Sei sulla pagina 1di 16

EPSY

Earthfault Protection System


Electronic-Components
Introduction Basic Units

EPSY (Earthfault Protection Sys- devices for the recognition and to the operators of medium-
tem) is a new and comprehensi- detection of earthfaults. Devices voltage networks. This is not
ve earthfault protection system and systems of traditional earth- available using the traditional
designed for compensated fault protection engineering do methods and devices.
networks. As compared to other not meet or only meet these
methods of neutral point requirements in a limited way. The electronic components of
treatment, earthfault compen- the new earthfault protection
sation shows clear advantages The protection system EPSY system (EPSY) and their configu-
in ensuring both the safety of essentially consists of a contin- rations are summarized as
personnel and supply as well as uously adjustable arc sup- follows.
limiting possible consequential pression coil combined with an
damages during an earthfault. automatic compensation con-
trol device and a selective,
In comparison with low highly sensitive earthfault
impedance neutral point detection device. In particular,
grounding, the reduction of the the newly developed method for
fault currents during earthfault selective detection of high-impe-
compensation places high requi- dance earthfaults, which is
rements on the reliability and the integrated in EPSY, offers the
selectivity of the protection possiblity of early fault detection

Earthfault Compensation Controller EFC30

Fig. 1 Front view EFC30

The controller EFC30, available since 1991, determines the resonance point using a short detuning of the
ASC-coil. Remarks: For details see page 9 and EFC30/EFC40 brochure.

2
Earthfault Compensation Controller EFC40

Fig. 2 Front view EFC40

For determination of the If the network is very symmetric, Remarks:


resonance point, the new the neutral to ground voltage is
method of the earthfault com- extremely low and there is no • The operation mode of the
pensation controller EFC40 uses marked resonance curve which EFC40 necessarily requires the
the current injection into the could be used as a control criterion. installation of the current
zero-phase sequence system and In this case it is possible to increase injecting device ECI.
therefore detuning of the arc the neutral-to-ground voltage, • Without the current injecting
suppression coil is not necessary. by using a permanent injection device ECI, the EFC40 can be
of a current into the zero sequence used in the EFC30 operation
The EFC40 calculates the zero- network, so that changes of the mode.
sequence impedance by measuring network configuration lead to a • For details see page 9 and the
the vectors of both the neutral- reliable trigger of the EFC40 EFC30/EFC40 brochure.
to-ground voltage and the controller. Furthermore, the
current injected into the zero- EFC40 is able to tune on-load
sequence system of the network adjustable step-coils s.
(according to the EDF licence)
before and during the injection.
3
Earthfault Detection Device EFD10
Fundamentals in Earth Fault Detection After this initial phase, a check
the Detection of the System EFD without current injection is made
Faulty Feeder periodically to identify the feeder
The core of the electronic part of in which the asymmetry chan-
If an earth fault appears in a net- EPSY is the earth fault detection ges.The calculations of this chan-
work, it leads to a steady-state device EFD, which is used both ge are made by using the vec-
asymmetry of the network after in the separate earthfault detec- torial measurements of the ac-
the decay of the transient pro- tion device EFD10 and in the com- tual values of Uo and Io and
cesses. The zero-sequence voltage bined control and detection unit their reference values recorded
(Uo) as well as the zero-sequence EFD40 (compact device). The during the initial phase. The feeder
currents of all feeders which are difference in the new earth fault indicating the greatest change of
supplied by the same busbar detection method compared to asymmetry is recognized as the
( Iol .... Ion ) are available as previous relay methods available faulty feeder. Using this method
measurement variables for the is that the measuring signals of it is possible to detect high-
detection of the feeder in which the zero-sequence currents are ohmic faults up to 100 kOhm.
the earth fault occurs. In the periodically recorded and combi- This selectivity and sensitivity can
case of an earthfault, the highest ned in a central unit for further not be achieved by using any de-
zero-sequence current does not processing. The zero-sequence vice or system of the traditional
flow in the faulty feeder but in admittances of the feeders (ad- earth fault protection technique.
the one that has the highest line mittance method) are determi-
to earth capacitance. Thus the ned by the vectorial measure-
amplitude of the zero-sequence ment of the zero- sequence
current cannot be used as a crite- currents (Iol .... Ion) and of the
rion for detecting the faulty fee- zero-sequence voltage (Uo) befo-
der. Traditional earthfault detec- re and during a defined modifi-
tion relays have problems to cation of the zero-sequence sy-
achieve a reliable and selective stem. The modifica-tion of the
detection of low and high impe- zero-sequence system is caused
dance earthfaults. This is due to by a current injection, i.e., with
a combination of the measure- the assistance of the current in-
ment principles used, the effects jection, in the healthy network,
of instrument transformer errors the EFD system determines the
and implications of fault evalua- reference values of admittance
tion in a single relay mode. against earth and their natural
asymmetry per feeder by vecto-
rial measurement of Uo and Io.

4
Fig. 3 Front view EFD10-16

EFD10-Types
(for details see page 9):
• EFD10-8 (Earth fault detection
device for a maximum of
8 feeders)
• EFD10-16 (Earth fault detection
device for a maximum of
16 feeders)

Remarks:
• If there are more than 16
feeders, the expansion unit
EFX10 is required.
• The EFD requires the
installation of the current in-
jecting device ECI.

5
Compact Device EFD40
(Earth Fault Compensation Controller and Detection)

Fig. 4 Front view EFD40-16

The compact device EFD40 EFD40-Types Remarks:


combines all the functions of the (for details see page 9):
earth fault compensation • If there are more than 16
controller EFC40 and the earth • EFD40-8 (earth fault controller feeders, the expansion unit
fault detection device EFD10. and detection device for a EFX10 is required.
maximum of 8 feeders) • The EFD necessarily requires
• EFD40-16 EFD40-16 (earth fault the installation of the current
controller and detection device injecting device ECI.
for a maximum of 16 feeders)

6
Expansion Unit EFX10

Fig. 5 Front view EFX10

In case it is necessary to monitor In addition, the expansion unit EFX10-Types


more than 16 feeders in one EFX10 can be used to increase (for details see page 9):
substation, the devices EFD10 the number of the digital inputs/
and EFD40 have to be extended outputs which are required, for • EFX10-8 (earth fault detection
with one expansion unit EFX10. example, for the replica of the expansion unit for 8 additional
switching state of the circuit- feeders)
breakers in multiple bus-bar • EFX10-16 (earth fault detection
operation. expansion unit for 16 additional
feeders)

7
Current Injection Device ECI

The current injection device ECI The current injection into the The current injection device ECI
is used to change the zero- zero-phase sequence system is essentially consists of a transform-
sequence voltage by injecting a usually done on the low-voltage er, capacitors for current-limiting,
current into the zero-sequence side via a secondary auxiliary relays, control- and signal
system. This change of the zero- winding and a sufficient dimen- contacts.
sequence voltage is required sioned voltage winding of the
both for the earth fault compen- arc suppression coil.
sation controller EFC40 (see
page 3) and for the earth fault
detection device EFD (see page 4).

ECI - Technical Data

Voltage supply
voltage 230 V AC, 50 Hz
current 7 A at healthy network condition
max. 23 A in case of an earth fault
inrush current approx. 140 A

Control contacts
voltage range 24...240 V AC oder V DC
current max. 40 mA
power consumption max. 2 W

Output to the ASC


injection voltage 230 V AC, 50 Hz
injection current approx. 7 A (max. 23 A))

Output to the controller


current transformer 1A
potential-free signal contacts 5 A / 250 V AC

Dimensions
width / height /depth 640 / 800 / 250 mm
mass approx. 75 kg

8
Technical Data for Basic Devices

Basic Device Controller Detection Controller & Expansion


Detection

EFC30

EFC40

EFD10-8

EFD10-16

EFD40-8

EFD40-16

EFX10-8

EFX10-16
Data
Hardware
CPU: 32 bit Transputer (RISC Prozessor)
x x x x x x x x
with floating point unit
ROM 1 MB 2 MB 2 MB 2 MB 2 MB 2 MB 2 MB 2MB
RAM 1 MB 8 MB 8 MB 8 MB 8 MB 8 MB 4 MB 4 MB
Display: double supertwist LCD 640 x 200 Pixel
x x x x x x
with back-light
Film designed keyboard x x x x x x
Power supply: 110-220 V DC, 230 V AC, 50 Hz, 50 W
x x x x x x x x
Optional: 24, 48, 60 V DC
Analogue inputs for voltage (amplitude):
1
3 mV...230 V AC
Analogue inputs for voltage (amplitude and phase):
4 4 4 4 4
3 mV...110 V AC
Analogue inputs for current injection (ECI):
4 4 4 4 4
0...1 A AC
Analogue inputs for zero-sequence currents:
8 16 8 16 8 16
0...1 A AC oder 0...5 A AC
Analogue input for coil position:
linear potentiometer 0...200 Ω bis 0...2 kΩ 1 1 1 1
or current imput 0...20 mA
Analogue output (for Uo, coil position, distance location):
2 2 2 2 2 2
0...20 mA, programmable
Digital inputs: potential free contacts
16 32 32 32 32 16 16
24...250 V AC od. DC
Digital inputs: potential free contacts
4
24 V DC, 60 mA
Digital inputs: potential free contacts
2
24...250 V AC od. DC
Digital autputs: potential free change over contacts
4 8 8 8 8 4 4
max: 250 V AC 1000 VA or 250 V DC 100 W
Digital autputs: potential free make contacts
7 12 24 24 24 24 12 12
max: 250 V AC 1000 VA or 250 V DC 100 W
Serial Interface: 3 x RS232 opt. opt. opt. opt. opt. opt.
Expansion with controller possible x x
Expansion with detection possible x x
Upgradeable for up to 24 feeders x x x x
Replica of the substation´s switching condition by means of groups x x x x x x
Replica of the substation´s switching board x x x x x x
100 V AC reference voltage necessary x x x x x
Software
Control operation by tuning of the ASC x x x x
Control operation by means of current injection x x x
Control operation at very low neutral-to-ground volt. x x x
Detection of high- and low-ohmic earth faults x x x x x x
Dual bus bar operation possible opt. x x x x x x x
SCADA system (SPABus, IEC/VDEW 6) opt. opt. opt. opt. opt. opt.
Mechanical Data
Mass in kg 8,2 13,5 18,0 19,5 18,0 19,5 15,5 18,0
Height of the 19“ rack in HE 3 6 6 6 6 6 6 6
W 483 483 483 483 483 483 483 483
Dimension in mm H 132,5 266 266 266 266 266 266 266
D 252 300 300 300 300 300 300 300
Case opt. opt. opt. opt. opt. opt. opt. opt.

9
Summary of the Electronic-Components
of EPSY (incl. Options)
EFC30 Basic device, earth fault compensation controller EFC30
EFD10-UD-8 EFC30-upgrade with the detection EFD10 for 8 feeders
EFD10-UD-16 EFC30-upgrade with the detection EFD10 for 16 feeders

EFC30-SIF Serial interface option


EFC30-AKL Terminal strip option
EFC30-WAND Wall-mounting option
EFC30-ADAPT EZR2-adapter
EFC30-DC Optional power supply voltage
EFC30-GEH Protective case for the EFC30
EFC30-HB Additional user manual
EFC30-SW-FIX Optional software for fixed coil control
EFC30-SW-RC* Optional software for resistor control
EFC30-SW-KN Optional software for KNOSPE resistor control
EFC30-SW-LS Optional software for control by external power switch
EFC30-SW-MR Optional software for more than one controller in the same network
EFC30-SW-UM Optional software for control at U>Umax
EFC30-SW-ZS* Optional software for time synchronisation by means of impulse input
EFC30-SW-U Optional software with special functions for large U0
EFC30-SW-LT Optional software for SCADA

EFC40 Basic device earth fault compensation controller EFC40


EFD40-UD-8 EFC40-upgrade by the detection for 8 feeders in the basic device
EFD40-UD-16 EFC40-upgrade by the detection for 16 feeders in the basic device

EFD10-8 Basic device for earth fault detection EFD10 for 8 feeders
EFD10-16 Basic device for earth fault detection EFD10 for 16 feeders
EFD40-UC EFD10-upgrade by the controller EFC40 in the basic device

EFD40-8 Compact device for 8 feeders, including controller and detection


EFD40-16 Compact device for 16 feeders, including controller and detection

EFD40-GEH Protective case for EFC40, EFD10 and EFD40


EFD40-SIF Serial interface option for EFC40, EFD10 and EFD40
EFD40-SW-LT Optional software for SCADA
EFD40-SW-STU Optional software for control of a step adjustable ASC
EFD40-SW-AWE Optional software for automatic reclosing function

EFX10-8 Expansion device for additional 8 feeders


EFX10-16 Expansion device for additional 16 feeders

EFX10-0 Expansion unit (empty)


EFX10-UD-8 EFX10 plug-in modul for additional 8 feeders
EFX10-UD-DI EFX10 plug-in modul for additional 16 digital inputs
EFX10-UD-DO EFX10 plug-in modul for additional 16 digital outputs

ECI-FL Current injection device (outdoor construction type)


ECI-IR Current injection device (indoor construction type)

EFD-EdC Detuning capacitor for polygon-method (fault distance location) incl. software

Remark: For detailed information about hard- and software-options please inquire and see the
corresponding user manual.
* These software options are also available in the EFC40 operation mode.
10
Examples for Upgrading Basic Devices

.... Necessary units for the upgrade

Upgrading of the controller EFC30 by the earth fault detection:

requested 8 Feeder 16 Feeder 24 Feeder


config. EFC30 EFC30 EFC30
EFD10-8 EFD10-16 EFD10-16
actual EFX10-8
config.
EFC30 EFD10-UD-8 EFD10-UD-16 EFD10-UD-16
EFX10-8

Upgrading of the controller EFC40 by the earth fault detection:

requested 8 Feeder 16 Feeder 24 Feeder


config. EFD40-8 EFD40-16 EFD40-16
EFX10-8
actual
config.
EFC40 EFD40-UD-8 EFD40-UD-16 EFD40-UD-16
EFX10-8

Upgrading of the earthfault detection EFD10 by additional feeders resp. by the controll function:

requested detection detection, control


config. 24 Feeder 16 Feeder
EFD10-16 EFD40-16
actual EFX10-8
config.
EFD10-16 EFX10-8 EFD40-UC

Upgrading of the compact device EFD40-16 by additional feeders:

requested 24 Feeder
config. EFD40-16
EFX10-8
actual
config.
EFD40-16 EFX10-8

11
Examples of System Configurations

Fig. 6 EFC30 in a one-busbar configuration

Fig. 7 EFC40 in a one-busbar configuration

12
Fig. 8 EFC40 in a two-busbar configuration

Fig. 9 EFD10 in a one-busbar configuration

13
Fig. 10 EFD10 in a two-busbar configuration

Fig. 11 Control and detection with EFD40 in a one-busbar configuration

14
Fig. 12 Control and detection with EFD40 in a two-busbar configuration with one tuneable and one fixed arc suppression coil

Fig. 13 Control and detection with EFD40 in a two-busbar configuration with two tuneable arc suppression coils

15
Trench Facilities

Trench® Austria GmbH Trench® Limited


Paschinger Strasse 49 Instrument Transformer Division
Postfach 13 390 Midwest Road
A-4060 Linz-Leonding Scarborough, Ontario
Austria Canada M1P 3B5
Phone: 43-732-6793-0 Phone: 416-751-8570
Fax: 43-732-671341 Fax: 416-751-6952

Trench® Brasil Ltda Trench® Limited


Via Expressa de Contagem, 2685 Power Line Carrier Division
Contagem, Minas Gerais 815 Middlefield Road, Unit 6A
CEP 32370-485 Scarborough, Ontario
Brazil Canada M1V 2P9
Phone: 55-31-3391-5959 Phone: 416-291-8544
Fax: 55-31-3391-1828 Fax: 416-291-5581

Trench® China Trench® France S.A.


MWB (Shanghai) Co., Ltd. 16, Rue du Général Cassagnou
No. 3658, Jiancheng Road B.P. 70 F-68 302
Minhang, Shanghai St. Louis, Cedex
Peoples Republic of China France
200245 Phone: 33-3 89-70-2323
The Trench Group is your Phone: 86-21-54720088 Fax: 33-3 89-67-2663
Fax: 86-21-54723118
Trench® Germany GmbH
partner of choice for electrical Trench® High Voltage Nürnberger Strasse 199
Products Ltd., Shenyang D-96050 Bamberg
No. 2 Zhengliang Er. Road Germany
power transmission and Jing Shen Xi San Street Phone: 49-951-1803-0
Dao Yi Economic Development Zone Fax: 49-951-1803-224
Shenyang 110136 P.R. China
distribution solutions today; Phone: 86-24-89722688 Trench® Switzerland AG
Fax: 86-24-89737200 Lehenmattstrasse 353
and for the development of CH-4028
Trench® Limited Basel
Bushing Division Switzerland
your new technology solutions 432 Monarch Avenue Phone: 41-61-315-51-11
Ajax, Ontario Fax: 41-61-315-59-00
Canada L1S 2G7
of tomorrow. Phone: 905-426-2665 Trench® (UK) Limited
Fax: 905-426-2671 South Drive
Hebburn
Trench® Limited Tyne & Wear
Coil Product Division NE 31 1 UW
71 Maybrook Drive Phone: 44-191-483-4711
Scarborough, Ontario Fax: 44-191-430-0633
Canada M1V 4B6
Phone: 416-298-8108
Fax: 416-298-2209

www.trenchgroup.com
E 665
Subject to change without notice (05.2006)
Printed in Canada.

Potrebbero piacerti anche