MANUAL
FIREALARMSYSTEMSDESIGN
5800Pleven
Bulgaria
47SanStefanoStr.
e-mail:office_pleven@unipos-bg.com
1784Sofia
Bulgaria
1Efr.NikolaPaskalevStr.,Mladost1,
tel./fax:+35929744469,9743925
06/2009
e-mail:office_sofia@unipos-bg.net
ThismanualisworkedoutbyateamofUniPOSLtd.based
CLASSIFICATIONOFTHEFIREALARMSYSTEM
ontheTechnicalSpecificationSDCEN/TS54-14:1996
PROTECTIONLEVELINABUILDING:
andRegulationBS5839,part1:2002CEN/TS54-14:2006
Class 1 Class 4
Class 1 Class 2
Class 2
Foradditionalinformation
regardingthedesignoffirealarmsystems
pleasecall“TrainingandConsultations”
DepartmentinUniPOSLtd.at:
+35929744469
Class 3
Class1:Fullprotection:
installedthroughoutallareas.
Class2:Sectionprotection:
installedonlyindefinedareas.
Class3:Protectionoftheescaperoute:
installedontheescaperoutesandthepremisesnextto
theseroutes.
Class4:Localprotection:
coversacertainfacilityorfunctioninthebuildingthatis
PublishedbyUniPOSLTDwiththeassistanceofthe notnecessarytoformawholefiresection.
nationalbranchassociation Class5:Propertyprotection:
“FIREANDEMERGENCYSAFETY” coversspecificapparatusesorequipment.
1
65dB (A)
500Hz to 2000Hz
maximum 30 m.
+5dB (A)
500Hz to 2000Hz
Theminimumsoundlevelofthesoundershouldbe65dB Apersonmustnotpassmorethan30mtoreachamanual
or+5dB(A)abovethebackgroundnoise(ifthelatterlasts callpoint.
morethan30seconds)andwithfrequencywithinthe
rangeof500Hzand2000Hz.
to 30 m.
1,2 to 1,6 m.
Inordertodirectthoserespondingtofirealarmsignal, Themanualcallpointsshouldbepositionedat1.2to1.6m
thenallbuildingsneedtobedividedintodetectionzones. fromthefloorlevel.
2 Thesearchdistancewithinthedetectionzoneshouldnot 3
exceed30m.
2m
75dB(A)
Allcablingshouldbemechanicallyprotectedfromfloor
leveluptoaheightof2m. Notlessthan75dB(A)atthebed-headwithinrooms(alldoors
Allmetalpartsofthesystem,includingtheinstallation shut)inwhichthefirealarmsystemisintendedtorousepeople
tubesandthecablinginstallationshouldbeisolatedbythe fromsleep.
lightningstrikesprotectionsystematthesite.
FS4000
1 2 3 4 5 6 7 8 -20dB(A) -30dB(A)
Sounderdevicecablingshouldbearrangedsothatin
theeventofafaultatleastonesounderwillremain
4 Thesounderlevelfadeswith20dB(A)throughnormal
operationalduringafirecondition.
doorandwith30dB(A)throughfiredoor. 5
7,5 m
Top < 150 mm Top < 600 mm TOP > 150 mm TOP > 600 mm
2
10,6m х 10,6 m =112 m Heat FD Smoke FD Heat FD Smoke FD
5,3m 10,6m
Whenmountedonaflatceiling,smokedetectorshaveanindividual Ceilingswithtopheightsmallerthan150mmforheatdetectors
coverageofa7.5mradius.Thesecircleareasshouldbeoverlapped orsmallerthan600mmforsmokedetectorscouldbeassumedto
sothatno“blindspots”areleft.Thustheindividualcoverage beflatceilings.Forceilingswithhighertop,thefiredetectors
isequaltoasquarewithdimensions10.6mх10.6m=112m2. shouldbeinstalledatthehighestpointoftheceiling.
Maximumallowedceilingheightforinstallationofthefire
5m detector:
Ceiling height (m.)
до 4,5 4,5 - 6 6-8 8 - 11 11 - 25 над 25
HEAT Protected surface radius
FIRE DETECTOR Heat :
EN 54-5 :
Class 1 5 5 5 Nn Np Np
Class 2 5 5 Nn Np Np Np
Class 3 5 Nn Np Np Np Np
7,1m х 7,1 m =50,4 m2
Smoke :
3,6m 7,1m
Point EN 54-7 7,5 7,5 7,5 7,5 Nn Np
Whenmountedonaflatceiling,heatdetectorshaveanindividual Beam EN 54-12 7,5 7,5 7,5 7,5 7,5* Np
coverageofa5.0mradius.Thesecircleareasshouldbeoverlapped
sothatno“blindspots”areleft.Thustheindividualcoverageis Np-notappropriatefortheseheights;
equaltoasquarewithdimensions7.1mх7.1mandprotected Nn-normallynotusedatthatheightbutinspecialcasesitmightbe
surfaceof50.4m2. used;
*-usuallyitisnecessaryasecondrowoffiredetectorsatabout
6 themiddleoftheceilingheight; 7
7,5 m 7,5 m 7,5 m <1m >1m
2m
15 m 15 m
Incorridorslessthan2m.widethehorizontalspacingof Donotinstallfiredetectoratadistancelessthan1mfrom
detectorsmaybeincreased,theareasofcoverageneednot supplyingandcirculatingunits.
overlapasinthecaseofaroom.Anycorridorover2misdeemed
aroomanddevicespacingshouldfollowthestandardforrooms.
premises height.
>5% from the
<300mm
Barrier
<500 mm <500 mm
5m 5m 5m
2m
Barrier
10 m 10 m
1600 m2 1600 m2
Theshortcircuitisolatorsmustlimittheeffectofasingle Neverinstallfiredetectoratadistancesmallerthantwotimes
faultconditioninthelinetofireprotectedareaof theheightofthelightingfitting.
2000m2or32firedetectors.
EOL
FS4000
>1m
1 2 3 4 5 6 7 8
EOL
EOL
Usefire-proofcableswhenlayingthefiredetector Itisnotnecessarytofireprotectholeswithheightsmaller
installationandfortheconnectionofthemainssupply. than800mmunlessthefireriskassessmentrequires
10 automaticfirealarmtobeinstalled. 11
Lift shaft Lift shaft
1,5 m
Forverticalshaftssuchasliftsandstaircases,firedetector Toavoidthefalsealarmsdonotusesmokeorrateofriseheat
shouldbeinstalledataminimumdistanceof1.5mfrom detectorsinholesorpremiseswithboilers.Insuchpremises
theshaft. areapplicablefixedtemperatureheatdetectorswithan
alarmthresholdat90°C.
100
90
80 <4°C
Maximum temperature
70 <29°C
Temperature
60
50
Average environmental
40 temperature
30
20
10
Time
Forclosedladdercagesonefiredetectorshouldbe Theactivationtemperatureofthefixedtemperatureheat
installedateachmainlanding. detectorshouldexceedwithmorethan29°C oftheaverage
temperatureandwithmorethan4°Cofthemaximum
12 temperatureofthefireprotectedenvironment. 13
>25 mm
Remote
Indicator
Thermistor
<150 mm
Thesensitiveelementoftheheatfiredetector Thestandardconventionalbasetype8000,manufacturedby
(thethermistor)shouldbeataminimumdistanceof UniPOSshouldbecableconnectedasshownabove.
25mmandmaximumof150mmfromtheceiling.
>25 mm
<600 mm Remote
Indicator
Optical Chamber
Thesensitiveelementofthesmokefiredetector Thestandardaddressbase,type7100,manufacturedby
(thephotoelectricopticalchamber)shouldbeataminimum UniPOSshouldbecableconnectedasshownabove.Please
distanceof25mmandmaximumof600mmfromtheceiling. considerthedifferenceintheRemoteIndicatorwiring!
14 15
1.Thefullrequirementslist,notdescribedinthe“Application
manualFireAlarmSystemsDesign”refertotheTechnical
SpecificationSDCEN/TS54-14:1996andRegulationBS5839,
part1:2002.
2.Forspecifictechnicalsolutionsinthedesigningoffirealarmsystems,
Optical Smoke
withUniPOSmanufactureddevices,refertothemanuals
Chamber andthepresentations,workedoutbytheUniPOSexperts.
components
Thephotoelectricopticalsmokefiredetectorshaveaneasy
todisassembleopticchamber.UniPOSrecommendsthe
opticalsmokechambertobecleanedatleastonceperyearin
16 ordertoprovidetheoptimalperformanceofthefiredetector.