Simple Self-Diagnosis by Malfunction Code

After Sales Service Division


(SM-TS2)

0 1 2 3 4 5 6 7 8 9 A C E F H J
Detail
code
Division
External Malfunction of Malfunction of Malfunction of High pressure Malfunction of Malfunction of Malfunction of Malfunction of Heater overheat Stop due to low Low water level · Malfunction of a Malfunction of Malfunction of

A
protection indoor unit PCB drain level freezing control in fan motor swing flap motor power supply or electronic water level no water supply humidifier dust collector of capacity setting
Indoor Unit

device activated system protection heating, freeze- AC input expansion valve system air cleaner (Indoor unit
up protection overcurrent PCB)
control in cooling
Malfunction of Failure of Malfunction of Malfunction of Malfunction of Malfunction of Front panel Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of

C
sensor system transmission drain level liquid pipe gas pipe fan motor driving motor AC input current suction air discharge air humidity sensor switch box high pressure thermostat
(unified) (between indoor sensor thermistor for thermistor for sensor or fan fault sensor system thermistor thermistor system thermistor switch sensor in
unit PCB and heat exchanger heat exchanger control driver remote
sub PCB) controller
Protection Defect of Malfunction of Actuation of Actuation of low Inverter STD Malfunction of Overcurrent of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Actuation of

E
devices outdoor unit cold room high pressure pressure switch compressor compressor outdoor unit fan inverter electronic four way valve entering water drain water level thermal storage cooling water option
activated PCB thermistor switch (HPS) (LPS) motor or motor motor system compressor expansion valve or cool/heat temperature unit pump protection
(unified) overheat overcurrent/lock coil switching device

Malfunction of Malfunction of Abnormal high Abnormal high Abnormal low Abnormal oil Abnormal oil Abnormal high Abnormal

F
discharge pipe suction pipe pressure or pressure pressure pressure level or temperature of exhaust
temperature thermistor refrigerant actuation of shortage of oil refrigerant oil temperature of
overcharged HPS engine

Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Alarm in thermal High room Malfunction of

H
Outdoor Unit

sensor system room temperature power supply high pressure low pressure compressor position outdoor fan compressor outdoor air discharge air (hot) water drain water level storage unit or temperature thermal storage
of compressor sensor or sensor switch (HPS) switch (LPS) motor overload detection sensor motor signal input (CT) thermistor thermistor temperature sensor storage alarm tank water level
humidifier unit thermistor system thermistor controller
damper
Miswiring of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of

J
thermistor pressure sensor current sensor discharge pipe low pressure suction pipe heat exchanger thermistor thermistor thermistor high pressure low pressure oil pressure oil level sensor oil temperature engine room
of compressor thermistor equivalent thermistor thermistor (Refrigerant (Refrigerant (Refrigerant sensor sensor sensor or sub- or heating heat thermistor temp. sensor or
saturated circuit) circuit) circuit) tank thermistor exchanger exhaust temp.
temperature
sensor system thermistor
Malfunction of Malfunction of Electrical box Malfunction of Inverter Inverter Total input Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Engine startup Malfunction of Engine stop

L
inverter system inverter PCB temperature rise inverter instantaneous instantaneous overcurrent overcurrent inverter power transistor transmission igniter system error generator
radiating fin overcurrent (DC overcurrent (AC inverter compressor between control converter
temperature rise output) output) compressor startup error and inverter
(Stall prevention) PCB
Shortage of Power voltage Automatic Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Heat exchanger Automatic Refrigerant Refrigerant Automatic Malfunction of Refrigerant Improper

P
refrigerant imbalance or refrigerant thermistor in radiating fin DC current AC or DC output total input freezing protection refrigerant cylinder during cylinder during refrigerant starter actuation cylinder during combination
amount inverter PCB charge switch box temperature sensor current sensor current sensor during automatic charge automatic automatic charge automatic between
(thermal storage operation stop sensor refrigerant operation refrigerant refrigerant operation nearly refrigerant inverter and fan
unit) charging completed charging charging completed charging driver
Shortage of Reverse phase, Malfunction of Check operation Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Improper Malfunction of Malfunction of Wiring and Malfunction of Malfunction of

U
refrigerant open phase power supply or not executed or transmission transmission transmission transmission transmission transmission combination of setting of transmission piping mismatch system transmission
instantaneous transmission between indoor between indoor between indoor between outdoor between remote (other system) indoor and centralized between indoor (accessory
unit and
System

power failure error and outdoor unit unit and remote units units or outdoor controllers outdoor units controller centralized device)
controller storage unit address controller
Malfunction of Malfunction of Improper Address

M
centralized transmission combination of duplication,
remote between optional optional improper setting
controller PCB controllers for controllers for
centralized control centralized control
External Malfunction of Ozone density Contaminated Malfunction of Malfunction of Supply air Exhaust air Malfunction of Malfunction of Replace the Replace the Simplified Door switch Replace the

6
protection PCB abnormal sensor error thermistor for thermistor for passage closed passage closed dust collection damper system humidify deodorising remote open (HRV) high efficient
device activated indoor air (HRV) outdoor air unit (HRV) (HRV) element catalyst controller filter
(HRV) (HRV) malfunction
(HRV)
System No. 2 System No. 2 System No. 2 System No. 2 System No. 2 System No. 2 System No. 2 System No. 1 System No. 2 System No. 2 Malfunction of

7
Compressor Compressor Fan motor Actuation of Actuation of low Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of pump inter lock
overheat overcurrent overcurrent high pressure pressure switch low pressure high pressure fan inter lock fan inter lock compressor
switch (HPS) (LPS) sensor sensor current sensor
Others

Malfunction of Malfunction of System No. 1 System No. 2 System No. 1 System No. 2 System No. 1 System No. 2 Malfunction of Malfunction of System No. 1 System No. 1 Abnormal hot

8
entering water leaving water Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of Malfunction of brazed-plate dehumidification Malfunction of Malfunction of water high
temperature temperature refrigerant refrigerant heat exchanger heat exchanger discharge pipe discharge pipe heat exchanger or leaving water suction pipe suction pipe temperature
thermistor thermistor or thermistor thermistor thermistor thermistor thermistor temperature freezing temperature thermistor 1 for thermistor 2 for
drain pipe heater thermistor heating heating
Abnormal System No. 2 System No. 2 Malfunction of System No. 1 System No. 2 Malfunction of Malfunction of Malfunction of System No. 2 System No. 2

9
chilled water Malfunction of Malfunction of transmission Malfunction of Malfunction of thermal storage thermal storage thermal storage Malfunction of Malfunction of
quantity or electronic suction pipe (between heat inverter system inverter system unit brine pump brine tank suction pipe suction pipe
abnormal AXP expansion valve thermistor reclaim ventilation thermistor 1 for thermistor 2 for
unit and fan unit) heating heating
Simple Self-Diagnosis by Malfunction Code
Objects Objects

Malfunction Malfunction Malfunction Malfunction

Package

Package
Supposed causes Supposed causes

SkyAir

SkyAir
Chiller

Chiller
code Contents code Contents

HRV

HRV
VRV

VRV
RA

RA
External protection device activated External protection device connected to the terminal strip Actuation of low pressure switch Clogged refrigerant piping Shortage of gas
A0 T1-T2 of indoor unit is activated k k k E4 (LPS) Defect of connecting connector Defect of outdoor unit PCB k k k k
Malfunction of indoor unit PCB Malfunction due to noise Overheat of inverter compressor Shortage of refrigerant amount Defect of connector contact
A1 Defect of indoor unit PCB k k k k E5 motor Leakage of four way valve k k
Malfunction of drain level control Drain piping clogging, improper drain piping work Inverter compressor motor lock Inverter compressor lock
A3 system Defect of drain pump Defect of float switch k k k E5 Incorrect wiring k k k
Malfunction of freezing protection Shortage of water volume Low water temperature setting STD compressor motor Closed stop valve
A4 Defect of 26WL Defect of water temperature thermistor k E6 overcurrent/lock STD compressor lock k k k k
High pressure control in heating, Clogged air filter of indoor unit and short-circuit System No.1 Defect of EXP. valve Shortage of refrigerant amount
A5 freeze-up protection control in cooling Defect of indoor unit heat exchanger thermistor k E6 Compressor overcurrent Defect of compressor k
Fan motor locked, overload, Defect of connector contact Defect of fan motor Malfunction of outdoor unit fan Faulty contact of fan motor connector
A6 overcurrent Defect of indoor unit PCB k k k k E7 motor Defect of fan motor Defect of fan motor driver k k k k k
Malfunction of swing flap motor Failure of swing flap motor Defect of indoor unit PCB Overcurrent of inverter compressor Defect of compressor Defect of outdoor unit PCB
A7 Jammed swing mechanism/blade k k E8 Defect of inverter main circuit capacitor Defect of power transistor k
Malfunction of power supply Overcurrent of AC input Malfunction of electronic expansion Defect of electronic expansion valve Defect of connector contact
A8 Defect of power supply voltage k k E9 valve coil Defect of outdoor unit PCB k k k k
Malfunction of electronic expansion Defect of electronic expansion valve coil Malfunction of four way valve Defect of four way valve Shortage of gas
A9 valve drive Defect of indoor unit PCB Defect of connector contact k k EA Defect of outdoor unit PCB Defect of thermistor k
Heater overheat 26WH is activated Malfunction of entering water Malfunction of cooling water temperature
AA k EC temperature Defect of thermistor Defect of outdoor unit PCB k
Indoor Unit

Malfunction of a humidifier system Water leakage of humidifier (option)


AF Failure of swing float switch Improper drain piping incline k k
EF
Malfunction of thermal storage unit Defect of electronic expansion valve of thermal storage unit
Defect of thermal storage PCB k
Malfunction of dust collector of air Defect of dust collecting element Stained insulator part
AH cleaner Defect of high voltage power supply unit Defect of indoor unit PCB k k k
F3
Malfunction of discharge pipe
temperature
Shortage of gas
Defect of connector contact
Clogged refrigerant piping
Defect fo discharge pipe thermistor k k k k k

Outdoor Unit
Malfunction of capacity setting Capacity setting adaptor is not installed when replacing PCB
AJ (Indoor unit PCB) Defect of indoor unit PCB k k k
F6
Abnormal high pressure in cooling Defect of outdoor unit fan motor
Defect of heat exchanger thermistor
Defect of electronic expansion valve
Defect of outdoor unit PCB k
Failure of transmission (between Defect of transmission of fan motor control driver
C1 indoor unit PCB and fan PCB) k k
F6
Refrigerant overcharged Refrigerant overcharged
Disconnection of heat exchanger thermistor
Disconnection of outdoor air thermistor
Disconnection of liquid pipe thermistor k k
Malfunction of liquid pipe thermistor Defect of connector contact
C4 for heat exchanger Defect of liquid pipe thermistor for heat exchanger k k k k
H0
Malfunction of sensor system of
compressor
Harness is disconnected, or defective connection
Defect of PCB k
Malfunction of gas pipe thermistor Defect of connector contact
C5 for heat exchanger Defect of gas pipe thermistor for heat exchanger k k k
H1
Malfunction of humidifier unit
damper
Defect of limit switch
Defect of damper k
Malfunction of fan motor control Defect of fan motor sensor system
C6 driver Defect of fan motor control driver k k
H3
Malfunction of high pressure switch Defect of high pressure switch
(HPS) Defect of connector contact
Broken wire
Defect of outdoor unit PCB k k k k
Front panel driving motor fault Defect of front panel driving motor
C7 Defect of limit switch k
H4
Malfunction of low pressure switch
(LPS)
Defect of low pressure switch
Defect of connector contact
Broken wire
Defect of outdoor unit PCB k k
Malfunction of suction air thermistor Defect of connector contact
C9 Defect of thermistor for suction air k k k k
H5
Malfunction of compressor motor
overload thermistor
Defect of connector contact
Defect of compressor motor overload thermistor k
Malfunction of discharge air Defect of connector contact
CA thermistor Defect of thermistor for discharge air k k
H6
Malfunction of position detection
sensor
Faulty contact of compress or cable
Defect of compressor Defect of outdoor unit PCB k
Malfunction of humidity sensor Defect of connector contact
CC system Defect of humidity sensor k k
H7
Malfunction of outdoor fan motor
signal
Faulty contact of fan wiring
Defect of fan motor driver
Defect of fan motor
k k k
Malfunction of thermostat sensor in Defect of remote controller thermistor Malfunction due to noise
CJ remote controller Defect of remote controller PCB k k k
H8
Malfunction of compressor input
(CT) system
Defect of power transistor Defect of reactor
Faulty wiring of inverter system Defect of outdoor unit PCB k
Protection devices actuated Protection device connected to outdoor PCB actuated
E0 (unified) Defect of protection device connector contact k k k
H9
Malfunction of outdoor air Defect of connector contact
k k k k k
Outdoor Unit

thermistor Defect of thermistor for outdoor air


Defect of outdoor unit PCB Malfunction due to noise
E1 Defect of outdoor unit PCB k k k k k
HC
Malfunction of (hot) water
temperature thermistor
Defect of connector contact Defect of outdoor unit PCB
Defect of thermistor for water temperature k k
Actuation of high pressure switch Dirty outdoor unit heat exchanger and suction filter Defect of HPS
E3 (HPS) Clogged refrigerant piping Defect of connector contact k k k k
HF
Alarm in thermal storage unit with
ice
Thermal storage group defective wiring Defect of setting
Excess of thermal storage tank numbers k k
System No.1 Dirty outdoor unit heat exchanger Shortage of water volume
Malfunction of thermal storage tank Low water level Defect of switch setting
E3 Actuation of high pressure switch (HPS) Clogged refrigerant piping
Defect of HPS
Defect of connector contact k HJ water level Water level detecting sensor failure Defect of connector contact k k
Simple Self-Diagnosis by Malfunction Code
Objects Objects

Malfunction Malfunction Malfunction Malfunction

Package

Package
Supposed causes Supposed causes

SkyAir

SkyAir
Chiller

Chiller
code Contents code Contents

HRV

HRV
VRV

VRV
RA

RA
Malfunction of pressure sensor Defect of pressure sensor connector contact Power voltage imbalance, open Open phase Voltage imbalance between phases
J1 Defect of pressure sensor Defect of outdoor unit PCB k k P1 phase Faulty main circuit capacitor Defect of wiring contact k k k k
Malfunction of current sensor of Defect of current sensor Defect of compressor Automatic refrigerant charge Closed stop valve
J2 compressor Defect of outdoor unit PCB k k k k P2 operation stop Closed valve of refrigerant tank k k
Malfunction of discharge pipe Defect of connector contact Defect of discharge pipe thermistor Malfunction of thermistor in Electrical box temperature rise (ambient temperature rise)
J3 thermistor Defect of outdoor unit PCB k k k k k P3 electrical box Defect of fin thermistor Defect of outdoor unit PCB k k
Malfunction of low pressure equivalent Defect of connector contact Defect of thermistor Malfunction of radiating fin Defect of radiating fin thermistor Defect of wiring contact
J4 saturated temperature sensor system Defect of outdoor unit PCB (Multi-split, Super-multi ) k P4 temperature sensor Defect of outdoor unit PCB k k k k
Malfunction of suction pipe Defect of connector contact Defect of suction pipe thermistor Heat exchanger freezing protection (Close the refrigerant cylinder. Start again from step 1.)
J5 thermistor Defect of outdoor unit PCB k k k k k P8 during automatic refrigerant charging k k
Malfunction of heat exchanger Defect of connector contact Defect of heat exchanger thermistor Malfunction of fan motor Defect of fan motor Defect of outdoor unit PCB
J6 thermistor Defect of outdoor unit PCB k k k k k P9 (humidifier unit) Broken relay harness Defect of connector contact k

Outdoor Unit
Malfunction of liquid pipe thermistor Defect of connector contact Defect of liquid pipe thermistor Automatic refrigerant charge
J7 (Refrigerant circuit and others) Defect of outdoor unit PCB k k k k P9 operation completed — k k
Malfunction of liquid pipe thermistor Defect of connector contact Defect of liquid pipe thermistor Broken wire of heater Defect of heater unit Defect of thermistor
J8 (Refrigerant circuit and others) Defect of outdoor unit PCB k PA (humidifier unit) Defect of outdoor unit PCB k
Malfunction of gas pipe thermistor Defect of connector contact Defect of gas pipe thermistor Empty refrigerant cylinder during Refrigerant cylinder of master unit is empty
J9 (Refrigerant circuit and others) Defect of outdoor unit PCB k k k k PA automatic refrigerant charging k k
Malfunction of high pressure sensor Defect of connector contact Defect of high pressure sensor Empty refrigerant cylinder during Refrigerant cylinder of slave unit 2 is empty
JA Defect of outdoor unit PCB k k k k PC automatic refrigerant charging k k
Malfunction of low pressure sensor Defect of connector contact Defect of low pressure sensor Automatic refrigerant charge
JC Defect of outdoor unit PCB k k k k PE operation nearly completed — k k
Malfunction of sub-tank thermistor Defect of connector contact Defect of sub-tank thermistor Malfunction of temperature Defect of heater unit Defect of connector contact
JE Defect of outdoor unit PCB k PH (humidifier unit) Defect of thermistor Defect of outdoor unit PCB k
Outdoor Unit

Malfunction of heating thermistor Defect of connector contact Defect of heat exchanger thermistor Empty refrigerant cylinder during Refrigerant cylinder of slave unit 1 is empty
JF for heat exchanger Defect of outdoor unit PCB k PH automatic refrigerant charging k k
Malfunction of oil temperature Defect of connector contact Defect of oil temperature thermistor Malfunction of capacity setting Capacity setting adaptor is not installed Improper capacity setting adaptor
JH thermistor Defect of outdoor unit PCB k PJ (Outdoor unit PCB) Defect of outdoor unit PCB k
Malfunction of inverter system Shortage of power supply capacity Defect of power transistor Improper combination between Mistake of inverter PCB Mistake of inverter fan PCB
L0 Defect of inverter PCB k PJ inverter and fan driver Mistake of control PCB k k
Malfunction of inverter PCB Defect of compressor wiring Defect of outdoor unit fan motor Shortage of refrigerant Shortage of refrigerant Clogged refrigerant piping
L1 Blown fuse Defect of inverter PCB k k U0 Closed stop valve k k k k k
Electrical box temperature rise Fin temperature rise due to short-circuit Defect of outdoor unit fan Reverse phase, open phase Reverse phase, open phase of power wiring
L3 Defect of power transistor Defect of outdoor unit PCB k U1 Wrong wiring Defect of outdoor unit PCB k k k k k
Malfunction of inverter radiating fin Fin temperature rise due to short-circuit Defect of power supply voltage or Defect of power supply voltage Instantaneous power failure
L4 temperature rise Defect of fin thermistor k k k k U2 instantaneous power failure Defect of wiring contact k k k k
Inverter instantaneous overcurrent Closed stop valve Check operation not executed Check operation not executed
L5 (DC) Defect of compressor k k k k U3 k k
Malfunction of transmission Malfunction due to noise Wrong wiring
L6
Inverter instantaneous overcurrent
(AC)
Overcharge of refrigerant amount Shortage of power supply capacity
Defect of compressor Defect of inverter unit k U3 Defect of outdoor unit PCB k
System

Malfunction of transmission Defect or indoor-outdoor transmission wiring


Overcurrent of inverter compressor Abnormal high pressure rise due to clogged refrigerant circuit and others
L8 Defect of compressor k k k U4 between indoor and outdoor unit Malfunction due to noise
Defect of indoor unit PCB and outdoor unit PCB
k k k k k
Malfunction of inverter compressor Faulty of pressure equalization Defect of compressor Malfunction of transmission between Defect of remote controller wiring Defect of indoor unit PCB
L9 startup Defect of compressor wiring k k k U5 indoor unit and remote controller Malfunction due to noise Defect of remote controller main/sub setting k k k k k k
Malfunction of power transistor Defect of power transistor Defect of compressor Malfunction of transmission Faulty wiring Malfunction due to noise
LA Defect of inverter PCB k U6 between indoor units Defect of indoor unit PCB k
Malfunction of transmission between Defect of grounding connection Malfunction due to noise Malfunction of transmission between main Harness disconnection/broken wire between PCB
LC outdoor unit PCB and micro-computer Defect of outdoor unit PCB k U7 body micro-computer - INV micro-computer Defect of outdoor unit PCB k
Malfunction of transmission Defect of connector contact Malfunction due to noise Malfunction of transmission Defect of wiring between outdoor units Defect of outdoor unit switch setting
LC between control and inverter PCB Defect of inverter PCB Defect of outdoor unit control PCB k k k U7 between outdoor units Defect of wiring between outdoor - thermal storage units k k k
Shortage of refrigerant amount Shortage of refrigerant Malfunction of transmission Defect of remote controller main/sub setting
P0 (thermal storage unit) Clogged refrigerant piping k U8 between remote controllers Defect of remote controller wiring Defect of remote controller PCB k k k k
Simple Self-Diagnosis by Malfunction Code
Objects Objects

Malfunction Malfunction Malfunction Malfunction

Package

Package
Supposed causes Supposed causes

SkyAir

SkyAir
Chiller

Chiller
code Contents code Contents

HRV

HRV
VRV

VRV
RA

RA
Malfunction of transmission (other Defect of communication between other indoor unit and outdoor unit System No. 1 Defect of relay contact
U9 system) Other indoor unit electronic expansion valve failure k k 77 Malfunction of fan inter lock Broken wire k
Defect of indoor/outdoor power Wrong model connections Improper power supply System No. 2 Defect of relay contact
UA supply Wrong PCB connected Defect of PCB k 78 Malfunction of fan inter lock Broken wire k
Malfunction of field setting Malfunction of field setting by remote controller System No. 2 Defect of current sensor Defect of compressor
UA Defect of remote controller wiring
Defect of indoor unit PCB
Defective connection of optional device k 7A Malfunction of current sensor of compressor Defect of outdoor unit PCB k
Improper combination of indoor and Excess of connected indoor units Malfunction of field setting System No. 2 Cooling water pump interlock actuated
UA outdoor units Uncanceled service mode Defect of outdoor unit PCB k k k 7C Malfunction of pump inter lock k
Remote temperature setting wire Remote temperature setting wire disconnection Malfunction of entering water Defect of connector contact
UA disconnection Defect of connector contact k 80 temperature thermistor Defect of entering water temperature thermistor k
Malfunction of setting of centralized Address duplication of centralized controller Malfunction of leaving water Defect of connector contact
UC controller address k k k 81 temperature thermistor Defect of leaving water temperature thermistor k
Malfunction of transmission between Malfunction of wiring between indoor unit and centralized controller System No. 1 Defect of connector contact
UE k k k k k 82 k
System

indoor unit and centralized controller Defect of setting of group number Defect of indoor unit PCB Malfunction of refrigerant thermistor Defect of refrigerant thermistor
Wiring and piping mismatch Improper connection of transmission wiring between System No. 2 Defect of connector contact
UF indoor-outdoor units and outdoor-outdoor units k k k 83 Malfunction of refrigerant thermistor Defect of refrigerant thermistor k
Malfunction of system Improper connection of transmission wiring between indoor- System No. 1 Defect of connector contact
UH
outdoor units and outdoor-outdoor units Defect of indoor
(k) k k 84 Malfunction of heat exchanger thermistor Defect of heat exchanger thermistor k
and outdoor unit PCB (RA: Mismatching indoor and outdoor
units, Defect of voltage, Freeze protection in other indoor unit System No. 2 Defect of connector contact
Malfunction of transmission Defect of accessory devices 85 Malfunction of heat exchanger thermistor Defect of heat exchanger thermistor k
UJ (Accessory devices) Faulty wiring k k System No. 2 Defect of connecting connector
Malfunction of centralized remote Defect of centralized remote controller PCB 86 Malfunction of discharge pipe thermistor Defect of discharge pipe thermistor k
M1 controller PCB k k k k k k System No. 2 Shortage of gas Defect of discharge pipe thermistor
Malfunction of transmission between Other centralized control power disconnection Centralized control reset switch ON 88 Malfunction of discharge pipe temperature Defect of connector contact Clogged refrigerant piping k

Others
M8 optional controllers for centralized control Defect of transmission wiring Central remote controller address change k k k k k k Malfunction of brazed-plate heat Dirty heat exchanger Shortage of refrigerant amount
Improper combination of optional Improper combination of optional controllers for centralized control 89 exchanger freezing Defect of thermistor k
controllers for centralized control More than one master controller is connected
MA Faulty setting of centralized control k k k k k k
8A
System No. 2
Malfunction of leaving water temperature thermistor
Defect of connector contact
Defect of leaving water temperature thermistor k
Defect of centralized control
Address duplication, improper Address duplication of central remote controller System No. 1 Defect of connector contact
MC setting k k k k k k 8E Malfunction of suction pipe thermistor 1 for heating Defect of suction pipe thermistor k
External protection device actuated Actuation of external protection device System No. 1 Defect of connector contact
60 Defect of output signal wiring Defect of control PCB k 8F Malfunction of suction pipe thermistor 2 for heating Defect of suction pipe thermistor k
Malfunction of indoor air thermistor Defect of connecting connector Defect of thermistor for indoor air Abnormal high hot water Three-way valve malfunction Defect of thermistor
64 Defect of control PCB k 8H temperature Defect of water temperature setting k
Malfunction of outdoor air Defect of connector contact Defect of outdoor air thermistor Abnormal chilled water quantity, Shortage of water volume
65 thermistor Defect of control PCB k 90 abnormal AXP Disconnection of AXP k
Malfunction of damper system Defect of connector contact Defect of limit switch System No. 2 Defect of connector contact
6A Defect of damper motor Defect of control PCB k 91 Malfunction of electronic expansion valve Defect of electronic expansion valve coil k
System No. 2 Shortage of refrigerant amount Defect of connector contact System No. 2 Defect of connector contact
92 k
Others

70 Compressor overload Leakage of four way valve k Malfunction of suction pipe thermistor Defect of suction pipe thermistor
System No. 2 Shortage of refrigerant amount Short-circuit Malfunction of transmission (between Defect of fan unit PCB
71 Compressor overcurrent Defect of compressor k 94 heat reclaim ventilation unit and fan unit) Defect of connecting wire between (1) and (2) k
System No. 2 Defect of fan motor connector contact System No. 1 Defect of fan inverter unit
72 Fan motor overcurrent Defect of fan motor Defect of PCB k 95 Malfunction of inverter system k
System No. 2 Dirty heat exchanger Shortage of water volume System No. 2 Defect of fan inverter unit
73 Malfunction of high pressure (HPS) actuated Clogged refrigerant piping
Defect of HPS
Defect of connector contact k 96 Malfunction of inverter system k
System No. 2 Clogged refrigerant piping Defect of connector contact Malfunction of thermal storage unit Defect of thermal storage unit
74 Malfunction of low pressure switch (LPS) Shortage of gas Defect of LPS k 97 k
System No. 2 Defect of connector contact Defect of low pressure sensor Malfunction of thermal storage Actuation of thermal storage brine pump overcurrent (OC)
75 Malfunction of low pressure sensor Defect of PCB k 98 brine pump k
System No. 2 Defect of connector contact Defect of high pressure sensor Malfunction of thermal storage Low water level of thermal storage brine tank
76 Malfunction of high pressure sensor Defect of PCB k 99 brine tank k