Column Design (BS 8110-1:1997)

Column size
b 200 mm
h 200 mm
Axial Load,N 150 kN
fy 460 N/mm2
fcu 30 N/mm2

Axial Load, N=0.7fyAsc 466 mm2

Provided 4T16 φbar 16 mm


804 mm2

As,min=0.002Ac 80 mm2
As,max=0.04Ac 1600 mm2

Links,φ=0.25φbar 4 mm or 10 mm
Sv,max=20φbar 320 mm or 250 mm

Provided T10 225

At section 350mm below and above


beam and at lapped joints, 135 mm
Sv,max=0.6*link spacing

Provided T10 125