Sei sulla pagina 1di 16

CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE

CHAPTER 3 – GENERAL REQUIREMENTS


(Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and building application.)
HCD DSA OSHPD
Adopting Agency BSC SFM BSCC DPH AGR DWR CA SL SLC
1 2 1-AC AC SS SS/CC 1 2 3 4

Adopt Entire Chapter X X X


Adopt Entire Chapter as amended
X X X X X X X
(amended sections listed below)

Adopt only those sections that are


listed below
Chapter/Section
303.3, Exception 2 X X X X
303.8 X X X
303.8.1 X X
315.0 X X X X

LY
323.0 X X X
324.1 X X
324.2 X X
325.1 X X
325.2
325.3
N X
X
X
O
326.0 X X X X
Table 325 X X X X
D
EA
R

2013 CALIFORNIA MECHANICAL CODE 43


LY
N
O
D
EA
R

44 2013 CALIFORNIA MECHANICAL CODE


CHAPTER 3
GENERAL REQUIREMENTS

301.0 General. Exceptions:


301.1 Applicability. This chapter covers general require- (1) The installation clearances for furnaces and boilers in
ments for heating, ventilating, air-conditioning, refrigeration, rooms not large in comparison with the size of the equip-
miscellaneous heat-producing, and energy-utilizing equip- ment shall be as specified in the appliance listing regard-
ment. Such equipment shall conform to the requirements of less of whether the enclosure is of combustible or
this code. noncombustible materials and shall not be reduced by the
Equipment shall not be installed or altered in violation protection methods described in Table 303.3(1) or any
of this code, nor shall the fuel input rate to equipment be other method.
increased in excess of the approved British thermal unit per (2) [OSHPD 1, 2, 3 & 4] A 25 percent reduction in the boiler
hour (Btu/h) (kW) rating at the altitude where it is being used. room volume is allowed with forced-draft boilers and
approved ventilation of the boiler room. In no case shall
Defective material or parts shall be replaced in such a
boiler room volume or clearances be reduced below
manner as not to invalidate an approval.
those required by the conditions of the boiler listing. The
boiler and the boiler room ventilation system, including

LY
302.0 Approval. fans, controls, and damper motors shall be on emergency
302.1 How Obtained. Each appliance shall be approved by power when required by Section 326.0. The ventilation
the Authority Having Jurisdiction for safe use or comply with system shall either operate continuously, or, if inter-
applicable nationally recognized standards as evidenced by locked with the boiler(s) it shall not interfere with the

standards is included in Chapter 17.


N
the listing and label of an approved agency. A list of accepted proper boiler operation.
Where the ceiling height of the room or space exceeds 8
feet (2438 mm), the volume shall be calculated on the basis
O
302.2 Complying Design of Equipment. Installers shall
furnish satisfactory evidence that the appliance is constructed of an 8 foot (2438 mm) height.
in accordance with the requirements of this code. The perma- 303.4 Unlisted Appliances. Unlisted appliances shall be
nently attached label of an approved agency shall be installed with the standard clearances from combustible
D

permitted to be accepted as such evidence. construction specified in Table 303.4. Unlisted appliances
302.3 Oil-Burning Appliances. The tank, piping, and valves shall have the standard clearances of Table 303.4 reduced by
for appliances burning oil shall be installed in accordance employing the forms of protection specified in Table
EA

with the requirements of NFPA 31. 303.3(1). Forms of protection specified in Table 303.3(1)
shall be permitted to be utilized to reduce clearances to
combustible construction for applicable appliances.
303.0 Installation. 303.5 Anchorage of Appliances. Appliances designed to be
303.1 Installation Practices. Mechanical systems shall be fixed in position shall be securely fastened in place in accor-
R

installed in a manner in accordance with this code, applicable dance with the manufacturer’s installation instructions.
standards, and the manufacturer’s installation instructions. Supports for appliances shall be designed and constructed to
303.2 Listed Appliances. Except as otherwise provided in sustain vertical and horizontal loads within the stress limita-
the code, the installation of appliances regulated by this code tions specified in the building code.
shall be in accordance with the conditions of listing. The 303.6 Movement. Movement of appliances with casters shall
appliance installer shall leave the manufacturer’s installation be limited by a restraining device installed in accordance with
and operating instructions attached to the appliance. Clear- the connector and appliance manufacturer’s installation
ances of listed appliances from combustible materials shall instructions.
be as specified in the listing or on the rating plate. 303.7 Identification of Equipment. Where more than one
303.3 Room Large in Comparison to Size of Equipment. heating, cooling, ventilating, or refrigerating system is
Central-heating furnaces not listed for closet or alcove instal- installed on the roof of a building or within a building, it shall
lation shall be installed in a room or space having a volume be permanently identified as to the area or space served by
not less than 12 times the total volume of the furnace; central- the equipment.
heating boilers not listed for closet or alcove installation shall 303.8 Liquefied Petroleum Gas Facilities. Containers,
be installed in a room or space having a volume 16 times the container valves regulating equipment, and appurtenances for
volume of the boiler. [OSHPD 1, 2, 3 & 4] The total volume the storage and supply of liquefied petroleum gas shall be
of the boilers shall be based on the total number of central- installed in accordance with NFPA 58 and the California Fire
heating boilers that can operate at the same time. Code.

2013 CALIFORNIA MECHANICAL CODE 45


GENERAL REQUIREMENTS

303.8.1 Liquefied Petroleum Gas Appliances. [HCD 1 & heaters or room heaters. The operating instructions shall be
HCD 2] Liquefied petroleum gas-burning appliances shall attached to the appliance where they are capable of being read
not be installed in a pit, basement, or similar location easily.
where heavier-than-air gas might collect. Appliances so 304.2 Access to Equipment and Appliances on Roofs.
fueled shall not be installed in an above-grade under-floor Appliances located on roofs or other elevated locations shall
space or basement unless such location is provided with be accessible. [NFPA 54:9.4.3.1]
an approved means for removal of unburned gas.
304.2.1 Access from Inside. Buildings exceeding 15 feet
303.9 Equipment on Roofs. Equipment on roofs shall be (4572 mm) in height shall have an inside means of access
designed or enclosed so as to withstand climatic conditions in to the roof, unless other means acceptable to the Authority
the areas in which it is installed. Where enclosures are Having Jurisdiction are used. [NFPA 54:9.4.3.2]
provided, each enclosure shall be of reasonable height, and
shall have not less than a 30 inch (762 mm) clearance between 304.2.1.1 Door or Scuttle. The inside means of
the entire service access panel(s) of the equipment and the access shall be a permanent or foldaway inside
wall of the enclosure. [NFPA 54:9.4.1.1] stairway or ladder, terminating in an enclosure,
scuttle, or trap door. Such scuttles or trap doors shall
303.9.1 Roof Support. Roofs on which equipment is to be not less than 22 inches by 24 inches (559 mm by
be installed shall be capable of supporting the additional
610 mm) in size, shall open easily and safely under
load or shall be reinforced to support the additional load.
all conditions, especially snow, and shall be
[NFPA 54:9.4.1.2]
constructed so as to permit access on the inside.
303.9.2 Corrosion Resistance. Access locks, screws,

LY
Not less than 6 feet (1829 mm) of clearance
and bolts shall be of corrosion-resistant material. [NFPA
shall be between the access opening and the edge of
54:9.4.1.3]
the roof or similar hazard, or rigidly fixed rails or
303.9.3 Roof Drainage and Rails. Equipment shall be guards not less than 42 inches (1067 mm) in height
installed on a well-drained surface of the roof. Not less shall be provided on the exposed side. Where para-
than 6 feet (1829 mm) between a part of the equipment
N
and the edge of a roof or similar hazard, or rigidly fixed
rail, guards, parapets, or other building structures not less
than 42 inches (1067 mm) in height shall be provided on
pets or other building structures are utilized in lieu of
guards or rails, they shall be not less than 42 inches
(1067 mm) in height. [NFPA 54:9.4.3.3]
O
the exposed side. [NFPA 54:9.4.2.2] 304.2.1.2 Permanent Ladders. Permanent ladders
required by Section 304.2.1.1 shall be constructed
303.9.4 Electrical Power. Equipment requiring an
in accordance with the following:
external source of electrical power for its operation shall
be provided with the following: (1) Have side railings which extend not less than 30
D

inches (762 mm) above the roof or parapet wall.


(1) Readily accessible electrical disconnecting means
within sight of the equipment. (2) Landings shall not exceed 18 feet (5486 mm)
EA

(2) A 120 VAC grounding-type receptacle outlet on the apart measured from the finished grade.
roof adjacent to the equipment. The receptacle outlet (3) Width shall be not less than 14 inches (356 mm)
shall be on the supply side of the disconnect switch. on center.
[NFPA 54:9.4.2.3] (4) Rungs shall not exceed 14 inches (356 mm) on
center.
R

304.0 Service and Access to Equipment and Appliances. (5) Toe space shall be not less than 6 inches (152
304.1 General. Equipment and appliances shall be accessible mm).
for inspection, service, repair, and replacement without 304.2.2 Permanent Lighting. Permanent lighting shall
removing permanent construction. Clearance shall be main- be provided at the roof access. The switch for such
tained to: lighting shall be located inside the building near the
(1) Clean heating surfaces. access means leading to the roof. [NFPA 54:9.4.3.4]
(2) Replace filters, blowers, motors, burners, controls, and 304.2.3 Standing Water. Where water stands on the roof
vent connections. at the equipment, in the passageways to the equipment,
(3) Lubricate moving parts. where the roof is of a design having a water seal, a plat-
form, walkway, or both shall be provided above the
(4) Adjust and clean burners, pilots, and the proper func- waterline. Such platform(s) or walkway(s) shall be
tioning of explosion vents, where provided. [NFPA located adjacent to the equipment and control panels so
54:9.2.1]
that the equipment is capable of being safely serviced
Unless otherwise specified, not less than 30 inches (762 where water stands on the roof. [NFPA 54:9.4.2.4]
mm) in depth, width, and height of working space shall be
provided.
Exception: Unit heaters and room heaters shall be permitted 305.0 Automatic Control Devices.
to be installed with an 18 inches (457 mm) minimum depth 305.1 General. Heating appliances shall be equipped with a
working space. A platform shall not be required for unit listed device or devices that will shut off the fuel supply to the

46 2013 CALIFORNIA MECHANICAL CODE


GENERAL REQUIREMENTS

main burner or burners in the event of pilot or ignition failure. 307.2 Fuel-Burning Appliances. Fuel-burning heating appli-
Liquefied petroleum gas-air-burning heating appliances shall ances shall bear a permanent and legible factory-applied
be equipped with a listed automatic device or devices that will nameplate on which shall appear:
shut off the flow of gas to the pilot in the event of ignition (1) The manufacturer’s name.
failure.
(2) The approved fuel input rating of the appliance,
Exception: The listed shutoff devices shall not be required expressed in Btu/h (kW).
on range or cooking tops, log lighters, lights, or other
(3) The model and serial number.
open-burner manually operated appliances, or listed appli-
ances not requiring such devices and specific industrial appli- (4) Instructions for the lighting, operation, and shutdown of
ances as approved by the Authority Having Jurisdiction. the appliance.
Heating appliances whose manual fuel controls are not (5) The type of fuel approved for use with the appliance.
readily accessible from the main portion of the building being (6) The symbol of an approved agency certifying compli-
heated shall be equipped with remote controls. ance of the equipment with recognized standards.
Forced-air and gravity-type warm air furnaces shall be (7) Required clearances from combustible surfaces on which
equipped with a listed air outlet temperature limit control that or adjacent to which it is permitted to be mounted.
cannot be set for temperatures exceeding 250˚F (121˚C). Such 307.3 Electric Heating Appliances. Electric heating appli-
controls shall be located in the bonnet or plenum, within 2 ances shall bear a permanent and legible factory-applied
feet (610 mm) of the discharge side of the heating element of nameplate on which shall appear:

LY
gravity furnaces or in accordance with the conditions of (1) The name or trademark of the manufacturer.
listing.
(2) The catalog (model) number or equivalent.
Electric duct heaters shall be equipped with an approved
automatic reset air outlet temperature limit control that will (3) The electrical rating in volts, amperes (or watts), and for
limit the outlet air temperature to not exceed 200°F (93°C). other than single phase, the number of phases.
N
The electric elements of the heater shall be equipped with
fusible links or a manual reset temperature limit control that
will prevent outlet air temperature in excess of 250°F (121°C).
(4) The output rating in Btu/h (kW).
(5) The electrical rating in volts, amperes, or watts of each
O
field-replaceable electrical component.
(6) The symbol of an approved agency certifying compli-
306.0 Standards. ance of equipment with recognized standards.
306.1 General. Standards listed or referred to in this chapter (7) Required clearances from combustible surfaces on which
D

or other chapters cover materials that will conform to the or adjacent to which it is permitted to be mounted.
requirements of this code, where used in accordance with the An appliance shall be accompanied by clear and
limitations imposed in this or other chapters thereof and their complete installation instructions, including required clear-
EA

listing. Where a standard covers materials of various grades, ances from combustibles other than mounting or adjacent
weights, quality, or configurations, the portion of the listed surfaces, and temperature rating of field-installed wiring
standard that is applicable shall be used. Design and mate- connections exceeding 140°F (60°C).
rials for special conditions or materials not provided for 307.4 Heat Pump and Electric Cooling Appliances. Heat
herein shall be permitted to be used by special permission of pumps and electric cooling appliances shall bear a permanent
R

the Authority Having Jurisdiction after the Authority Having and legible factory-applied nameplate on which shall appear:
Jurisdiction has been satisfied as to their adequacy. A list of
(1) The name or trademark of the manufacturer.
accepted mechanical material standards is included in Table
1701.0. (2) The catalog model nomenclature.
(3) The amount and type of refrigerant.
307.0 Labeling. (4) The factory test pressures or pressures applied.
307.1 Marking. Each length of pipe and each pipe fitting, (5) The electrical rating in volts, amperes, and for other than
material, and device used in a mechanical system shall have single phase, the number of phases.
cast, stamped, or indelibly marked on it the manufacturer’s (6) The output rating in Btu/h (kW).
mark or name, which shall readily identify the manufacturer (7) The electrical rating in volts, amperes, or watts of each
to the end user of the product. Where required by the field replaceable electrical component.
approved standard that applies, the product shall be marked (8) The symbol of an approved agency certifying compli-
with the weight and the quality of the product. Materials and ance of the equipment with recognized standards.
devices used or entering into the construction of mechanical
systems, or parts thereof, shall be marked and identified in a (9) Required clearances from combustible surfaces on which
manner satisfactory to the Authority Having Jurisdiction. or adjacent to which it is permitted to be mounted.
Such marking shall be done by the manufacturer. Field mark- An appliance shall be accompanied by clear and
ings shall not be acceptable. complete installation instructions, including required clear-

2013 CALIFORNIA MECHANICAL CODE 47


GENERAL REQUIREMENTS

ances from combustible other than mounting or adjacent 309.0 Improper Location.
surfaces, and temperature rating of field-installed wiring 309.1 General. Piping or equipment shall not be so located as
connections exceeding 140°F (60°C). to interfere with the normal use thereof or with the normal oper-
ation and use of windows, doors, or other required facilities.
308.0 Location.
308.1 Protection Against Damage. Gas utilization appli- 310.0 Electrical Connections.
ances in garages and in adjacent spaces that open to the 310.1 General. Equipment regulated by this code requiring
garage and are not part of the living space of a dwelling unit electrical connections of more than 50 volts shall have a posi-
shall be installed so that burners and burner-ignition devices tive means of disconnect adjacent to and in sight from the
are located not less than 18 inches (457 mm) above the floor equipment served. A 120 volt receptacle shall be located
unless listed as flammable vapor ignition resistant. [NFPA within 25 feet (7620 mm) of the equipment for service and
54:9.1.10.1] maintenance purposes. The receptacle need not be located on
308.1.1 Physical Damage. Appliances installed in the same level as the equipment. Low-voltage wiring of 50
garages, warehouses, or other areas subject to mechan- volts or less within a structure shall be installed in a manner
ical damage shall be guarded against such damage by to prevent physical damage.
being installed behind protective barriers or by being
elevated or located out of the normal path of vehicles.
311.0 Workmanship.
308.1.2 Access from the Outside. Where such appli-

LY
ances installed within a garage are enclosed in a sepa- 311.1 Engineering Practices. Design, construction, and
rate, approved compartment having access from outside workmanship shall comply with accepted engineering prac-
of the garage, such appliances shall be permitted to be tices and shall be of such character as to secure the results
installed at floor level, provided the required combustion sought to be obtained by this code.
air is taken from and discharged to the exterior of the 311.2 Concealing Imperfections. It is unlawful to conceal
garage. [NFPA 54:9.1.10.3]
308.1.3 Cellulose Nitrate Plastic Storage. Heating
N cracks, holes, or other imperfections in materials by welding,
brazing, or soldering, by using therein or thereon paint, wax,
tar, solvent cement, other leak-sealing or repair agent.
O
equipment located in rooms where cellulose nitrate
plastic is stored or processed shall be in accordance with
the fire code.
312.0 Condensate Wastes and Control.
308.2 Protection Against Flood Damage. For buildings
312.1 Condensate Disposal. Condensate from air washers,
D

located in flood hazard areas, heating, ventilating, air-condi-


tioning, refrigeration, miscellaneous heat-producing, and air-cooling coils, fuel-burning condensing appliances, and the
energy-utilizing equipment and appliances shall be elevated overflow from evaporative coolers and similar water-supplied
equipment or similar air-conditioning equipment shall be
EA

at or above the elevation required by the building code for


utilities and attendant equipment or the elevation of the lowest collected and discharged to an approved plumbing fixture or
floor, whichever is higher. disposal area. Where discharged into the drainage system,
equipment shall drain by means of an indirect waste pipe. The
Exception: Equipment and appliances are permitted to be
located below the elevation required by the building code for waste pipe shall have a slope of not less than 1⁄8 inch per foot
(10.4 mm/m) or 1 percent slope and shall be of approved corro-
R

utilities and attendant equipment or the elevation of the lowest


floor, whichever is higher, provided that they are designed sion-resistant material not smaller than the outlet size in accor-
and installed to prevent water from entering or accumulating dance with either Section 312.3 or Section 312.4 for air-cooling
within the components and to resist hydrostatic and hydro- coils or condensing fuel-burning appliances, respectively.
dynamic loads and stresses, including the effects of buoyancy, Condensate or wastewater shall not drain over a public way.
during the occurrence of flooding to such elevation in accor- 312.2 Condensate Control. Where a cooling coil or cooling
dance with the flood-resistant construction requirements of unit is located in an attic or furred space where damage is
the building code. capable of resulting from condensate overflow, an additional
308.2.1 Walls Below Buildings in Flood Hazard Areas watertight pan of corrosion-resistant metal shall be installed
Subject to High Velocity Wave Action. In flood hazard beneath the cooling coil or unit top to catch the overflow
areas subject to high velocity wave action, equipment condensate due to a clogged primary condensate drain, or one
and appliances, including piping, shall not be mounted pan with a standing overflow and a separate secondary drain
on or penetrate walls intended to break away under flood shall be permitted to be provided in lieu of the secondary
loads. drain pan. The additional pan or the standing overflow shall
308.2.2 Air Exhaust and Intake Openings. Outside air be provided with a drain pipe, not less than 3⁄4 of an inch (20
exhaust openings and air intake openings shall be located mm) nominal pipe size, discharging at a point that is readily
at or above the elevation required by the building code observed.
for utilities and attendant equipment or the elevation of This requirement is in addition to the requirements in
the lowest floor, whichever is higher. Section 312.3 and Section 312.4.

48 2013 CALIFORNIA MECHANICAL CODE


GENERAL REQUIREMENTS

312.3 Condensate Waste Sizing. Condensate waste pipes 314.0 Heating or Cooling Air System.
from air-cooling coils shall be sized in accordance with equip- 314.1 Source. A heating or cooling air system shall be
ment capacity as specified in Table 312.3. provided with return air, outside air, or both. A heating or
cooling air system regulated by this code and designed to
replace required ventilation shall be arranged to discharge
TABLE 312.3 into a conditioned space not less than the amount of outside
MINIMUM CONDENSATE PIPE SIZE air specified in Chapter 4.
EQUIPMENT CAPACITY IN
MINIMUM CONDENSATE 314.2 Air Filters. Air filters shall be installed in a heating,
PIPE DIAMETER
TONS OF REFRIGERATION
(inches) cooling or makeup air system. Such filters shall comply with
the standard, Air Filter Units, Test Performance of, that is
Up to 20 ⁄4
3
referenced in Chapter 17, as Class I or II filters.
21 – 40 1 Exception: Systems serving single guest rooms or dwelling
41 – 90 11⁄4 units shall not require a listed filter.
91 – 125 11⁄2 314.3 Prohibited Source. Outside or return air for a heating
126 – 250 2 or cooling air system shall not be taken from the following
For SI units: 1 inch = 25 mm, 1 ton of refrigeration = 3.52 kW locations:
(1) Less than 10 feet (3048 mm) in distance from an appli-
The size of condensate waste pipes is for one unit or a
ance vent outlet, a vent opening of a plumbing drainage

LY
combination of units, or as recommended by the manufac-
system, or the discharge outlet of an exhaust fan, unless
turer. The capacity of waste pipes assumes a 1⁄8 inch per foot
the outlet is 3 feet (914 mm) above the outside-air inlet.
(10.4 mm/m) or 1 percent slope, with the pipe running three-
quarters full at the following conditions: (2) Less than 10 feet (3048 mm) above the surface of an
abutting public way, driveway, sidewalk, street, alley, or
Outside Air – 20%
DB WB
Room Air – 80%
DB WB
N driveway.
(3) A hazardous or insanitary location, or a refrigeration
machinery room as defined in this code.
O
90°F 73°F 75°F 62.5°F
(4) An area, the volume of which is less than 25 percent of
For SI units: °C = (°F-32)/1.8
the entire volume served by such system, unless there is
a permanent opening to an area the volume of which is
D

Condensate drain sizing for other slopes or other condi- equal to 25 percent of the entire volume served.
tions shall be approved by the Authority Having Jurisdiction. Exception: Such openings where used for a heating or
312.4 Fuel-Burning Appliance Condensate Drains. cooling air system in a dwelling unit shall be permitted
EA

Condensate drain lines from individual fuel-burning to be reduced to not less than 50 percent of the required
condensing appliances shall be sized as required by the manu- area, provided the balance of the required return air is
facturer’s instructions. Condensate drain lines serving more taken from a room or hall having not less than three doors
than one appliance shall be approved by the Authority Having leading to other rooms served by the furnace.
Jurisdiction prior to installation. (5) A closet, bathroom, toilet room, or kitchen.
R

312.5 Condensate Waste. Where the condensate waste from (6) Rooms or spaces containing a fuel-burning appliance
air-conditioning coils discharges by direct connection to a lava- therein. Where such room or space serves as source of
tory tailpiece or to an approved accessible inlet on a bathtub return-air.
overflow, the connection shall be located in the area controlled
by the same person controlling the air-conditioned space. Exceptions:
312.6 Point of Discharge. Air-conditioning condensate waste (1) This shall not apply to fireplaces, fireplace appli-
pipes shall connect indirectly to the drainage system through ances, residential cooking appliances, direct-vent
an airgap or airbreak to properly trapped and vented recep- appliances, enclosed furnaces, and domestic-type
tors, dry wells, leach pits, or the tailpiece of plumbing clothes dryers installed within the room or space.
fixtures. (2) This shall not apply to a gravity-type or listed vented
312.7 Plastic Fittings. Female PVC screwed fittings shall be wall heating or cooling air system.
used with plastic male fittings and plastic male threads. (3) This shall not apply to a blower-type heating or
cooling air system installed in accordance with the
313.0 Personnel Protection. following requirements:
313.1 General. A metal guard shall be provided around (a) Where the return air is taken from a room or
exposed flywheels, fans, pulleys, belts, and moving space having a volume exceeding 1 cubic foot
machinery that are portions of a heating, ventilating, or refrig- (0.03 m3) for each 10 Btu/h (0.003 kW) fuel
erating system. input rating of fuel-burning appliances therein.

2013 CALIFORNIA MECHANICAL CODE 49


GENERAL REQUIREMENTS

(b) Not less than 75 percent of the supply air is (3) ASHRAE 111
discharged back into the same room or space. (4) NEBB Procedural Standards for Testing Adjusting
(c) Return-air inlets shall not be located within 10 Balancing of Environmental Systems
feet (3048 mm) from an appliance firebox or (5) SMACNA HVAC Systems Testing, Adjusting, and
draft diverter in the same enclosed room or Balancing
confined space.
314.4 Return-Air Limitations. Return air from one dwelling
unit shall not discharge into another dwelling unit through the 318.0 Louvers in Hurricane Prone Regions.
heating or cooling air system. 318.1 General. Louvers located in areas within hurricane-
prone regions that are within 1 mile (2 km) of the coastal mean
high water line where the basic wind speed is 110 miles per
315.0 Water Supply. hour (mi/h) (49.2 m/s) or greater; or portions of hurricane-
315.1 General. Water supply and backflow protection shall prone regions where the basic wind speed is 120 mi/h (53.6
be in accordance with the California Plumbing Code. m/s) or greater; or Hawaii, as described in ASCE 7 shall be
tested in accordance with Section 318.1.1 and Section 318.1.2.
316.0 Pipe, Tube Hangers, and Supports. 318.1.1 Testing. Louvers that protect air intake or
316.1 General. Piping and tubing shall be supported in accor- exhaust openings shall be tested in accordance with
dance with this section, the manufacturer’s instructions, and AMCA 550 for resistance to wind-driven rain.

LY
in accordance with the Authority Having Jurisdiction. 318.1.2 Impact Resistance Test. Upon request by the
316.2 Suspended Piping. Suspended piping shall be Authority Having Jurisdiction, louvers protecting intake
supported at intervals not to exceed those shown in Table and exhaust ventilation ducts that are not fixed in the
316.2. open position and located within 30 feet (9144 mm) of
316.3 Piping Support. Piping shall be supported in such a the grade shall be tested for impact resistance in accor-
manner as to maintain its alignment and prevent sagging.
316.4 Strength. Hangers and anchors shall be of sufficient
N dance with AMCA 540.

319.0 Protection of Piping, Materials, and Structures.


O
strength to support the weight of the pipe and its contents.
Piping shall be isolated from incompatible materials. 319.1 General. Piping passing under or through walls shall
316.5 Hanger Rod Sizes. Hanger rod sizes shall be not be protected from breakage. Piping passing through or under
smaller than those shown in Table 316.5. cinders or other corrosive materials shall be protected from
D

external corrosion in an approved manner. Approved provi-


TABLE 316.5 sions shall be made for expansion of hot water piping. Voids
HANGER ROD SIZES around piping passing through concrete floors on the ground
EA

PIPE AND TUBE SIZE ROD SIZES shall be sealed.


(inches) (inches)
⁄2 - 4 ⁄8
320.0 Sleeves for Piping.
1 3

5-8 ⁄2
320.1 General. Sleeves shall be provided to protect piping
1

10 - 12 ⁄8
through concrete and masonry walls and concrete floors.
5
R

For SI units: 1 inch = 25.4 mm Exception: Sleeves shall not be required where openings are
drilled or bored.
316.6 Gas Piping. Gas piping shall be supported by metal 320.2 Bearing. Piping through concrete or masonry walls
straps or hooks at intervals not to exceed those shown in Table shall not be subject to a load from building construction.
1311.2.5.1. 320.3 Sealing. In exterior walls, annular space between sleeves
316.7 In Ground. Piping and tubing in the ground shall be and pipes shall be sealed and made watertight, as approved by
laid on a firm bed for its entire length except where otherwise the Authority Having Jurisdiction. A penetration through fire-
approved by the Authority Having Jurisdiction. Asbestos- resistive construction shall be in accordance with the building
cement piping shall be provided with approved thrust code and applicable standards referenced in Table 1701.0.
blocking. 320.4 Through Firewall. A pipe sleeve through a firewall
shall have the space around the pipe completely sealed with
317.0 Balancing. an approved fire-resistive material in accordance with other
317.1 General. Heating, ventilating, and air-conditioning codes.
systems (including hydronic systems) shall be balanced in
accordance with one of the following methods: 321.0 Cutting Structure.
(1) AABC National Standards for Total System Balance 321.1 General. A structural member weakened or impaired
(2) ACCA Manual B by cutting, notching, or otherwise shall be reinforced,

50 2013 CALIFORNIA MECHANICAL CODE


GENERAL REQUIREMENTS

repaired, or replaced so as to be left in a safe structural condi- such as handwashing and baths. Booster heaters for
tion in accordance with the requirements of the building code. dishwashing providing 125°F to 180°F (52°C to 82°C)
water may be counted as the second source of heat for
that service.
322.0 Ratproofing.
324.2 Requirements for Skilled Nursing, Intermediate Care
322.1 General. Mechanical system shall be constructed in
Facilities and Basic Services Provided in Correctional
such a manner that rats cannot enter a building by following
Treatment Centers. [For OSHPD 2 & 4]
the duct work from the outside into the building.
324.2.1 Boilers, if provided, shall accommodate Section
322.2 Ductwork or Pipes. In or on buildings where openings
324.1.
have been made in walls, floors, or ceilings for the passage of
ductwork or pipes, such openings shall be closed and 324.2.2 Two or more interconnected water heaters are
protected by the installation of approved metal collars an acceptable means to provide two sources of heat for
securely fastened to the adjoining structure. hot water (See Section 324.1.5).

323.0 Scope. 325.0 Air Conditioning and Heating Systems.


323.1 Applicability. This part is applicable to health facili- 325.1 Requirements for Hospitals and Optional Services
ties regulated by OSHPD (See Adoption Tables for applica- Provided in Correctional Treatment Centers. [OSHPD 1 & 4]
tion for specific sections). 325.1.1 The systems shall be designed to provide the
Note: This section has no corresponding provisions in the temperatures and relative humidity for sensitive areas or

LY
UMC. For the scope and authority of each state agency, refer rooms shown in Table 325.0. When outdoor humidity and
to Chapter 1. internal moisture sources are not sufficient to meet the
323.2 Services/Systems and Utilities. Refer to Section requirements of Table 325.0, humidification shall be
1224.4.1 of the California Building Code. provided by means of the health-care facility air-
handling systems. Temperature shall be individually

324.0 Steam and Hot-Water Systems.


N controlled for each operating and delivery room. Burn
unit patient rooms that require humidifiers to comply
O
324.1 Requirements for Hospitals and Optional Services with Table 325.0 shall be provided with individual
Provided in Correctional Treatment Centers. [OSHPD 1 & 4] humidity control.
324.1.1 Boilers shall have the capacity, based upon the 325.1.2 For occupied areas not shown in Table 325.0,
rest ratings published by the Hydronics Institute or heating systems shall be designed to provide 70°F to
D

another acceptable national standard to supply the 75°F (21.1°C to 23.9°C) based on the Median of
normal operating requirements of all connected systems Extremes shown by the 1982 ASHRAE Climatic Data for
and equipment. Region X and ASHRAE 1994 Supplement to Climatic
EA

324.1.2 A minimum of two boilers shall be provided. The Data for Region X. The systems shall be thermostatically
arrangement of boilers shall be based on the capacity controlled with appropriate zoning to achieve the above
conditions.
and capability of a boiler or boilers to operate all
systems during-periods of breakdown or maintenance of 325.1.3 For occupied areas not shown in Table 325.0,
any one boiler. cooling systems shall be designed to provide 75°F
R

(23.9°C) maximum based on the 0.5 percent summer


324.1.3 Boiler systems providing space heating shall be
design dry bulb temperatures shown by the 1982
designed to maintain a minimum temperature of 60°F
ASHRAE Climatic Data for Region X and ASHRAE 1994
(15.6°C) in general patient areas and the temperatures
Supplement to Climatic Data for Region X. The systems
specified in Table 325.0 for sensitive areas during
shall be thermostatically controlled with appropriate
periods of breakdown or maintenance of any one boiler. zoning to achieve the above conditions.
Winter design temperature shall be based on the Median
of Extremes shown by the 1982 ASHRAE Climatic Data 325.2 Requirements for Skilled Nursing, Intermediate Care
for Region X and ASHRAE 1994 Supplement to Climatic Facilities and Basic Services Provided in Correctional
Data for Region X. Treatment Centers. [For OSHPD 2 & 4]
324.1.4 Boiler feed pumps, condensate return pumps, 325.2.1 Systems shall accommodate the provisions of
fuel oil pumps, and heating circulating pumps shall be Section 325.1.2 through 325.1.3.
connected and installed to provide standby service in the 325.2.2 Where air conditioning is provided, the system
event of pump failure. Installation of duplex pumps or shall be thermostatically controlled in one or more zones.
provision of a spare pump will meet this requirement. 325.3 Requirements for Outpatient Facilities and Licensed
324.1.5 At least two sources of heat (e.g. two pieces of Clinics. [For OSHPD 3]
equipment) shall be provided for supplying essential 325.3.1 The system shall be designed to provide the
services such as sterilizers, hot water for dishwashing, temperature and humidities for sensitive areas for rooms
and domestic hot water for minimum patient service, shown in Table 325.0.

2013 CALIFORNIA MECHANICAL CODE 51


GENERAL REQUIREMENTS

TABLE 325.0
HEATING, COOLING, AND RELATIVE HUMIDITY
REQUIREMENTS FOR SENSITIVE AREAS OR ROOMS

TEMPERATURE RELATIVE
RANGE1, 2 HUMIDITY1, 3
Area or Rooms Designation °F Percent
Operating room 68-75 20-60
Cystoscopy 68-75 20-60
Cardiac catheterization lab 70-75 max 60
Trauma/cardiac room 70-75 20-60
Delivery room, Caesarean
68-75 20-60
operating room
Gastrointestinal endoscopy
68-73 20-60
procedure room
Post-Anesthesia Care Unit 70-75 30-60
Newborn nursery 72-78 30-60
Newborn Intensive-care nursery unit 70-75 30-60
Intensive care4 70-75 30-60

LY
Burn Unit 70-75 40-60
1 Thermostats and humidistat shall be either locally resetable and of the
non-locking type or remotely resetable and of the locking type.
2 Systems shall be capable of maintaining the rooms within the range
during normal operation. Lower or higher temperature shall be permitted
when patients’ comfort and/or medical conditions require those condi-
tions.
N
O
3 The ranges listed are the minimum and maximum limits where control is
specifically needed.
4
Types of intensive care service spaces are listed in the California
D

Building Code.

326.0 Essential Mechanical Provisions. [OSHPD 1, 2, 3


EA

(Surgical Clinics only) & 4] During periods of power


outages essential electrical power shall be provided for the
following equipment:
326.1 (Does not apply to OSHPD 3 surgical clinic.) All
heating equipment necessary to maintain a minimum temper-
R

ature of 60°F (15.6°) in patient areas which are not specified


in Table 325.0.
326.2 All heating equipment necessary to maintain the
minimum temperatures for sensitive areas as specified in
Table 325.0.
326.3 Equipment necessary for humidification of the areas
listed in Table 325.0.
326.4 All supply, return, and exhaust fans required to main-
tain the positive and negative air balances as required in
Table 4-A.
326.5 All control components and control systems necessary
for the normal operation of equipment required to have essen-
tial electrical power.
326.6 Alarms for airborne infection isolation rooms and
protective environment rooms.

52 2013 CALIFORNIA MECHANICAL CODE


GENERAL REQUIREMENTS

TABLE 303.3(1)
CLEARANCES, IN INCHES, WITH SPECIFIED FORMS OF PROTECTION1, 2
TYPE OF PROTECTION4 WHERE THE STANDARD CLEARANCE IN TABLE 303.4 WITH NO PROTECTION IS:
Applied to the Combustible Mate- 36 (inches) 18 (inches) 12 (inches) 9 (inches) 6 (inches)
rial Unless Otherwise Specified and
Covering All Surfaces within the SIDES CHIMNEY OR SIDES CHIMNEY OR SIDES CHIMNEY OR SIDES CHIMNEY OR
Distance Specified as the Required ABOVE AND VENT ABOVE AND VENT ABOVE AND VENT ABOVE AND VENT
Clearance with No Protection REAR CONNECTOR REAR CONNECTOR REAR CONNECTOR REAR CONNECTOR
(Thicknesses Are Minimum)
(a) 1⁄4 of an inch insulating mill-
board spaced out 1 inch3 30 18 30 15 9 12 9 6 6 3 2 3
(b) 0.013 inch (No. 28 manu-
facturer’s standard gauge) 24 18 24 12 9 12 9 6 4 3 2 2
steel sheet on 1⁄4 of an inch
insulating millboard
(c) 0.013 inch (No. 28 manu-
facturer’s standard gauge)
steel sheet spaced out 1 18 12 18 9 6 9 6 4 4 2 2 2
inch3
(d) 0.013 inch (No. 28 manu-
facturer’s standard gauge)
steel sheet on 1⁄8 of an inch 18 12 18 9 6 9 6 4 4 2 2 2
insulating millboard spaced
out 1 inch3

LY
(e) 11⁄2 inch insulating cement
covering on heating appli- 18 12 36 9 6 18 6 4 9 2 1 6
ance
(f) 1⁄4 of an inch insulating mill-
board on 1 inch mineral 18 12 18 6 6 6 4 4 4 2 2 2
fiber batts reinforced with
wire mesh or equivalent
(g) 0.027 inch (No. 22 manu-
facturer’s standard gauge)
N
O
steel sheet on 1 inch mineral 18 12 12 4 3 3 2 2 2 2 2 2
fiber batts reinforced with
wire or equivalent
(h) 1⁄4 of an inch insulating mill- 36 36 36 18 18 18 12 12 9 4 4 4
board
D

For SI units: 1 inch = 25.4 mm


Notes:
1
For appliances complying with Section 303.3 and Section 303.4.
EA

2
Except for the protection described in (e), clearances shall be measured from the outer surface of the appliance to the combustible material, disregarding an
intervening protection applied to the combustible material.
3
Spacers shall be of noncombustible material.
4
Insulating millboard is a factory-made product formed of noncombustible materials, normally fibers, and having a thermal conductivity of 1 British thermal
unit inch per hour square foot degree Fahrenheit [Btu•in/(h•ft2•°F)] [0.1 W/(m•K)] or less.
R

Notes:
1. Dimension shall be not less than the required clearance with no protection set forth in Table 303.4 and Table 303.3(2) and in section applying to various
types of appliances.
2. Dimension shall be not less than the reduced clearance set forth in Table 303.3(1).
3. Dimension shall be not less than the clearance required for dimension A.
FIGURE 303.3
EXTENT OF PROTECTION REQUIRED TO REDUCE CLEARANCES FROM APPLIANCE, CHIMNEY, OR VENT CONNECTORS
[NFPA 211: FIGURE 9.5.1.1]

2013 CALIFORNIA MECHANICAL CODE 53


GENERAL REQUIREMENTS

TABLE 303.3(2)
CHIMNEY CONNECTOR AND VENT CONNECTOR CLEARANCES
FROM COMBUSTIBLE MATERIALS
[NFPA 211: TABLE 9.5.1.1]
MINIMUM CLEARANCE1
DESCRIPTION OF APPLIANCES
(inches)
RESIDENTIAL-TYPE APPLIANCES ––
SINGLE-WALL METAL PIPE CONNECTORS2 ––
Gas appliances without draft hoods 18
Electric, gas, and oil incinerators 18
Oil and solid-fuel appliances 18
Unlisted gas appliances with draft hoods 9
Boilers and furnaces equipped with listed gas burners and with draft hoods3 9
Oil appliances listed as approved for use with Type L venting systems (but only where connected to
9
chimneys)
Listed gas appliances with draft hoods 6
TYPE L VENTING SYSTEM PIPING CONNECTORS
Gas appliances without draft hoods 9

LY
Electric, gas, and oil incinerators 9
Oil and solid-fuel appliances 9
Unlisted gas appliances with draft hoods 6
Boilers and furnaces equipped with listed gas burners and with draft hoods 6
Oil appliances listed as suitable for use with Type L venting systems4 ––
Listed gas appliances with draft hoods5
TYPE B GAS VENT PIPING CONNECTORS
N ––
––
O
Listed gas appliances with draft hoods 5 ––
COMMERCIAL-INDUSTRIAL TYPE APPLIANCES ––
LOW-HEAT APPLIANCES ––
SINGLE-WALL METAL PIPE CONNECTORS2 ––
D

Gas, oil, and solid-fuel boilers, furnaces, and water heaters 18


Ranges, restaurant-type 18
Oil unit heaters 18
EA

Unlisted gas unit heaters 18


Listed gas unit heaters with draft hoods 6
Other low-heat industrial appliances 18
MEDIUM-HEAT APPLIANCES ––
R

SINGLE-WALL METAL PIPE CONNECTORS2 ––


All gas, oil, and solid-fuel appliances 36
For SI units: 1 inch = 25.4 mm
Notes:
1
These clearances apply except where the listing of an appliance specifies different clearance, in which case the listed clearance takes precedence.
2
The clearances from connectors to combustible materials shall be permitted to be reduced where the combustible material is protected in accordance with
Table 303.3(1).
3
The dimension shall be permitted to be 6 inches (152 mm), provided the maximum flue temperatures entering the draft hood do not exceed 550°F (288°C).
4
Where listed Type L venting system piping is used, the clearance shall be permitted to be in accordance with the venting system listing.
5
Where listed Type B or Type L venting system piping is used, the clearance shall be permitted to be in accordance with the venting system listing.

54 2013 CALIFORNIA MECHANICAL CODE


GENERAL REQUIREMENTS

TABLE 303.3(3)
CAPACITIES OF LISTED METAL APPLIANCE CONNECTORS1
FOR USE WITH GAS PRESSURES 8-INCH OR MORE WATER COLUMN

FLEXIBLE CAPACITIES FOR VARIOUS LENGTHS, NATURAL GAS AT 1100 Btu/ft3


SEMIRIGID (BASED ON A PRESSURE DROP OF 0.2 INCH WATER COLUMN)4
CONNECTOR
CONNECTOR
NOMINAL
O.D.2
I.D.3
1 (foot) 11⁄2 (feet) 2 (feet) 21⁄2 (feet) 3 (feet) 4 (feet) 5 (feet) 6 (feet)
RANGES AND CLOTHES DRYERS
(inches) (inches) ALL GAS APPLIANCES (thousands of Btu/h)
(thousands of Btu/h)
3
⁄8 1
⁄4 40 33 29 27 25 — — —
1
⁄2 3
⁄8 93 76 66 62 58 — — —
5
⁄8 1
⁄2 189 155 134 125 116 101 90 80
— 3
⁄4 404 330 287 266 244 — — —
— 1 803 661 573 534 500 — — —
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per cubic foot = 0.01035 kW•h/m3, 1000 British thermal units per hour = 0.293 kW,
1 inch water column = 0.249 kPa
Notes:

LY
1
Gas connectors are certified by the testing agency as complete assemblies, including the fittings and valves. Capacities shown are based on the use of fittings
and valves supplied with the connector.
2
Outside diameter.
3
Internal diameter.
4
For liquefied petroleum gas, use 1.6 times the natural gas capacities shown.

N
TABLE 303.3(4)
O
CAPACITIES OF LISTED METAL APPLIANCE CONNECTORS1
FOR USE WITH GAS PRESSURES LESS THAN 8-INCH WATER COLUMN

FLEXIBLE CAPACITIES FOR VARIOUS LENGTHS, NATURAL GAS AT 1100 Btu/ft3


SEMIRIGID
CONNECTOR
D

CONNECTOR (BASED ON A PRESSURE DROP OF 0.2 INCH WATER COLUMN)4


NOMINAL
O.D.2
I.D.3 1 (foot) 11⁄2 (feet) 2 (feet) 21⁄2 (feet) 3 (feet) 4 (feet) 5 (feet) 6 (feet)
EA

RANGES AND CLOTHES DRYERS


(inches) (inches) ALL GAS APPLIANCES (thousands of Btu/h)
(thousands of Btu/h)
3
⁄8 1
⁄4 28 23 20 19 17 — — —
1
⁄2 3
⁄8 66 54 47 44 41 — — —
5
⁄8 1
⁄2 134 110 95 88 82 72 63 57
R

— 3
⁄4 285 233 202 188 174 — — —
— 1 567 467 405 378 353 — — —
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 British thermal unit per cubic foot = 0.01035 kW•h/m , 1000 British thermal units per hour = 0.293 kW,
3

1 inch water column = 0.249 kPa


Notes:
1
Gas connectors are certified by the testing agency as complete assemblies, including the fittings and valves. Capacities shown are based on the use of fittings
and valves supplied with the connector.
2
Semirigid connector listings are based on the outside diameter.
3
Flexible connector listings are based on nominal diameter.
4
For liquefied petroleum gas, use 1.6 times the natural gas capacities shown.

2013 CALIFORNIA MECHANICAL CODE 55


GENERAL REQUIREMENTS

TABLE 303.4
STANDARD INSTALLATION CLEARANCES IN INCHES FOR UNLISTED HEAT-PRODUCING APPLIANCES
APPLIANCE

FROM TOP AND


RESIDENTIAL-TYPE APPLIANCES FUEL ABOVE TOP OF
SIDES OF WARM- FROM FROM FROM
CASING OR
AIR BONNET OR FRONT1 BACK SIDES
APPLIANCE
PLENUM

BOILERS AND WATER HEATERS11


Steam Boilers – 15 pounds-force per square inch (psi) Automatic Oil or
Water Boilers – 250°F Comb. Gas-Oil 6 – 24 6 6
Water Heaters – 200°F Automatic Gas 6 – 18 6 6
All Water Walled or Jacketed Solid 6 – 48 6 6

FURNACES – CENTRAL; OR HEATERS11 – Automatic Oil or


ELECTRIC CENTRAL WARM AIR FURNACES Comb. Gas-Oil 62 24 6 6 6
Gravity, Upflow, Downflow, Horizontal and Duct Automatic Gas 62 62 18 6 6
Warm Air – 250°F max. Solid 183 183 48 18 18
Electric 62 62 18 6 6
FURNACES – FLOOR Automatic Oil or
For Mounting in Combustible Floors Comb. Gas-Oil 36 – 12 12 12
Automatic Gas 36 – 12 12 12

LY
HEAT EXCHANGERS
Steam – 15 psi max. – 1 1 1 1 1
Hot Water – 250°F max.
ROOM HEATERS4 Oil or Solid 36 – 24 12 12
Circulating Type Gas 36 – 24 12 12
Radiant or Other Type Oil or Solid 36 – 36 36 36
N
Gas
Gas with double
metal or ceramic
back
36

36


36

36
18

12
18

18
O
Fireplace Stove Solid 485 –
54 485 485
RADIATORS
Steam or Hot Water6 – 36 – 6 6 6
RANGES – COOKING STOVES Firing Opp.
D

– Side Side
Oil 307 – – 9 24 18
Gas 307 – – 6 6 6
EA

Solid Clay-Lined
Firepot 307 – – 24 24 18
Solid Unlined

Firepot 307 –
– 36 36 18
Electric 307 –
6 6
INCINERATORS
R

Domestic Types – 368 – 48 36 36


APPLIANCE
COMMERCIAL INDUSTRIAL-TYPE APPLIANCES FROM TOP AND
FUEL ABOVE TOP OF
ANY AND ALL PHYSICAL SIZES EXCEPT AS NOTED11 SIDES OF WARM- FROM FROM FROM
CASING OR
AIR BONNET OR FRONT1 BACK9 SIDES9
APPLIANCE
PLENUM
BOILERS AND WATER HEATERS11
100 cubic feet or less All Fuels 18 – 48 18 18
Steam, any pressure
50 psi or less All Fuels 18 – 48 18 18
Any size
UNIT HEATERS Steam or Hot
Floor Mounted or Suspended – Any Size Water 1 – – 1 1
Suspended – 100 cubic feet or less Oil or Comb.
Gas-Oil 6 – 24 18 18
Suspended – 100 cubic feet or less Gas 6 – 18 18 18
Suspended – Over 100 cubic feet
All Fuels 18 – 48 18 18
All Fuels 18 – 48 18 18
RANGES – RESTAURANT – TYPE
Floor Mounted All Fuels 48 – 48 18 18
OTHER LOW-HEAT INDUSTRIAL APPLIANCES
Floor Mounted or Suspended – 18 18 48 18 18

56 2013 CALIFORNIA MECHANICAL CODE


GENERAL REQUIREMENTS

TABLE 303.4 (continued)


STANDARD INSTALLATION CLEARANCES IN INCHES FOR UNLISTED HEAT-PRODUCING APPLIANCES

APPLIANCE

COMMERCIAL INDUSTRIAL-TYPE APPLIANCES FROM TOP AND


FUEL ABOVE TOP
ANY AND ALL PHYSICAL SIZES EXCEPT AS NOTED11 SIDES OF WARM- FROM FROM FROM
OF CASING OR
AIR BONNET OR FRONT1 BACK9 SIDES9
APPLIANCE
PLENUM

BOILERS AND WATER HEATERS


Over 50 psi All Fuels 48 –– 96 36 36
Over 100 cubic feet
OTHER MEDIUM-HEAT INDUSTRIAL
Appliances All Fuels 48 36 96 36 36
All Sizes
INCINERATORS
–– ––
All Sizes 48 96 36 36
INDUSTRIAL-TYPE HIGH-HEAT APPLIANCES
HIGH-HEAT INDUSTRIAL APPLIANCES All Fuels 180 –– 360 120 120
All Sizes

LY
For SI units: 1 inch = 25.4 mm, 1 pound-force per square inch = 6.8947 kPa, 1 cubic foot = 0.0283 m3, °C = (°F-32)/1.8
Notes:
1
The minimum dimension shall be that necessary for servicing the appliance, including access for cleaning and normal care, tube removal, etc.
2
For a listed oil, combination gas-oil, gas, or electric furnace, this dimension shall be permitted to be 2 inches (51 mm) where the furnace limit control cannot
be set exceeding than 250˚F (121°C), or this dimension shall be permitted to be 1 inch (25.4 mm) where the limit control cannot be set exceeding 200˚F (93°C),

3
N
or the appliance shall be marked to indicate that the outlet air temperature cannot exceed 200˚F (93°C).
The dimension shall be permitted to be 6 inches (152 mm) for an automatically stoker-fired forced-warm air furnace equipped with 250˚F (121°C) limit control
and with barometric draft control operated by draft intensity and permanently set to limit draft not to exceed intensity of 0.13 inch (3.3 mm) water gauge.
O
4
Unlisted appliances shall be installed on noncombustible floors and shall be permitted to be installed on protected combustible floors. Heating appliances
approved for installation on protected combustible flooring shall be so constructed that flame and hot gases do not come in contact with the appliance base.
Protection for combustible floors shall consist of 4 inches (102 mm) hollow masonry covered with sheet metal not less than 0.021 of an inch (0.53 mm) thick
(No. 24 manufacturer’s standard gauge). Masonry shall be permanently fastened in place in an approved manner with the ends unsealed and joints matched
D

so as to provide free circulation of air through the masonry. Floor protection shall extend 12 inches (305 mm) at the sides and rear of the appliance, except
that not less than 18 inches (457 mm) shall be required on the appliance opening side or sides measured horizontally from the edges of the opening.
5
The 48 inch (1219 mm) clearance shall be permitted to be reduced to 36 inches (914 mm) where protection equivalent to that provided by footnote 1 through
EA

footnote 7 of Table 303.4 is applied to the combustible construction.


6
Steam pipes and hot water heating pipes shall be installed with a clearance of not less than 1 inch (25.4 mm) from combustible construction or materials, except
that at the points where pipes carrying steam 15 pounds-force per square inch gauge pressure (psig) (103 kPa) or less or hot water that emerge from a floor,
wall, or ceiling, the clearance at the opening through the finish floorboards or wall-ceiling boards shall be permitted to be reduced to not less than 1⁄2 of an
inch (12.7 mm). Each such opening shall be covered with a plate of noncombustible material.
Such pipes passing through stock shelving shall be covered with not less than 1 inch (25.4 mm) of approved insulation.
R

Wood boxes or casings enclosing uninsulated steam or hot water heating pipes or wooden covers to recesses in walls in which such uninsulated pipes are placed
shall be lined with metal or insulating millboard.
Where the temperature of the boiler piping does not exceed 160˚F (71°C), the provisions of this table shall not apply.
Coverings or insulation used on steam or hot water pipes shall be of material approved for the operating temperature of the system. The insulation or jackets shall
be of noncombustible materials, or the insulation or jackets and lap-seal adhesives shall be tested as a composite product. Such composite product shall have a
flame-spread rating of not more than 25 and a smoke-developed rating not to exceed 50 where tested in accordance with ASTM E 84 or UL 723.
7
To combustible material or metal cabinets. Where the underside of such combustible material or metal cabinet is protected with insulating millboard not less than
1
⁄4 of an inch (6.4 mm) thick covered with sheet metal of not less than 0.013 of an inch (0.33 mm) (No. 28 gauge), the distance shall be permitted to be reduced to
24 inches (610 mm).
8
Clearance above charging door shall be not less than 48 inches (1219 mm).
9
Where the appliance is encased in brick, the 18 inch (457 mm) clearance above and at the sides and rear shall be permitted to be reduced to 12 inches (305 mm).
10
Where the appliance is encased in brick, the clearance above shall be permitted to be reduced to 36 inches (914 mm) and at the sides and rear shall be permitted to
be reduced to 18 inches (457 mm).
11
A central heating boiler or furnace shall be installed in accordance with the manufacturer's installation instructions, and shall be installed on a floor of noncom-
bustible construction with noncombustible flooring and surface finish and no combustible material against the underside thereof, or on fire-resistive slabs or
arches having no combustible material against the underside thereof.
Exceptions:
(1) Appliances listed for installation on a combustible floor.
(2) Installation on a floor protected in an approved manner.

2013 CALIFORNIA MECHANICAL CODE 57


GENERAL REQUIREMENTS

TABLE 316.2
HANGER AND SUPPORTS
MATERIALS TYPES OF JOINTS HORIZONTAL VERTICAL
5 feet, except 10 feet where 10 foot
Lead and Oakum Base and each floor, not to exceed 15 feet
lengths are installed1, 2, 3
Cast
Every other joint, unless over 4 feet
Compression Gasket Base and each floor, not to exceed 15 feet
then support each joint1, 2, 3

Every other joint, unless over 4 feet


Cast-Iron Hubless Shielded Coupling Base and each floor, not to exceed 15 feet
then support each joint1, 2, 3, 4

11⁄2 inches and smaller, 6 feet; 2 inches


Copper Tube and Pipe Soldered or Brazed Each floor, not to exceed 10 feet5
and larger, 10 feet
Steel and Brass Pipe for 3
⁄4 inch and smaller, 10 feet; 1 inch and
Threaded or Welded Every other floor, not to exceed 25 feet5
Water DWV larger, 12 feet
Steel, Brass, and Tinned 1
⁄2 inch, 6 feet; 3⁄4 inch and 1 inch 8 1
⁄2 inch, 6 feet; 3⁄4 and 1 inch, 8 feet;
Threaded or Welded
Copper Pipe for Gas feet; 11⁄4 and larger, 10 feet 11⁄4 every floor level

Schedule 40 PVC and All sizes, 4 feet; allow for expansion Base and each floor; provide mid-story
Solvent Cemented

LY
ABS every 30 feet3 guides; provide for expansion every 30 feet

1 inch and smaller, 3 feet; 11⁄4 inch and


CPVC Solvent Cemented Base and each floor; provide mid-story guides
larger, 4 feet
Lead Wiped or Burned Continuous Support Not to exceed 4 feet
Copper
Steel and Brass
Mechanical
Mechanical
Metal insert and metal
N
In accordance with standards acceptable to the Authority Having Jurisdiction
In accordance with standards acceptable to the Authority Having Jurisdiction
Base and each floor;

}
O
PEX 32 inches
compression provide mid-story guides
1
⁄2 inch
Metal insert and metal Base and each floor;

}
PEX-AL-PEX 3
⁄4 inch All sizes 98 inches
compression provide mid-story guides
1 inch
D

1
⁄2 inch
Metal insert and metal Base and each floor;
PE-AL-PE 3
⁄4 inch All sizes 98 inches
compression provide mid-story guides
1 inch
EA

Fusion weld (socket, butt,


saddle, electrofusion), 1 inch and smaller, 32 inches; Base and each floor;
Polypropylene
threaded (metal threads 11⁄4 inches and larger, 4 feet provide mid-story guides
only), or mechanical
R

For SI unit: 1 inch = 25.4 mm, 1 foot = 304.8 mm


Notes:
1
Support adjacent to joint, not to exceed 18 inches (457 mm).
2
Brace not to exceed 40 feet (12 192 mm) intervals to prevent horizontal movement.
3
Support at each horizontal branch connection.
4
Hangers shall not be placed on the coupling.
5
Vertical water lines shall be permitted to be supported in accordance with recognized engineering principles with regard to expansion and contraction, where
first approved by the Authority Having Jurisdiction.

58 2013 CALIFORNIA MECHANICAL CODE

Potrebbero piacerti anche