Sealing fittings prevent passage of Class I, Div. 1 and 2 Class I, Div. 1 and 2
gases, vapors or flames from one por- Seals must be placed in each conduit Where 2” or larger conduit enters enclo-
tion of a conduit system to another. within 18” of a device that may produce sure, fitting housing terminals, splices
They also restrict large amounts of ig- arcs, sparks, or high temperatures. or taps, seals are required within 18” or
nitable gases or vapors from accumu- such enclosure.
lating to confine explosive pressure.
Sec. 501-5(a)(1)
permits explosion-
proof unions,
couplings, elbows,
and Appleton ER
Conduit Outlet
Bodies between 2” or larger conduit
seal and appara-
tus enclosure.