4:00 h, but as the brewing water pump was mended value of 100 W=ðm2ap KÞ in (VDI 6002, 2004).
switched off the day before until it is switched on only at The heat exchanger for discharging was designed with a
5:00 h, the store is mixed by the discharge loop. The tem- UA-value of 23.5 kW/K (logarithmic temperature differ-
perature in the discharge return is close to the one at the ence of 6.5 K at a nominal heat capacity of 153 kW). The
top of the store and the lower part is heated up (2). The measured UA-value for this heat exchanger is lower at an
brewing water pump is switched on after 1 h and both tem- average of 15.5 kW/K because the mass flow rates in oper-
peratures in the discharge return and in the lowest store ation are lower than assumed.
level drop. The logarithmic temperature difference for the charging
After charging the store at around 16:00 h, it can be seen heat exchanger was much higher than its design value of
from the figure that both the highest and the lowest tem- 5.7 K and reaches values up to 25 K. The UA-value is far
below its design value of 20.2 kW/K at an average of
90 10
T_0.9
4.7 kW/K because a wrong model of the designed heat
9
80 exchanger was delivered by the manufacturer. This
T_0.1
T_0.5 (3) 8 heat exchanger was replaced with the correct model
70
Volume flow [m3/h]
Temperature [ ° C]

60
7 that reached its design values. Replacing the charging heat
(2)
T_discharge return 6 exchanger leads to a 6% increase of system yield. Correct-
50
5 ing the UA-value of the discharge heat exchanger leads to a
40 further increase of three percentage points (see Fig. 9 in
4
30
T_room 3
Section 4).
Volume flow brewing water

20 2
Volume flow
discharge 3. Validation of simulation model
10 Volume flow charge 1
(1)
0 0
0:00 4:00 8:00 12:00 16:00 20:00 0:00 4:00
This section explains the development of the simulation
model of the pilot plant at the brewery and displays the
Fig. 7. Temperatures within the store, the discharge return, the room results of validation.
temperature and the volume flows in charging, discharging and brewing
water loop for a day in August 2011.
124 C. Lauterbach et al. / Solar Energy 101 (2014) 117–130

Table 2 2006).The parameters and input values for the model were
Main parameters of the simulation model. either taken from a test report (ITW, 2009) in case of the
Parameter Value Unit collector or determined from the monitoring data (e.g.
General mass flows, UA-values of heat exchangers). The UA-value
Weather data Kassel, Germany for the bottom of the store was raised due to the missing
Collector loop insulation. Further, additional heat losses (UA convection
Collector aperture area – Aap 155.5 m2 losses in Table 2) were added for the piping and various fit-
Collector type Flate plate – tings due to pipe internal recirculation in the discharge
Optical efficiency – g0 0.76 –
return pipe, as described in Section 2.5. A measured load
Heat loss coefficients – a1 3.779 W=ðm2ap KÞ
Heat loss coefficients – a2 0.009 W=ðm2ap K2 Þ profile for the entire year 2011 was used as an input for
IAMdirect(50°) 0.9 – the model in the brewing water loop to consider the manual
IAMdiffuse 0.9 – interference of the discharge control.
Heat capacity 10.5 kJ=ðm2ap KÞ
Collector loop – specific mass flow 15.5 kg=ðm2ap hÞ
Charging loop – specific mass flow 12.5 kg=ðm2ap hÞ
Share of glycol 35 % 3.2. Validation results
Azimuth 40 SW °
Tilt angle 28 ° The validation of the simulation model was based on the
UA – charging heat exchanger 4.7 kW/K
comparison of simulated and measured data for the year
Collector pipe – length (flow) 41.5 m
Collector pipe – U-value piping 2.8 W/(m2K) 2011. The comparison between measured and simulated
heat quantities is displayed in Table 3. The measured irra-
Storage
diation on the collector plane is an input to the simulation
Volume 10 m3
UA sides 8.9 W/K model. As the table shows, the heat quantities for charging
UA top 1.4 W/K the store are in very good agreement with a deviation of
UA bottom 5.0 W/K only 0.5%. The simulated heat discharged from the store
UA convection losses 15.3 W/K is slightly higher than the measured value. Nevertheless,
Discharge the deviation of 2.2% is still within the uncertainty margin
Discharge loop – specific mass flow 9.2 kg=ðm2ap hÞ of the measured heat flows of 4%.
Brewing water – specific mass flow 8.9 kg=ðm2ap hÞ Only a minor part of this deviation can be explained
UA – discharging heat exchanger 15.5 kW/K
with lower heat losses by night cooling in the simulation
compared to the measurement, as shown in Table 3. The
3.1. Simulation model relative deviation of night cooling in the discharging loop
appears large at first sight. As the absolute heat quantities
The simulation model of the STS was developed in for night cooling are very small, this can be caused by one
TRNSYS 17 (Klein et al., 2009). The model includes all or two additional nights of night cooling due to slightly
components shown in Fig. 3 except for the variable volume higher simulated temperatures in the store. Fig. 8 shows
tank. Table 2 shows an overview of the most important the monthly measured and simulated heat quantities for
parameters of the simulation model. 2011. The measured collector yield is slightly higher than
A modular approach was applied to model the solar the simulated one except for June and July.
loop as well as the thermal storage. These modules were In contrast, the measured system yield is slightly below
developed and tested on different field test systems by the simulated values except for March and November,
de Keizer (2012) and offer a variety of control options. where the absolute heat quantities are quite low. These
The control strategy of the pilot plant could be modeled deviations indicate that the model probably underestimates
as described in Section 2.1. The collector is modeled with the heat losses of the store. Nevertheless, as the comparison
Type 832, developed by Perers (Haller et al., 2009). The of utilization ratios shows, the simulation results are in
model for the thermal storage is Type 340 (Drück, good agreement with the measured values.

Table 3
Measured and simulated heat quantities for 2011.
Energy quantity/performance indicator Measured Simulated Deviation [%]
Irradiation on collector plane [kWh=m2ap ] 1167 1167 0.0
Heat charging the store [kWh=m2ap ] 373 371 -0.5
Heat discharging the store [kWh=m2ap ] 311 318 2.2
Night cooling: charging loop [kWh=m2ap ] 8 9 11.1
Night cooling: discharging loop [kWh=m2ap ] 3 1 200.0
Charging loop utilization ratio [%] 32.0 31.8 0.5
System utilization ratio [%] 26.6 27.2 2.2
C. Lauterbach et al. / Solar Energy 101 (2014) 117–130 125

Measured yield of solar loop Simulated yield of solar loop specific system yield, the collector loop and system utiliza-
Measured system yield Simulated system yield
Simulated system utilization ratio Measured system utilization ratio tion ratio are used as main performance indicators.
Monthly specific energy yield [kWh/m2ap]

70 45%

60
40% 4.1. Identified faults and influence on system performance
35%
50

Utilization ratio
30% The faults described in Sections 2.4 and 2.5 all have a
40 25% negative influence on the system performance. The different
30 20% faults were modeled to determine their quantitative impact.
15% Fig. 9 summarizes the results of the simulated faults. The
20
10% first column shows the results of the validated model as a
10
5%
base case. To evaluate the impact of the individual faults
0 0%
on the system performance one fault at a time was cor-
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec rected in the model. While store losses, UA-values and dis-
Fig. 8. Monthly measured and simulated heat quantities for 2011; in
charge control were corrected individually, the minimum
January, February and December the discharge was turned off manually; temperature of the discharge control and the heat recovery
the yield of solar loop was measured as indicated in Fig. 3 (Q_Charge); the operation were corrected after implementing the auto-
simulated yield of solar loop was calculated using the corresponding mated discharge. This was necessary as the effect of elimi-
temperatures and flow rate in the simulation model. nating both faults can only be evaluated for an
automated discharge control.
4. System analysis with simulations First, the losses of the heat store were reduced to a the-
oretically calculated UA-value considering a correction
Within this section, the STS is analyzed by simulating factor for real installation of insulation (UA-value for the
the different faults which were detected within the monitor- whole store = 7.2 W/K). The difference between collector
ing and component analysis. Further, a global and a local and system yield is reduced due to lower heat losses of
sensitivity analysis are performed. the store and thus less charging, but the impact is rather
Decisions about the realization of projects and their small. Afterwards, the UA-value of the charging heat
subsequent evaluation afterwards are mainly based on an exchanger was changed to 100 W=ðm2ap KÞ related to the
economic analysis. Therefore, the specific system yield is collector field aperture area as suggested in (VDI 6002,
an important performance indicator as it directly influences 2004), replacing the initial value from validation (Table 2).
the economic feasibility of a solar process heat system This change has a considerable impact of 6% of the system
in combination with the specific system cost. Besides the yield, whereas the change of UA-value for the discharge

Collector yield (q_charge) System yield (q_discharge)


600

+29 % +1 %
500
Annual specific energy yield

+15 % +18 % +20 % +43 % -3 % -7 % -8 %


+14 % -7 % -8 %
+8 % +9 % +27 %
+21 % +22 % +25% -19 %
400
-4 %
[kWh/m2ap ]

+6 % +9 % -23 %
+3 %
300

200

100

Fig. 9. Simulated heat quantities for different faults; the first red (filled) and shaded columns show the values for the validated model; afterwards one fault
at a time was corrected in the model; the increase/decrease compared to the validated model is given in percent; after “design values”, one fault at a time
was added to the model; the increase/decrease compared to the model without faults is provided. (For interpretation of the references to color in this figure
legend, the reader is referred to the web version of this article.)
126 C. Lauterbach et al. / Solar Energy 101 (2014) 117–130

Table 4
Simulated heat quantities for validated model and model without faults for 2011 as well as for the design model.
Energy quantity/performance indicator Validated [kWh=m2ap ] Without faults [kWh=m2ap ] Design [kWh=m2ap ]
Irradiation on collector plane 1167 1167 1076
Solar heat from collector 394 496 475
Heat losses solar loop piping 23 19 15
Solar heat charging the store (collector yield) 371 477 460
Heat losses store 42 10 12
Solar heat discharging the store (system yield) 318 455 448
Night cooling charging loop 10 12 0
Night cooling discharging loop 0.6 0.2 0
Solar loop utilization ratio 31.8% 40.9% 42.8%
System utilization ratio 27.2% 39.0% 41.6%

heat exchanger to 23.5 kW/K leads only to a minor devia- twice as high. A reduced value (Table 2) for the discharging
tion of the collector and system yield. Collector and system heat exchanger has only a very small impact. Adding the
yield rise by 14% and 21% respectively after implementa- manual interference to the model has the largest impact
tion of an automated control for discharging. The mini- on collector and system yield. Table 4 shows an overview
mum temperature for discharging and an ideal operation of simulated heat quantities for the validated model and
of heat recovery only cause a minor increase of collector model without faults for 2011 as well as the design model.
and system yield. If all faults are removed from the model, The system utilization ratio for the model without faults
the collector yield is 29% higher and the system yield 43% is about 12% points higher than in the validated model.
higher than for the validated model. The average temperature of the store and therefore its heat
After removing all faults, single ones were implemented losses decline significantly for the model without faults
again to evaluate their impact on a properly running sys- because the store is discharged more often. Further, the
tem. Increasing the heat losses of the store to the measured heat losses of the solar loop piping are lower than in the
values, the system yield falls by 3%. The influence of validated model. Both utilization ratios for the model
reduced UA-values of the charging heat exchanger is about without faults are below the design values because the
irradiation in the design case was lower than in 2011.
Table 5 Therefore, the system performance is slightly lower than
Considered parameters for the global sensitivity analysis and their designed, although collector and system yield are higher.
variation range; parameters were varied about ±20% from their value of
Table 2; in case this leads to unrealistic values (e.g. g0 = 0.91), the other
4.2. Global sensitivity analysis
limit was extended accordingly to ensure a constant variation range for all
parameters; the UA-value for the charging heat exchanger was varied
from 100 W=ðm2ap KÞ related to collector field aperture area (VDI 6002, This section describes the results of a global sensitivity
2004). analysis performed for the STS with the Morris method
No. Parameter Variation Unit (Saltelli, 2004). Table 5 shows the considered parameters
range for the global sensitivity analysis and their variation range.
Collector loop As a first step, parameters of the simulation model
1 Optical efficiency – g0 0.55–0.85 – described in Section 3.1 but no external inputs were consid-
2 Heat loss coefficient – a1 2.5–4.0 W/(m2K)
120%
3 Heat loss coefficient – a2 0.007–0.011 W/(m2K2) 6 14

4 b0 0.15–0.22 – 7

5 IAMdiffuse 0.83–0.90 – 100%


6 Collector loop – specific mass flow 12.5–18.5 kg=ðm2ap hÞ
7 Charging loop – specific mass flow 10–15 kg=ðm2ap hÞ 80%
non-linearity

13
8 UA – charging heat exchanger 80–120 W=ðm2ap KÞ
9 Collector pipe – length (flow) 40–60 m 60%
10 Collector pipe – U-value piping 2.2;3.4 W/(m2K)
Storage 40% 8
15
11 Heat loss coefficient sides 4–6a W/K 3
16
9 10
12/ Heat loss coefficient top/bottom 0.9–1.3a W/K 20%
11
13 4
12 5 2 1
Discharge 0%
0 10 20 30 40 50 60 70 80
14 Discharge loop – specific mass 7.4–11 kg=ðm2ap hÞ
flow Overall influence of the parameter [kWh/m2a]
15 Brewing water – specific mass flow 7.1–10.7 kg=ðm2ap hÞ
16 UA – discharging heat exchanger 12.4–18.6 kW/K Fig. 10. Ranking of parameters by the Morris method. The value for the
overall influence is the average change of the specific system yield if a
a
Both changed from the corrected UA-value as described in Section parameter is changed from a certain point by half of its variation range,
4.1.5. shown in Table 5.
C. Lauterbach et al. / Solar Energy 101 (2014) 117–130 127

Table 6
Investigated cases for sensitivity analysis of the load profile.
No Description Days Time Profile
1 Profile with optimized heat recovery Monday–Friday Varies

2 Load on 5 days in the morning Monday–Friday 4:00 h–13:00 h

3 Load on 5 days in the afternoon Monday–Friday 14:00 h–23:00 h

4 Extended load on 3 days Monday, Wednesday, Friday 4:00 h–19:00 h

5 Shorter load on 7 days Monday–Sunday 4:00 h–10:27 h

6 Extended load on 5 days with halved mass flow Monday–Friday 4:00 h–22:00 h

7 Shorter load on 5 days with doubled mass flow Monday–Friday 4:00 h–8:30 h

ered for the sensitivity analysis. As a second step, the influ- 4.3. Local sensitivity analysis of load and influential
ence of the most important parameters identified in the glo- parameters
bal sensitivity analysis was compared to external inputs
(temperature and load profile). Control parameters were The brewing water return temperature (T_BWR) and
not considered, as Kusyy et al. (2008) found that they have the load profile are expected to be the most important influ-
minor influence on the fractional energy savings, which can ence factors for the system performance of a solar process
be assumed for system yield as well. heat system (Schmitt et al., 2012). This section describes the
Fig. 10 shows the overall influence and the non-linearity results of a local sensitivity analysis performed for the most
of the influence of the investigated parameters after evalu- important parameters identified in the global sensitivity
ating 453 simulations according to the Morris method. The analysis as well as the load return temperature (T_BWR)
value for the overall influence is the average change of the and the load profile. The local sensitivity analysis directly
specific system yield, if a parameter is changed from a cer- shows the influence of a parameter on the system yield.
tain point by half of its variation range, as shown in In order to investigate the influence of the load profile,
Table 5. different cases were developed to investigate the influence
The optical efficiency of the collector is by far the most of the load profile. In all cases, 63 m3 of cold water are
influential parameter. As its value for non-linearity is very heated within the brewing water loop as this is the average
low, its influence on the system yield is similar within the load of a typical production week. The difference between
variation range. In case of a high non-linearity (e.g. charg- the cases is the distribution of these 63 m3 over one week,
ing loop mass flow) the influence of the parameter changes which means that the total load is constant and only its dis-
within the variation range. tribution changes. Table 6 shows the investigated cases for
The heat loss coefficient (a1) of the collector and the sensitivity analysis of the load profile.
mass flow in the brewing water loop are two additional Fig. 11 shows the results of the local sensitivity analysis
parameters which have a considerable influence within for the most important parameters. The high influence of
the varied range. The value for non-linearity of the mass the optical efficiency, which the global sensitive analysis
flow in the brewing water loop is higher than the ones showed, is also visible in the upper left of Fig.11. The
 sys-
for optical efficiency and heat loss coefficient (a1) which tem yield
 declines
 from 479 kWh= m2ap a to
means that its influence varies for different points. The 357 kWh= m2ap a from the optical efficiency for a good flat
overall influence of the other mass flows (6,7,14) is low, plate collector of 0.84 to a lower optical efficiency of 0.6.
although their influence is highly variable. The influence of the heat loss coefficient (a1) and the spe-
128 C. Lauterbach et al. / Solar Energy 101 (2014) 117–130

Annual solar system yield [kWh/(m2ap a)]

Annual solar system yield [kWh/(m2ap a)]


600 600

550 550

500 500

450 450

400 400

350 350

300 300

Optical efficiency ( η0) Heat loss coefficient (a1) [W/(m2K)]


Annual solar system yield [kWh/(m2ap a)]

600 600

Annual solar system yield kWh/(m2a)


550 550

500 500

450 450

400 400

350 350

300 300
1 2 3 4 5 6 7
Load profile
Brewing water -spec. mass fl. [kg/(m2aph)]
Annual solar system yield [kWh/(m2apa)]

600

550

500

450

400

350

300
15.0 17.5 20.0 22.5 25.0
Brewing water return temperature (T_BWR) [ °C]

Fig. 11. Results of local sensitivity analysis.

cific mass flow in the brewing water are much smaller but in base case (Case 1). This is possible because the store is
case of a badly insulated collector (e.g. 4.5 W=ðm2ap KÞ) the charged on days without load and discharged longer on
system yield is reduced by 5% compared to the one used for others. This means that processes with operation on more
the studied STS. days of the week are not always preferable unless the total
Regarding the load profile, the first case shows the load is higher. The advantage of a process requiring heat
weekly profile with optimized heat recovery as described on more consecutive days is the lower necessarystorevol-
in Section 2.1. If the load is distributed equally between ume. Accordingly, the highest yield (475 kWh= m2ap a ) is
Monday and Friday (Case 2) the system yield declines
slightly by 4% and further by 2% if the load is shifted to achieved with a shorter load on seven days (Case 5). A
the afternoon (Case 3). This can be explained by operation longer operation (Case 6) compared to Case 2 with halved
of the STS at lower efficiencies as the temperatures in the mass flow only leads to a minor increase of system yield.
store and thus the collector field rise before the store is A shorter operation with doubled mass flow (Case 7)
discharged. decreases the system yield. The temperature of the load
An extended load on 3 non consecutive days (Case 4) or process, which is in this case the brewing water return
temperature (T_BWR) has a largest impact on the system
leads to the same system yield (454 kWh= m2ap a ) as the yield as Fig. 11 shows. An increased return temperature
C. Lauterbach et al. / Solar Energy 101 (2014) 117–130 129

from 20 °C  40 °C reduces
 to even  the system yield from
Systemtechnik und Planungshinweise. ZfS –Rationelle Energietechnik
GmbH, Hilden, Germany.
475 kWh= map a to 310 kWh= m2ap a which would lead
2
de Keizer, C., 2012. Simulation-based long-term fault detection of solar
to a system that is not economically viable. thermal systems. Dissertation, Kassel University Press, Kassel. ISBN
9783862194001.
Deutsches Institut für Normung e. V., 2006. Thermal Solar Systems and
5. Conclusion Components – Solar Collectors – Part 2: Test Methods. Beuth Verlag,
Berlin.
At first, this paper describes the integration of an STS Deutsches Institut für Normung e. V., 2009. DIN EN 60751:2009-05:
into the hot water supply of a brewery. It was shown that Industrial Platinum Resistance Thermometers and Platinum Temper-
ature Sensors. German version. Deutsches Institut für Normung e. V.,
a large effort can be necessary to integrate solar heat into Berlin.
an industrial process. The analysis of the STS and its com- Drück, H., 2006. MULTIPORT Store – Model for TRNSYS Type 340
ponents showed that faults of single components can have version 1.99F. Institut für Thermodynamik und Wärmetechnik –
a considerable impact on overall performance. Universität Stuttgart, Stuttgart, Germany.
To evaluate the identified faults, a TRNSYS simula- Eskin, N., 2000. Performance analysis of a solar process heat system.
Energy Convers. Manage. 41, 1141–1154.
tion model for a solar process heat system was developed Haller, M., Paavilainen, J., Dalibard, A., Perers, B., 2009. TRNSYS Type
and validated with measurements. The simulated and 832 v3.07 Dynamic Collector Model by Bengt Perers. Updated Input-
measured heat quantities for 2011 are in good agreement. Output Reference.
The analysis of several faults detected in the system Heimrath, R., 2004. Simulation, Optimization and Comparison of Solar
showed that the amount of available load has the highest Assisted Heating Systems for the Space Heating of Multi-Family
Houses. Dissertation. Graz University of Technology, Graz,
impact on system performance. In case of the studied Austria.
system, the load was reduced by manual interference in Institut für Thermodynamik und Wärmetechnik (ITW) - Universität
the discharge control, leading to a substantially lower Stuttgart, 2009. Test Report: Durability, Reliability and Thermal
system yield than expected. The correct estimation of Performance of a Solar Collector – Thüsol S, Stuttgart. <http://
available load is crucial to predict the performance of www.thuesolar.de/fileadmin/Download/Pruefbericht_ITW.pdf>.
Karagiorgas, M., Botzios, A., Tsoutsos, T., 2001. Industrial solar thermal
an STS before installation. Further faults which have a applications in Greece - Economic evaluation, quality requirements
considerable impact are a reduced UA-value of the and case studies. Renew. Sustain. Energy Rev., 157–173.
charging heat exchanger due to wrong design or mal- Kipp, Zonen, 2011. Pyranometers: For the Accurate Measurement of
function and increased heat losses of the store. If all Solar Irradiance. Delft, Netherlands.
faults are corrected, the design values can be reached. Klein, S., Beckman, W., Mitchell, J., Duffie, J., Duffie, N., 2009. TRNSYS
17: A Transient System Simulation Program. Solar Energy Labora-
Therefore, monitoring and failure detection of solar pro- tory, University of Wisconsin, Madison, USA.
cess heat systems is especially important as many faults Kusyy, O., Vajen, K., Jordan, U., 2008. Application of Sensitivity
can occur and reduce the system yield considerably. Analysis to Parameters of Large Solar Water Heating Systems.
Finally, a global and local sensitivity analysis showed Proceedings Eurosun Graz, Austria.
that the most important factors for system yield are the Kutscher, C.F., Davenport, R.L., 1980. Preliminary Operational Results
of the Low-Temperature Solar Industrial Process Heat Field Tests.
process temperature, the choice of a suitable and well-func- Golden, USA.
tioning collector and, to certain extend, the load profile. Lauterbach, C., Schmitt, B., Jordan, U., Vajen, K., 2012. The potential of
Further investigation regarding the influence of the load solar heat for industrial processes in Germany. Renew. Sustain. Energy
profile is therefore necessary as considerable effort is asso- Rev. 16, 5121–5130.
ciated with its determination in the design phase of a solar Mies, M., Rehrmann, U., Szablinski, D., 2006. Abschlussbericht für das
Projekt Neubaugebiet “Badener Hof” Heilbronn. ZfS – Rationelle
process heat system. Additionally, a methodology for Energietechnik GmbH, Hilden, Germany.
choosing a suitable collector for a certain process heat Müller, T., Weiß, W., Schnitzer, H., Brunner, C., Begander, U., Themel,
application is necessary. O., 2004. PROMISE - Produzieren mit Sonnenenergie. Potenzialstudie
zur thermischen Solarenergienutzung in österreichischen Gewerbe-
und Industriebetrieben. Arbeitsgemeinschaft Erneuerbare Energien –
Acknowledgement Institut für Nachhaltige Technologien, Vienna.
Saltelli, A., 2004. Sensitivity Analysis in Practice. A Guide to Assessing
The authors gratefully acknowledge the financial sup- Scientific Models, Wiley, Chichester, United Kingdom, ISBN
0470870931.
port provided by the German Federal Ministry for the
Schmitt, B., Lauterbach, C., Dittmar, M., Vajen, K., 2012. Guideline for
Environment, Nature Conservation and Nuclear Safety, the Utilization of Solar Heat in Breweries. Proceedings Eurosun
contract No. 0329601T. Rijeka, Croatia.
Schweiger, H., Mendes, J., Schwenk, C., Hennecke, K., Barquero, C.,
Sarvisé, A., Carvalho, M., 2001. POSHIP – The Potential of Solar
References Heat for Industrial Processes, Barcelona, Spain.
Taibi, E., Gielen, D., Bazilian, M., 2012. The potential for renewable
Aquametro, A.G., 2012. TOPAS PMW-Basic: Hot water meter. <http:// energy in industrial applications. Renew. Sustain. Energy Rev. 16,
www.aquametro.com/> accessed on 04.12.2012. 735–744.
Croy, R., Mies, M., Rehrmann, U., Wirth, H.P., 2011. Solarthermie-2000, Taylor, J.R., 1997. An Introduction to Error Analysis. The Study of
Teilprogramm 2 und Solarthermie2000plus: Wissenschaftlich-techni- Uncertainties in Physical Measurements 2. University Science Books,
sche Programmbegleitung und Messprogramm (Phase 4). Teil 2: Sausalito, California, USA, ISBN 0935702423.
130 C. Lauterbach et al. / Solar Energy 101 (2014) 117–130

Vannoni, C., Battisti, R., Drigo, S., 2008. Potential for Solar Heat in Application in Residential Buildings. Verein Deutsche Ingenieure,
Industrial Processes. Report within IEA SHC Task 33/IV. Department Berlin, Germany.
of Mechanics and Aeronautics – University of Rome “La Sapienza”, Wutzler, M., Schirmer, U., Platzer, B., 2011. Solar process heat applica-
Rome, Italy. tion at the Hofmuehl brewery at Eichstaett/Germany. Proceedings
Verein Deutsche Ingenieure, 2004. VDI 6002 Blatt 1: Solar Heating for ISES Solar World Congress Kassel, Germany.
Potable Water – General Principles – System Technology and

Potrebbero piacerti anche